Rockwell Automation T7454 User Manual

ICS Regent+Plus
®
PD-7018
AC Isolated Digital Output Module
110 VAC
(T7454)
Issue 1,
The AC isolated digital output module provides control of eight isolated user output loads. One type of module is available to interface to outputs powered from is VAC field power supplies. Each module's triplicated I/O Safetybus interface ensures that no Regent system failure can incorrectly apply power to an output, and that no failure in the module can affect the operation of the Regent system or other I/O modules in the system.
olated 110
March, 06
Module
Features
·
Eight isolated 110 VAC output circuits.
·
Hot-replaceable.
·
Automatic self-testing of triplicated I/O Safetybus circuits many simplex logic circuits.
·
2 amp output circuits.
·
Zero-cross load switching.
·
Individual front panel indicators on each module show active and fault, shutdown, blown fuse, and output on/off status (logic side).
·
2500 volt minimum electrical isolation between field and logic circuits.
·
TÜV certified, Risk Class 5, non-interfering.
Operation
A block diagram of a typical 110 VAC isolated digital output module is shown in Figure 1.
and
1
AC Isolated Digital Output Module
The processor modules send triplicated write data commands to the output module over the I/O Safetybus. The processors’ addressing data and data write commands are voted by the module (preventing I/O Safetybus failures upstream from the module from affecting module operation). The voted result is then passed to the I/O bus interface logic.
(T7454)
2
Fig
ure 1. Block Diagram of 110 VAC Isolated Digital Output Module.
The voted output data from the I/O bus interface logic is then used to drive the output circuits. Zero crossing turn-on TRIAC drivers are used to convert the logic level output drive signals to switch 110 VAC power to load devices.
When the output is logically turned on, the field device is energized, and when the output is logically turned off, the field device is de-energized.
Optical isolation between the module’s logic and fi provides logic-to-field isolation
— protecting the output module from field signal over voltages, transients, and other electrical disturbances. It also provides a safety barrier between the primary field voltages and user accessible circuits. Additionally each output is isolated from the other
Industrial Control Services
eld circuits
(T7454)
outputs, to operate load devices powered from isolated field power supplies.
Each output is individually fused to protect the circuits from short circuit conditions in output wiring and field devices.
AC Isolated Digital Output Module

Testing and Diagnostics

Each module’s voter circuits are periodically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module’s voter is able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module.
Each type of module has a unique identification code that is read by t which type of module is installed in each I/O chassis slot and how to address that module and its points specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error.
Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly.
Fuses are continually checked for continuity. the minimum load (see Specifications, page 12) must be connected to each output in order to detect a blown fuse.
he controller. This code lets the controller know
Field power and
PD-7018
Mar-06

Front Panel Indicators

The 110 VAC isolated digital output module is shown in Figure 2. The front panel contains the active and fault status indicators, shutdown indicator, and output status and blown fuse indicators for each output circuit.

Active and Fault Status Indicators

These green and red LEDs indicate the overall health module. During normal operation, the green ACTIVE indicator flashes at the controller’s scan rate. If a module fault is detected the red FAULT indicator turns on and the green indicator turns off.
3
of the
Note:
AC Isolated Digital Output Module
(T7454)

Shutdown Indicator

Upon loss of communications with the controller, output modules enter either a shutdown or hold fault mode. If the I/O assembly is set to shutdown, the red SHUTDOWN indicator will turn on when communications with the controller are lost. If the I/O assembly is set to hold, the SHUTDOW will always be off (see page 7, Fault Mode Jumper).
N indicator
When the module is installed in the I/O chassis or when logic
power (from the I/O power supply modules) is first applied to the module, it will be in the shutdown mode until the first output scan, regardless of the fault mode jumper settings. Also, removing two I/O transceiver modules, two I/O power supply modules, or two power legs will cause the module to be in the shutdown mode.

Output Status Indicators

The output status indicators are yellow LEDs, located on the logic side of the output. There are 8 output status indicators — one for each output. These indicators are lit when the output TRIAC is energized to turn on the load.

Blown Fuse Indicators

The red BLOWN FUSE indicators turn on when the associated output’s internal fuse opens. A blown fuse will also cause the module’s FAULT indicator to turn on.
The module must be connected to a load and field power must be present to detect a blown fuse. Refer to Maintenance, page 11
, for fuse replacement instructions.
4
Industrial Control Services
Loading...
+ 9 hidden pages