Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
12Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 13
Product Overview
Chapter 1
Overview
The E300™ Electronic Overload Relay is a microprocessor-based electronic
overload relay that is designed to help protect three-phase or single-phase AC
electric induction motors that are rated from 0.5…65,000 A. Its modular design,
communication options, diagnostic information, simplified wiring, and
integration into Logix makes the E300 the ideal overload for motor control
applications in an automation system. The E300 Electronic Overload Relay
provides flexibility, reduces engineering time, and maximizes uptime for
important motor starter applications.
Modular Design
You can select the specific options that you need for your motor starter
application. The E300 Electronic Overload Relay consists of three modules:
sensing, control, and communications. You can customize each of the three with
accessories to tailor the electronic motor overload for your application’s exact
needs.
You can select from multiple communication options that integrate with Logixbased control systems. Developers can easily add the E300 Electronic Overload
Relay to Logix-based control systems using Integrated Architecture tools like
Add-on Profiles, Add-on Instructions, and Faceplates.
• EtherNet/IP (DLR)
• DeviceNet
Rockwell Automation Publication 193-UM015D-EN-P - February 201513
Page 14
Chapter 1 Product Overview
Diagnostic Information
The E300 Electronic Overload Relay provides a wide variety of diagnostic
information to monitor motor performance, proactively alert you to possible
motor issues, or identify the reason for an unplanned shutdown. Information
includes:
• Voltage, Current, and Energy
• Tri p / War ning Hi sto ri es
• % Thermal Capacity Utilization
• Time to Trip
• Time to Reset
• Operational Hours
• Number of Starts
• Tri p S naps ho t
Simplified Wiring
The E300 Electronic Overload Relay provides an easy means to mount to both
IEC and NEMA Allen-Bradley contactors. A contactor coil adapter is available
for the 100-C contactor, which allows the you to create a functional motor
starter with only two control wires.
14Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 15
Product Overview Chapter 1
193 - ESM - VIG - 30A - C23
592
Module Type
ESM Sensing Module
Sensing Module Type
VIG Current, Ground Fault Current,
Voltage, and Power
IG Current and Ground Fault Current
ICurrent
Sensing Module Mounting Style
C23 Mounts to 100-C09…-C23 Contactor
C55 Mounts to 100-C30…-C55 Contactor
C97 Mounts to 100-C60…-C97 Contactor
D180 Mounts to 100-D115…-D180 Contactor
S2Mounts to Bulletin 500 NEMA Size 0-2 Contactor
S3Mounts to Bulletin 500 NEMA Size 3 Contactor
S4Mounts to Bulletin 500 NEMA Size 4 Contactor
TDIN Rail / Panel Mount with Power Terminals
E3TReplacement DIN Rail / Panel Mount with Power Terminals for an E3 Plus Panel Mount Adapter
PDIN Rail / Panel Mount with Pass-thru Power Conductors
CTDIN Rail / Panel Mount with Pass-thru Power Conductors (used with External CTs)
SCS Starter Control Station
SDS Starter Diagnostic Station
Bulletin Number
193 IEC Overload Relay
193 - EXP - PS - AC
Module Type
EXP Expansion Module
Func tion Type
PS Expansion Bus Power Supply
Bulletin Number
193 IEC Overload Relay
Supply Voltage
AC 110-240V AC, 50/60Hz control voltage
DC 24V DC control voltage
Digital Expansion Module
Analog Expansion Module
Operator Station
Power Supply
16Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 17
Product Overview Chapter 1
Module Description
The E300 Electronic Overload Relay is comprised of three modules. All three
modules are required to make a functional overload relay.
• Sensing Module
• Control Module
• Communication Module
Sensing Module
Figure 1 - Sensing Module
The sensing module electronically samples data about the current, voltage, power,
and energy that are consumed by the electric motor internal to the module. You
can choose from one of three varieties of the sensing modules depending on the
motor diagnostic information that is needed for the motor protection
application:
• Current Sensing
• Current and Ground Fault Current Sensing
• Current, Ground Fault Current, Voltage, and Power Sensing
The current ranges for each of three varieties of sensing module are as follows:
• 0.5…30 A
• 6…60 A
• 10…100 A
• 20…200 A
You can choose how the sensing module mechanically mounts inside the
electrical enclosure. The following mounting mechanisms are available for the
sensing module.
• Mount to the load side of an Allen-Bradley Bulletin 100 IEC Contactor
• Mount to the load side of an Allen-Bradley Bulletin 500 NEMA
Contactor
• DIN Rail / Panel Mount with power terminals
• Replacement DIN Rail / Panel Mount with power terminals for an
Allen-Bradley E3 Plus panel mount adapter
• DIN Rail / Panel Mount with pass-thru power conductors
Rockwell Automation Publication 193-UM015D-EN-P - February 201517
Page 18
Chapter 1 Product Overview
Control Module
Figure 2 - Control Module
The control module is the heart of the E300 Electronic Overload Relay and can
attach to any sensing module. The control module performs all protection and
motor control algorithms and contains the native I/O for the system. The control
module has two varieties:
• I/O only
• I/O and protection (PTC and External Ground Fault Current Sensing)
The control module is offered in three control voltages:
• 110…120V AC, 50/60Hz
• 220…240V AC, 50/60Hz
• 24V DC
External control voltage is required to power the E300 Electronic Overload Relay
and activate the digital inputs.
Communication Module
Figure 3 - Communication Module
The communication module allows the E300 Electronic Overload Relay to be
integrated into an automation system, and it can attach to any control module.
All communication modules allow you to set the node address with rotary turn
18Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 19
Product Overview Chapter 1
dials, and it provides diagnostic status indicators to provide system status at the
panel. The E300 Electronic Overload Relay supports two network protocols:
• EtherNet/IP
• DeviceNet
The E300 EtherNet/IP Communication Module has two RJ45 connectors that
function as a switch. You can daisy chain multiple E300 Electronic Overload
Relays with Ethernet cable, and the module supports a Device Level Ring (DLR).
Optional Add-On Modules
Optional Expansion I/O
The E300 Electronic Overload Relay allows you to add more digital and analog
I/O to the system via the E300 Electronic Overload Relay Expansion Bus if the
native I/O count is not sufficient for the application on the base relay. You can
add any combination of up to four Digital I/O Expansion Modules that have four
inputs (120V AC, 240V AC, or 24V DC) and two relay outputs.
You can also add up to four Analog I/O Expansion Modules, which have three
independent universal analog inputs and one isolated analog output. The Analog
I/O Expansion Modules require Control Module firmware v3.000 or higher. The
independent universal analog inputs can accept the following signals:
• 4…20 mA
• 0…20 mA
• 0…10V DC
• 1…5V DC
• 0…5V DC
• RTD Sensors (Pt 385, Pt 3916, Cu 426, Ni 618, Ni 672, and NiFe 518)
• Resistance (150 , 750 , 3000 , and 6000 )
The isolated analog output can be programmed to reference a traditional analog
signal (4…20 mA, 0…20 mA, 0…10V DC, 1…5V, or 0…10V) to represent the
following diagnostic values:
• Average %FLA
• %TCU
• Ground Fault Current
• Current Imbalance
• Average L-L Voltage
• Voltage Imbalance
• To ta l kW
• To ta l kVA R
• To ta l kVA
• To ta l P ow er Fa c tor
• User-defined Value
Rockwell Automation Publication 193-UM015D-EN-P - February 201519
Page 20
Chapter 1 Product Overview
Control StationDiagnostic Station
Optional Operator Station
Figure 4 - Operator Stations
Power LED
Trip / Warn LED
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Escape
Up
Select
ESC
SELECT
0
RESET
Enter
Down
Stop
LOCAL
REMOTE
Reset
Power LED
Trip / Warn LED
0
RESET
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Stop
LOCAL
REMOTE
Reset
The E300 Electronic Overload Relay offers you the capability to add one
operator interface to the Expansion Bus. You can choose between two types of
operator stations: Control Station or a Diagnostic Station. Both types of operator
stations mount into a standard 22 mm push button knockout, and they provide
diagnostic status indicators that allow you to view the status of the E300
Electronic Overload Relay from the outside of an electrical enclosure. Both
operator stations provide push buttons that can be used for motor control logic,
and they both can be used to upload and download parameter configuration data
from the base relay.
The Diagnostic Station contains a display and navigation buttons that allows you
to view and edit parameters in the base relay. The Diagnostic Station requires
Control Module firmware v3.000 or higher.
Optional Expansion Bus Power Supply
Figure 5 - Expansion Bus Power Supply
The E300 Electronic Overload Relay expansion bus provides enough current to
operate a system that has (1) Digital Expansion Module and (1) Operator
Station. An E300 Electronic Overload Relay system that contains more
expansion modules needs supplemental current for the Expansion Bus. The E300
Electronic Overload Relay offers you two types of Expansion Bus Power
Supplies: AC (110…240V AC, 50/60 Hz) and DC (24V DC). One Expansion
20Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 21
Product Overview Chapter 1
Bus Power Supply supplies enough current for a fully loaded E300 Electronic
Overload Relay Expansion Bus (four Digital Expansion Modules, four Analog
Expansion Modules, and one Operator Station). You can use either Expansion
Bus Power Supply with any combination of Digital and Analog Expansion
Modules.
Protection Features
Standard Current-Based Protection
All versions of the E300 Electronic Overload Relay provide the following motor
protection functions:
• Thermal Overload (51)
• Phase Loss
• Current Imbalance (46)
• Undercurrent – load loss (37)
• Overcurrent – load jam (48)
• Overcurrent – load stall
• Start Inhibit (66)
Ground Fault Current-based Protection
The E300 Electronic Overload Relay sensing modules and control modules with
a ground fault current option provides the following motor protection function:
• Ground Fault – zero sequence method (50N)
Voltage- and Power-based Protection
The E300 Electronic Overload Relay sensing modules with voltage sensing
provides the following motor protection functions:
• Undervoltage (27)
• Overvoltage (59)
• Phase Reversal (47) – voltage-based
• Over and Under Frequency (81) – voltage-based
• Voltage Imbalance (46)
• Over and Under Power (37)
• Over and Under Leading/Lagging Power Factor (55)
• Over and Under Reactive Power Generated
• Over and Under Reactive Power Consumed
• Over and Under Apparent Power
Rockwell Automation Publication 193-UM015D-EN-P - February 201521
Page 22
Chapter 1 Product Overview
Applications:
The E300 Electronic Overload Relay can be used with the following across the
line starter applications:
• Non-reversing starter
• Reversing starter
• Wye (Star) / Delta starter
• Two -s pe ed m ot or s
• Low and medium voltage with two or three potential transformers
• With or without Phase current transformers
• With or without zero-sequence core balanced current transformer
22Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 23
Installation and Wiring
Chapter 2
Introduction
Receiving
Unpacking/Inspecting
Storing
This chapter provides instructions for receiving, unpacking, inspecting, and
storing the E300™ Electronic Overload Relay. Assembly, installation, and wiring
instructions for common applications are also included in this chapter.
It is your responsibility to thoroughly inspect the equipment before accepting the
shipment from the freight company. Check the item(s) received against the
purchase order. If any items are damaged, it is your responsibility not to accept
delivery until the freight agent has noted the damage on the freight bill. If any
concealed damage is found during unpacking, it is again your responsibility to
notify the freight agent. The shipping container must be left intact and the
freight agent should be requested to make a visual inspection of the equipment.
Remove all packing material from around the E300 Electronic Overload Relay.
After unpacking, check the item’s nameplate catalog number against the purchase
order.
The E300 Electronic Overload Relay should remain in its shipping container
before installation. If you will not use the equipment immediately, you must store
it according to the following instructions to maintain warranty coverage:
• Store in a clean, dry location.
• Store within an ambient temperature range
of -40…+85 °C (-40…+185 °F).
• Store within a relative humidity range of 0…95%, non-condensing.
• Do not store where the device could be exposed to a corrosive atmosphere.
• Do not store in a construction area.
Rockwell Automation Publication 193-UM015D-EN-P - February 201523
Page 24
Chapter 2 Installation and Wiring
General Precautions
If the E300 Electronic Overload Relay is being deployed in an environment with
an ambient temperature greater than 30 °C (86 °F), please see the Environmental
Specifications on page 456 for the appropriate temperature derating. In addition
to the specific precautions listed throughout this manual, the following general
statements must be observed.
ATT EN TI ON : The E300 Electronic Overload Relay contains electrostatic
discharge (ESD) sensitive parts and assemblies. Status control precautions are
required when installing, testing, servicing, or repairing this assembly.
Component damage may result if ESD control procedures are not followed. If
you are not familiar with static control procedures, see Allen-Bradley
publication 8000-SB001_-en-p, “Guarding Against Electrostatic Damage”, or
any other applicable ESD protection handbook.
ATT EN TI ON : An incorrectly applied or installed E300 Electronic Overload Relay
can result in damage to the components or reduction in product life. Wiring or
application errors (for example, incorrectly calculating the FLA setting,
supplying incorrect or inadequate supply voltage, connecting an external
supply voltage to the thermistor terminals, or operating or storing in excessive
ambient temperatures) may result in malfunction of the E300 Electronic
Overload Relay.
Base Relay Assembly
ATT EN TI ON : Only personnel familiar with the E300 Electronic Overload Relay
and associated machinery should plan to install, start up, and maintain the
system. Failure to comply may result in personal injury or equipment damage.
