Rockwell Automation Allen-Bradley E300 User Manual

Page 1
User Manual

E300 Electronic Overload Relay

Bul. 193/592
Page 2

Important User Information

IMPORTANT
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Page 3
Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table of Contents Chapter 1

Table of Contents

Product Overview
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Modular Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Diagnostic Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Simplified Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Sensing Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Control Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Communication Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Digital Expansion Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Analog Expansion Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Operator Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Module Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Sensing Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Control Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Communication Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Optional Add-On Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Optional Expansion I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Optional Operator Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Optional Expansion Bus Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . 20
Protection Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Standard Current-Based Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Ground Fault Current-based Protection. . . . . . . . . . . . . . . . . . . . . . . . 21
Voltage- and Power-based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Applications: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Installation and Wiring
Chapter 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Receiving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Unpacking/Inspecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Storing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Base Relay Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Control Module to Sensing Module Assembly. . . . . . . . . . . . . . . . . . . . . . 25
Communication Module to Control Module Assembly . . . . . . . . . . . . . 26
Expansion Bus Peripherals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Expansion Bus Digital and Analog I/O Modules and Power Supply
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Expansion Bus Operator Station Installation . . . . . . . . . . . . . . . . . . . . . . . 28
Expansion Bus Network Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Starter Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
100-C09…-C55 Starter Assembly Installation . . . . . . . . . . . . . . . . . . 30
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 3
Page 4
Table of Contents
Starter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
DIN Rail / Panel Mount Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Expansion Bus Peripherals Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Sensing Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Expansion Digital Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Expansion Analog Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Expansion Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Short-Circuit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fuse Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Typical Motor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
External Line Current Transformer Application . . . . . . . . . . . . . . . . . . . . 48
Current Transformer Ratio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Control Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Full-Voltage Non-Reversing Starter (with Network Control). . . . . 52
Full-Voltage Reversing Starter (with Network Control). . . . . . . . . . 53
Diagnostic Station
System Operation and Configuration
Chapter 3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Navigation Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Displaying a Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Parameter Group Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Linear List Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
System Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Editing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Editing a Configuration Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Editing a Numeric Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Editing a Bit Enumerated Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Programmable Display Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Display Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Stopping the Display Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Automatic Trip and Warning Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Chapter 4
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Device Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Administration Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Operation Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Invalid Configuration Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Option Match . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Enable Option Match Protection Trip (Parameter 186). . . . . . . . . . 67
Enable Option Match Protection Warning (Parameter 192) . . . . . 68
4 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 5
Table of Contents
Control Module Type (Parameter 221) . . . . . . . . . . . . . . . . . . . . . . . . 68
Sensing Module Type (Parameter 222). . . . . . . . . . . . . . . . . . . . . . . . . 69
Communication Module Type (Parameter 223) . . . . . . . . . . . . . . . . 69
Operator Station Type (Parameter 224). . . . . . . . . . . . . . . . . . . . . . . . 70
Digital I/O Expansion Module 1 Type (Parameter 225) . . . . . . . . . 70
Digital I/O Expansion Module 2 Type (Parameter 226) . . . . . . . . . 71
Digital I/O Expansion Module 3 Type (Parameter 227) . . . . . . . . . 71
Digital I/O Expansion Module 4 Type (Parameter 228) . . . . . . . . . 71
Analog I/O Expansion Module 1 Type (Parameter 229) . . . . . . . . . 72
Analog I/O Expansion Module 2 Type (Parameter 230) . . . . . . . . . 73
Analog I/O Expansion Module 3 Type (Parameter 231) . . . . . . . . . 73
Analog I/O Expansion Module 4 Type (Parameter 232) . . . . . . . . . 74
Option Match Action (Parameter 233) . . . . . . . . . . . . . . . . . . . . . . . . 74
Security Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Device Configuration Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Device Reset Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Firmware Update Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Security Configuration Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
I/O Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Input Pt00 Assignment (Parameter 196) . . . . . . . . . . . . . . . . . . . . . . . 76
Input Pt01 Assignment (Parameter 197) . . . . . . . . . . . . . . . . . . . . . . . 77
Input Pt02 Assignment (Parameter 198) . . . . . . . . . . . . . . . . . . . . . . . 77
Input Pt03 Assignment (Parameter 199) . . . . . . . . . . . . . . . . . . . . . . . 78
Input Pt04 Assignment (Parameter 200) . . . . . . . . . . . . . . . . . . . . . . . 78
Input Pt05 Assignment (Parameter 201) . . . . . . . . . . . . . . . . . . . . . . . 79
Output Pt00 Assignment (Parameter 202) . . . . . . . . . . . . . . . . . . . . . 80
Output Pt01 Assignment (Parameter 203) . . . . . . . . . . . . . . . . . . . . . 81
Output Pt02 Assignment (Parameter 204) . . . . . . . . . . . . . . . . . . . . . 82
Expansion Bus Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Expansion Bus Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Expansion Bus Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Emergency Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Diagnostic Station User-defined Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
User-defined Screen 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
User-defined Screen 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
User-defined Screen 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
User-defined Screen 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Display Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Analog I/O Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Analog Input Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Analog Output Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Update Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Analog Module 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Analog Module 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Analog Module 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Analog Module 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Introduction to Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 5
Page 6
Table of Contents
Chapter 5
Operating Modes
Protective Trip and Warning Functions
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Overload (Network). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Monitor (Custom) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Chapter 6
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Current-based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Phase Loss Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Ground Fault Current Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Stall Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Jam Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Underload Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Current Imbalance Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Line Under Current Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Line Over Current Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Line Loss Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Voltage-based Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Under Voltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Over Voltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Voltage Imbalance Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Phase Rotation Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Frequency Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Power-based Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Real Power (kW) Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Reactive Power (kVAR) Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Apparent Power (kVA) Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Power Factor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Control-Based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Test Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Operator Station Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Remote Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Start Inhibit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Hardware Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Configuration Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
Option Match. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
Expansion Bus Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
Nonvolatile Storage Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
Test Mode Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Analog-based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Analog Module 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Analog Module 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
Analog Module 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
Analog Module 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
6 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 7
Chapter 7
Table of Contents
Commands
Metering and Diagnostics
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Trip Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Configuration Preset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Factory Defaults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
Clear Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
Clear Operating Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Clear History Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Clear %TCU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Clear kWh. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Clear kVARh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
Clear kVAh. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
Clear Max kW Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
Clear Max kVAR Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
Clear Max kVA Demand. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
Clear All. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
Chapter 8
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
Device Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
Percent Thermal Capacity Utilized . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
Time to Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Time To Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Current Trip Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Voltage Trip Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
Power Trip Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Control Trip Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Current Warning Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Voltage Warning Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Power Warning Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Control Warning Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Input Status 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Input Status 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Output Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
