Rockwell Automation T8013 User Manual

TrustedTM
PD-T8013
TM
Trusted
SOE and Process Historian
Introduction
The Sequence of Events (SOE) Collection program generates a time-stamped log of all faults, field trips, output actions etc. recorded by the 8000 Series System provides the user with the facility to log and record analogue variables. Both programs are supplied on a single disk, part No. T8013.
The programs enable the user to collect the appropriate data from the Controller via the TMR Communications Interface module. Communications between the Engineering Workstation and the System may be configured using the Serial or Ethernet ports.
. The Process Historian (PH) program
Note that SOE software build 6 or later is required for use with 32 character tags in Toolset build 3.51.
Features
Inherent Sequence of Events logging of all Boolean type input states
Time resolution to 1ms
User defined tag, description, state and display colours
Text based log file for import into other programs
Issue 16 April 2010 PD-T8013 1
Trusted
Issue Record
Issue
Number Date Revised by Technical CheckAuthorised by Modification
10 Dec 04 N Owens G Creech R Cockman
11 Sep 05 J W Clark Format
12 Aug 06 N Owens I Vince P Stock Compilation, use
13 Dec 06 N Owens I Vince P Stock Corrections
14 Sep 07 N Owens I Vince P Stock Comms setup
15 Nov 07 N Owens A Holgate P Stock SOE initial states
TM
SOE and Process Historian Package T8013
16 April 10 S. Blackett A Holgate P Stock Start-up: cable change
Issue 16 April 2010 PD-T8013 2
Trusted
TM
SOE and Process Historian Package T8013
This page is intentionally blank
Issue 16 April 2010 PD-T8013 3
Trusted
TM
SOE and Process Historian Package T8013
Table of Contents
1. Installation ................................................................................................................................. 8
2. Startup ....................................................................................................................................... 9
3. Collecting SOE Data ............................................................................................................... 10
3.1. SOE Communications Port Configuration .................................................................................11
3.2. SOE Symbol File Selection........................................................................................................12
3.3. SOE Target ID Selection............................................................................................................12
3.4. SOE Sort Mode..........................................................................................................................12
3.5. SOE Log File Selection..............................................................................................................12
3.6. SOE Collection Mode.................................................................................................................13
3.7. SOE Start Collecting ..................................................................................................................13
3.8. Additional SOE Features ...........................................................................................................14
3.8.1. Copy To Clipboard .....................................................................................................................14
3.8.2. Print............................................................................................................................................14
3.8.3. Save To File...............................................................................................................................14
3.9. SOE Example Display................................................................................................................14
3.10. Assigning variables for SOE ......................................................................................................16
3.10.1. Boolean SOE Variables .............................................................................................................16
3.10.2. Intermediate SOE Variables ......................................................................................................18
3.10.3. Analogue SOE Variables ...........................................................................................................19
4. Collecting Process Historian (PH) Data................................................................................ 21
4.1. Date Format...............................................................................................................................21
4.2. PH Communications Port Configuration ....................................................................................22
4.3. PH Symbol File Selection ..........................................................................................................22
4.4. PH Target ID Selection ..............................................................................................................22
4.5. PH Log File Selection ................................................................................................................23
4.6. PH Start Collecting.....................................................................................................................23
4.7. Additional PH Features ..............................................................................................................23
4.7.1. Auto Advance.............................................................................................................................23
4.7.2. Print............................................................................................................................................23
4.7.3. Auto Track..................................................................................................................................23
4.7.4. Zoom/Pan ..................................................................................................................................23
4.8. PH Example Display ..................................................................................................................24
4.9. Assigning variables for PH.........................................................................................................25
4.9.1. PH Connection...........................................................................................................................25
5. SOE and Initial States............................................................................................................. 27
Issue 16 April 2010 PD-T8013 4
Trusted
TM
SOE and Process Historian Package T8013
Figures
Figure 1 Fresh Installation Screen............................................................................................................8
Figure 2 Initial Display...............................................................................................................................9
Figure 3 Launcher Window.......................................................................................................................9
Figure 4 SOE Collector...........................................................................................................................10
Figure 5 Port Configuration Window.......................................................................................................11
Figure 6 SOE Display .............................................................................................................................14