ATT EN TI ON : The purpose of this user manual is to serve as a guide for proper
installation. The National Electrical Code (NEC) and any other governing
regional or local code overrules this information. Rockwell Automation cannot
assume responsibility for the compliance or proper installation of the E300
Electronic Overload Relay or associated equipment. A hazard of personal injury
and/or equipment damage exists if codes are ignored during installation.
ATT EN TI ON : The earth ground terminal of the E300 Electronic Overload Relay
shall be connected to a solid earth ground via a low-impedance connection.
The following section illustrates the E300 Electronic Overload Relay base relay
assembly instructions.
24Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 25
Installation and Wiring Chapter 2
Control Module to Sensing
Module Assembly
1
You can connect any E300 Control Module to any E300 Sensing Module. The
following illustrations show the steps that are required to make this connection.
Figure 6 - Control Module to Sensing Module Assembly
2
3
Rockwell Automation Publication 193-UM015D-EN-P - February 201525
Page 26
Chapter 2 Installation and Wiring
1
3
2
Communication Module to
Control Module Assembly
You can connect any E300 Communication Module to any E300 Control
Module. The illustrations below show the steps required to make this
connection.
Figure 7 - Communication Module to Control Module Assembly
26Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 27
Installation and Wiring Chapter 2
Note: If the expansion bus does not have an operator station, then the
last expansion module number must be set to terminated.
Color
Status LED
O
Blinking Green
No power applied
Description
Module OK with no connection
GreenModule OK and active
RedError Detected
Digital Module Number Selector
Number
D1 - D4
D1T - D4T
Module number
Description
Module number with
expansion bus terminating
resistor applied
Analog Module Number Selector
Number
A1 - A4
A1T - A4T
Module number
Description
Module number with
expansion bus terminating
resistor applied
Panel Mount
Hole
DIN Rail Mount
Removable I/O Terminals
Expansion Bus In
Expansion Bus Out
Panel Mount Hole
D1
D1T
D2T
D3T
D4T
D2
D3
D4
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Stop
Reset
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Stop
Up
Down
Reset
Escape
Power LED
Trip / Warn LED
Power LED
Trip / Warn LED
Enter
Select
0
RESET
LOCAL
REMOTE
0
RESET
SELECT
ESC
REMOTE
LOCAL
Control StationDiagnostic Station
Expansion Bus Peripherals
The E300 Electronic Overload Relay offers a range of Expansion Digital and
Analog I/O modules that simply connect to the E300 Electronic Overload
Relay’s Expansion Bus.
Figure 8 - Expansion Bus Peripherals
You can also add one of the two available operator stations to the end of the
Expansion Bus.
Figure 9 - Expansion Operator Stations
The following illustrations show how to mount and connect the E300 Electronic
Overload Relay expansion bus I/O modules, expansion power supplies, and
operator stations.
Rockwell Automation Publication 193-UM015D-EN-P - February 201527
Page 28
Chapter 2 Installation and Wiring
1
2
Click
2
1
1.7 N.m
(15 lb-in)
0
R
E
SE
T
S
E
LECT
ES
C
REMO
TE
LOC
AL
800F-AW2
3
22 mm
Expansion Bus Digital and
Analog I/O Modules and
Power Supply Installation
Figure 10 - Expansion Bus Digital and Analog I/O Modules and Power Supply
Expansion Bus Operator
Figure 11 - Expansion Bus Operator Station
Station Installation
Expansion Bus Network
Installation
28Rockwell Automation Publication 193-UM015D-EN-P - February 2015
The E300 Electronic Overload Relay supports up to (4) Expansion Digital I/O
modules, (4) Expansion Analog I/O modules, and (1) Operation Station. The
E300 Base Relay can supply enough power for (1) Expansion Digital I/O module
and (1) Operator Station. Any other combination of E300
Expansion Bus
Page 29
Installation and Wiring Chapter 2
0
RESET
SELECT
ESC
REMOTE
LOCAL
Click
1
2
peripherals requires an Expansion Bus Power Supply, which connects as the first
module on the Expansion Bus.
Set the module number dial of the Expansion Digital Module to a unique digital
module number (D1-D4). If the Expansion Digital Module is the last device on
the Expansion Bus, set the module number to the value that enables the internal
terminating resistor (D1T-D4T). A power cycle is required when changes are
made to the module number dial.
Set the module number dial of the Expansion Analog Module to a unique analog
module number (A1-A4). If the Expansion Analog Module is the last device on
the Expansion Bus, set the module number to the value that enables the internal
terminating resistor (A1T-A4T). A power cycle is required when changes are
made to the module number dial.
Connect the E300 Base Relay to the Expansion Module’s Input Port using the
supplied Expansion Bus cable. Add the next Expansion Module by connecting
the supplied Expansion Bus cable to the Output Port of the previous Expansion
Module and into the Input Port of the additional Expansion Module. The
Operator Station is the last device on the E300 Expansion Bus; it only has an
Input Port with an internal Expansion Bus terminating resistor.
If the user-supplied Expansion Bus cable is not long enough for the installation,
1-meter (Cat. No. 193-EXP-CBL-1M) and 3-meter (Cat. No.
193-EXP-CBL-3M) Expansion Bus cables are available as accessories. The E300
expansion bus can support a maximum distance of 5 meters (16 ft.).
Figure 12 - Expansion Bus Network Installation
Rockwell Automation Publication 193-UM015D-EN-P - February 201529
Page 30
Chapter 2 Installation and Wiring
Starter Assembly
5 - 7 lb-in
IN1
The following illustrations show how to assemble an E300 Electronic Overload
Relay as a motor starter with an Allen-Bradley Bulletin 100-C contactor.
100-C09…-C55 Starter Assembly Installation
The starter assembly installation instructions are for use with E300 Sensing
Module catalog numbers 193-ESM-___-___-C23 and 193-ESM-___-___-C55
Figure 28 - E300 Control Module Terminal Designations
38Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 39
Table 2 - E300 Control Module Wire Size and Torque Specifications
R24R23
RELAY 2RELAY 1
R14R13
IN3
IN2
Additional Inputs for 193-EIO-63-_ _ _
IN0
IN1
A2
PE
A1A1
A1
R03
R04
A2
IN5
IN4
(+)
(-)
RELAY 0
S2S1
RELAY 1
R14R13
IN3
IN2
IN0
IN1
A2
A1A1
A1
R03
R04
A2
IT2
IT1
(+)
(-)
RELAY 0
193-EIOGP-_ _-_ _ _193-EIO-_ _-_ _ _
PE
Ground
Fault
PTC
Additional Inputs for 193-EIOGP-42-_ _ _
+
t
Cat. No.
Wire TypeConductor Torque
193-EIO-_ _-_ _ _
193-EIOGP-_ _-_ _ _
24...12 AWG
4lb-in
24...16 AWG
4 lb-in
0.25…2.5 mm
0.45 N•m
0.5...0.75 mm
0.45 N•m
0.2...2.5 mm
0.45 N•m
0.2...1.5 mm
0.45 N•m
2
2
2
2
Stranded/Solid [AWG]
Flexible-Stranded with Ferrule
Metric
Coarse-Stranded/Solid Metric
Single
Multiple
(stranded only)
Single
Multiple
Single
Multiple
Figure 29 - Control Module Wiring
Installation and Wiring Chapter 2
Rockwell Automation Publication 193-UM015D-EN-P - February 201539
Page 40
Chapter 2 Installation and Wiring
IN0 IN1 INC
IN2 IN3
RS2
R04 R14 RC3
Expansion Digital Module
Figure 30 - E300 Expansion Digital Module Terminal Designations
Table 3 - E300 Expansion Digital Module Wire Size and Torque Specifications
Wire TypeConductor Torque
Single
Stranded/Solid [AWG]
Multiple
(stranded only)
Single
Flexible-Stranded with Ferrule Metric
Multiple
Single
Coarse-Stranded/Solid Metric
Multiple
Cat. No.
193-EXP-DIO-42-_ _ _
24...12 AWG
5 lb-in
24...16 AWG
5 lb-in
0.25…2.5 mm
0.55 N•m
0.5...0.75 mm
0.55 N•m
0.2...2.5 mm
0.55 N•m
0.2...1.5 mm
0.55 N•m
2
2
2
2
40Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 41
Figure 31 - E300 Expansion Digital Module Wiring Diagram
R04R14RC3
IN0INCIN1IN2IN3
Source
+
-
IN1+ IN1- RS1
IN2+ IN2- RS2
OUT+OUT-
IN0+ IN0- RS0
Expansion Analog Module
Installation and Wiring Chapter 2
Figure 32 - E300 Expansion Analog Module Terminal Designations
Rockwell Automation Publication 193-UM015D-EN-P - February 201541
Page 42
Chapter 2 Installation and Wiring
Analog Current InputAnalog Voltage Input
24V DC
Power
Supply
INx+
IN
x
-
+
-
Current
Input
Device
INx+
-
V
+V
INx-
Analog Voltage or Current Output
+
Out
-
Out+
Device
-
2 Wire RTD/Resistance
INx+
INx-
INx-
3 Wire RTD
INx+
RS
x
Table 4 - E300 Expansion Analog Module Wire Size and Torque Specifications
Wire TypeConductor Torque
Single
Stranded/Solid [AWG]
Flexible-Stranded with Ferrule Metric
Coarse-Stranded/Solid Metric
Multiple
(stranded only)
Single
Multiple
Single
Multiple
Figure 33 - E300 Expansion Analog I/O Modules 193-EXP-AIO-__
Cat. No.
193-EXP-AIO-31
24...12 AWG
5 lb-in
24...16 AWG
5 lb-in
0.25…2.5 mm
0.55 N•m
0.5...0.75 mm
0.55 N•m
0.2...2.5 mm
0.55 N•m
0.2...1.5 mm
0.55 N•m
2
2
2
2
42Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 43
Expansion Power Supply
A1 A2
Figure 34 - E300 Expansion Power Supply Terminal Designations
Installation and Wiring Chapter 2
Table 5 - E300 Expansion Power Supply Wire Size and Torque Specifications
Wire TypeConductor Torque
Single
Stranded/Solid [AWG]
Multiple
(stranded only)
Single
Flexible-Stranded with Ferrule Metric
Multiple
(stranded only)
Single
Coarse-Stranded/Solid Metric
Multiple
(stranded only)
Cat. No.
193-EXP-PS-_ _
24...12 AWG
5 lb-in
24...16 AWG
5 lb-in
0.25…2.5 mm
0.55 N•m
0.5...0.75 mm
0.55 N•m
0.2...2.5 mm
0.55 N•m
0.2...1.5 mm
0.55 N•m
2
2
2
2
Rockwell Automation Publication 193-UM015D-EN-P - February 201543
Page 44
Chapter 2 Installation and Wiring
A1A2
Source
+
-
Figure 35 - E300 Expansion Power Supply Wiring Diagram
Grounding
Short-Circuit Ratings
The following grounding recommendations are provided to help ensure EMC
requirements during installation
.
• The earth ground terminal of the E300 Electronic Overload Relay shall be
connected to a solid earth ground via a low-impedance connection.
• Wire the green shield wire of the Cat. No. 193-ECM-ETR into the earth
ground terminal of the E300 control module.
• Installations employing an external ground fault sensor shall ground the
cable shield at the sensor with no connection made at the E300 Electronic
Overload Relay.
• The PTC thermistor cable shield shall be grounded at the E300 Electronic
Overload Relay with no connection made at the opposite end.
The E300 Electronic Overload Relay is suitable for use on circuits capable of
delivering not more than the RMS symmetrical amperes listed in the following
tables.
Table 6 - Standard Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1
Overload Relay with Sensing Module Cat. No.Max. Available Fault Current [A] Maximum Voltage [V]
193-ESM-___-30A-C23
193-ESM-___-30A-C55
193-ESM-___-30A-E3T
193-ESM-___-30A-P
193-ESM-___-30A-T
193-ESM-VIG-30A-CT
592-ESM-___-30A-S2
193-ESM-___-60A-C55
193-ESM-___-60A-E3T
193-ESM-___-60A-P
193-ESM-___-60A-T
592-ESM-___-60A-S2
193-ESM-___-100A-C97
193-ESM-___-100A-E3T
193-ESM-___-100A-T
592-ESM-___-100A-S3
5,000600
10,000600
44Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 45
Table 7 - Short Circuit Ratings per EN60947-4-1
Installation and Wiring Chapter 2
Overload Relay with
Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C55,
193-ESM-___-60A-C55
193-ESM-___-100A-C97
Overload Relay with Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C55
193-ESM-___-30A-E3T
193-ESM-___-30A-P
193-ESM-___-30A-T
193-ESM-VIG-30A-CT
592-ESM-___-30A-S2
193-ESM-___-60A-C55
193-ESM-___-60A-E3T
193-ESM-___-60A-P
193-ESM-___-60A-T
592-ESM-___-60A-S2
193-ESM-___-100A-C97
193-ESM-___-100A-E3T
193-ESM-___-100A-T
592-ESM-___-100A-S3
Prospective Short-
Circuit Current, Ir [A]
3,000100,000690
5,000100,000690
Conditional Short-Circuit
Current, Iq [A]
Table 8 - High Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul.