Operator Station Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
Device Status 0. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
Device Status 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
Firmware Revision Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
Control Module ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
Sensing Module ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
Operator Station ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
Expansion Digital Module ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318
Operating Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318
Starts Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
Starts Available. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
Time to Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 7
Page 8
Table of Contents
Year . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Month. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Day. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Hour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
Minute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
Second. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322
Invalid Configuration Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322
Invalid Configuration Cause. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322
Mismatch Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
Current Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
L1 Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
L2 Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324
L3 Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324
Average Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324
L1 Percent FLA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
L2 Percent FLA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
L3 Percent FLA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
Average Percent FLA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
Ground Fault Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
Current Imbalance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
Voltage Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
L1-L2 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
L2-L3 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328
Average L-L Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328
L1-N Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
L2-N Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
L3-N Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
Average L-N Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
Voltage Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
Phase Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
Power Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
Power Scale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
L1 Real Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
L2 Real Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
L3 Real Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
Total Real Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333
L1 Reactive Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333
L2 Reactive Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
L3 Reactive Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Total Reactive Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
L1 Apparent Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
L2 Apparent Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
L3 Apparent Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
Total Apparent Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
L1 Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
L2 Power Factor Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
8 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 9
Table of Contents
L3 Power Factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
Total Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
Energy Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
kWh 109 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
kWh 106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
kWh 103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
kWh 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
kWh 10-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
kVARh Consumed 109 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
kVARh Consumed 106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
kVARh Consumed 103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
kVARh Consumed 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342
kVARh Consumed 10-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342
kVARh Generated 109 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342
kVARh Generated 106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
kVARh Generated 103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
kVARh Generated 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344
kVARh Generated 10-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344
kVARh Net 109. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344
kVARh Net 106. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345
kVARh Net 103. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345
kVARh Net 100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
kVARh Net 10-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
kVAh 109 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
kVAh 106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
kVAh 103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
kVAh 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348
kVAh 10-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348
kW Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348
Max kW Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349
kVAR Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349
Max kVAR Demand. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349
kVA Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349
Max kVA Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
Analog Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
Analog Module 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
Analog Module 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352
Analog Module 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354
Analog Module 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355
Trip / Warning History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
The E300 Electronic Overload Relay provides a trip and warning
history in which the last five trips and last five warnings are recorded
into nonvolatile storage. A mask is available to limit which trip and
warning events are logged to the history's memory. . . . . . . . . . . . . . 357
Trip History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Warning History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
Trip Snapshot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 9
Page 10
Table of Contents
EtherNet/IP Communications
Trip Snapshot L1-L2 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
Trip Snapshot L2-L3 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
Trip Snapshot L3-L1 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
Trip Snapshot Total Real Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
Trip Snapshot Total Reactive Power . . . . . . . . . . . . . . . . . . . . . . . . . . 370
Trip Snapshot Total Apparent Power . . . . . . . . . . . . . . . . . . . . . . . . . 371
Trip Snapshot Total Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371
Chapter 9
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Network Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Determining Network Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375
Setting the IP Network Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
EtherNet/IP Node Address Selection Switches. . . . . . . . . . . . . . . . . 376
Assign Network Parameters via the BOOTP/ DHCP Utility. . . . 377
Assign Network Parameters Via a Web Browser and MAC Scanner
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379
Other Factors to Consider When Assigning Network Parameters 379
Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
Web Server Security and System Password . . . . . . . . . . . . . . . . . . . . . 380
Permanently Enabling the Web Server. . . . . . . . . . . . . . . . . . . . . . . . . 382
Duplicate IP Address Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 383
Behavior of Modules With Duplicate IP Addresses . . . . . . . . . . . . . 383
DNS Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 384
Electronic Data Sheet (EDS) File Installation . . . . . . . . . . . . . . . . . . . . . . 384
Download the EDS File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385
View and Configure Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
Viewing Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
Editing Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
Automation Controller Communications . . . . . . . . . . . . . . . . . . . . . . . . . 391
I/O Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
Preconfigured E300 Electronic Overload Relay Logix Integration with
an Add-On Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392
Offline E300 Electronic Overload Relay Logix Integration with Add-
on Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408
Offline E300 Electronic Overload Relay Integration with a Generic
Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
E-mail/Text. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 420
E-mail Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
Text Notifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
Chapter 10
Firmware Updates
10 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
Firmware Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
Page 11
Table of Contents
Updating Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 426
E300 Firmware Update Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
Control Module Boot Code Firmware Update. . . . . . . . . . . . . . . . . 433
Control Module Application Code Firmware Update . . . . . . . . . . 436
Control Module Uncompressed EtherNet/IP EDS File Firmware
Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
Control Module Compressed EtherNet/IP EDS File Firmware
Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 441
Control Module Compressed DeviceNet EDS File Firmware Update 443
Completed Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446
Chapter 11
Troubleshooting
Specifications
Parameter List
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Advisory LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Power LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Trip/Warn LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 448
Resetting a Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 450
Trip/Warn LED Troubleshooting Procedures. . . . . . . . . . . . . . . . . . . . . 450
Appendix A
Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453
Low Voltage Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Electromagnetic Compatibility Specifications . . . . . . . . . . . . . . . . . . . . . 457
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
Protection Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
Appendix B
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
EtherNet/IP Information
Appendix C
Common Industrial Protocol (CIP) Objects . . . . . . . . . . . . . . . . . . . . . . 503
Identity Object — CLASS CODE 0x0001 . . . . . . . . . . . . . . . . . . . . 504
Message Router — CLASS CODE 0x0002. . . . . . . . . . . . . . . . . . . . 506
Assembly Object — CLASS CODE 0x0004. . . . . . . . . . . . . . . . . . . 506
Instance 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507
Instance 50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508
Instance 120 - Configuration Assembly Revision 2 . . . . . . . . . . . . . 508
Instance 120 - Configuration Assembly Revision 1 . . . . . . . . . . . . . 518
Instance 144 – Default Consumed Assembly . . . . . . . . . . . . . . . . . . 518
Instance 198 - Current Diagnostics Produced Assembly . . . . . . . . 518
Instance 199 - All Diagnostics Produced Assembly . . . . . . . . . . . . . 520
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 11
Page 12
Table of Contents
Connection Object — CLASS CODE 0x0005. . . . . . . . . . . . . . . . . 522
Discrete Input Point Object — CLASS CODE 0x0008. . . . . . . . . 525
Discrete Output Point Object — CLASS CODE 0x0009. . . . . . . 526
Analog Input Point Object — CLASS CODE 0x000A . . . . . . . . . 528
Parameter Object — CLASS CODE 0x000F . . . . . . . . . . . . . . . . . . 529
Parameter Group Object — CLASS CODE 0x0010. . . . . . . . . . . . 530
Discrete Output Group Object — CLASS CODE 0x001E . . . . . 530
Control Supervisor Object — CLASS CODE 0x0029 . . . . . . . . . . 531
Overload Object — CLASS CODE 0x002c . . . . . . . . . . . . . . . . . . . 532
Base Energy Object — CLASS CODE 0x004E. . . . . . . . . . . . . . . . . 532
Electrical Energy Object — CLASS CODE 0x004F . . . . . . . . . . . . 534
Wall Clock Time Object — CLASS CODE 0x008B . . . . . . . . . . . 536
DPI Fault Object — CLASS CODE 0x0097. . . . . . . . . . . . . . . . . . . 537
DPI Warning Object — CLASS CODE 0x0098 . . . . . . . . . . . . . . . 541
MCC Object — CLASS CODE 0x00C2. . . . . . . . . . . . . . . . . . . . . . 544
12 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 13
Product Overview
Chapter 1

