Application Note
Replacement of Power Supplies
These replacement supplies should be fitted completely before transferring duty from the old to the new supplies. Do not fit replacement supplies that partly share duty with existing supplies; nonlinearities in existing supplies may prove difficult to track in the power sharing circuits of replacement supplies, which could cause them to trip on overload.
Note that existing supplies may have their own circuit breakers/isolation switches, bridging diodes and power failure relays. These must be replicated in the new design. T824x series supplies will need circuit breakers. Bridging diodes are only necessary where linking dual redundant supplies into one feed, to protect against an output short in one supply. Each T8240 chassis may be fitted with a T8243 power port which provides failure relays for AC feed and DC output.
Issue Record
Issue Number
1 Feb 07 Nick Owens Ray Brown Pete Stock Initial Issue
Date Revised by Technical
Check
Authorised by Modification
Issue 1 Feb 07 AN-T80002 1
ICS Triplex technologies and services are available worldwide.
Regional Headquarters:
Americas:
4325 West Sam Houston
arkway North, Suite 100
P
Houston
Texas 77043-1219
USA
Tel: +1 713 353 2400
Fax: +1 713 353 2401
Europe, ME & Africa:
Hall Road
Maldon Essex
CM9 4LA
UK
Tel: +44 1621 854444
Fax: +44 1621 851531
Asia Pacific:
Unit 2/12 Keegan Street
O’Connor
Western Australia
Tel: +61 89 314 7787
Fax: +61 89 314 7786
www.icstriplex.com
For technical support email: support@icstriplex.com
Sales enquiries: sales@icstriplex.com
Technology Driven Customer Led
Loading...