100-C and 100-D IEC contactors that are protected by fuses
Contactor Cat. No.Max. S tarter FLC [A]
100-C099
100-C121220
100-C161630
100-C232330
100-C303050
100-C373750
100-C434370
100-C555580
100-C7272100
100-C8585150
100-C9797200
Max. Available Fault
Current [A]
100,000600
Max. Voltage [V]Class C or JJ fuse [A]
Maximum Voltage [V]
20
Rockwell Automation Publication 193-UM015D-EN-P - February 201545
Page 46
Chapter 2 Installation and Wiring
Table 9 - Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul. 100-C IEC
contactors that are protected by Bul. 140U-D circuit breakers
Overload Relay with
Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C23
193-ESM-___-30A-C23
Contactor Cat. No.Max. Starter FLC[A]
100-C099
100-C1212
100-C1616
100-C2323
100-C099
100-C1212
100-C1616
100-C2323
100-C099
100-C1212
100-C1616
100-C2323
Table 10 - High Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with
Bul. 500 line NEMA contactors that are protected by fuses
Overload Relay with Sensing Module
Cat. No.
592-ESM-___-30A-S2009
592-ESM-___-30A-S2018
592-ESM-___-30A-S2127
592-ESM-___-60A-S2245
592-ESM-___-100A-S3390
Contactor SizeMax. Starter FLC [A]
Max. Available Fault
Current [A]
65,000480Y/277VC30 (30 A)
35,000600Y/347VC30 (30 A)
5,000600Y/347VC30 (30 A)
Max. Available Fault
Current [A]
100,000
Max. Voltage [V]
Max. Voltage
[V]
600—20
2403030
6003030
24060100
6003050
240100200
60060100
240200350
600100200
Max. Circuit Breaker
Cat. No. 140U-D6D3-
Max. UL Fuse [A]
RJ
Fuse Coordination
The following tables list Type I and Type II Fuse Coordination when used with
Bulletin 100-C and 100-D and Bulletin 500 NEMA Size 00… 2 Contactors.
ATT EN TI ON : Select the motor branch circuit protection that complies with the
NEC and any other governing regional or local codes.
46Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 47
Installation and Wiring Chapter 2
Table 11 - Type 1 and Type II fuse coordination with Bul. 100-C and 100-D contactors per
EN60947-4-1
Overload Relay with
Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C55,
193-ESM-___-60A-C55
193-ESM-___-100A-C97
Contactor Cat.
No.
100-C099
100-C12122020
100-C16163030
100-C2323
100-C30305050
100-C37375050
100-C43437070
100-C55558080
100-C7272
100-C8585150150
100-C9797200200
Max. Starter
FLC[A]
Prospective Short-Circuit
Current, Ir [A]
1000
3,000
5,000
Conditional Short-
Circuit Current, Iq [A]
100,000600
Max. Voltage
[V]
Type I C lass J or
CC Fuse [A]
2015
4040
100100
Type II Class J
or CC Fuse [A]
Table 12 - Type 1 and Type II fuse coordination with Bul. 100-C and 100-D contactors
per EN60947-4-1
Overload Relay with Sensing
Module Cat. No.
592-ESM-___-30A-S2018
592-ESM-___-30A-S21273030
592-ESM-___-60A-S22456060
592-ESM-___-100A-S33905,000200200
Contactor SizeMax. Starter FLC[A]
Prospective Short-
Circuit Current, Ir [A]
3,000
Conditional Short-
Circuit Current, Iq
[A]
100,000600
Max. Voltage
[V]
Type I C lass J
Fuse [A]
3030
Type II Class J
Fuse [A]
Typical Motor Connections
ATT EN TI ON : When working on energized circuits, DO NOT rely on voltage and
current information that is provided by the E300 Electronic Overload Relay for
personal safety. Always use a portable voltage or current measurement device
to measure the signal locally.
Three-Phase Direct On-Line (DOL) and Single-Phase Full-voltage
The following wiring diagram illustrates the E300 Electronic Overload Relay
typical motor connections in a three-phase DOL and single-phase full-voltage
applications.
Rockwell Automation Publication 193-UM015D-EN-P - February 201547
Page 48
Chapter 2 Installation and Wiring
Figure 36 - E300 DOL and Single-Phase Full-voltage Connections
Three-Phase Direct-On-Line
S.C.P.D.
L1
2/T1
T1T2T3
L2
E300
4/T2
M
L3
6/T3
Single-Phase Full-Voltage
S.C.P.D.
L1
2/T1
T1
T2
M
L2
E300
4/T2
6/T3
External Line Current
Transformer Application
Current Transformer Ratio
The following E300 Electronic Overload Relay sensing module catalog numbers
can be used with step down current transformers:
• 193-ESM-IG-30A-E3T
• 193-ESM-IG-30A-T
• 193-ESM-IG-30A-P
• 193-ESM-I-30A-E3T
• 193-ESM-I-30A-T
• 193-ESM-I-30A-P
• 193-ESM-VIG-30A-CT
CT Primary (Parameter 263) and CT Secondary (Parameter 264) allows you to
identify the turns ratio of the step down current transformers in use. Based on
these two configuration parameters, the E300 Electronic Overload Relay will
automatically adjust the measured current. Use the primary current for your FLA
settings.
48Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 49
Table 13 - CT Primary (Parameter 263)
IMPORTANT
CT Primary (Parameter 263)
Default Value5
Minimum Value1
Maximum Value65535
Param eter TypeUINT
Size (Bytes)2
Scaling Factor1
UnitsAmps
Table 14 - CT Secondary (Parameter 264)
CT Secondary (Parameter 264)
Default Value5
Minimum Value1
Maximum Value65535
Parameter TypeUINT
Size (Bytes)2
Scaling Factor1
UnitsAmps
Installation and Wiring Chapter 2
ATT EN TI ON : Improper configuration of the CT Ratio parameters can make the
E300 Electronic Overload Relay report inaccurate motor operational data and
possible motor damage.
The E300 Electronic Overload Relay trip on a configuration fault when the FLA
setting is outside of the legal range of the selected CT Ratio settings. The TRIP/
WARN LED status indicator flashes red 3-long, 8-short blinking pattern.
You shall (1) provide one CT for each motor phase and shall (2) connect the
CT’s secondary leads to the appropriate sensing module power terminals. The
CTs shall be selected to be capable of providing the required VA to the secondary
load, which includes the E300 Sensing Module burden of 0.1 VA at the rated
secondary current and the wiring burden. Finally, the CT shall (1) be rated for
Protective Relaying to accommodate the high inrush currents associated with
motor startup and shall (2) be accurate to within ≤±2% over its normal operating
range. Typical CT ratings include:
• ANSI USA
• CSA (Canada)
• IEC (Europe)
• Class C5 BO.1
• Class 10L5
• 5 VA Class SP10
Rockwell Automation Publication 193-UM015D-EN-P - February 201549
Page 50
Chapter 2 Installation and Wiring
NEMA
L1L2
L3
L1/1 L2/3 L3/5
T1/2 T2/4 T3/6
M
T1
T2
T3
IEC
L1L2
L3
K1
L1/1 L2/3 L3/5
T1/2 T2/4 T3/6
E300
M
Primary
Current
Transformers
Primary
Current
Transformers
E300
ATT EN TI ON : The improper selection of a current transformer can result in the
E300 Electronic Overload Relay reporting inaccurate motor operational data and
possible motor damage. The selected current transformer must be rated for
protective relaying applications.
Figure 37 - External Current Transformer Connection
The E300 Electronic Overload Relay voltage-based sensing modules support a
wide variety of power systems. Tab le 1 5
lists the power systems supported by the
specific sensing module.
Table 15 - Supported Power Systems
Catalog NumberConnection TypePower System
193-ESM-VIG-__-__
592-ESM-VIG-__-__
193-ESM-VIG-30A-CT
Direct
Direct
3 PT
2 PT
Single Phase
Delta
Wye
Grounded B Phase Delta
Single Phase
Delta
Wye
Grounded B Phase Delta
Delta
Wye
Single Phase
Open Delta
50Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 51
Installation and Wiring Chapter 2
Voltage Mode
Voltage Mode (Parameter 252) determines the method for how voltage is
monitored E300 Electronic Overload Relay. Select the connection type for the
appropriate power system.
Table 16 - Voltage Mode (Parameter 352)
Default Value0 = Delta direct or with PTs
0 = Delta direct or with PTs
1 = Wye direct or with PTs
Range
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor1
Units
2 = Delta with Delta to Wye PTs
3 = Wye with D elta to Wye PTs
4 = Delta with Wye to Delta PTs
5 = Wye with Wye to Delta PTs
Potential (Voltage) Transformer Ratio
The E300 Electronic Overload Relay sensing module catalog number
193-ESM-VIG-30A-CT can be used with step down potential (voltage)
transformers. PT Primary (Parameter 353) and PT Secondary (Parameter 354)
allows you to identify the turns ratio of the step down potential (voltage)
transformers in use. The E300 Electronic Overload Relay will automatically
adjust the measured voltage based on these two configuration parameters. Use
the primary voltage for your voltage protection settings.
Table 17 - PT Primary (Parameter 353)
Default Value480
Minimum Value1
Maximum Value65535
Param eter TypeUINT
Size (Bytes)2
Scaling Factor1
UnitsAmps
Table 18 - PT Secondary (Parameter 354)
Default Value480
Minimum Value165535
Maximum Value
Param eter TypeUINT
Size (Bytes)2
Scaling Factor1
UnitsAmps
Rockwell Automation Publication 193-UM015D-EN-P - February 201551
Page 52
Chapter 2 Installation and Wiring
Control Circuits
ATT EN TI ON : Do not exceed the ratings of the E300 Electronic Overload Relay’s
output and trip relay. If the coil current or voltage of the contactor exceeds the
overload relay’s ratings, an interposing relay must be used.
ATT EN TI ON : When the power is applied to the E300 Electronic Overload Relay’s
A1 and A2 terminals, the N.O. relay contact that is assigned as a Trip Relay closes
after approximately 2 seconds if no trip condition exists.
ATT EN TI ON : More control circuit protection may be required. See the
applicable electrical codes.
The E300 Electronic Overload Relay can provide motor control logic for many
different types of motor starters (see Chapter 5
Operating Modes). By default, the E300 is configured for the Overload-Network
operating mode. The following wiring diagrams are typical control circuits for
Non-Reversing and Reversing Motor starters that use the Overload-Network
operating mode when Relay 0 (terminals R03 and R04) is configured to be a
normally closed Trip Relay.
Rockwell Automation Publication 193-UM015D-EN-P - February 201553
Page 54
Chapter 2 Installation and Wiring
Figure 41 - CENELEC Nomenclature
L1
Relay 0
Configured as a
Trip Relay
R03
2
R04
Relay 1
K2
R13
R14
Relay 2
R23
R24
K1
A1A1
K1
A2
N
K2
A2
2
Contact shown with supply voltage applied.
54Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 55
Diagnostic Station
Chapter 3
Introduction
Navigation Keys
KeyNameDescription
The E300 Electronic Overload Relay supports a Diagnostic Station on the E300
Expansion Bus (requires Control Module firmware v3.000 and higher). The
Diagnostic Station allows you to view any E300 parameter and edit any
configuration parameter. This chapter explains the Diagnostic Station’s
navigation keys, how to view a parameter, how to edit a configuration parameter,
and the Diagnostic Station’s programmable display sequence.
The E300 Diagnostic Station has five navigation keys that are used to navigate
through the Diagnostic Station’s display menu system and edit configuration
parameters.
Up Arrow
Down Arrow
Escape
Select
Enter
Scroll through the display parameters or groups.
Increment or decrement values.
Back one step in the navigation menu.
Cancel a change to a configuration parameter value
Select the next bit when viewing a bit enumerated parameter.
Select the next digit when editing a configuration value.
Select the next bit when editing a bit enumerated parameter.
Start the navigation menu.
Advance one step in the navigation menu.
Display the description for a bit enumerated parameter.
Edit a configuration parameter value.
Save the change to the configuration parameter value.
Displaying a Parameter
The E300 Diagnostic Station allows you to view parameters using a group menu
system or by a linear list. To start the navigation menu, press the key. The
menu prompts you to view parameters by groups, parameters in a linear list, or
E300 system information.
Rockwell Automation Publication 193-UM015D-EN-P - February 201555
Page 56
Chapter 3 Diagnostic Station
Parameter Group Navigation
To start the navigation menu, press the key. Use the or keys to
select the Groups navigation method and press .
Use the or keys to select the parameter group to display and press
.
Use the or keys to view the parameters that are associated with that
group.
When viewing a bit enumerated parameter, press to view the description of
each bit. Press to view the next bit. Press to return to the parameter.
Press to return to the parameter group navigation system.
56Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 57
Diagnostic Station Chapter 3
If you do not press any navigation keys for a period that is Defined by Display
Timeout (Parameter 436), then the E300 Diagnostic Station automatically
returns to its programmable display sequence.
Linear List Navigation
To start the navigation menu, press the key. Use the or keys to
select the Linear List navigation method and press .
Use the or and keys to select the parameter number to display
and press .
Use the or keys to view the next sequential parameter.
When viewing a bit enumerated parameter, press to view the description of
each bit. Press to view the next bit. Press to return to the parameter.
Rockwell Automation Publication 193-UM015D-EN-P - February 201557
Page 58
Chapter 3 Diagnostic Station
Press to return to the linear list navigation system.
If you do not press any navigation keys for a period that is Defined by Display
Timeout (Parameter 436), then the E300 Diagnostic Station automatically
returns to its programmable display sequence.