Figure 7 Boolean Variable Setup............................................................................................................16
Figure 8 Boolean Extended Attributes ....................................................................................................17
Figure 9 Unattached variable connection ...............................................................................................17
Figure 10 Entering an SOE board ..........................................................................................................18
Figure 11 SOE Board Connection ..........................................................................................................18
Figure 12 Analogue Variable Setup........................................................................................................19
Figure 13 Analogue Extended Attributes ................................................................................................19
Figure 14 STATE I/O Connection board.................................................................................................20
Figure 15 STATE board connection .......................................................................................................20
Figure 16 Process Historian Collector ....................................................................................................21
Figure 17 Port Configuration Window.....................................................................................................22
Figure 18 PH Data Display .....................................................................................................................24
Figure 19 Analogue Output PH Tag .......................................................................................................25
Figure 20 Entering a prochist Board .......................................................................................................25
Figure 21 SOE Board Connection ..........................................................................................................26
Tab l es
Table 1 SOE Colour Specifiers...............................................................................................................15
Table 2 SOE State Definitions ................................................................................................................20
Issue 16 April 2010 PD-T8013 5
Trusted
TM
SOE and Process Historian Package T8013
Notice
The content of this document is confidential to ICS Triplex Technology Ltd. companies and their partners. It may not be given away, lent, resold, hired out or made available to a third party for any purpose without the written consent of ICS Triplex Technology Ltd.
This document contains proprietary information that is protected by copyright. All rights are reserved.
icrosoft, Windows, Windows 95, Windows NT, Windows 2000, and Windows XP are registered
M trademarks of Microsoft Corporation.
The information contained in this document is subject to change without notice. The reader should, in all cases, consult ICS Triplex Technology Ltd. to determine whether any such changes have been made. From time to time, amendments to this document will be made as necessary and will be distributed by ICS Triplex Technology Ltd.
Information in this documentation set may be subject to change without notice and does not represent a commitment on the part of ICS Triplex Technology Ltd.
The contents of this document, which may also include the loan of software tools, are subject to the confidentiality and other clause(s) within the Integrator Agreement and Software License Agreement.
No part of this documentation may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, for any purpose, without the express written permission of ICS Triplex Technology Ltd.
Disclaimer
The illustrations, figures, charts, and layout examples in this manual are intended solely to illustrate the text of this manual.
The user of, and those responsible for applying this equipment, must satisfy themselves as to the acceptability of each application and use of this equipment.
This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware or software, nor to provide for every possible contingency in connection with installation, operation, or maintenance. Features may be described herein which are present in all hardware or software systems. ICS Triplex Technology Ltd. assumes no obligation of notice to holders of this document with respect to changes subsequently made.
ICS Triplex Technology Ltd. makes no representation or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability or fitness for purpose shall apply.
Issue 16 April 2010 PD-T8013 6
Trusted
TM
SOE and Process Historian Package T8013
Revision and Updating Policy
All new and revised information pertinent to this document shall be issued by ICS Triplex Technology Ltd. and shall be incorporated into this document in accordance with the enclosed instructions. The change is to be recorded on the Amendment Record of this document.
Precautionary Information
WARNING
Warning notices call attention to the use of materials, processes, methods, procedures or limits which must be followed precisely to avoid personal injury or death.
CAUTION
Caution notices call attention to methods and procedures which must be followed to avoid damage to the equipment.
Notes:
Notes highlight procedures and contain information to assist the user in the understanding of the information contained in this document
Warning
RADIO FREQUENCY INTERFERENCE
Most electronic equipment is influenced by Radio Frequency Interference (RFI). Caution should be exercised with regard to the use of portable communications equipment around such equipment. Signs should be posted in the vicinity of the equipment cautioning against the use of portable communications equipment.
MAINTENANCE
Maintenance must be performed only by qualified personnel, otherwise personal injury or death, or damage to the system may be caused.
Caution
HANDLING
Under no circumstances should the module housing be removed.
Associated Documents
Product Descriptions (PD) provide product specific information.
The Safety Manual contains the recommended safety requirements for the safety system design.
The PD8082B – Toolset Suite provides specific guidance on system configuration and application generation.
The Operator and Maintenance Manual contains general guidelines on maintenance and diagnostic procedures.
For technical support email: support@icstriplex.com
Issue 16 April 2010 PD-T8013 7
Trusted
TM
SOE and Process Historian Package T8013
1. Installation
Insert the 8013 CD into the computer CD drive. If Autorun is enabled, the InstallShield wizard runs and
repares files for installation. Click Next on the introductory screen and read and accept the license
p agreement. The next screen allows entry of a user and company name, and chooses to install the icons in ‘All Users’ or your local profile.
Three choices are available, as shown in Figure 1. Selecting Typical will install the programs, help files and documentation, which is the recommended option.
Figure 1 Fresh Installation Screen
TM
The installation creates icons in the Trusted
On subsequently running the installation CD, the InstallShield allows the options of Modify (changing installation options), Repair (reinstalling the programs) or removing the programs.
directory and the desktop.
Issue 16 April 2010 PD-T8013 8
Trusted
TM
SOE and Process Historian Package T8013

