Rockwell Automation T7411 User Manual

ICS Regent+Plus
®
PD-7031
Monitored Digital Input Modules
24 VDC
(T7411)
Issue 1,
Monitored digital input modules provide input sensing for 16 field input devices. With a line monitor device installed at the field switch, monitored digital input switch status and field wiring open and short circuits. Input and line status are reported back to the controller for use in application program logic.
Features
modules detect input
March, 06
·
Sixteen input points.
·
Fault tolerant operation when connected in parallel with another module of the same type.
·
Hot-replaceable.
Complete, automatic testing of all input circuits.
Automatic line monitoring detects open and short field wiring faults.
·
Individual front panel indicators on each module show the module’s active/fault and power status, as well as input status and line fault status for each point.
·
2500 volt minimum electrical isolation between field and logic circuits.
·
TÜV certified, Risk Class 5.
The input module circuits are completely and automatically tested, providing a fail-safe interface for safety-critical inputs. Two or three monitored digital input modules can be connected in parallel to obtain fault tolerant input sensing. In these fault tolerant configurations, a failed module can be removed and replaced without interrupting the input signals.
1
Monitored Digital Input Modules
The module requires connection to a field power supply voltage, ranging from 15 to 80 VDC. This field power is internally regulated by the module to 24 VDC to power the field inputs — common in safety system applications.
(T7411)
providing safe, low-voltage inputs signals

Module Operation

A block diagram of a typical monitored digital input module is shown in Figure 1.
2
Figure 1. Block Diagram of the Monitored Digital Input Module.
A field power supply is connected to the monitored input module. The field power is internally regulated to 24 Vdc to power the input module’s field interface circuits. For each input ci dropping resistor to the input screw terminal which is wired to the field input switch. The other side of the field switch is
rcuit, the regulated power passes through an internal
Industrial Control Services
Monitored Digital Input Modules
(T7411)
wired back to the field power supply return. Optionally a line monitor device can be connected across the input switch in the field (as shown in Figure 1).
The input module monitors the voltage of the input circuit after the internal dropping resistor, comparing it to a reference voltage generated by the D/A converter inside the module. The comparator generates an on or off state depending on which voltage signal is greater than the other.
The field-side FPGA controls and monitors the reference voltage signal and reads the status of all 16 input comparators. This information is stored and sent through optical isolation to the logic-side FPGA. The logic-side FPGA interfaces the input data to the I/O Safetybus and drives the module’s front panel status LEDs.

Testing and Diagnostics

Standard I/O Module Testing

The processor modules send triplicated read data requests to the input module over the I/O Safetybus. The processors’ addressing data and data read requests are voted by the module (preventing I/O Safetybus failures upstream from the module from affecting its ability to be read). The voted result is then passed to the I/O bus interface logic.
After receiving the voted data read request, the I/O bus interface logic sends its input data to the module’s three bus drivers. Each of the three bus drivers is independently controlled — preventing failures in a single driver from being propagated into the rest of the system.
The bus drivers then move the data onto the I/O Safetybus which, in turn, passes it to the processors.
Each module’s voter circuits are periodically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module’s voter is able to outvote the incorrect data. A failure to return the correct majority-voted result t
o the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module.
PD-7031
Mar-06
3
Monitored Digital Input Modules
Each type of module has a unique identification code that is read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and address that module and its points specifically. The processor modules periodically check each module’s identification code to determine whether the type of module installed matches type of module loaded when the system was started. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate I/O module errors.
Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly.
(T7411)
indicated in the I/O configuration that was

Input Circuit Testing

The field interface circuits of the monitored input module are completely tested to detect stuck-on or stuck-off i
nput circuit faults and optionally identify input wiring open and short circuits. The automatic execution and evaluation of the input testing is controlled by the triplicated Regent processor modules.
During normal operations, the internal reference voltage is set to three levels and the comparator output is read. These three reference voltage levels represent thresholds that determine whether the input signal is on or off and if the field wiring is open circuit or short circuit. The logic-side FPGA dete
rmines input status and line fault status based on the comparator data for the three voltage levels. The FPGA data is provided to the I/O processors for application processing.
On a background basis, the I/O processors test the input circuit comparators and logic circuits for stuck-on and stuck
­off failure modes. During testing the D/A converter generates two reference voltages outside the normal operating range of the field input voltages to test that the comparator output can turn-off and turn-on. The
I/O processors read the resulting input status, line fault status, and reference voltage readings for the test cycle to determine if there are faults in the input circuits or the common data paths.
4
Industrial Control Services
Monitored Digital Input Modules
Note:
(T7411)
If the I/O processors detect a faulted input circuit, an I/O module fault is indicated at the processor modules and the Fault LED on the face of the input module is turned on.

Input Circuit Test Interval

The Regent processor modules schedule testing of the input circuits on a background basis. The test interval
for these circuits may range from a few seconds to several minutes, depending on the application program scan time and the size of the I/O configuration. The equation below can be used to estimate the test interval for monitored digital inputs.
TI = 172 * IOU
where:
TI
IOU
TSCAN
=
=
QTY
=
* TSCAN + 2
QTY
Test interval, seconds Quantity of I/O Units in the system (1 to 16) The application program scan time, seconds
For example, for a system with 8 I/O units and an application scan time of 60 milliseconds, the
TI = 172 * IOU TI = 84.6 seconds
* TSCAN + 2 = 172 * 8 * 0.060 + 2
QTY
test interval would be:
In this system, all of the monitored input modules would be tested for stuck-on and stuck-off faults approximately every 85 seconds. This test interval can be used in reliability and availability calculations to select the fault tolerant input configuration that meet the application’s safety requirements.
PD-7031
Mar-06
Due to I/O processor fault filtering algorithms, it may take up to four test intervals to report a failed input module as a permanent fault

Front Panel Indicators

Figure 2 shows the physical features of the monitored digital input module. The front panel of each module contains fault/active and power indicators for the module as well as input status indicators for each channel.

Active/Fault Status Indicator

This green and red LED pair indicates the overall health of the module and its field circuits. During normal operation the
5
Monitored Digital Input Modules
(T7411)
green ACTIVE indicator flashes at the
controller's scan rate. If a module fault occurs the red FAULT indicator turns on and the green indicator turns off.

Power Status Indicator

The POWER GOOD LED indicates the presence of field voltage at the module’s field power input terminals and the overall health of the module’s field power regulator circuits.

Input Status Indicators

Input status indicators show contact and line status for each point.
A yellow contact status indicator is turned on when the contact is closed or the line has shorted.
A red line status indicator is turned on when the field wiring is open circuit or short circuit. If line monitoring is not desired, this LED can be disabled (see Disable Fault LED, page 17 for more details).
6
Industrial Control Services
Monitored Digital Input Modules
(T7411)
PD-7031
Mar-06
Figure 2. Monitored Digital Input Module.
7