System Info
The E300 Diagnostic Station can display firmware revision information, view the
time and date of the E300 virtual clock, and edit the time and date of the E300
virtual clock. To view E300 system information, start the navigation menu by
pressing key. Use the or keys to select System Info and press
.
Use the or keys to view the E300 system information.
To edit the system date or time, press to modify the value. Use the or
keys to select the new value. Press to select the next system value. Press
to save the new system values or press to cancel the modification and
restore the previous system values.
58Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 59
Diagnostic Station Chapter 3
Press to return to the navigation menu.
If you do not press any navigation keys for a period that is Defined by Display
Timeout (Parameter 436), then the E300 Diagnostic Station automatically
cancels the modification, restores the previous value, and returns to its
programmable display sequence.
Editing Parameters
Editing a Configuration Parameter
The E300 Diagnostic Station allows you to edit configuration parameters using a
group menu system or by a linear list. To start the navigation menu, press the
key. You will be prompted to view parameters by groups, parameters in a
linear list, or E300 system information. Choose the appropriate method and
navigate to the parameter to be modified.
Editing a Numeric Parameter
To edit a configuration parameter, press the key to modify the value. Use
the or keys to select the new value. Press to save the new system
values or press to cancel the modification and restore the previous value.
Press to return to the navigation menu.
If you do not press any navigation keys for a period that is Defined by Display
Timeout (Parameter 436), then the E300 Diagnostic Station automatically
cancels the modification, restores the previous value, and returns to its
programmable display sequence.
Rockwell Automation Publication 193-UM015D-EN-P - February 201559
Page 60
Chapter 3 Diagnostic Station
Editing a Bit Enumerated Parameter
When editing a bit enumerated parameter, press the key to view the
description of each bit. Use the or keys to select the new bit value.
Press to edit the next bit. Press to save the new value or press to
cancel the modification and restore the previous value.
Press to return to the navigation menu.
If you do not press any navigation keys for a period that is Defined by Display
Timeout (Parameter 436), then the E300 Diagnostic Station automatically
cancels the modification, restores the previous value, and returns to its
programmable display sequence.
Programmable Display
Sequence
Display Sequence
The E300 Diagnostic Station sequentially displays up to seven screens every five
seconds.
• Three-phase current
• Three-phase voltage
• To ta l p ow er
• User-defined screen 1
• User-defined screen 2
• User-defined screen 3
• User-defined screen 4
The three-phase voltage and total power screens are only included in the
sequence when the E300 Electronic Overload Relay has a voltage, current, and
ground fault current (VIG)-based Sensing Module.
60Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 61
Diagnostic Station Chapter 3
The user-defined screens allow you to select up to two parameters per screen.
Refer to Diagnostic Station User-defined Screens on page 86
to configure the
Screen# and Parameter# (Parameters 428…435).
If you do not press any navigation keys for a period that is Defined by Display
Timeout (Parameter 436), then the Diagnostic Station will automatically cancel
any editing modifications, restore the previous value, and return to its
programmable display sequence.
Stopping the Display Sequence
To stop the display sequence, press . Use the or keys to manually
sequence through the displays. Press to return to the automatic display
sequence.
If you do not press any navigation keys for a period that is Defined by Display
Timeout (Parameter 436), then the E300 Diagnostic Station automatically
returns to its programmable display sequence.
Rockwell Automation Publication 193-UM015D-EN-P - February 201561
Page 62
Chapter 3 Diagnostic Station
Automatic Trip and Warning
Screens
When the E300 Electronic Overload Relay is in a trip or warning state, the E300
Diagnostic Station automatically displays the trip or warning event.
Press any of the navigation keys (, , , , or ) to return to
the automatic display sequence.
When the trip or warning event clears, the E300 Diagnostic Station
automatically returns to its programmable display sequence.
If a different parameter is displayed and you do not press any navigation keys for a
period that is Defined by Display Timeout (Parameter 436), then the E300
Diagnostic Station will automatically return to the trip or warning screen if the
trip or warning event is not cleared.
62Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 63
System Operation and Configuration
Chapter 4
Introduction
Device Modes
This chapter provides instructions for operating and configuring an E300
Electronic Overload Relay system. Settings for Device Modes, Option Match,
Security Policy, I/O Assignments, Expansion Bus Fault, Emergency Start, and an
introduction to Operating Modes are included in this chapter.
The E300 Electronic Overload Relay has five device modes to validate
configuration of the device and limit when you can configure the E300
Electronic Overload Relay, perform a firmware update, and issue commands.
• Administration Mode
• Operation Mode
• Run Mode
• Te st Mo de
• Invalid Configuration Mode
Administration Mode
Administration Mode is a maintenance mode for the E300 Electronic Overload
Relay, which allows you to configure parameters, modify security policies, enable
web servers (see page 382
firmware updates, and issue commands.
to enable the EtherNet/IP web server), perform
Follow these steps to enter into Administration Mode:
1. Set the rotary dials on the E300 Communication Module to the following
values
– For EtherNet/IP set the rotary dials to 0-0-0
– For DeviceNet set the rotary dials to 7-7
2. Cycle power on the E300 Electronic Overload Relay
After commissioning activities and maintenance tasks are completed, return the
E300 Electronic Overload Relay back to Operation or Run Mode by setting the
rotary dials of the E300 communication module back to its previous positions
and cycle power.
Rockwell Automation Publication 193-UM015D-EN-P - February 201563
Page 64
Chapter 4 System Operation and Configuration
Bit
1514131211109876543210Function
Operation Mode
Operation Mode is a standby mode for the E300 Electronic Overload Relay in
which the E300 is ready to help protect an electric motor and no electrical
current has been detected. You can modify configuration parameters, update
firmware, and issue commands if the appropriate security policies are enabled.
The Power LED on the Communication Module and Operator Stations will be
flashing green and bit 14 in Device Status 0 (Parameter 20) is set to 1 when the
device is in Operation Mode.
Table 19 - Operation Mode Bit Function Detail — Device Status 0 (Parameter 20)
X Trip Present
XWarning Present
XInvalid Configuration
XCurrent Present
XGFCurrent Present
XVoltage Present
XEmergency Start Enabled
XDeviceLogix Enabled
XFeedback Timeout Enabled
XOperator Station Present
XVoltage Sensing Present
XIntern Ground Fault Sensing Present
XExtern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved
Run Mode
Run Mode is an active mode for the E300 Electronic Overload Relay in which
the E300 is sensing electrical current and is actively protecting an electric motor.
Only non-motor protection configuration parameters can be modified if the
appropriate security policies are enabled. The Power LED on the
Communication Module and Operator Stations will be solid green and bits 3, 4,
and/or 5 in Device Status 0 (Parameter 20) are set to 1 when the device is in Run
Mode.
64Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 65
System Operation and Configuration Chapter 4
Table 20 - Run Mode Bit Function Detail — Device Status 0 (Parameter 20)
Bit
1514131211109876543210Function
X Trip Present
XWarning Present
XInvalid Configuration
XCurrent Present
XGFCurrent Present
XVoltage Present
XEmergency Start Enabled
XDeviceLogix Enabled
XFeedback Timeout Enabled
XOperator Station Present
XVoltage Sensing Present
XIntern Ground Fault Sensing Present
XExtern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved
Test Mode
Test Mode is used by installers of motor control centers who are testing and
commissioning motor starters with an automation system. A digital input of the
E300 Electronic Overload Relay is assigned to monitor the motor control center
enclosure’s Test Position. The Input Assignments (Parameters 196…201) are
described later in this chapter.
Anyone commissioning motor starters in an automation system can put their
motor control center enclosure into the Test Position to activate Test Mode and
verify that the digital inputs and relay outputs of the E300 Electronic Overload
Relay are operating properly with the motor starter without energizing power to
the motor. If the E300
Electronic Overload Relay senses current or voltage in Test
Mode, the E300 Electronic Overload Relay will generate a Test Mode Trip.
Invalid Configuration Mode
Invalid Configuration Mode is an active mode for the E300 Electronic Overload
Relay in which the E300 is in a tripped state due to invalid configuration data.
Invalid Configuration Parameter (Parameter 38) indicates the parameter number
that is causing the fault. Invalid Configuration Cause (Parameter 39) identifies
the reason for Invalid Configuration Mode.
Rockwell Automation Publication 193-UM015D-EN-P - February 201565
Page 66
Chapter 4 System Operation and Configuration
Bit
1514131211109876543210Function
Table 21 - Invalid Configuration Cause (Parameter 39)
CodeDescription
0No Error
1Value over maximum value
2Value under minimum value
3Illegal value
4L3 Current detected (for single-phase applications)
5CopyCat error
The Trip/Warn LED on the Communication Module and Operator Stations will
be flashing a pattern of red, 3 long and 8 short blinks, and bits 0 and 2 in Device
Status 0 (Parameter 20) are set to 1 when the device is in Invalid Configuration
Mode.
Table 22 - Invalid Configuration Mode Bit Function Detail — Device Status 0 (Parameter 20)
X Trip Present
XWarning Present
XInvalid Configuration
XCurrent Present
XGFCurrent Present
XVoltage Present
XEmergency Start Enabled
XDeviceLogix Enabled
XFeedback Timeout Enabled
XOperator Station Present
XVoltage Sensing Present
XIntern Ground Fault Sensing Present
XExtern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved
To return to Operation/Run Mode, place a valid configuration value in the
parameter identified by Invalid Configuration Parameter (Parameter 38) and
Invalid Configuration Cause (Parameter 39). Reset the trip state of the E300
Electronic Overload Relay by pressing the blue reset button on the
Communication Module, via network communications, with the internal web
server of the EtherNet/IP communications module, or by an assigned digital
input.
Option Match
Due to the modular nature of the E300 Electronic Overload Relay, you can
enable the Option Match feature to ensure that the options that were expected
for the motor protection application are the ones that are present on the E300
66Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 67
System Operation and Configuration Chapter 4
Electronic Overload Relay system. You can configure an option mismatch to
cause a protection trip or provide a warning within the E300.
Enable Option Match Protection Trip (Parameter 186)
To enable the E300 Electronic Overload Relay’s Option Match feature to cause a
protection trip in the event of an option mismatch, place a (1) in bit position 8 of
Parameter 186 (Control Trip Enable). You can select the specific option match
features to cause a protection trip in Parameter 233 (Option Match Action).
Table 23 - Enable Option Match Protection Trip Bit Function Detail— Control Trip Enable
(Parameter 186)
Bit
1514131211109876543210Function
XTest Trip Enable
XPTC Trip Enable
XDeviceLogix Trip Enable
XOperator Station Trip Enable
XRemote Trip Enable
XBlocked Start Trip Enable
XHardware Fault Trip Enable
XConfiguration Trip Enable
XOption Match Trip Enable
XFeedback Timeout Trip Enable
XExpansion Bus Trip Enable
Reserved
Reserved
XNonvolatile Memory Trip Enable
XReady
Reserved
Rockwell Automation Publication 193-UM015D-EN-P - February 201567
Page 68
Chapter 4 System Operation and Configuration
Bit
1514131211109876543210Function
Enable Option Match Protection Warning (Parameter 192)
To enable the E300 Electronic Overload Relay’s Option Match feature to cause a
warning in the event of an option mismatch, place a (1) in bit position 8 of
Parameter 192 (Control Warning Enable). You can select the specific option
match features to cause a warning in Parameter 233 (Option Match Action).
Table 24 - Enable Option Match Protection Warning Bit Function Detail— Control Warning
Enable (Parameter 192)
Reserved
Reserved
XDeviceLogix Warning Enable
Reserved
Reserved
Reserved
Reserved
Reserved
XOption Match Warning Enable
XFeedback Timeout Warning Enable
XExpansion Bus Warning Enable
XNumber Of Starts Warning Enable
XOperating Hours Warning Enable
Reserved
Control Module Type (Parameter 221)
The E300 Electronic Overload Relay offers six different control modules. Place
the value of the expected control module into Parameter 221. A value of (0)
disables the Option Match feature for the control module.
Table 25 - Control Module Type (Parameter 221)
Code DescriptionControl Module Cat. No.
0Ignore—
16 Inputs, 24V DC / 3 Relay Outputs193-EIO-63-24D
24 Inputs, 110-120V AC 50/60Hz / 3 Relay Outputs193-EIO-43-120
34 Inputs, 220-240V AC 50/60Hz / 3 Relay Outputs193-EIO-43-240
68Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 69
System Operation and Configuration Chapter 4
Sensing Module Type (Parameter 222)
The E300 Electronic Overload Relay offers 12 different sensing modules. Place
the value of the expected sensing module into Parameter 222. A value of (0)
disables the Option Match feature for the sensing module.
Table 26 - Sensing Module Type (Parameter 222)
CodeDescriptionSensing Module Cat. No.