2. Startup

Connect the Engineering Workstation to the TMR Communications Interface using the Communication
able TC-304-01-Xm0. Double clicking the ‘SOE and Process Historian’ application icon at the
C Engineering Workstation will initiate the screen display shown in Figure 2.
Figure 2 Initial Display
After a few seconds, the screen display shown above will be replaced with the SOE/PH ‘launcher’ window shown in Figure 3.
Figure 3 Launcher Window
Pressing the ‘SOE Collector’ button will initiate the display showing the SOE log. Similarly, pressing the ‘Process Historian’ button will initiate the PH log. Pressing the ‘Exit’ button will simply terminate the programs and shut down all SOE and PH displays.
An SOE or PH Collector window can only communicate with one controller. It is possible to initiate more than one SOE or PH display on a PC. However, each display will only communicate with one controller. A single instance of the SOE or PH program cannot collect data from multiple controllers.
Issue 16 April 2010 PD-T8013 9
Trusted
TM
SOE and Process Historian Package T8013

3. Collecting SOE Data

As previously stated, pressing the ‘SOE Collector’ button will initiate the SOE display shown in
Figure 4.
Figure 4 SOE Collector
To start collecting SOE data, the user must first implement a number of actions as detailed below:
1. Configure the SOE communications port.
2. Select the appropriate SOE symbol file
3. Select the SOE target ID
4. Select the sort mode (time or tag)
5. Select the SOE log file
6. Start collecting SOE data
Each action mentioned above is described in the following paragraphs.
Issue 16 April 2010 PD-T8013 10
Trusted
TM
SOE and Process Historian Package T8013

3.1. SOE Communications Port Configuration

M
The ports on the Trusted data collection using serial comms or via the Ethernet. The required method is chosen by first selecting the ‘Configure Port’ option from the ‘File’ menu.
Selecting serial ports COM 1 and 2 enable the selection of Baud rate and parity.
Selection of Ethernet permits the selection of the target system IP address and port number. In almost every case, the port number should be left at 2000.
Note that the Communications Interface must have a Modbus slave configured in the parameters for the module in the system configuration. The disconnection timeout must be set to 300 seconds to prevent the connection from being lost during data retrieval. In the Communications Interface Modbus Slave window, select a Modbus Slave and check ‘Use This Slave’. The defaults will work with the SOE collector. Refer to product description PD-8151B.
T
TMR Communications Interface module may be configured to allow SOE
Figure 5 Port Configuration Window
Issue 16 April 2010 PD-T8013 11
Trusted
TM
SOE and Process Historian Package T8013

3.2. SOE Symbol File Selection

Tag, true/false state information and description text is retrieved from database files produced by the IEC1131 TOOLSET as part of the program creation/compilation process. The Trusted contains memory run-time addresses and state information. The file that contains the bulk of the information is called ‘Appli.tst’ and is found in the same directory as the user’s application. For
xample, if the application is called ‘TFAT_1’, then the ‘Appli.tst’ file would be found in
e ‘C:\Trusted\Toolset\apl\TFAT_1’. Other files used by the SOE Collector include appli.dlo and appli.dco which contain the variable dictionaries. The application must be fully compiled to generate these files.
The symbol files are made available to the SOE Collector by initiating the ‘Select Symbol File’ option from the ‘File’ menu. Once the file has been loaded, the file path is displayed in the status banner at the bottom of the SOE Collector window. If the application is changed and recompiled, the SOE Collector will need to be loaded with the new copies of the files.
If the SOE collector is left running permanently as an event logger, it should be stopped whilst the application is compiled, otherwise it will hold some of the application files open. The buffers in the system will store the SOE events during this compilation.
TM
system only

3.3. SOE Target ID Selection

The Controller is allocated a Target, or Modbus Slave, ID, in the appropriate Modbus Slave configuration in the System Configuration Tool.
In the SOE Collector, the Target ID is selected using the ‘Set ID’ option, which may be found in the ‘Target’ menu.