Overview

The E300™ Electronic Overload Relay is a microprocessor-based electronic overload relay that is designed to help protect three-phase or single-phase AC electric induction motors that are rated from 0.5…65,000 A. Its modular design, communication options, diagnostic information, simplified wiring, and integration into Logix makes the E300 the ideal overload for motor control applications in an automation system. The E300 Electronic Overload Relay provides flexibility, reduces engineering time, and maximizes uptime for important motor starter applications.

Modular Design

You can select the specific options that you need for your motor starter application. The E300 Electronic Overload Relay consists of three modules: sensing, control, and communications. You can customize each of the three with accessories to tailor the electronic motor overload for your application’s exact needs.
Wide current range
Sensing capabilities (Current, Ground Fault Current, and/or Voltage)
Expansion I/O
Operator interfaces

Communication Options

You can select from multiple communication options that integrate with Logix­based control systems. Developers can easily add the E300 Electronic Overload Relay to Logix-based control systems using Integrated Architecture tools like Add-on Profiles, Add-on Instructions, and Faceplates.
EtherNet/IP (DLR)
DeviceNet
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 13
Page 14
Chapter 1 Product Overview

Diagnostic Information

The E300 Electronic Overload Relay provides a wide variety of diagnostic information to monitor motor performance, proactively alert you to possible motor issues, or identify the reason for an unplanned shutdown. Information includes:
Voltage, Current, and Energy
Tri p / War ning Hi sto ri es
% Thermal Capacity Utilization
Time to Trip
Time to Reset
Operational Hours
Number of Starts
Tri p S naps ho t

Simplified Wiring

The E300 Electronic Overload Relay provides an easy means to mount to both IEC and NEMA Allen-Bradley contactors. A contactor coil adapter is available for the 100-C contactor, which allows the you to create a functional motor starter with only two control wires.
14 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 15
Product Overview Chapter 1
193 - ESM - VIG - 30A - C23 592
Module Type
ESM Sensing Module
Sensing Module Type
VIG Current, Ground Fault Current,
Voltage, and Power IG Current and Ground Fault Current ICurrent
Sensing Module Mounting Style
C23 Mounts to 100-C09…-C23 Contactor C55 Mounts to 100-C30…-C55 Contactor C97 Mounts to 100-C60…-C97 Contactor D180 Mounts to 100-D115…-D180 Contactor S2 Mounts to Bulletin 500 NEMA Size 0-2 Contactor S3 Mounts to Bulletin 500 NEMA Size 3 Contactor S4 Mounts to Bulletin 500 NEMA Size 4 Contactor T DIN Rail / Panel Mount with Power Terminals E3T Replacement DIN Rail / Panel Mount with Power Terminals for an E3 Plus Panel Mount Adapter P DIN Rail / Panel Mount with Pass-thru Power Conductors CT DIN Rail / Panel Mount with Pass-thru Power Conductors (used with External CTs)
Bulletin Number
193 IEC Overload Relay 592 NEMA Overload Relay
Sensing Current Range
30A 0.5…30 A 60A 6…60 A 100A 10…100 A 200A 20…200 A
193 - EIO - 43 - 120
Module Type
EIO I/O Only Control Module EIOGP I/O and Protection Control Module
(External Ground Fault Sensing and PTC)
I/O Count
63 6 Inputs / 3 Relay Outputs 43 4 Inputs / 3 Relay Outputs 42 4 Inputs / 2 Relay Outputs 22 2 Inputs / 2 Relay Outputs
Bulletin Number
193 IEC Overload Relay
Control Voltage
24D 24V DC 120 110…120V AC, 50/60 Hz 240 220…240V AC, 50/60 H
193 - ECM - ETR
Module Type
ECM Communication Module
Communication Type
ETR EtherNet/IP with Dual Ethernet Ports DNT DeviceNet
Bulletin Number
193 IEC Overload Relay

Catalog Number Explanation

E300 Electronic Overload Relay modules have their own catalog number.

Sensing Module

Control Module

Communication Module

Rockwell Automation Publication 193-UM015D-EN-P - February 2015 15
Page 16
Chapter 1 Product Overview
193 - EXP - DIO - 42 - 120
Module Type
EXP Expansion Module
I/O Type
DIO Digital I/O
Bulletin Number
193 IEC Overload Relay
Communication Type
120 110…120V AC, 50/60 Hz Inputs 240 220…240V AC, 50/60 Hz Inputs 24D 24V DC Inputs
I/O Count
42 4 Inputs / 2 Relay Outputs
193 - EXP - AIO - 31
Module Type
EXP Expansion Module
I/O Type
AIO Analog I/O
Bulletin Number
193 IEC Overload Relay
I/O Count
31 3 Universal Analog Inputs / 1 Analog Output
193 - EOS - SCS
Module Type
EOS Operator Station
I/O Type
SCS Starter Control Station SDS Starter Diagnostic Station
Bulletin Number
193 IEC Overload Relay
193 - EXP - PS - AC
Module Type
EXP Expansion Module
Func tion Type
PS Expansion Bus Power Supply
Bulletin Number
193 IEC Overload Relay
Supply Voltage
AC 110-240V AC, 50/60Hz control voltage DC 24V DC control voltage

Digital Expansion Module

Analog Expansion Module

Operator Station

Power Supply

16 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 17
Product Overview Chapter 1

Module Description

The E300 Electronic Overload Relay is comprised of three modules. All three modules are required to make a functional overload relay.
Sensing Module
Control Module
Communication Module

Sensing Module

Figure 1 - Sensing Module
The sensing module electronically samples data about the current, voltage, power, and energy that are consumed by the electric motor internal to the module. You can choose from one of three varieties of the sensing modules depending on the motor diagnostic information that is needed for the motor protection application:
Current Sensing
Current and Ground Fault Current Sensing
Current, Ground Fault Current, Voltage, and Power Sensing
The current ranges for each of three varieties of sensing module are as follows:
0.5…30 A
6…60 A
10…100 A
20…200 A
You can choose how the sensing module mechanically mounts inside the electrical enclosure. The following mounting mechanisms are available for the sensing module.
Mount to the load side of an Allen-Bradley Bulletin 100 IEC Contactor
Mount to the load side of an Allen-Bradley Bulletin 500 NEMA
Contactor
DIN Rail / Panel Mount with power terminals
Replacement DIN Rail / Panel Mount with power terminals for an
Allen-Bradley E3 Plus panel mount adapter
DIN Rail / Panel Mount with pass-thru power conductors
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 17
Page 18
Chapter 1 Product Overview

Control Module

Figure 2 - Control Module
The control module is the heart of the E300 Electronic Overload Relay and can attach to any sensing module. The control module performs all protection and motor control algorithms and contains the native I/O for the system. The control module has two varieties:
I/O only
I/O and protection (PTC and External Ground Fault Current Sensing)
The control module is offered in three control voltages:
110…120V AC, 50/60Hz
220…240V AC, 50/60Hz
24V DC
External control voltage is required to power the E300 Electronic Overload Relay and activate the digital inputs.

Communication Module

Figure 3 - Communication Module
The communication module allows the E300 Electronic Overload Relay to be integrated into an automation system, and it can attach to any control module. All communication modules allow you to set the node address with rotary turn
18 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 19
Product Overview Chapter 1
dials, and it provides diagnostic status indicators to provide system status at the panel. The E300 Electronic Overload Relay supports two network protocols:
EtherNet/IP
DeviceNet
The E300 EtherNet/IP Communication Module has two RJ45 connectors that function as a switch. You can daisy chain multiple E300 Electronic Overload Relays with Ethernet cable, and the module supports a Device Level Ring (DLR).