0Ignore—
1Voltage / Current 0.5…30 A / Ground Fault193-ESM-VIG-30A-__ or 592-ESM-VIG-30A-__
2Voltage / Current 6…60 A / Ground Fault193-ESM-VIG-60A-__ or 592-ESM-VIG-60A-__
3Voltage / Current 10…100 A / Ground Fault 193-ESM-VIG-100A-__ or 592-ESM-VIG-100A-__
4Voltage / Current 20…200 A / Ground Fault193-ESM-VIG-200A-__ or 592-ESM-VIG-200A-__
5Current 0.5…30 A / Ground Fault 193-ESM-IG-30A-__ or 592-ESM-IG-30A-__
6Current 6…60 A / Ground Fault 193-ESM-IG-60A-__ or 592-ESM-IG-60A-__
7Current 10…100 A / Ground Fault 193-ESM-IG-100A-__ or 592-ESM-IG-100A-__
8Current 20…200 A / Ground Fault193-ESM-IG-200A-__ or 592-ESM-IG-200A-__
9Current 0.5…30 A 193-ESM-I-30A-__ or 592--ESM-I-30A-__
10 Current 6…60 A193-ESM-I-60A-__ or 592--ESM-I-60A-__
11Current 10…100 A 193-ESM-I-100A-__ or 592--ESM-I-100A-__
12Current 20…200 A193-ESM-I-200A-__ or 592--ESM-I-200A-__
Communication Module Type (Parameter 223)
The E300 Electronic Overload Relay offers two different communication
modules. Place the value of the expected communication module into Parameter
223. A value of (0) disables the Option Match feature for the communication
module.
Table 27 - Communication Module Type (Parameter 223)
CodeDescriptionCommunication Module Cat. No.
0Ignore—
1EtherNet/IP with Dual Port Switch supporting DLR 193-ECM-ETR
2DeviceNet193-ECM-DNT
Rockwell Automation Publication 193-UM015D-EN-P - February 201569
Page 70
Chapter 4 System Operation and Configuration
Operator Station Type (Parameter 224)
The E300 Electronic Overload Relay offers two different types of operator
stations. Place the value of the expected operator station into Parameter 224. A
value of (0) disables the Option Match feature for the operator station. A value of
(1), “No Operator Station”, makes the operator station not allowed on the
Expansion Bus and prevents you from connecting an operator station to the E300
Electronic Overload Relay system.
Table 28 - Operator Station Type (Parameter 224)
CodeDescriptionOperator Station Cat. No.
0Ignore—
1No Operator Station (Operator Station Not Allowed)—
2Control Station193-EOS-SCS
3Diagnostic Station with LCD 193-EOS-SDS
Digital I/O Expansion Module 1 Type (Parameter 225)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Digital I/O expansion module set to Digital Module 1. There are three different
types of Digital I/O expansion modules. Place the value of the expected Digital
I/O expansion module set to Digital Module 1 into Parameter 225. A value of (0)
disables the Option Match feature for this Digital I/O expansion module. A
value of (1), “No Digital I/O Expansion Module”, makes the Digital I/O
expansion module set to Digital Module 1 not allowed on the Expansion Bus and
prevents you from connecting a Digital I/O expansion module set to Digital
Module 1 to the E300 Electronic Overload Relay system.
Table 29 - Digital I/O Expansion Module 1 Type (Parameter 225)
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Allowed)
24 Inputs, 24V DC / 2 Relay Outputs193-EXP-DIO-42-24D
34 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
44 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs193-EXP-DIO-42-240
—
70Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 71
System Operation and Configuration Chapter 4
Digital I/O Expansion Module 2 Type (Parameter 226)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Digital I/O expansion module set to Digital Module 2. There are three different
types of Digital I/O expansion modules. Place the value of the expected Digital
I/O expansion module set to Digital Module 2 into Parameter 226. A value of (0)
disables the Option Match feature for this Digital I/O expansion module. A
value of (1),“No Digital I/O Expansion Module”, makes the Digital I/O expansion
module set to Digital Module 2 not allowed on the Expansion Bus and prevents
you from connecting a Digital I/O expansion module set to Digital Module 2 to
the E300 Electronic Overload Relay system.
Table 30 - Digital I/O Expansion Module 2 Type (Parameter 226)
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Allowed)
24 Inputs, 24V DC / 2 Relay Outputs193-EXP-DIO-42-24D
34 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
44 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs193-EXP-DIO-42-240
—
Digital I/O Expansion Module 3 Type (Parameter 227)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Digital I/O expansion module set to Digital Module 3. There are three different
types of Digital I/O expansion modules. Place the value of the expected Digital
I/O expansion module set to Digital Module 3 into Parameter 227. A value of (0)
disables the Option Match feature for this Digital I/O expansion module. A
value of (1),“No Digital I/O Expansion Module”, makes the Digital I/O expansion
module set to Digital Module 3 not allowed on the Expansion Bus and prevents
you from connecting a Digital I/O expansion module set to Digital Module 3 to
the E300 Electronic Overload Relay system.
Table 31 - Digital I/O Expansion Module 3 Type (Parameter 227)
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Allowed)
24 Inputs, 24V DC / 2 Relay Outputs193-EXP-DIO-42-24D
34 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
44 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs193-EXP-DIO-42-240
—
Digital I/O Expansion Module 4 Type (Parameter 228)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Rockwell Automation Publication 193-UM015D-EN-P - February 201571
Page 72
Chapter 4 System Operation and Configuration
Digital I/O expansion module set to Digital Module 4. There are three different
types of Digital I/O expansion modules. Place the value of the expected Digital
I/O expansion module set to Digital Module 4 into Parameter 228. A value of (0)
disables the Option Match feature for this Digital I/O expansion module. A
value of (1), “No Digital I/O Expansion Module ”, makes the Digital I/O
expansion module set to Digital Module 4 not allowed on the Expansion Bus and
prevents you from connecting a Digital I/O expansion module set to Digital
Module 4 to the E300 Electronic Overload Relay system.
Table 32 - Digital I/O Expansion Module 4 Type (Parameter 228)
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Allowed)
24 Inputs, 24V DC / 2 Relay Outputs193-EXP-DIO-42-24D
34 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
44 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs193-EXP-DIO-42-240
—
Analog I/O Expansion Module 1 Type (Parameter 229)
The E300 Electronic Overload Relay supports up to four additional Analog I/O
expansion modules. This parameter configures the Option Match feature for the
Analog I/O expansion module set to Analog Module 1. There is one type of
Analog I/O expansion module. Place the value of the expected Analog I/O
expansion module set to Analog Module 1 into Parameter 229. A value of (0)
disables the Option Match feature for this Analog I/O expansion module. A
value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O
expansion module set to Analog Module 1 not allowed on the Expansion Bus and
prevents you from connecting an Analog I/O expansion module set to Analog
Module 1 to the E300 Electronic Overload Relay system.
Table 33 - Analog I/O Expansion Module 1 Type (Parameter 229)
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Allowed)
23 Universal Analog Inputs / 1 Analog Output193-EXP-AIO-31
—
72Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 73
System Operation and Configuration Chapter 4
Analog I/O Expansion Module 2 Type (Parameter 230)
The E300 Electronic Overload Relay supports up to four additional Analog I/O
expansion modules. This parameter configures the Option Match feature for the
Analog I/O expansion module set to Analog Module 2. There is one type of
Analog I/O expansion module. Place the value of the expected Analog I/O
expansion module set to Analog Module 2 into Parameter 230. A value of (0)
disables the Option Match feature for this Analog I/O expansion module. A
value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O
expansion module set to Analog Module 2 not allowed on the Expansion Bus and
prevents you from connecting an Analog I/O expansion module set to Analog
Module 2 to the E300 Electronic Overload Relay system.
Table 34 - Analog I/O Expansion Module 2 Type (Parameter 230)
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Allowed)
23 Universal Analog Inputs / 1 Analog Output193-EXP-AIO-31
—
Analog I/O Expansion Module 3 Type (Parameter 231)
The E300 Electronic Overload Relay supports up to four additional Analog I/O
expansion modules. This parameter configures the Option Match feature for the
Analog I/O expansion module set to Analog Module 3. There is one type of
Analog I/O expansion module. Place the value of the expected Analog I/O
expansion module set to Analog Module 3 into Parameter 231. A value of (0)
disables the Option Match feature for this Analog I/O expansion module. A
value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O
expansion module set to Analog Module 3 not allowed on the Expansion Bus and
prevents you from connecting an Analog I/O expansion module set to Analog
Module 3 to the E300 Electronic Overload Relay system.
Table 35 - Analog I/O Expansion Module 3 Type (Parameter 231)
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Allowed)
23 Universal Analog Inputs / 1 Analog Output193-EXP-AIO-31
—
Rockwell Automation Publication 193-UM015D-EN-P - February 201573
Page 74
Chapter 4 System Operation and Configuration
Analog I/O Expansion Module 4 Type (Parameter 232)
The E300 Electronic Overload Relay supports up to four additional Analog I/O
expansion modules. This parameter configures the Option Match feature for the
Analog I/O expansion module set to Analog Module 4. There is one type of
Analog I/O expansion module. Place the value of the expected Analog I/O
expansion module set to Analog Module 4 into Parameter 232. A value of (0)
disables the Option Match feature for this Analog I/O expansion module. A
value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O
expansion module set to Analog Module 4 not allowed on the Expansion Bus and
prevents you from connecting an Analog I/O expansion module set to Analog
Module 4 to the E300 Electronic Overload Relay system.
Table 36 - Analog I/O Expansion Module 4 Type (Parameter 232)
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Allowed)
23 Universal Analog Inputs / 1 Analog Output193-EXP-AIO-31
—
Option Match Action (Parameter 233)
The Option Match feature for the E300 Electronic Overload Relay allows you to
specify an action when there is an option mismatch – Protection Trip or
Warning. Place a (0) in the appropriate bit position for a warning, and place a
(1) in the appropriate bit position to cause a protection trip if there is an option
mismatch.
Table 37 - Option Match Action (Parameter 233) Bit Function Detail
Bit
1514131211109876543210Function
XControl Module Mismatch Action
XSensing Module Mismatch Action
X
XOperator Station Mismatch Action
XDigital Module 1 Mismatch Action
XDigital Module 2 Mismatch Action
XDigital Module 3 Mismatch Action
XDigital Module 4 Mismatch Action
XAnalog Module 1 Mismatch Action
XAnalog Module 2 Mismatch Action
XAnalog Module 3 Mismatch Action
XAnalog Module 4 Mismatch Action
Communication Module Mismatch
Action
74Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 75
System Operation and Configuration Chapter 4
Security Policy
The E300 Electronic Overload Relay has a security policy that can be used to
prevent anyone with malicious intent to potentially damage a motor or piece of
equipment. By default, you can only modify the security policy when the E300
Electronic Overload Relay is in Administration Mode (see page 63
to learn how
to enable Administration Mode).
Table 38 - Security Policy (Parameter 211) Bit Function Detail
Bit
1514131211109876543210Function
XDevice Configuration Enable
XDevice Reset Enable
XFirmware Update Enable
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
XSecurity Policy Config Enable
Device Configuration Policy
The Device Configuration Policy allows you to send external message
instructions via a communications network to write values to configuration
parameters. When this policy is disabled, all external message instructions with
configuration data will return a communications error when the E300 Electronic
Overload Relay is in Operation Mode or Run Mode.
Device Reset Policy
The Device Reset Policy allows you to send external message instruction via a
communications network to perform a soft device reset when the E300
Electronic Overload Relay is in Operation Mode. When this policy is disabled,
all external reset message instructions will return a communications error when
the E300 Electronic Overload Relay is in Operation Mode or Run Mode.
Rockwell Automation Publication 193-UM015D-EN-P - February 201575
Page 76
Chapter 4 System Operation and Configuration
Firmware Update Policy
The Firmware Update Policy allows you to update the internal firmware of the
communication module and control module via ControlFlash when the E300
Electronic Overload Relay is in Operation Mode. When this policy is disabled,
firmware updates will return a communications error when the E300 Electronic
Overload Relay is in Operation Mode or Run Mode.
Security Configuration Policy
The Security Configuration Policy allows you to modify the Security Policy of
the E300 Electronic Overload Relay in Operation Mode. When this policy is
disabled, the Security Policy can only be modified when the E300 Electronic
Overload Relay is in Administration Mode.
I/O Assignments
The E300 Electronic Overload Relay has native digital inputs and relay outputs
in the Control Module. This I/O can be assign to dedicated functions. the
following sections list the function assignments for the available Control
Module I/O.
Input Pt00 Assignment (Parameter 196)
Input Pt00 Assignment (Parameter 196) allows you to assign this digital input
for the following functions:
Table 39 - Input Pt00 Assignment (Parameter 196)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss ArmActivate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
76Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 77
System Operation and Configuration Chapter 4
Input Pt01 Assignment (Parameter 197)
Input Pt01 Assignment (Parameter 197) allows you to assign this digital input
for the following functions:
Table 40 - Input Pt01 Assignment (Parameter 197)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
Input Pt02 Assignment (Parameter 198)
Input Pt02 Assignment (Parameter 198) allows you to assign this digital input
for the following functions:
Table 41 - Input Pt02 Assignment (Parameter 198)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
Rockwell Automation Publication 193-UM015D-EN-P - February 201577
Page 78
Chapter 4 System Operation and Configuration
Input Pt03 Assignment (Parameter 199)
Input Pt03 Assignment (Parameter 199) allows you to assign this digital input
for the following functions:
Table 42 - Input Pt03 Assignment (Parameter 199)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
Input Pt04 Assignment (Parameter 200)
Input Pt04 Assignment (Parameter 200) allows you to assign this digital input
for the following functions:
Table 43 - Input Pt04 Assignment (Parameter 200)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
78Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 79
System Operation and Configuration Chapter 4
Input Pt05 Assignment (Parameter 201)
Input Pt05 Assignment (Parameter 201) allows you to assign this digital input
for the following functions:
Table 44 - Input Pt05 Assignment (Parameter 201)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
Rockwell Automation Publication 193-UM015D-EN-P - February 201579
Page 80
Chapter 4 System Operation and Configuration
Output Pt00 Assignment (Parameter 202)
Output Pt00 Assignment (Parameter 202) allows you to assign this relay output
for the following functions:
Table 45 - Output Pt00 Assignment (Parameter 202)
Value
Assignmen
t
Descripti
on
0NormalFunction as a relay output
1Trip Relay
Function as a normally closed contact until the E300 is in a tripped state in which the relay opens. The Trip Relay
remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
2Control Relay
commanded to close by communications or via a DeviceLogix program. When the E300 enters into a tripped state
the Control Relay opens and remains open until a trip reset is issued.
