The TrustedTM Output Power Distribution Unit is designed to provide 24-120V dc for use with TrustedTM
sourcing output modules, e.g. T8451 and T8471, 24V dc and 120V dc Digital Output Modules
respectively. The Unit is designed to be mounted on a DIN rail above the relevant output module I/O
connectors.
TM
Note: New developments using Trusted
their 0V reference via Trusted
the Trusted
Features
TM
Output Power Distribution Unit (Diode Protected) T8297.
• Supports up to three Trusted
Analogue output modules, or for output modules obtaining
M
T
Versatile Field Termination Assemblies (VFTAs) should use
TM
sourcing output modules.
• Dual stud power connection for either single or dual feed.
• 0V module reference via BLZ 2-part connectors.
Issue 6 Sep 05 PD-T8290 1
Trusted
Issue Record
Issue
Number Date Revised by Technical CheckAuthorised by Modification
Figure 2 TrustedTM Output Power Distribution Unit – Wiring Diagram .....................................................7
Issue 6 Sep 05 PD-T8290 4
Trusted
TM
Output Power Distribution Unit T8290
Notice
The content of this document is confidential to ICS Triplex Technology Ltd. companies and their
partners. It may not be given away, lent, resold, hired out or made available to a third party for any
purpose without the written consent of ICS Triplex Technology Ltd.
This document contains proprietary information that is protected by copyright. All rights are reserved.
icrosoft, Windows, Windows 95, Windows NT, Windows 2000, and Windows XP are registered
M
trademarks of Microsoft Corporation.
The information contained in this document is subject to change without notice. The reader should, in
all cases, consult ICS Triplex Technology Ltd. to determine whether any such changes have been
made. From time to time, amendments to this document will be made as necessary and will be
distributed by ICS Triplex Technology Ltd.
Information in this documentation set may be subject to change without notice and does not represent
a commitment on the part of ICS Triplex Technology Ltd.
The contents of this document, which may also include the loan of software tools, are subject to the
confidentiality and other clause(s) within the Integrator Agreement and Software License Agreement.
No part of this documentation may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying and recording, for any purpose, without the express
written permission of ICS Triplex Technology Ltd.
Disclaimer
The illustrations, figures, charts, and layout examples in this manual are intended solely to illustrate the
text of this manual.
The user of, and those responsible for applying this equipment, must satisfy themselves as to the
acceptability of each application and use of this equipment.
This document is based on information available at the time of its publication. While efforts have been
made to be accurate, the information contained herein does not purport to cover all details or variations
in hardware or software, nor to provide for every possible contingency in connection with installation,
operation, or maintenance. Features may be described herein which are present in all hardware or
software systems. ICS Triplex Technology Ltd. assumes no obligation of notice to holders of this
document with respect to changes subsequently made.
ICS Triplex Technology Ltd. makes no representation or warranty, expressed, implied, or statutory with
respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of
the information contained herein. No warranties of merchantability or fitness for purpose shall apply.
Issue 6 Sep 05 PD-T8290 5
Trusted
TM
Output Power Distribution Unit T8290
Revision and Updating Policy
All new and revised information pertinent to this document shall be issued by ICS Triplex Technology
Ltd. and shall be incorporated into this document in accordance with the enclosed instructions. The
change is to be recorded on the Amendment Record of this document.
Precautionary Information
WARNING
Warning notices call attention to the use of materials, processes, methods, procedures or limits which
must be followed precisely to avoid personal injury or death.
CAUTION
Caution notices call attention to methods and procedures which must be followed to avoid damage to
the equipment.
Notes:
Notes highlight procedures and contain information to assist the user in the understanding of the
information contained in this document
Warning
RADIO FREQUENCY INTERFERENCE
Most electronic equipment is influenced by Radio Frequency Interference (RFI). Caution should be
exercised with regard to the use of portable communications equipment around such equipment.
Signs should be posted in the vicinity of the equipment cautioning against the use of portable
communications equipment.
MAINTENANCE
Maintenance must be performed only by qualified personnel, otherwise personal injury or death, or
damage to the system may be caused.
Caution
HANDLING
Under no circumstances should the module housing be removed.
Associated Documents
Product Descriptions (PD) provide product specific information.
The Safety Manual contains the recommended safety requirements for the safety system design.
The PD8082B – Toolset Suite provides specific guidance on system configuration and application
generation.
The Operator and Maintenance Manual contains general guidelines on maintenance and diagnostic
procedures.
For technical support email: support@icstriplex.com
Issue 6 Sep 05 PD-T8290 6
Trusted
TM
Output Power Distribution Unit T8290
1. Description
The Wiring Diagram of the TrustedTM Output Power Distribution Unit is shown in Figure 2.
TM
Figure 2 Trusted
TM
The Trusted
reference (not 0V return) for the 24-120V dc range of Trusted
0V return is via the Trusted
Up to three output modules may be supported providing the total load does not exceed the maximum
rated capacity of the Unit.
Each supply stud is capable is of supplying the maximum rated capacity and can be used in single or
dual configuration as required. Dual configuration may be used where the supply is fed via blocking
diodes.
Output Power Distribution Unit is designed to distribute the +ve field loop power and 0V
TM
Output Power Distribution Unit – Wiring Diagram
TM
sourcing output modules. The output
Field Termination Assemble (FTA) or field terminal as appropriate.
2. Installation
The TrustedTM Output Power Distribution Unit may be mounted on TS32 or TS35 DIN rails.
3. Associated Cable Selection
The output cables detailed in PD-TC100 and PD-TC200 may be used to connect the Unit to the
associated output modules
4. Pinout Connections
Refer to Figure 2.
Issue 6 Sep 05 PD-T8290 7
Trusted
TM
Output Power Distribution Unit T8290
5. Specifications
Voltage Range
Supply Current
Supply Connection +ve
0V Reference Connector (not 0V return)
Power Output (3-off)
0V Reference Connector (3-off)
Conductor Clamping Range
Operating Temperature
Non-operating Temperature
Operating Humidity
Environmental Specifications
Dimensions
Width:
Depth: (including mounting rail)
Weight
Height:
22-120V dc
60A max
2-off M6 x 25mm studs
BLZ 2-part terminal
6-way AMP MATE-N-LOK
connector
5-way BLZ two-part terminal
0.5 to 2.5mm
2
-50C to 600C (230F to 1400F)
0
-25
C to 700C (-130F to 1580F)
5 to 95% RH
Refer to Document 552517
70mm (2.75ins)
90mm (3.54ins)
50mm (1.97ins)
106gms (0.23lbs)
Issue 6 Sep 05 PD-T8290 8
Trusted
TM
Output Power Distribution Unit T8290
This page intentionally blank
Issue 6 Sep 05 PD-T8290 9