Optional Add-On Modules

Optional Expansion I/O

The E300 Electronic Overload Relay allows you to add more digital and analog I/O to the system via the E300 Electronic Overload Relay Expansion Bus if the native I/O count is not sufficient for the application on the base relay. You can add any combination of up to four Digital I/O Expansion Modules that have four inputs (120V AC, 240V AC, or 24V DC) and two relay outputs.
You can also add up to four Analog I/O Expansion Modules, which have three independent universal analog inputs and one isolated analog output. The Analog I/O Expansion Modules require Control Module firmware v3.000 or higher. The independent universal analog inputs can accept the following signals:
4…20 mA
0…20 mA
0…10V DC
1…5V DC
0…5V DC
RTD Sensors (Pt 385, Pt 3916, Cu 426, Ni 618, Ni 672, and NiFe 518)
Resistance (150 , 750 , 3000 , and 6000 )
The isolated analog output can be programmed to reference a traditional analog signal (4…20 mA, 0…20 mA, 0…10V DC, 1…5V, or 0…10V) to represent the following diagnostic values:
Average %FLA
%TCU
Ground Fault Current
Current Imbalance
Average L-L Voltage
Voltage Imbalance
To ta l kW
To ta l kVA R
To ta l kVA
To ta l P ow er Fa c tor
User-defined Value
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 19
Page 20
Chapter 1 Product Overview
Control Station Diagnostic Station

Optional Operator Station

Figure 4 - Operator Stations
Power LED
Trip / Warn LED
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Escape
Up
Select
ESC
SELECT
0
RESET
Enter
Down
Stop
LOCAL
REMOTE
Reset
Power LED
Trip / Warn LED
0
RESET
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Stop
LOCAL
REMOTE
Reset
The E300 Electronic Overload Relay offers you the capability to add one operator interface to the Expansion Bus. You can choose between two types of operator stations: Control Station or a Diagnostic Station. Both types of operator stations mount into a standard 22 mm push button knockout, and they provide diagnostic status indicators that allow you to view the status of the E300 Electronic Overload Relay from the outside of an electrical enclosure. Both operator stations provide push buttons that can be used for motor control logic, and they both can be used to upload and download parameter configuration data from the base relay.
The Diagnostic Station contains a display and navigation buttons that allows you to view and edit parameters in the base relay. The Diagnostic Station requires Control Module firmware v3.000 or higher.

Optional Expansion Bus Power Supply

Figure 5 - Expansion Bus Power Supply
The E300 Electronic Overload Relay expansion bus provides enough current to operate a system that has (1) Digital Expansion Module and (1) Operator Station. An E300 Electronic Overload Relay system that contains more expansion modules needs supplemental current for the Expansion Bus. The E300 Electronic Overload Relay offers you two types of Expansion Bus Power Supplies: AC (110…240V AC, 50/60 Hz) and DC (24V DC). One Expansion
20 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 21
Product Overview Chapter 1
Bus Power Supply supplies enough current for a fully loaded E300 Electronic Overload Relay Expansion Bus (four Digital Expansion Modules, four Analog Expansion Modules, and one Operator Station). You can use either Expansion Bus Power Supply with any combination of Digital and Analog Expansion Modules.

Protection Features

Standard Current-Based Protection

All versions of the E300 Electronic Overload Relay provide the following motor protection functions:
Thermal Overload (51)
Phase Loss
Current Imbalance (46)
Undercurrent – load loss (37)
Overcurrent – load jam (48)
Overcurrent – load stall
Start Inhibit (66)

Ground Fault Current-based Protection

The E300 Electronic Overload Relay sensing modules and control modules with a ground fault current option provides the following motor protection function:
Ground Fault – zero sequence method (50N)

Voltage- and Power-based Protection

The E300 Electronic Overload Relay sensing modules with voltage sensing provides the following motor protection functions:
Undervoltage (27)
Overvoltage (59)
Phase Reversal (47) – voltage-based
Over and Under Frequency (81) – voltage-based
Voltage Imbalance (46)
Over and Under Power (37)
Over and Under Leading/Lagging Power Factor (55)
Over and Under Reactive Power Generated
Over and Under Reactive Power Consumed
Over and Under Apparent Power
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 21
Page 22
Chapter 1 Product Overview

Applications:

The E300 Electronic Overload Relay can be used with the following across the line starter applications:
Non-reversing starter
Reversing starter
Wye (Star) / Delta starter
Two -s pe ed m ot or s
Low and medium voltage with two or three potential transformers
With or without Phase current transformers
With or without zero-sequence core balanced current transformer
22 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 23
Installation and Wiring
Chapter 2

Introduction

Receiving

Unpacking/Inspecting

Storing

This chapter provides instructions for receiving, unpacking, inspecting, and storing the E300™ Electronic Overload Relay. Assembly, installation, and wiring instructions for common applications are also included in this chapter.
It is your responsibility to thoroughly inspect the equipment before accepting the shipment from the freight company. Check the item(s) received against the purchase order. If any items are damaged, it is your responsibility not to accept delivery until the freight agent has noted the damage on the freight bill. If any concealed damage is found during unpacking, it is again your responsibility to notify the freight agent. The shipping container must be left intact and the freight agent should be requested to make a visual inspection of the equipment.
Remove all packing material from around the E300 Electronic Overload Relay. After unpacking, check the item’s nameplate catalog number against the purchase order.
The E300 Electronic Overload Relay should remain in its shipping container before installation. If you will not use the equipment immediately, you must store it according to the following instructions to maintain warranty coverage:
Store in a clean, dry location.
Store within an ambient temperature range
of -40…+85 °C (-40…+185 °F).
Store within a relative humidity range of 0…95%, non-condensing.
Do not store where the device could be exposed to a corrosive atmosphere.
Do not store in a construction area.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 23
Page 24
Chapter 2 Installation and Wiring

General Precautions

If the E300 Electronic Overload Relay is being deployed in an environment with an ambient temperature greater than 30 °C (86 °F), please see the Environmental
Specifications on page 456 for the appropriate temperature derating. In addition
to the specific precautions listed throughout this manual, the following general statements must be observed.
ATT EN TI ON : The E300 Electronic Overload Relay contains electrostatic discharge (ESD) sensitive parts and assemblies. Status control precautions are required when installing, testing, servicing, or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, see Allen-Bradley publication 8000-SB001_-en-p, “Guarding Against Electrostatic Damage”, or any other applicable ESD protection handbook.
ATT EN TI ON : An incorrectly applied or installed E300 Electronic Overload Relay can result in damage to the components or reduction in product life. Wiring or application errors (for example, incorrectly calculating the FLA setting, supplying incorrect or inadequate supply voltage, connecting an external supply voltage to the thermistor terminals, or operating or storing in excessive ambient temperatures) may result in malfunction of the E300 Electronic Overload Relay.

