SDS-8270
TM
Trusted
Industrial Control System
TrustedTM Fan Tray 24V dc Rack Mounted-T8270
FRONT PANEL
DESCRIPTION
The Trusted
cooling within a module rack of a Trusted
trays within a module rack is on a basis of one per module chassis.
The Trusted
mounted vertically at the rear of a 2U high chassis (the illustration above is a
view of the Fan Tray from the rear of the chassis). The chassis containing
the fans incorporates a baffle to prevent air drawn by the fans flowing
through the module chassis immediately above the Fan Tray. Air exhausted
by the fans into the rear of the System cabinet is drawn upwards and out of
the cabinet by roof-mounted fans – see SDS-8271
The Fan Tray is powered from dual 24V dc supplies arranged such that
the fans are supplied in pairs via 250mA anti-surge fuses. The 0V supply is
connected via a terminal block – see block diagram overleaf.
Each fan is capable of moving 69m
speed of 3100 rpm. Protection against overloading and reverse polarity is
provided electronically for each fan.
M
T
Fan Tray 24V dc Rack Mounted is designed to provide forced
TM
Fan Tray 24V dc Rack Mounted comprises four fans
M
T
System. The distribution of fan
3
/h when operating at a nominal rotor
FEATURES
Simple installation and
connection
Capable of moving 276m
24V dc operation
Low noise (32db per fan)
TÜV certified for safety,
Risk Class 5
3
/h
Issue 6 Jan 2006
SDS-8270
Trusted
TM
Industrial Control System
TrustedTM Fan Tray 24V dc Rack Mounted-T8270
BLOCK DIAGRAM
ELECTRICAL SPECIFICATION
Voltage Range
Fans
Fusing
Power Consumption
Air Flow (at 3100 rpm)
18 to 28V dc
4-off Papst Type 8414NG
Internal 250mA anti-surge
2 x 4W
3
276m
/h
MECHANICAL
SPECIFICATION
Dimensions (HxWxD):
88mm x 483mm x 267mm
(3.46ins x 19ins x
10.5ins)
Weight (fully populated)
1.8kg
(3.97lbs)
ENVIRONMENTAL
Operating Temperature:
-5°C to 60°C
(23°F to 140°F)
Operating Humidity:
5 to 95%, noncondensing
Vibration:
10 to 57Hz ±0.075mm
57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV
Radiated Fields
10V/m, 27MHz to
500MHz
Transients and Bursts
2kV, 2.5kHz for
t=60 seconds
ICS Triplex
Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit