Application Note
Termination of Class 1 Division 2 Outputs
Underwriters Laboratories Inc have confirmed that suitable non UL recognised termination resistors may be used in Trusted systems, configured for Class 1 Division 2 applications.
The value of terminating resistors should be sized to provide the minimum load for the type of output module; be capable of dissipating at least 2.5W and not have a surface temperature in excess of 50 degrees Centigrade above ambient temperature, when operating at maximum applied voltage.
For example, an 8451 requires a minimum load of 50mA, therefore a 680R +/- 5% resistor rated at
2.5W, mounted such that its maximum surface temperature does not exceed 50C above ambient, when operating at a field voltage of 32Vdc, will comply with the requirements of Class 1 Division 2.
All termination resistors must be mechanically secured into terminal blocks or similar and need the use of a tool to remove or disconnect them.
Issue Record
Issue Number
1 Jan 07 Pete Stock Ray Brown Pete Stock Initial Issue
Issue 1 Sep 06 AN-T80001 1
Date Revised by Technical
Check
Authorised by Modification
ICS Triplex technologies and services are available worldwide.
Regional Headquarters:
Americas:
4325 West Sam Houston
arkway North, Suite 100
P
Houston
Texas 77043-1219
USA
Tel: +1 713 353 2400
Fax: +1 713 353 2401
Europe, ME & Africa:
Hall Road
Maldon Essex
CM9 4LA
UK
Tel: +44 1621 854444
Fax: +44 1621 851531
Asia Pacific:
Unit 2/12 Keegan Street
O’Connor
Western Australia
Tel: +61 89 314 7787
Fax: +61 89 314 7786
www.icstriplex.com
For technical support email: support@icstriplex.com
Sales enquiries: sales@icstriplex.com
Technology Driven Customer Led
Loading...