Base Relay Assembly

ATT EN TI ON : Only personnel familiar with the E300 Electronic Overload Relay
and associated machinery should plan to install, start up, and maintain the system. Failure to comply may result in personal injury or equipment damage.
ATT EN TI ON : The purpose of this user manual is to serve as a guide for proper installation. The National Electrical Code (NEC) and any other governing regional or local code overrules this information. Rockwell Automation cannot assume responsibility for the compliance or proper installation of the E300 Electronic Overload Relay or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
ATT EN TI ON : The earth ground terminal of the E300 Electronic Overload Relay shall be connected to a solid earth ground via a low-impedance connection.
The following section illustrates the E300 Electronic Overload Relay base relay assembly instructions.
24 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 25
Installation and Wiring Chapter 2

Control Module to Sensing Module Assembly

1
You can connect any E300 Control Module to any E300 Sensing Module. The following illustrations show the steps that are required to make this connection.
Figure 6 - Control Module to Sensing Module Assembly
2
3
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 25
Page 26
Chapter 2 Installation and Wiring
1
3
2

Communication Module to Control Module Assembly

You can connect any E300 Communication Module to any E300 Control Module. The illustrations below show the steps required to make this connection.
Figure 7 - Communication Module to Control Module Assembly
26 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 27
Installation and Wiring Chapter 2
Note: If the expansion bus does not have an operator station, then the last expansion module number must be set to terminated.
Color
Status LED
O
Blinking Green
No power applied
Description
Module OK with no connection
Green Module OK and active
Red Error Detected
Digital Module Number Selector
Number
D1 - D4
D1T - D4T
Module number
Description
Module number with
expansion bus terminating
resistor applied
Analog Module Number Selector
Number
A1 - A4
A1T - A4T
Module number
Description
Module number with
expansion bus terminating
resistor applied
Panel Mount
Hole
DIN Rail Mount
Removable I/O Terminals
Expansion Bus In
Expansion Bus Out
Panel Mount Hole
D1
D1T
D2T
D3T
D4T
D2
D3
D4
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Stop
Reset
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Stop
Up
Down
Reset
Escape
Power LED
Trip / Warn LED
Power LED
Trip / Warn LED
Enter
Select
0
RESET
LOCAL
REMOTE
0
RESET
SELECT
ESC
REMOTE
LOCAL
Control Station Diagnostic Station

Expansion Bus Peripherals

The E300 Electronic Overload Relay offers a range of Expansion Digital and Analog I/O modules that simply connect to the E300 Electronic Overload Relay’s Expansion Bus.
Figure 8 - Expansion Bus Peripherals
You can also add one of the two available operator stations to the end of the Expansion Bus.
Figure 9 - Expansion Operator Stations
The following illustrations show how to mount and connect the E300 Electronic Overload Relay expansion bus I/O modules, expansion power supplies, and operator stations.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 27
Page 28
Chapter 2 Installation and Wiring
1
2
Click
2
1
1.7 N.m
(15 lb-in)
0
R
E
SE
T
S
E
LECT
ES
C
REMO
TE
LOC
AL
800F-AW2
3
22 mm

Expansion Bus Digital and Analog I/O Modules and Power Supply Installation

Figure 10 - Expansion Bus Digital and Analog I/O Modules and Power Supply
Expansion Bus Operator
Figure 11 - Expansion Bus Operator Station
Station Installation

Expansion Bus Network Installation

28 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
The E300 Electronic Overload Relay supports up to (4) Expansion Digital I/O modules, (4) Expansion Analog I/O modules, and (1) Operation Station. The E300 Base Relay can supply enough power for (1) Expansion Digital I/O module
and (1) Operator Station. Any other combination of E300
Expansion Bus
Page 29
Installation and Wiring Chapter 2
0
RESET
SELECT
ESC
REMOTE
LOCAL
Click
1
2
peripherals requires an Expansion Bus Power Supply, which connects as the first module on the Expansion Bus.
Set the module number dial of the Expansion Digital Module to a unique digital module number (D1-D4). If the Expansion Digital Module is the last device on the Expansion Bus, set the module number to the value that enables the internal terminating resistor (D1T-D4T). A power cycle is required when changes are made to the module number dial.
Set the module number dial of the Expansion Analog Module to a unique analog module number (A1-A4). If the Expansion Analog Module is the last device on the Expansion Bus, set the module number to the value that enables the internal terminating resistor (A1T-A4T). A power cycle is required when changes are made to the module number dial.
Connect the E300 Base Relay to the Expansion Module’s Input Port using the supplied Expansion Bus cable. Add the next Expansion Module by connecting the supplied Expansion Bus cable to the Output Port of the previous Expansion Module and into the Input Port of the additional Expansion Module. The Operator Station is the last device on the E300 Expansion Bus; it only has an Input Port with an internal Expansion Bus terminating resistor.
If the user-supplied Expansion Bus cable is not long enough for the installation, 1-meter (Cat. No. 193-EXP-CBL-1M) and 3-meter (Cat. No. 193-EXP-CBL-3M) Expansion Bus cables are available as accessories. The E300 expansion bus can support a maximum distance of 5 meters (16 ft.).
Figure 12 - Expansion Bus Network Installation
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 29
Page 30
Chapter 2 Installation and Wiring

Starter Assembly

5 - 7 lb-in
IN1
The following illustrations show how to assemble an E300 Electronic Overload Relay as a motor starter with an Allen-Bradley Bulletin 100-C contactor.

100-C09…-C55 Starter Assembly Installation

The starter assembly installation instructions are for use with E300 Sensing Module catalog numbers 193-ESM-___-___-C23 and 193-ESM-___-___-C55
Figure 13 - 100-C09…-C55 Starter Assembly Installation
6
9 - 22 lb-in
IN0
A2
R04
R03
A1
4
5
3
2
7 -11 lb-in
1
30 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 31
Installation and Wiring Chapter 2
45
(1.76)
87
(3.40)
60 (2.3
35
(1.37)
n 5 (0.18)
190 (7.49)
37 (1.47)
122 (4.81)
29 (1.14)
122
(4.78)
152 (5.98)
67 (2.65)
FROM CONTACTOR MTG. HOLE
FROM CONTACTOR MTG. HOLE
(ADD 5 mm (0.19 in.) FOR CONTACTOR COIL ON LINE SIDE)
37 (1.48)
122 (4.81)
29 (1.13)
190 (7.49)
67 (2.65)
152 (5.98)
45
(1.76)
122
(4.78)
104
(4.10)
35
(1.374)
60 (2.36)
n 5 (0.18)
(ADD 5 mm (0.19 in.) FOR CONTACTOR COIL ON LINE SIDE)
FROM CONTACTOR MTG. HOLE
FROM
CONTACTOR
MTG. HOLE