3.4. SOE Sort Mode

Prior to starting the collection process, the user may select the order in which SOE data is presented.
The user may select ‘Sort By Time’, or ‘Sort By Tag’ using the appropriate button on the button bar or the menu options under ‘Sort’.
If ‘Sort By Time’ is selected, the SOE data is displayed in time order with the most recent event shown at the top of the display.
If ‘Sort By Tag’ is selected, the SOE data is displayed in alphabetical order. In addition, groups of events for the same tag are sorted in time order.

3.5. SOE Log File Selection

All SOE entries may optionally be logged to a log file held on the user’s Engineering Workstation. To enable a log file, the user must select the ‘Log File’ option which may be found in the ‘Logging’ Menu.
Entries are appended to the end of the file as they are collected. There is no sorting of tag information, even if ‘Sort By Tag’ is selected.
Issue 16 April 2010 PD-T8013 12
Trusted
TM
SOE and Process Historian Package T8013

3.6. SOE Collection Mode

The Communications Interface has a large buffer of events. It is possible to gather this buffer first until the collector has caught up with current events, but this can take a long time. Therefore there is an option under the Mode menu for choosing how much of this buffer is collected.
From Now Ignore all buffered events and only collect real time events
All Buffered Gather the entire buffer first before waiting for real time events
25% of Buffer Gather the last quarter of the buffer first
50% if Buffer Gather the last half of the buffer first
75% of Buffer Gather the last three-quarters of the buffer first

3.7. SOE Start Collecting

Once the procedures detailed above have been completed, the user may start the collection process. If any buffered events have been selected in 3.6, events currently buffered in the Trusted Communications Interface module will be collected and added to the SOE display. Once the SOE Collector has retrieved all buffered events, it will regularly poll for new events. All new events will be added to the display.
To initiate the collection of SOE data, the user must select the ‘Start Collecting’ option from the ‘File’ menu
The collection of SOE data is stopped by selecting the ‘Stop Collecting’ option which is also in the ‘File’ menu.
The initial collection process can take a long time before events are displayed on the screen. The program is parsing through events gathered before the end of the log, and it will display log entries once the date and time of events is past the end of the current log.
If the SOE or PH collector is running when the system application is compiled in the Toolset, then the dictionary files appli.tst, appli.dco and appli.dlo will be locked by the collector and the compilation will fail. If it is necessary to keep the collector running during a long compilation, copy the files to another location. Note that if the dictionary is changed in a way that affects event variables, the SOE collector will need to be stopped to load the new symbol files.
TM
TMR
Issue 16 April 2010 PD-T8013 13
Trusted
TM
SOE and Process Historian Package T8013

3.8. Additional SOE Features

Additional features of SOE include the following:
1. Copy to Clipboard
. Print
2
3. Save To File

3.8.1. Copy To Clipboard

It is possible to copy the contents of the current display to the Windows clipboard for pasting into other applications. This is achieved by using the ‘Copy To Clipboard’ option from the ‘File’ menu. The text copied may then be pasted into other Windows applications, e.g. Excel.

3.8.2. Print

The current display may be sent to a user selected printer using the ‘Print’ menu option from the ‘File’ menu.

3.8.3. Save To File

The current display may be saved as a text file using the ‘Save’ menu option from the ‘File’ menu.