3Trip Alarm
4Warning Alarm
5Monitor L1 Trip Relay
6Monitor L2 Trip Relay
7Monitor L3 Trip Relay
Function as a normally open contact until the E300 is in a tripped state in which the relay closes. The Trip Alarm
remains closed until a trip reset is issued.
Function as a normally open contact until the E300 is in a protection warning state in which the relay closes. The
Warning Alarm remains closed until the protection warning clears.
Function as a normally closed contact until the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or
(1)
L1 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or
(1)
L2 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or
(1)
L3 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L1
8Monitor L1 Control Relay
(1)
Under Current, L1 Over Current, or L1 Line Loss, the relay opens. The Control Relay remains open until a trip reset is
issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L2
9Monitor L2 Control Relay
(1)
Under Current, L2 Over Current, or L2 Line Loss, the relay opens. The Control Relay remains open until a trip reset is
issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L3
10Monitor L3 Control Relay
(1)
Under Current, L3 Over Current, or L3 Line Loss, the relay opens. The Control Relay remains open until a trip reset is
issued.
(1) Req uires Control M odule firmw are v3.000 or higher
80Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 81
System Operation and Configuration Chapter 4
Output Pt01 Assignment (Parameter 203)
Output Pt01 Assignment (Parameter 203) allows you to assign this relay output
for the following functions:
Table 46 - Output Pt01 Assignment (Parameter 203)
Value
Assignmen
t
Descripti
on
0NormalFunction as a relay output
1Trip Relay
Function as a normally closed contact until the E300 is in a tripped state in which the relay opens. The Trip Relay
remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
2Control Relay
commanded to close by communications or via a DeviceLogix program. When the E300 enters into a tripped state
the Control Relay opens and remains open until a trip reset is issued.
3Trip Alarm
4Warning Alarm
5Monitor L1 Trip Relay
6Monitor L2 Trip Relay
7Monitor L3 Trip Relay
Function as a normally open contact until the E300 is in a tripped state in which the relay closes. The Trip Alarm
remains closed until a trip reset is issued.
Function as a normally open contact until the E300 is in a protection warning state in which the relay closes. The
Warning Alarm remains closed until the protection warning clears.
Function as a normally closed contact until the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or
(1)
L1 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or
(1)
L2 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or
(1)
L3 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L1
8Monitor L1 Control Relay
(1)
Under Current, L1 Over Current, or L1 Line Loss, the relay opens. The Control Relay remains open until a trip reset is
issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L2
9Monitor L2 Control Relay
(1)
Under Current, L2 Over Current, or L2 Line Loss, the relay opens. The Control Relay remains open until a trip reset is
issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L3
10Monitor L3 Control Relay
(1)
Under Current, L3 Over Current, or L3 Line Loss, the relay opens. The Control Relay remains open until a trip reset is
issued.
(1) Req uires Control M odule firmw are v3.000 or higher
Rockwell Automation Publication 193-UM015D-EN-P - February 201581
Page 82
Chapter 4 System Operation and Configuration
Output Pt02 Assignment (Parameter 204)
Output Pt02 Assignment (Parameter 204) allows you to assign this relay output
for the following functions:
Table 47 - Output Pt02 Assignment (Parameter 204)
Value
0NormalFunction as a relay output
1Trip Relay
2Control Relay
3Trip Alarm
4Warning Alarm
5Monitor L1 Trip Relay
6Monitor L2 Trip Relay
7Monitor L3 Trip Relay
8Monitor L1 Control Relay
9Monitor L2 Control Relay
10Monitor L3 Control Relay
(1) Req uires Control M odule firmw are v3.000 or higher
Assignmen
t
Descripti
on
Function as a normally closed contact until the E300 is in a tripped state in which the relay opens. The Trip Relay
remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
commanded to close by communications or via a DeviceLogix program. When the E300 enters into a tripped state
the Control Relay opens and remains open until a trip reset is issued.
Function as a normally open contact until the E300 is in a tripped state in which the relay closes. The Trip Alarm
remains closed until a trip reset is issued.
Function as a normally open contact until the E300 is in a protection warning state in which the relay closes. The
Warning Alarm remains closed until the protection warning clears.
Function as a normally closed contact until the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or
(1)
L1 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or
(1)
L2 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or
(1)
L3 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L1
(1)
Under Current, L1 Over Current, or L1 Line Loss, the relay opens. The Control Relay remains open until a trip reset is
issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L2
(1)
Under Current, L2 Over Current, or L2 Line Loss, the relay opens. The Control Relay remains open until a trip reset is
issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L3
(1)
Under Current, L3 Over Current, or L3 Line Loss, the relay opens. The Control Relay remains open until a trip reset is
issued.
Table 48 - Activate FLA2 with Output Relay (Parameter 209)
Activate FLA2 with Output Relay (Parameter 209) allows you to activate the
value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms when the assigned output relay is in an energized state.
Table 49 - Activate FLA2 with Output Relay (Parameter 209)
ValueDescription
0Disable
1Pt00 Output
2Pt01 Output
3Pt02 Output
Expansion Bus Fault
The E300 Electronic Overload Relay’s expansion bus can be used to expand the
I/O capabilities of the E300 Electronic Overload Relay with the addition of
digital and analog expansion I/O modules. The Expansion Bus Fault allows you
to have the E300 Electronic Overload Relay go into a Trip or Warning state when
82Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 83
System Operation and Configuration Chapter 4
established Expansion Bus communications is disrupted between the Control
Module and any digital and analog expansion I/O modules.
The Expansion Bus Fault is used when the Option Match feature is not enabled
for the digital and/or analog expansion I/O modules. The Expansion Bus Fault
only monitors for communication disruptions between the Control Module and
digital and/or analog expansion I/O modules. Expansion bus communication
disruptions between the Control Module and Operator Station do not affect the
Expansion Bus fault.
Expansion Bus Trip
Expansion Bus Trip is enabled by setting Control Trip Enable (Parameter 186)
bit 10 to 1. When communications is disrupted between the Control Module
and digital and/or analog expansion I/O modules, the E300 Electronic Overload
Relay will go into a tripped state in which the Trip/Warn LED on the
Communication Module and Operator station will blink a red 3 long and 11
short blinking pattern.
Table 50 - Expansion Bus Trip Bit Function Detail— Control Trip Enable (Parameter 186)
Bit
1514131211109876543210Function
XTest Trip Enable
XPTC Trip Enable
XDeviceLogix Trip Enable
XOperator Station Trip Enable
XRemote Trip Enable
XBlocked Start Trip Enable
XHardware Fault Trip Enable
XConfiguration Trip Enable
XOption Match Trip Enable
XFeedback Timeout Trip Enable
XExpansion Bus Trip Enable
Reserved
Reserved
XNonvolatile Memory Trip Enable
XReady
Reserved
To return to Operation/Run Mode, verify that the expansion bus cables are
properly plugged into the Bus In and Bus Out ports of all of the expansion
modules. When all of the expansion I/O modules’ status LEDs are solid green,
reset the trip state of the E300 Electronic Overload Relay by pressing the blue
reset button on the Communication Module, via network communications, with
the internal web server of the EtherNet/IP communications module, or by an
assigned digital input.
Rockwell Automation Publication 193-UM015D-EN-P - February 201583
Page 84
Chapter 4 System Operation and Configuration
IMPORTANT
Bit
1514131211109876543210Function
Expansion Bus Warning
Expansion Bus Warning is enabled by setting Control Warning Enable
(Parameter 192) bit 10 to 1. When communications is disrupted between the
Control Module and digital and/or analog expansion I/O modules, the E300
Electronic Overload Relay will go into a warning state in which the Trip/Warn
LED on the Communication Module and Operator station will blink a yellow 3
long and 11 short blinking pattern.
Table 51 - Expansion Bus Warning Bit Function Detail— Control Warning Enable (Parameter 192)
Reserved
XP TC Warni ng En able
XDeviceLogix Warning Enable
XOperator Station Warning Enable
Reserved
Reserved
Reserved
Reserved
XOption Match Warning Enable
XFeedback Timeout Warning Enable
XExpansion Bus Warning Enable
XNumber Of Starts Warning Enable
XOperating Hours Warning Enable
Reserved
Emergency Start
To return to Operation/Run Mode, verify that the expansion bus cables are
properly plugged into the Bus In and Bus Out ports of all of the expansion
modules. When all of the expansion I/O modules’ status LEDs are solid green,
the warning state of the E300 Electronic Overload Relay will automatically clear.
In an emergency, it may be necessary to start a motor even if a protection fault or
a communication fault exists. The trip condition may be the result of a thermal
overload condition or the number of starts exceeded its configuration. These
conditions can be overridden using the Emergency Start feature of the E300
Electronic Overload Relay.
Activating Emergency Start inhibits overload and blocked start protection.
Running in this mode can cause equipment overheating and fire.
To enable the Emergency Start feature in the E300 Electronic Overload Relay set
the Emergency Start Enable (Parameter 216) to Enable.
84Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 85
System Operation and Configuration Chapter 4
Table 52 - Emergency Start (Parameter 216)
ValueDescription
0Disable
1Enable
Configure one of the Ptxx Input Assignments (Parameters 196…201) to
Emergency Start and activate the corresponding digital input.
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
Use the value in FLA2 Setting (Parameter 177) for the current-based
protection algorithms
You can also use a network command to activate the Emergency Start feature. For
the EtherNet/IP communications module, you would set the Emergency Start
bit to 1 in Output Assembly 144. See EtherNet/IP Communications on
page 373 for more information on EtherNet/IP communications.
When the Emergency Start feature is active, the following actions occur in the
E300 Electronic Overload Relay:
• Protection trips are ignored
• Output relays configured as Trip Relays are put into closed state
• Normal operation resumes with any Normal or Control Relay assigned
output relay
• The Emergency Start Active bit is set to 1 in Device Status 0
(Parameter
20) bit 6
Rockwell Automation Publication 193-UM015D-EN-P - February 201585
Page 86
Chapter 4 System Operation and Configuration
Bit
1514131211109876543210Function
Table 54 - Emergency Start Bit Function Detail— Device Status 0 (Parameter 20)
XTrip Present
XWarning Present
XInvalid Configuration
XCurrent Present
XGFCurrent Present
XVoltage Present
XEmergency Start Enabled
XDeviceLogix Enabled
XFeedback Timeout Enabled
XOperator Station Present
XVoltage Sensing Present
XIntern Ground Fault Sensing Present
XExtern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved
Diagnostic Station Userdefined Screens
The E300 Electronic Overload Relay’s Diagnostic Station has four user-defined
screens that are part of the Diagnostic Station’s display sequence in which you can
define up to two parameters per screen.
User-defined Screen 1
User-defined Screen 1 – Parameter 1
User-defined Screen 1 - Parameter 1 (Parameter 428) is the E300 parameter
number to display for the first parameter in user-defined screen 1. You can select
one of the 560 available E300 Electronic Overload Relay parameters.
Table 55 - Screen 1 - Parameter 1 (Parameter 428)
Default Value1
Minimum Value0
Maximum Value560
Parameter TypeUIN T
Size (Bytes)2
Scaling Factor1
Units
User-defined Screen 1 – Parameter 2
User-defined Screen 1 - Parameter 2 (Parameter 429) is the E300 parameter
number to display for the second parameter in user-defined screen 1. You can
select one of the 560 available E300 Electronic Overload Relay parameters.
86Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 87
System Operation and Configuration Chapter 4
Table 56 - Screen 1 - Parameter 2 (Parameter 429)
Default Value50
Minimum Value0
Maximum Value560
Parameter TypeUIN T
Size (Bytes)2
Scaling Factor1
Units
User-defined Screen 2
User-defined Screen 2 – Parameter 1
User-defined Screen 2 - Parameter 1 (Parameter 430) is the E300 parameter
number to display for the first parameter in user-defined screen 2. You can select
one of the 560 available E300 Electronic Overload Relay parameters.
Table 57 - Screen 2 - Parameter 1 (Parameter 430)
Default Value2
Minimum Value0
Maximum Value560
Parameter TypeUIN T
Size (Bytes)2
Scaling Factor1
Units
User-defined Screen 2 – Parameter 2
User-defined Screen 2 - Parameter 2 (Parameter 431) is the E300 parameter
number to display for the second parameter in user-defined screen 2. You can
select one of the 560 available E300 Electronic Overload Relay parameters.