Starter Dimensions

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Figure 14 - E300 Sensing Module 193-ESM-___-__-C23 with 100-C09…-C23 Contactor
Figure 15 - E300 Sensing Module 193-ESM-___-__-C55 with 100-C30…-C37 Contactor
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 31
Page 32
Chapter 2 Installation and Wiring
54
(2.12)
45 (1.76)
190 (7.49)
107
(4.21)
60 (2.
45 (1.75)
n 5 (0.18)
37 (1.48)
34 (1.34)
122
(4.82)
152 (5.98)
67 (2.65)
FROM CONTACTOR MTG. HOLE
FROM
CONTACTOR
MTG. HOLE
(ADD 5 mm (0.19 in.) FOR CONTACTOR COIL ON LINE SIDE)
2.82
(71.6)
1.71
(43.5)
5.10
129.5)
1.53 (38.9)
3.60
(91.6)
6.99
(177.6)
9.26
(235.1)
(ADD 0.24 FOR
CONTACTOR COIL
ON LINE SIDE)
4.97
(126.2)
5.32
(135.2)
3.98
(101)
0.21 (5.4)
2.165 (55)
FROM CONTACTOR MTG. HOLE
FROM CONTACTOR MTG. HOLE
Figure 16 - E300 Sensing Module 193-ESM-___-__-C55 with 100-C43…-C55 Contactor
Figure 17 - E300 Sensing Module 193-ESM-___-__-C97 with 100-C60…-C97 Contactor
32 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 33
Installation and Wiring Chapter 2
180 (7.06)
157 (6.17)
249 (9.78)
35 (1.38)
70
(2.75)
12 (0.46)
n 6 (0.22)
90
(3.56)
125
(4.91)
219 (8.63)
184 (7.24)
276 (10.85)
n 6 (0.22)
100
(3.94)
40 (1.58)
80
(3.15)
125
(4.91)
12 (0.46)
Figure 18 - E300 Sensing Module 592-ESM-___-__-S2 with NEMA Contactor Size 0 and Size 1
Figure 19 - E300 Sensing Module 592-ESM-___-__-S2 with NEMA Contactor Size 2
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 33
Page 34
Chapter 2 Installation and Wiring
45
(1.764)
135 (5.32)
30
(1.18)
n 5 (0.17)
6 (0.24)
6 (0.217)
9 (0.33)
148 (5.83)
4 (0.154)
46 (1.81)
4 (0.14)
126
(4.94)
101 (3.96)
4 (0.16)
8 (0.30)
q
5.32
(135)
WITH MTG. FEET
0.18 (4.5)
4.921 (125)
0.197 (5)
n 0.189 (4.8)
4.58
(116.2)
W/O MTG. FEET
1.53 (39)
0.45 (11.35)
1.19
(30.1)
1.76 (45)
4.88
(124)
SHOWN WITH PANEL MOUNT FEET ACCESSORY
q
Mount feet accessory Cat. No.: 140M-C-N45

DIN Rail / Panel Mount Dimensions

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Figure 20 - E300 Sensing Module 193-ESM-___-30A-E3T and 193-ESM-___-60A-E3T
Figure 21 - E300 Sensing Module 193-ESM-___-30A-T and 193-ESM-___-60A-T
34 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 35
Figure 22 - E300 Sensing Module 193-ESM-___-100A-E3T
2.82
(71.6)
1.62
(41.2)
1.63
(41.4)
5.51
(139.9)
5.57
(141.5)
0.70 (17.7)
0.16 (4.05)
3.02
(76.6)
2.36 (60)
5.12
(130)
0.22 (5.5)
q
2 x 4.5 (0.18) dia.
22.5
(0.89)
80.75 (3.18)
120
(4.73)
98 (3.86)
87 (3.43)
Installation and Wiring Chapter 2

Expansion Bus Peripherals Dimensions

Approximate dimensions are shown in millimeters. Dimensions are not intended to be used for manufacturing purposes.
Figure 23 - E300 Digital Expansion Module 193-EXP-DIO-___
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 35
Page 36
Chapter 2 Installation and Wiring
2 x 4.5 (0.18) dia.
22.5
(0.89)
80.75 (3.18)
120
(4.73)
98 (3.86)
87 (3.43)
120
(4.73)
80.75 (3.18)
45
(1.77)
4x 4.5 (0.18) dia
98
(3.86)87(3.43)
12
(0.47)
Figure 24 - E300 Expansion Analog Module 193-EXP-AIO
Figure 25 - E300 Expansion Power Supply 193-EXP-PS-___
36 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 37
Figure 26 - E300 Starter Control Station 193-EOS-SCS
22.5 (0.89) dia.
18.5
(0.73)
13.5 (0.53)
100
(3.94)
70
(2.76)
Installation and Wiring Chapter 2
100
(3.94)
18.5
(0.73)
13.5
(0.53)
45 (1.77)
Figure 27 - E300 Starter Diagnostic Station 193-EOS-SDS
22.5 (0.89) dia.

Terminal s

Sensing Module

Table 1 - E300 Sensing Module Wire Size and Torque Specifications
Cat. No.
Wire Type Conductor Torque
Single
Stranded/Solid [AWG]
Multiple
Single
Flexible-Stranded with Ferrule Metric
Multiple
Coarse-Stranded/Solid Metric
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 37
Single
Multiple
193-ESM-_ _ _-30A-_ _ _ 193-ESM-_ _ _-60A-_ _ _ 592-ESM-_ _ _-30A-_ _ _ 592-ESM-_ _ _-60A-_ _ _
#14…6 AWG 22 lb-in.
#10…6 AWG 30 lb-in.
2.5…16 mm2
2.5 N•m
6…10 mm2
3.4 N•m
2.5…25 mm2
2.5 N•m
6…16 mm2
3.4 N•m
193-ESM-_ _ _-100A-_ _ _ 592-ESM-_ _ _-100A-_ _ _
#12…1 AWG 35 lb-in.
#6…2 AWG 35 lb-in.
4…35 mm2 4 N•m
4…25 mm2 4 N•m
4…50 mm2 4 N•m
4…35 mm2 4 N•m
Page 38
Chapter 2 Installation and Wiring
193-EIOGP-42- _ _ _
193-EIOGP-22- _ _ _
Sensing Module Latch
Power / PTC
Terminals
Expansion Bus Connector
Relay / Ground Fault Terminals
R13
R14
S1
S2
A1
A1
A2
IN2
IN3
IT1
IT2
R13
R14
S1
S2
193-EIO-63- _ _ _
193-EIO-43- _ _ _
R13
R14
R23
R24
A1
A1
A2
IN2
IN3
IN4
IN5
R13
R14
R23
R24
A1
A1
A2
IN2
IN3
A1
A1
A2
IT1
IT2
Input / Output Terminals
Communication Module Latch
IN1
IN0
A2
A1
R04
R03

Control Module

Figure 28 - E300 Control Module Terminal Designations
38 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 39
Table 2 - E300 Control Module Wire Size and Torque Specifications
R24R23
RELAY 2RELAY 1
R14R13
IN3
IN2
Additional Inputs for 193-EIO-63-_ _ _
IN0
IN1
A2
PE
A1A1
A1
R03
R04
A2
IN5
IN4
(+)
(-)
RELAY 0
S2S1
RELAY 1
R14R13
IN3
IN2
IN0
IN1
A2
A1A1
A1
R03
R04
A2
IT2
IT1
(+)
(-)
RELAY 0
193-EIOGP-_ _-_ _ _193-EIO-_ _-_ _ _
PE
Ground
Fault
PTC
Additional Inputs for 193-EIOGP-42-_ _ _
+
t
Cat. No.
Wire Type Conductor Torque
193-EIO-_ _-_ _ _ 193-EIOGP-_ _-_ _ _
24...12 AWG 4lb-in
24...16 AWG 4 lb-in
0.25…2.5 mm
0.45 N•m
0.5...0.75 mm
0.45 N•m
0.2...2.5 mm
0.45 N•m
0.2...1.5 mm
0.45 N•m
2
2
2
2
Stranded/Solid [AWG]
Flexible-Stranded with Ferrule Metric
Coarse-Stranded/Solid Metric
Single
Multiple (stranded only)
Single
Multiple
Single
Multiple
Figure 29 - Control Module Wiring
Installation and Wiring Chapter 2
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 39
Page 40
Chapter 2 Installation and Wiring
IN0 IN1 INC
IN2 IN3
RS2
R04 R14 RC3