3.9. SOE Example Display

An example of an SOE display is shown in Figure 6 below.
Figure 6 SOE Display
Issue 16 April 2010 PD-T8013 14
Trusted
Different colours may be used for the display point status. This is achieved by appending a colour specifier to the True/False strings declared for the point in the IEC1131 TOOLSET dictionary. For example, to make ‘TRUE’ appear in green, the true text would be set to ‘TRUE_g’ where ‘_g’ is the specifier for green.
Colour specifiers available to the user are detailed in Table 1 below.
TM
SOE and Process Historian Package T8013
_r = red
_g = green
_y = yellow
_b = blue
_w = white
_m = maroon
_l = lime
_p = purple
_o = olive
_s = silver
_t = teal
Table 1 SOE Colour Specifiers
Issue 16 April 2010 PD-T8013 15
Trusted
TM
SOE and Process Historian Package T8013

3.10. Assigning variables for SOE

The SOE collector provides the user with two options. The user may tag changes for a Boolean variable which only has two states. However, the collector will also allow the user to add “Channel state” changes. These channel state changes are described in the ANALOGUE SOE VARIABLES paragraph.
Note: All SOE variables must either be defined as INPUT or OUTPUT. Intermediate application
variables can be assigned for SOE collection using the SOE board, if they are configured as outputs in the dictionary as below.

3.10.1. Boolean SOE Variables

To select Boolean variables for collection by the SOE, the user must first open the Data Dictionary within the IEC1131 TOOLSET, then select the variable to be included in the SOE log. This will initiate the dialogue box shown in Figure 7.
Figure 7 Boolean Variable Setup
With the above dialogue box open, the user must name the variable by entering the appropriate data in the Name: window. If the variable is, for example, a field device driven by an output from the System, the user must enable the O dialogue box shown in Figure 8.
utput option, then select the Extended button. This will initiate the
Issue 16 April 2010 PD-T8013 16
Trusted
The user should enable the Boolean I/O Enable SOE logging option to provide the variable with SOE attributes. The user must select the OK button, then select OK to exit the next window.
This variable must be attached to an I/O board within the application program for the System. To select the appropriate board to which the variable is to be attached, the user must determine the module and channel driving the output. Double clicking the mouse on this output channel will provide the user with a list of unattached variables as shown in Figure 9.
TM
SOE and Process Historian Package T8013
Figure 8 Boolean Extended Attributes
Figure 9 Unattached variable connection
The variable may now be attached to this channel by selecting the Connect button.
Issue 16 April 2010 PD-T8013 17
Trusted
TM
SOE and Process Historian Package T8013

3.10.2. Intermediate SOE Variables

To select intermediate variables for collection by the SOE, the user must first declare an soe board from the board library within the IEC1131 TOOLSET I/O connection.
Double click on a free number in the I/O Connection. Select boards, find soe and select OK. This will enter an soe board in the I/O Connection table as shown in Figure 10 below.
Figure 10 Entering an SOE board
Once defined, the user enables soe logging by attaching the intermediate variable to a channel on this board.
Note: Intermediate soe variables have to be declared as outputs in the dictionary.
Double click on the appropriate channel of the soe board. This will display all the internal output variables available for soe collection as shown in Figure 11 below.
Figure 11 SOE Board Connection
The variable may now be attached to this channel by selecting the Connect button or by double clicking on the tagname.
Issue 16 April 2010 PD-T8013 18
Trusted
TM
SOE and Process Historian Package T8013

3.10.3. Analogue SOE Variables

The TrustedTM SOE collector also allows the user to enter analogue variables to the SOE log. This will allow the user to attach a channel state to an SOE tag. To do this the user must create the variable within the IEC1131 TOOLSET Data Dictionary. Creating or selecting this variable will initiate the dialogue box shown in Figure 12 below.
Figure 12 Analogue Variable Setup
With the above dialogue box open, the user must name the variable by entering the appropriate data in the Name and Comment boxes. For the purpose of this example, the variable is a process temperature actuator forming an input to the System. Input and Integer must be enabled, then the user must select the Extended button. This will initiate the window shown in Figure 13 below.
Figure 13 Analogue Extended Attributes
The user should enable the Boolean I/O Enable SOE logging option to provide the variable with SOE attributes. The user must select the OK button, then select OK to exit the next window.
Issue 16 April 2010 PD-T8013 19
Trusted
Unlike a Boolean SOE variable which may be attached to any I/O board within the application program, an analogue SOE variable must be attached to the STATE rack of a High Integrity I/O board as defined
n the application program and shown in Figure 14 below.
i
Double clicking the mouse on the selected channel will provide the user with a list of unattached variables as shown in Figure 15 below.
TM
SOE and Process Historian Package T8013
Figure 14 STATE I/O Connection board
Figure 15 STATE board connection
The variable may now be attached to the channel by selecting the Connect button. By default, each channel attached to the STATE rack of a High Integrity I/O board only has seven values. These states are defined in the SOE Collector as shown in Table 2 below.
0 Under Range
1 Low Low
2 Low
3 Normal
4 High
5 High High
6 Over Range
Table 2 SOE State Definitions
The SOE collector will display the string defined above for each state as changes occur.
Issue 16 April 2010 PD-T8013 20
Trusted
TM
SOE and Process Historian Package T8013