Table 58 - Screen 2 - Parameter 2 (Parameter 431)
Default Value3
Minimum Value0
Maximum Value560
Parameter TypeUIN T
Size (Bytes)2
Scaling Factor1
Units
Rockwell Automation Publication 193-UM015D-EN-P - February 201587
Page 88
Chapter 4 System Operation and Configuration
User-defined Screen 3
User-defined Screen 3 – Parameter 1
User-defined Screen 3 - Parameter 1 (Parameter 432) is the E300 parameter
number to display for the first parameter in user-defined screen 3. You can select
one of the 560 available E300 Electronic Overload Relay parameters.
Table 59 - Screen 3 - Parameter 1 (Parameter 432)
Default Value51
Minimum Value0
Maximum Value560
Parameter TypeUIN T
Size (Bytes)2
Scaling Factor1
Units
User-defined Screen 3 – Parameter 2
User-defined Screen 3 - Parameter 2 (Parameter 433) is the E300 parameter
number to display for the second parameter in user-defined screen 3. You can
select one of the 560 available E300 Electronic Overload Relay parameters.
Table 60 - Screen 3 - Parameter 2 (Parameter 433)
Default Value52
Minimum Value0
Maximum Value560
Parameter TypeUIN T
Size (Bytes)2
Scaling Factor1
Units
User-defined Screen 4
User-defined Screen 4 – Parameter 1
User-defined Screen 4 - Parameter 1 (Parameter 434) is the E300 parameter
number to display for the first parameter in user-defined screen 4. You can select
one of the 560 available E300 Electronic Overload Relay parameters.
Table 61 - Screen 4 - Parameter 1 (Parameter 434)
Default Value38
Minimum Value0
Maximum Value560
Parameter TypeUIN T
Size (Bytes)2
Scaling Factor1
Units
88Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 89
System Operation and Configuration Chapter 4
User-defined Screen 4 – Parameter 2
User-defined Screen 4 - Parameter 2 (Parameter 435) is the E300 parameter
number to display for the second parameter in user-defined screen 4. You can
select one of the 560 available E300 Electronic Overload Relay parameters.
Screen4‐Parameter2(Parameter435)
Default Value39
Minimum Value0
Maximum Value560
Parameter TypeUIN T
Size (Bytes)2
Scaling Factor1
Units
Display Timeout
Display Timeout (Parameter 436) defines the time duration in which there is no
display navigation activity, and the E300 Diagnostic Station returns to its normal
display sequence. Any configuration parameters that were left in an edit state will
be canceled. A value of zero disables the display timeout function.
Table 62 - Display Timeout (Parameter 436)
Default Value300
Minimum Value0
Maximum Value65535
Parameter TypeUIN T
Size (Bytes)2
Scaling Factor1
Units Seconds
Rockwell Automation Publication 193-UM015D-EN-P - February 201589
Page 90
Chapter 4 System Operation and Configuration
Analog I/O Expansion
Modules
The E300 Electronic Overload Relay supports up to four Analog I/O Expansion
Modules on the E300 Expansion Bus. The E300 Analog Expansion Module has
three independent universal inputs and one analog output.
Analog Input Channels
The universal analog inputs can accept the following analog signals:
The analog inputs can report data in four different formats. Tab le 6 3 through
Tab le 66
display the data ranges for all of the available analog input types for the
four available data formats.
Table 63 - Analog Input Data Format for Current Input Type
Input Range Input ValueCondition
21.00 mAHigh Limit2100021003276717407
4…20 mA
0…20 mA
90Rockwell Automation Publication 193-UM015D-EN-P - February 2015
20.00 mAHigh Range2000020003276716383
4.00 mALow Range4000400-327680
3.00 mALow Limit3000300-32768-1024
21.00 mAHigh Limit2100021003276717202
20.00 mAHigh Range2000020003276716383
0.00 mALow Range00-327680
0.00 mALow Limit00-327680
Engineering
Units
Engineering
Units x 10
Raw /
Proportional
PID
Page 91
System Operation and Configuration Chapter 4
Table 64 - Analog Input Data Format for Voltage Input Type
Input Range Input ValueCondition
10.50V DCHigh Limit1050010503276717202
0…10 V DC
1…5 V DC
0…5V DC
10.00V DCHigh Range1000010003276716383
0.00V DCLow Range00-327680
0.00V DCLow Limit00-327680
5.25V DCHigh Limit52505253276717407
5.00V DCHigh Range50005003276716383
1.00V DCLow Range1000100-327680
0.50V DCLow Limit50050-32768-2048
5.25V DCHigh Limit52505253276717202
5.00V DCHigh Range50005003276716383
0.00V DCLow Range00-327680
0.00V DCLow Limit00-327680
Engineering
Units
Table 65 - Analog Input Data Format for RTD Input Type
Input Range Input ValueCondition
850.0 °CHigh Limit85008503276716383
850.0 °CHigh Range85008503276716383
RTD
100 Ω, 200 Ω,
500 Ω, 1000 Ω
Pt 385
RTD
100 Ω, 200 Ω,
500 Ω, 1000 Ω
Pt 3916
RTD
10 Ω Cu 426
RTD
100 Ω Ni 618
-200.0 °CLow Range-2000-200-327680
-200.0 °CLow Limit-2000-200-327680
1562.0 °FHigh Limit1562015623276716383
1562.0 °FHigh Range1562015623276716383
-328.0 °FLow Range-3280-328-327680
-328.0 °FLow Limit-3280-328-327680
630.0 °CHigh Limit63006303276716383
630.0 °CHigh Range63006303276716383
-200.0 °CLow Range-2000-200-327680
-200.0 °CLow Limit-2000-200-327680
1166.0 °FHigh Limit1166011663276716383
1166.0 °FHigh Range1166011663276716383
-328.0 °FLow Range-3280-328-327680
-328.0 °FLow Limit-3280-328-327680
260.0 °CHigh Limit26002603276716383
260.0 °CHigh Range26002603276716383
-100.0 °CLow Range-1000-100-327680
-100.0 °CLow Limit-1000-100-327680
500.0 °FHigh Limit50005003276716383
500.0 °FHigh Range50005003276716383
-148.0 °FLow Range-1480-148-327680
-148.0 °FLow Limit-1480-148-327680
260.0 °CHigh Limit26002603276716383
260.0 °CHigh Range26002603276716383
-100.0 °CLow Range-1000-100-327680
-100.0 °CLow Limit-1000-100-327680
500.0 °FHigh Limit50005003276716383
500.0 °FHigh Range50005003276716383
-148.0 °FLow Range-1480-148-327680
-148.0 °FLow Limit-1480-148-327680
Engineering
Units
Engineering
Units x 10
Engineering
Units x 10
Raw /
Proportional
Raw /
Proportional
PID
PID
Rockwell Automation Publication 193-UM015D-EN-P - February 201591
Page 92
Chapter 4 System Operation and Configuration
Input Range Input ValueCondition
260.0 °CHigh Limit26002603276716383
260.0 °CHigh Range26002603276716383
-80.0 °CLow Range-800-80-327680
RTD
120 Ω Ni 672
RTD
100 Ω NiFe
518
-80.0 °CLow Limit-800-80-327680
500.0 °FHigh Limit50005003276716383
500.0 °FHigh Range50005003276716383
-112.0 °FLow Range-1120-112-327680
-112.0 °FLow Limit-1120-112-327680
200.0 °CHigh Limit20002003276716383
200.0 °CHigh Range20002003276716383
-100.0 °CLow Range-1000-100-327680
-100.0 °CLow Limit-1000-100-327680
392.0 °FHigh Limit39203923276716383
392.0 °FHigh Range39203923276716383
-148.0 °FLow Range-1480-148-327680
-148.0 °FLow Limit-1480-148-327680
Engineering
Units
Engineering
Units x 10
Table 66 - Analog Input Data Format for Resistance Input Type
Input Range Input ValueCondition
150.00 ΩHigh Limit1500015003276716383
Resistance
0-150 Ω
Resistance
0-750 Ω
Resistance
0-3000 Ω
Resistance
0-6000 Ω
(PTC / NTC)
150.00 ΩHigh Range1500015003276716383
0.00 ΩLow Range00-327680
0.00 ΩLow Limit00-327680
750.0 ΩHigh Limit75007503276716383
750.0 ΩHigh Range75007503276716383
0.0 ΩLow Range00-327680
0.0 ΩLow Limit00-327680
3000.0 ΩHigh Limit3000030003276716383
3000.0 ΩHigh Range3000030003276716383
0.0 ΩLow Range00-327680
0.0 ΩLow Limit00-327680
6000 ΩHigh Limit60006003276716383
6000 ΩHigh Range60006003276716383
0 ΩLow Range00-327680
0 ΩLow Limit00-327680
Engineering
Units
Engineering
Units x 10
Raw /
Proportional
Raw /
Proportional
PID
PID
Analog Output Channel
The isolated analog output can be programmed to provide one of the following
analog output signal types:
• Current
– 4…20 mA
– 0…20 mA
92Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 93
System Operation and Configuration Chapter 4
• Vo l t a g e
– 0…10V DC
– 1…5V DC
– 0…5V DC
The analog outputs can report data as a percent of range. Tab le 6 7 and Tabl e 6 8
display the data ranges for all of the available analog output types.
Table 67 - Analog Output Data Format for Current Output Type
Output RangeOutput SignalCondition% Range
21.000 mAHigh Limit106.25%
4…20 mA
0…20 mA
20.000 mAHigh Range100.00%
4.000 mALow Range0.00%
3.000 mALow Limit-6.25%
21.00 mAHigh Limit105.00%
20.00 mAHigh Range100.00%
0.00 mALow Range0.00%
0.00 mALow Limit0.00%
Table 68 - Analog Output Data Format for Voltage Output Type
Output RangeOutput ValueCondition% Range
10.50V DCHigh Limit105.00%
0…10 V DC
1…5 V DC
0…5 V DC
10.00V DCHigh Range100.00%
0.00V DCLow Range0.00%
0.00V DCLow Limit0.00%
5.25V DCHigh Limit106.25%
5.00V DCHigh Range100.00%
1.00V DCLow Range0.00%
0.50V DCLow Limit-6.25%
5.25V DCHigh Limit105.00%
5.00V DCHigh Range100.00%
0.00V DCLow Range0.00%
0.00V DCLow Limit0.00%
The analog output can be used to communicate E300 diagnostic information via
an analog signal to distributed control systems, programmable logic controllers,
or panel-mounted analog meters. The analog output can represent one of the
following E300 diagnostic parameters:
• Average %FLA
• %TCU
• Ground Fault Current
• Current Imbalance
• Average L-L Voltage
• Voltage Imbalance
• To ta l kW
• To ta l kVA R
• To ta l kVA
Rockwell Automation Publication 193-UM015D-EN-P - February 201593
Page 94
Chapter 4 System Operation and Configuration
Output SelectionLow RangeHigh Range
Average % FLA0%100%
Scaled Average % FLA0%200%
% TCU0%100%
Ground Fault Current
Internal, 0.50…5.00 A0.50 A5.00 A
External, 0.02…0.10 A0.02 A0.10 A
External, 0.10…0.50 A0.10 A0.50 A
External, 0.20…1.00 A0.20 A1.00 A
External, 1.00…5.00 A1.00 A5.00 A
Current Imbalance0%100%
Average L-L Voltage0V(PT Primary) V
Voltage Imbalance0%100%
Total kW0 kW(FLA1 x PT Primary x 1.732) V
Total kVAR5.25V DC(FLA1 x PT Primary x 1.732) V
Total kVA5.00V DC(FLA1 x PT Primary x 1.732) V
Total Power Factor-50% (Lagging)+50% (Leading)
User-defined Value-3276832767
• To ta l P ow er Fa c tor
• User-defined Value
Table 69 - Analog Output Selection Type
Update Rate
Analog Input Channels
The performance for the input channels of the E300 Analog I/O Expansion
Module is dependent on the filter setting for each channel. The total scan time
for the input channels of the module is determined by adding the conversion time
for all enabled input channels.
Table 70 - Analog Input Channel Conversion Time
Input TypeFilter FrequencyConversion Time
17 Hz153 ms
Current, Volta ge,
2-Wire RTD, Resistance
3-Wire RTD
Example:
• Channel 00 is configured for a 3-wire RTD and 4 Hz filter (conversion
time = 1024 ms).
• Channel 01 is configured for 17Hz voltage (conversion time = 153 ms).
• Channel 02 is configured for 62Hz current (conversion time = 65 ms).
4 Hz512 ms
62 Hz65 ms
470 Hz37 ms
17 Hz306 ms
4 Hz1024 ms
62 Hz130 ms
470 Hz74 ms
94Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 95
System Operation and Configuration Chapter 4
The E300 Analog I/O Expansion Module input channel scan time will be
1242 ms (1024+153+65).
Analog Output Channel
The E300 Analog I/O Expansion Module output channel update rate is 10 ms.
Analog Module 1
Analog Module 1 – Input Channel 00 Type
Analog Module 1 – Input Channel 00 Type (Parameter 437) defines the type of
analog signal that Input Channel 00 of Analog Module 1 will be monitoring.