Expansion Digital Module

Figure 30 - E300 Expansion Digital Module Terminal Designations
Table 3 - E300 Expansion Digital Module Wire Size and Torque Specifications
Wire Type Conductor Torque
Single
Stranded/Solid [AWG]
Multiple (stranded only)
Single
Flexible-Stranded with Ferrule Metric
Multiple
Single
Coarse-Stranded/Solid Metric
Multiple
Cat. No. 193-EXP-DIO-42-_ _ _
24...12 AWG 5 lb-in
24...16 AWG 5 lb-in
0.25…2.5 mm
0.55 N•m
0.5...0.75 mm
0.55 N•m
0.2...2.5 mm
0.55 N•m
0.2...1.5 mm
0.55 N•m
2
2
2
2
40 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 41
Figure 31 - E300 Expansion Digital Module Wiring Diagram
R04 R14 RC3
IN0 INCIN1 IN2 IN3
Source
+
-
IN1+ IN1- RS1
IN2+ IN2- RS2
OUT+OUT-
IN0+ IN0- RS0

Expansion Analog Module

Installation and Wiring Chapter 2
Figure 32 - E300 Expansion Analog Module Terminal Designations
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 41
Page 42
Chapter 2 Installation and Wiring
Analog Current Input Analog Voltage Input
24V DC
Power
Supply
INx+
IN
x
-
+
-
Current
Input
Device
INx+
-
V
+V
INx-
Analog Voltage or Current Output
+
Out
-
Out+
Device
-
2 Wire RTD/Resistance
INx+
INx-
INx-
3 Wire RTD
INx+
RS
x
Table 4 - E300 Expansion Analog Module Wire Size and Torque Specifications
Wire Type Conductor Torque
Single
Stranded/Solid [AWG]
Flexible-Stranded with Ferrule Metric
Coarse-Stranded/Solid Metric
Multiple (stranded only)
Single
Multiple
Single
Multiple
Figure 33 - E300 Expansion Analog I/O Modules 193-EXP-AIO-__
Cat. No. 193-EXP-AIO-31
24...12 AWG 5 lb-in
24...16 AWG 5 lb-in
0.25…2.5 mm
0.55 N•m
0.5...0.75 mm
0.55 N•m
0.2...2.5 mm
0.55 N•m
0.2...1.5 mm
0.55 N•m
2
2
2
2
42 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 43

Expansion Power Supply

A1 A2
Figure 34 - E300 Expansion Power Supply Terminal Designations
Installation and Wiring Chapter 2
Table 5 - E300 Expansion Power Supply Wire Size and Torque Specifications
Wire Type Conductor Torque
Single
Stranded/Solid [AWG]
Multiple (stranded only)
Single
Flexible-Stranded with Ferrule Metric
Multiple (stranded only)
Single
Coarse-Stranded/Solid Metric
Multiple (stranded only)
Cat. No. 193-EXP-PS-_ _
24...12 AWG 5 lb-in
24...16 AWG 5 lb-in
0.25…2.5 mm
0.55 N•m
0.5...0.75 mm
0.55 N•m
0.2...2.5 mm
0.55 N•m
0.2...1.5 mm
0.55 N•m
2
2
2
2
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 43
Page 44
Chapter 2 Installation and Wiring
A1 A2
Source
+
-
Figure 35 - E300 Expansion Power Supply Wiring Diagram

Grounding

Short-Circuit Ratings

The following grounding recommendations are provided to help ensure EMC requirements during installation
.
The earth ground terminal of the E300 Electronic Overload Relay shall be
connected to a solid earth ground via a low-impedance connection.
Wire the green shield wire of the Cat. No. 193-ECM-ETR into the earth ground terminal of the E300 control module.
Installations employing an external ground fault sensor shall ground the cable shield at the sensor with no connection made at the E300 Electronic Overload Relay.
The PTC thermistor cable shield shall be grounded at the E300 Electronic Overload Relay with no connection made at the opposite end.
The E300 Electronic Overload Relay is suitable for use on circuits capable of delivering not more than the RMS symmetrical amperes listed in the following tables.
Table 6 - Standard Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1
Overload Relay with Sensing Module Cat. No. Max. Available Fault Current [A] Maximum Voltage [V]
193-ESM-___-30A-C23
193-ESM-___-30A-C55
193-ESM-___-30A-E3T
193-ESM-___-30A-P
193-ESM-___-30A-T
193-ESM-VIG-30A-CT
592-ESM-___-30A-S2
193-ESM-___-60A-C55
193-ESM-___-60A-E3T
193-ESM-___-60A-P
193-ESM-___-60A-T
592-ESM-___-60A-S2
193-ESM-___-100A-C97
193-ESM-___-100A-E3T
193-ESM-___-100A-T
592-ESM-___-100A-S3
5,000 600
10,000 600
44 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 45
Table 7 - Short Circuit Ratings per EN60947-4-1
Installation and Wiring Chapter 2
Overload Relay with Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C55, 193-ESM-___-60A-C55
193-ESM-___-100A-C97
Overload Relay with Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C55
193-ESM-___-30A-E3T
193-ESM-___-30A-P
193-ESM-___-30A-T
193-ESM-VIG-30A-CT
592-ESM-___-30A-S2
193-ESM-___-60A-C55
193-ESM-___-60A-E3T
193-ESM-___-60A-P
193-ESM-___-60A-T
592-ESM-___-60A-S2
193-ESM-___-100A-C97
193-ESM-___-100A-E3T
193-ESM-___-100A-T
592-ESM-___-100A-S3
Prospective Short-
Circuit Current, Ir [A]
3,000 100,000 690
5,000 100,000 690
Conditional Short-Circuit
Current, Iq [A]
Table 8 - High Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul. 100-C and 100-D IEC contactors that are protected by fuses
Contactor Cat. No. Max. S tarter FLC [A]
100-C09 9
100-C12 12 20
100-C16 16 30
100-C23 23 30
100-C30 30 50
100-C37 37 50
100-C43 43 70
100-C55 55 80
100-C72 72 100
100-C85 85 150
100-C97 97 200
Max. Available Fault
Current [A]
100,000 600
Max. Voltage [V] Class C or JJ fuse [A]
Maximum Voltage [V]
20
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 45
Page 46
Chapter 2 Installation and Wiring
Table 9 - Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul. 100-C IEC contactors that are protected by Bul. 140U-D circuit breakers
Overload Relay with Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C23
193-ESM-___-30A-C23
Contactor Cat. No. Max. Starter FLC[A]
100-C09 9
100-C12 12
100-C16 16
100-C23 23
100-C09 9
100-C12 12
100-C16 16
100-C23 23
100-C09 9
100-C12 12
100-C16 16
100-C23 23
Table 10 - High Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul. 500 line NEMA contactors that are protected by fuses
Overload Relay with Sensing Module Cat. No.
592-ESM-___-30A-S2 00 9
592-ESM-___-30A-S2 0 18
592-ESM-___-30A-S2 1 27
592-ESM-___-60A-S2 2 45
592-ESM-___-100A-S3 3 90
Contactor Size Max. Starter FLC [A]
Max. Available Fault
Current [A]
65,000 480Y/277V C30 (30 A)
35,000 600Y/347V C30 (30 A)
5,000 600Y/347V C30 (30 A)
Max. Available Fault
Current [A]
100,000
Max. Voltage [V]
Max. Voltage
[V]
600 20
240 30 30
600 30 30
240 60 100
600 30 50
240 100 200
600 60 100
240 200 350
600 100 200
Max. Circuit Breaker Cat. No. 140U-D6D3-
Max. UL Fuse [A]
RJ