4. Collecting Process Historian (PH) Data

Pressing the ‘Process Historian’ button in Figure 3 will initiate the PH display shown in Figure 16 below.
Figure 16 Process Historian Collector
To start collecting PH data, the user must first implement a number of actions as detailed below:
1. Configure the PH communications port.
2. Select the appropriate PH symbol file
3. Select the PH target ID
4. Select the PH log file
5. Start collecting PH data
Each action mentioned above is described in the following paragraphs.

4.1. Date Format

Note that Process Historian will only recognise PC local date formats in the form month/day/year. In regions where the local date format is different, set the short date format to mm/dd/yyyy. This may be set in Control Panel | Regional and Language Options, Regional Options tab, Customize…, Date tab, Short date format. Type mm/dd/yyyy into the Short date format entry box. Click Apply.
Issue 16 April 2010 PD-T8013 21
Trusted
TM
SOE and Process Historian Package T8013

4.2. PH Communications Port Configuration

M
The ports on the Trusted data collection using serial comms or via the Ethernet. The required method is chosen by first selecting the ‘Configure Port’ option from the ‘File’ menu.
Selecting serial ports COM 1 and 2 enable the selection of Baud rate and parity.
Selection of Ethernet permits the selection of the target system IP address and port number. In almost every case, the port number should be left at 2000.
Note that the Communications Interface must have a Modbus slave configured in the parameters for the module in the system configuration. The , and that the disconnection timeout must be set to 300 seconds to prevent the connection from being lost during data retrieval. In the Communications Interface Modbus Slave window, select a Modbus Slave and check ‘Use This Slave’. The defaults will work with the SOE collector. Refer to product description PD-8151B.
T
TMR Communications Interface module may be configured to allow SOE
Figure 17 Port Configuration Window

4.3. PH Symbol File Selection

Tag, state information and description text is retrieved from database files produced by the IEC1131 TOOLSET as part of the program creation/compilation process. The Trusted run-time addresses and state information. The file that contains the bulk of the information is called ‘Appli.tst’ and is found in the same directory as the user’s application. For example, if the application is called ‘TFAT_1’, then the ‘Appli.tst’ file would be found in ‘C:\Trusted\Toolset\apl\TFAT_1’. The application must be fully compiled to generate this file.
The symbol file is made available to the PH Collector by initiating the ‘Select Symbol File’ option from the ‘File’ menu. Once the file has been loaded, the file path is displayed in the status banner at the bottom of the PH Collector window. If the application is changed and recompiled, the PH Collector will need to be loaded with the new copy of the appli.txt file.
TM
only contains memory

4.4. PH Target ID Selection

The Controller is allocated a Target, or Modbus Slave, ID, in the appropriate Modbus Slave configuration in the System Configuration Tool.
Issue 16 April 2010 PD-T8013 22
Trusted
In the PH Collector, the Target ID is selected using the ‘Set ID’ option, which may be found in the ‘Target’ menu.
TM
SOE and Process Historian Package T8013

4.5. PH Log File Selection

All PH entries may optionally be logged to a log file held on the user’s Engineering Workstation. To enable a log file, the user must select the ‘Log File’ option which may be found in the ‘Logging Menu’.
Entries are appended to the end of the file as they are collected.