Table 71 - Analog Module 1 – Input Channel 00 Type (Parameter 437)
ValueAssignmentDescription
0DisabledDisable the analog input
14To20mARead an analog current signal from 4…20 mA
20To20mARead an analog current signal from 0…20 mA
30To10VoltsRead an analog voltage signal from 0…10 V DC
41To5VoltsRead an analog voltage signal from 1…5 V DC
50To5VoltsRead an analog voltage signal from 0…5 V DC
6100Pt385Read a 100 Ω Pt 385 RTD Sensor
7200Pt385Read a 200 Ω Pt 385 RTD Sensor
8500Pt385Read a 500 Ω Pt 385 RTD Sensor
91000Pt385Read a 1000 Ω Pt 385 RTD Sensor
10100Pt3916Read a 100 Ω Pt 3916 RTD Sensor
11200Pt3916Read a 200 Ω Pt 3916 RTD Sensor
12500Pt3916Read a 500 Ω Pt 3916 RTD Sensor
131000Pt3916Read a 1000 Ω Pt 3916 RTD Sensor
1410Cu426Read a 10 Ω Cu 426 RTD Sensor
15100Ni618Read a 100 Ω Ni 618 RTD Sensor
16120Ni672Read a 120 Ω Ni 672 RTD Sensor
17604NiFe518Read a 604Ω NiFe 518 RTD Sensor
18150ohmRead a resistance signal from 0…150 Ω
19750ohmRead a resistance signal from 0…750 Ω
203000ohmRead a resistance signal from 0…3000 Ω
216000ohm
Read a resistance signal from 0…6000 Ω. This setting
can be used with PTC and NTC sensors.
Analog Module 1 – Input Channel 00 Format
Analog Module 1 – Input Channel 00 Format (Parameter 438) defines the data
format for how the analog reading is reported.
Rockwell Automation Publication 193-UM015D-EN-P - February 201595
Page 96
Chapter 4 System Operation and Configuration
Table 72 - Analog Module 1 – Input Channel 00 Format (Parameter 438)
ValueAssignmentDescription
0EngUnitsEngineering Units (mA, V, °C, °F, or Ω)
1EngUnitsTimes10Engineering Units x 10 (mA, V, °C, °F, or Ω)
Analog Module 1 – Input Channel 00 Temperature Unit
Analog Module 1 – Input Channel 00 Temperature Unit (Parameter 439)
defines the temperate unit for RTD sensor readings.
Table 73 - Analog Module 1 – Input Channel 00 Temperature Unit (Parameter 439)
ValueAssignmentDescription
0DegreesCReport RTD Temperature Data in °C
1DegreesFReport RTD Temperature Data in °F
Analog Module 1 – Input Channel 00 Filter Frequency
Analog Module 1 – Input Channel 00 Filter Frequency (Parameter 440) defines
update rate for the analog module’s input channels.
Table 74 - Analog Module 1 – Input Channel 00 Filter Frequency (Parameter 440)
ValueAssignmentDescription
017 HzAnalog to D igital Conversion Update Frequency of 17 Hz
14 HzAnalog to Digital Conversion Update Frequency of 4 Hz
262 HzAnalog to D igital Conversion Update Frequency of 62 Hz
3470 HzAnalog to Digital Conversion Update Frequency of 470Hz
Analog Module 1 – Input Channel 00 Open Circuit State
Analog Module 1 – Input Channel 00 Open Circuit State (Parameter 441)
defines what the input channel reports when the input channel has an open
circuit. Open circuit detection is always enabled for this input channel.
Table 75 - Analog Module 1 – Input Channel 00 Open Circuit State (Parameter 441)
ValueAssignmentDescription
0UpscaleRepor ts the high limit of the input channel type
1DownscaleReports the low limit of the input channel type
2ZeroReports zero
Analog Module 1 – Input Channel 00 RTD Type Enable
Analog Module 1 – Input Channel 00 RTD Type Enable (Parameter 442)
defines the type of RTD to monitor when the input channel type is configured to
scan an RTD sensor.
96Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 97
System Operation and Configuration Chapter 4
Table 76 - Analog Module 1 – Input Channel 00 RTD Type Enable (Parameter 442)
ValueAssignmentDescription
03-WireScan a 3-wire RTD sensor
12-WireScan a 2-wire RTD sensor
Analog Module 1 – Input Channel 01 Type
Analog Module 1 – Input Channel 01 Type (Parameter 446) defines the type of
analog signal that Input Channel 01 of Analog Module 1 will be monitoring.
Table 77 - Analog Module 1 – Input Channel 01 Type (Parameter 446)
ValueAssignmentDescription
0DisabledDisable the analog input
14To20mARead an analog current signal from 4…20 mA
20To20mARead an analog current signal from 0…20 mA
30To10VoltsRead an analog voltage signal from 0…10 V DC
41To5VoltsRead an analog voltage signal from 1…5 V DC
50To5VoltsRead an analog voltage signal from 0…5 V DC
6100Pt385Read a 100 Ω Pt 385 RTD Sensor
7200Pt385Read a 200 Ω Pt 385 RTD Sensor
8500Pt385Read a 500 Ω Pt 385 RTD Sensor
91000Pt385Read a 1000 Ω Pt 385 RTD Sensor
10100Pt3916Read a 100 Ω Pt 3916 RTD Sensor
11200Pt3916Read a 200 Ω Pt 3916 RTD Sensor
12500Pt3916Read a 500 Ω Pt 3916 RTD Sensor
131000Pt3916Read a 1000 Ω Pt 3916 RTD Sensor
1410Cu426Read a 10 Ω Cu 426 RTD Sensor
15100Ni618Read a 100 Ω Ni 618 RTD Sensor
16120Ni672Read a 120 Ω Ni 672 RTD Sensor
17604NiFe518Read a 604Ω NiFe 518 RTD Sensor
18150ohmRead a resistance signal from 0…150 Ω
19750ohmRead a resistance signal from 0…750 Ω
203000ohmRead a resistance signal from 0…3000 Ω
216000ohm
Read a resistance signal from 0…6000 Ω. This
setting can be used with PTC and NTC sensors.
Analog Module 1 – Input Channel 01 Format
Analog Module 1 – Input Channel 01 Format (Parameter 447) defines the data
format for howthe analog reading is reported.
Table 78 - Analog Module 1 – Input Channel 01 Format (Parameter 447)
ValueAssignmentDescription
0EngUnitsEngineering Units (mA, V, °C, °F, or Ω)
1EngUnitsTimes10Engineering Units x 10 (mA, V, °C, °F, or Ω)
Rockwell Automation Publication 193-UM015D-EN-P - February 201597
Page 98
Chapter 4 System Operation and Configuration
Analog Module 1 – Input Channel 01 Temperature Unit (Parameter 448)
defines the temperate unit for RTD sensor readings.
Table 79 - Analog Module 1 – Input Channel 01 Temperature Unit (Parameter 448)
ValueAssignmentDescription
0DegreesCReport RTD Temperature Data in °C
1DegreesFReport RTD Temperature Data in °F
Analog Module 1 – Input Channel 01 Filter Frequency
Analog Module 1 – Input Channel 01 Filter Frequency (Parameter 449) defines
update rate for the analog module’s input channels.
Table 80 - Analog Module 1 – Input Channel 01 Filter Frequency (Parameter 449)
ValueAssignmentDescription
017 HzAnalog to Digital Conversion Update Frequency of 17 Hz
14 HzAnalog to Digital Conversion Update Frequency of 4 Hz
262 HzAnalog to Digital Conversion Update Frequency of 62 Hz
3470 HzAnalog to Digital Conversion Update Frequency of 470Hz
Analog Module 1 – Input Channel 01 Open Circuit State
Analog Module 1 – Input Channel 01 Open Circuit State (Parameter 450)
defines what the input channel reports when the input channel has an open
circuit. Open circuit detection is always enabled for this input channel.
Table 81 - Analog Module 1 – Input Channel 01 Open Circuit State (Parameter 450)
ValueAssignmentDescription
0UpscaleReports the high limit of the input channel type
1DownscaleReports the low limit of the input channel type
2ZeroReports zero
Analog Module 1 – Input Channel 01 RTD Type Enable
Analog Module 1 – Input Channel 01 RTD Type Enable (Parameter 451)
defines the type of RTD to monitor when the input channel type is configured to
scan an RTD sensor.
Table 82 - Analog Module 1 – Input Channel 01 RTD Type Enable (Parameter 451)
ValueAssignmentDescription
03-WireScan a 3-wire RTD sensor
12-WireScan a 2-wire RTD sensor
Analog Module 1 – Input Channel 02 Type
Analog Module 1 – Input Channel 02 Type (Parameter 455) defines the type of
analog signal that Input Channel 02 of Analog Module 1 will be monitoring.
98Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 99
System Operation and Configuration Chapter 4
Table 83 - Analog Module 1 – Input Channel 02 Type (Parameter 455)
ValueAssignmentDescription
0DisabledDisable the analog input
14To20mARead an analog current signal from 4…20 mA
20To20mARead an analog current signal from 0…20 mA
30To10VoltsRead an analog voltage signal from 0…10 V DC
41To5VoltsRead an analog voltage signal from 1…5 V DC
50To5VoltsRead an analog voltage signal from 0…5 V DC
6100Pt385Read a 100 Ω Pt 385 RTD Sensor
7200Pt385Read a 200 Ω Pt 385 RTD Sensor
8500Pt385Read a 500 Ω Pt 385 RTD Sensor
91000Pt385Read a 1000 Ω Pt 385 RTD Sensor
10100Pt3916Read a 100 Ω Pt 3916 RTD Sensor
11200Pt3916Read a 200 Ω Pt 3916 RTD Sensor
12500Pt3916Read a 500 Ω Pt 3916 RTD Sensor
131000Pt3916Read a 1000 Ω P t 3916 RTD Sensor
1410Cu426Read a 10 Ω Cu 426 RTD Sensor
15100Ni618Read a 100 Ω Ni 618 RTD Sensor
16120Ni672Read a 120 Ω Ni 672 RTD Sensor
17604NiFe518Read a 604Ω NiFe 518 RTD Sensor
18150ohmRead a resistance signal from 0…150 Ω
19750ohmRead a resistance signal from 0…750 Ω
203000ohmRead a resistance signal from 0…3000 Ω
216000ohm
Read a resistance signal from 0…6000 Ω. This
setting can be used with PTC and NTC sensors.
Analog Module 1 – Input Channel 02 Format
Analog Module 1 – Input Channel 02 Format (Parameter 456) defines the data
format for how the analog reading is reported.
Table 84 - Analog Module 1 – Input Channel 02 Format (Parameter 456)
ValueAssignmentDescription
0EngUnitsEngineering Units (mA, V, °C, °F, or Ω)
1EngUnitsTimes10Engineering Units x 10 (mA, V, °C, °F, or Ω)
2RawProportionalRaw / Proportional (-32768…32767)
3ScaledForPIDScaled for PID (0 …16383)
Analog Module 1 – Input Channel 02 Temperature Unit
Analog Module 1 – Input Channel 02 Temperature Unit (Parameter 457)
defines the temperate unit for RTD sensor readings.
Table 85 - Analog Module 1 – Input Channel 02 Temperature Unit (Parameter 457)
ValueAssignmentDescription
0DegreesCReport RTD Temperature Data in °C
1DegreesFReport RTD Temperature Data in °F
Rockwell Automation Publication 193-UM015D-EN-P - February 201599
Page 100
Chapter 4 System Operation and Configuration
Analog Module 1 – Input Channel 02 Filter Frequency
Analog Module 1 – Input Channel 02 Filter Frequency (Parameter 458) defines
update rate for the analog module’s input channels.
Table 86 - Analog Module 1 – Input Channel 02 Filter Frequency (Parameter 458)
ValueAssignmentDescription
017 HzAnalog to Digital Conversion Update Frequency of 17 Hz
14 HzAnalog to Digital Conversion Update Frequency of 4 Hz
262 HzAnalog to Digital Conversion Update Frequency of 62 Hz
3470 HzAnalog to Digital Conversion Update Frequency of 470Hz
Analog Module 1 – Input Channel 02 Open Circuit State
Analog Module 1 – Input Channel 02 Open Circuit State (Parameter 459)
defines what the input channel reports when the input channel has an open
circuit. Open circuit detection is always enabled for this input channel.
Table 87 - Analog Module 1 – Input Channel 02 Open Circuit State (Parameter 459)
ValueAssignmentDescription
0UpscaleReports the high limit of the input channel type
1DownscaleRepor ts the low limit of the input channel type
2ZeroRepor ts zero
Analog Module 1 – Input Channel 02 RTD Type Enable
Analog Module 1 – Input Channel 02 RTD Type Enable (Parameter 460)
defines the type of RTD to monitor when the input channel type is configured to
scan an RTD sensor.
Table 88 - Analog Module 1 – Input Channel 02 RTD Type Enable (Parameter 460)
ValueAssignmentDescription
03-WireScan a 3-wire RTD sensor
12-WireScan a 2-wire RTD sensor
AnalogModule1–OutputChannel00Type
Analog Module 1 – Output Channel 00 Type (Parameter 464) defines the type
of analog signal that Output Channel 00 of Analog Module 1 will be providing.
Table 89 - Analog Module 1 – Output Channel 00 Type (Parameter 464)
ValueAssignmentDescription
0DisabledDisable the analog input
14To20mAProvide an analog current signal from 4…20 mA
20To20mAProvide an analog current signal from 0…20 mA
30To10VoltsProvide an analog voltage signal from 0…10 V DC
41To5VoltsProvide an analog voltage signal from 1…5 V DC
50To5VoltsProvide an analog voltage signal from 0…5 V DC
100Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.