4.6. PH Start Collecting

Once the procedures detailed above have been completed, the user may start the collection process. Any events currently buffered in the Trusted and added to the PH display. Once the PH Collector has retrieved all buffered events, it will regularly poll for new events. All new events will be added to the display.
To initiate the collection of PH data, the user must select the ‘Start Collecting’ option from the ‘File’ menu
The collection of PH data is stopped by selecting the ‘Stop Collecting’ option which is also in the ‘File’ menu.
If the SOE or PH collector is running when the system application is compiled in the Toolset, then the dictionary files appli.tst, appli.dco and appli.dlo will be locked by the collector and the compilation will fail. If it is necessary to keep the collector running during a long compilation, copy the files to another location. Note that if the dictionary is changed in a way that affects event variables, the SOE collector will need to be stopped to load the new symbol files.
M
T
TMR Communications Interface module will be collected

4.7. Additional PH Features

4.7.1. Auto Advance

It is possible to extend the data collected for each point in real time even though no new state information is reported by Trusted ‘Advance’ menu items. This option is useful if the data rate is very slow, but is irrelevant for rapid updates. It provides a guessed trend of where the collector expects the point to be.
TM
. Each point’s data set may be extended by selecting one of the

4.7.2. Print

The current display may be sent to a user selected printer using the ‘Print’ menu option from the ‘File’ menu.

4.7.3. Auto Track

Enabling this option forces the display to follow the most recent data point received. This option must be disabled if the user wishes to zoom/scroll around the current data.

4.7.4. Zoom/Pan

Pressing the ‘+’ or ‘-‘ keys zooms the display in or out respectively. Holding the right-hand mouse button pressed and dragging in the direction required ‘pans’ the display. Mouse-clicking on a point on the line provides a readout window of the value at that moment (this requires the mouse point to be precisely on the line). Left-mouse dragging a rectangle on the graph zooms the vertical axis to the height of the rectangle.
Issue 16 April 2010 PD-T8013 23
Trusted
TM
SOE and Process Historian Package T8013

4.8. PH Example Display

An example of a PH display is shown in Figure 18 below.
Figure 18 PH Data Display
The example shown displays a single channel from the set of all analogue channels available.
Note: The list box at the right of the display provides the names of the available tags.
Issue 16 April 2010 PD-T8013 24
Trusted
TM
SOE and Process Historian Package T8013

4.9. Assigning variables for PH

Process Historian deals with analogue tags only and is intended to compliment SOE. Tags must have the suffix ‘_PH’ at the end of the tagname and must be connected to a prochist board. A Modbus address is not necessary.

4.9.1. PH Connection

To configure a tag for connection to Process Historian it should be configured as an output. Figure 19 shows a tag created to connect to a prochist board. The tag may be a real or integer. There is no need to enter extended attributes. The tagname must end with _PH.
Figure 19 Analogue Output PH Tag
A prochist board must be declared within the IEC1131 TOOLSET I/O connection.
Double click on a free number in the I/O Connection. Select boards, find prochist and select OK. This will enter a prochist board in the I/O Connection table as shown in Figure 10 above.
Figure 20 Entering a prochist Board
Issue 16 April 2010 PD-T8013 25
Trusted
Once defined, the user enables process historian logging by attaching the variable created above to a channel on this board.
Double click on the appropriate channel of the prochist board. This will display all the unconnected output variables available for PH collection as shown in Figure 21 below.
TM
SOE and Process Historian Package T8013
Figure 21 SOE Board Connection
The variable may now be attached to this channel by selecting the Connect button or by double clicking on the tagname.
The prochist board has two parameters.
BANK Index number of the prochist board. Each prochist board should have a unique index.
DELTA Change required in each connected tag before a change is logged (i.e. event
hysteresis). This value may be in floating point.
Issue 16 April 2010 PD-T8013 26
Trusted
TM
SOE and Process Historian Package T8013

5. SOE and Initial States

The following should be noted when using SOE data collection by any method.
‘Native’ output modules (P8451,61,71 etc.) never record the initial state of an output as an SOE event.
Non-native output modules (e.g. Regent modules) record an initial state of TRUE as an SOE event.
All inputs supporting SOE will always record an event if the initial input state is TRUE.
No SOE is recorded if a variable is locked, either input or output.
At an MP handover, Regent outputs, Peer to Peer outputs, MP complex equipment definition
board TTMRP_2 and SOE board points that are TRUE at an MP handover will generate an SOE event.
Issue 16 April 2010 PD-T8013 27
Loading...