Fuse Coordination

The following tables list Type I and Type II Fuse Coordination when used with Bulletin 100-C and 100-D and Bulletin 500 NEMA Size 00… 2 Contactors.
ATT EN TI ON : Select the motor branch circuit protection that complies with the NEC and any other governing regional or local codes.
46 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 47
Installation and Wiring Chapter 2
Table 11 - Type 1 and Type II fuse coordination with Bul. 100-C and 100-D contactors per EN60947-4-1
Overload Relay with Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C55, 193-ESM-___-60A-C55
193-ESM-___-100A-C97
Contactor Cat.
No.
100-C09 9
100-C12 12 20 20
100-C16 16 30 30
100-C23 23
100-C30 30 50 50
100-C37 37 50 50
100-C43 43 70 70
100-C55 55 80 80
100-C72 72
100-C85 85 150 150
100-C97 97 200 200
Max. Starter
FLC[A]
Prospective Short-Circuit
Current, Ir [A]
1000
3,000
5,000
Conditional Short-
Circuit Current, Iq [A]
100,000 600
Max. Voltage
[V]
Type I C lass J or
CC Fuse [A]
20 15
40 40
100 100
Type II Class J or CC Fuse [A]
Table 12 - Type 1 and Type II fuse coordination with Bul. 100-C and 100-D contactors per EN60947-4-1
Overload Relay with Sensing Module Cat. No.
592-ESM-___-30A-S2 0 18
592-ESM-___-30A-S2 1 27 30 30
592-ESM-___-60A-S2 2 45 60 60
592-ESM-___-100A-S3 3 90 5,000 200 200
Contactor Size Max. Starter FLC[A]
Prospective Short-
Circuit Current, Ir [A]
3,000
Conditional Short-
Circuit Current, Iq
[A]
100,000 600
Max. Voltage
[V]
Type I C lass J
Fuse [A]
30 30
Type II Class J
Fuse [A]

Typical Motor Connections

ATT EN TI ON : When working on energized circuits, DO NOT rely on voltage and
current information that is provided by the E300 Electronic Overload Relay for personal safety. Always use a portable voltage or current measurement device to measure the signal locally.
Three-Phase Direct On-Line (DOL) and Single-Phase Full-voltage
The following wiring diagram illustrates the E300 Electronic Overload Relay typical motor connections in a three-phase DOL and single-phase full-voltage applications.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 47
Page 48
Chapter 2 Installation and Wiring
Figure 36 - E300 DOL and Single-Phase Full-voltage Connections
Three-Phase Direct-On-Line
S.C.P.D.
L1
2/T1
T1T2T3
L2
E300
4/T2
M
L3
6/T3
Single-Phase Full-Voltage
S.C.P.D.
L1
2/T1
T1
T2
M
L2
E300
4/T2
6/T3

External Line Current Transformer Application

Current Transformer Ratio

The following E300 Electronic Overload Relay sensing module catalog numbers can be used with step down current transformers:
193-ESM-IG-30A-E3T
193-ESM-IG-30A-T
193-ESM-IG-30A-P
193-ESM-I-30A-E3T
193-ESM-I-30A-T
193-ESM-I-30A-P
193-ESM-VIG-30A-CT
CT Primary (Parameter 263) and CT Secondary (Parameter 264) allows you to identify the turns ratio of the step down current transformers in use. Based on these two configuration parameters, the E300 Electronic Overload Relay will automatically adjust the measured current. Use the primary current for your FLA settings.
48 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 49
Table 13 - CT Primary (Parameter 263)
IMPORTANT
CT Primary (Parameter 263)
Default Value 5
Minimum Value 1
Maximum Value 65535
Param eter Type UINT
Size (Bytes) 2
Scaling Factor 1
Units Amps
Table 14 - CT Secondary (Parameter 264)
CT Secondary (Parameter 264)
Default Value 5
Minimum Value 1
Maximum Value 65535
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 1
Units Amps
Installation and Wiring Chapter 2
ATT EN TI ON : Improper configuration of the CT Ratio parameters can make the E300 Electronic Overload Relay report inaccurate motor operational data and possible motor damage.
The E300 Electronic Overload Relay trip on a configuration fault when the FLA setting is outside of the legal range of the selected CT Ratio settings. The TRIP/ WARN LED status indicator flashes red 3-long, 8-short blinking pattern.
You shall (1) provide one CT for each motor phase and shall (2) connect the CT’s secondary leads to the appropriate sensing module power terminals. The CTs shall be selected to be capable of providing the required VA to the secondary load, which includes the E300 Sensing Module burden of 0.1 VA at the rated secondary current and the wiring burden. Finally, the CT shall (1) be rated for Protective Relaying to accommodate the high inrush currents associated with motor startup and shall (2) be accurate to within ≤±2% over its normal operating range. Typical CT ratings include:
ANSI USA
CSA (Canada)
IEC (Europe)
Class C5 BO.1
Class 10L5
5 VA Class SP10
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 49
Page 50
Chapter 2 Installation and Wiring
NEMA
L1 L2
L3
L1/1 L2/3 L3/5
T1/2 T2/4 T3/6
M
T1
T2
T3
IEC
L1 L2
L3
K1
L1/1 L2/3 L3/5
T1/2 T2/4 T3/6
E300
M
Primary
Current
Transformers
Primary
Current
Transformers
E300
ATT EN TI ON : The improper selection of a current transformer can result in the E300 Electronic Overload Relay reporting inaccurate motor operational data and possible motor damage. The selected current transformer must be rated for protective relaying applications.
Figure 37 - External Current Transformer Connection
The E300 Electronic Overload Relay voltage-based sensing modules support a wide variety of power systems. Tab le 1 5
lists the power systems supported by the
specific sensing module.
Table 15 - Supported Power Systems
Catalog Number Connection Type Power System
193-ESM-VIG-__-__ 592-ESM-VIG-__-__
193-ESM-VIG-30A-CT
Direct
Direct
3 PT
2 PT
Single Phase
Delta
Wye
Grounded B Phase Delta
Single Phase
Delta
Wye
Grounded B Phase Delta
Delta
Wye
Single Phase
Open Delta
50 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 51
Installation and Wiring Chapter 2
Voltage Mode
Voltage Mode (Parameter 252) determines the method for how voltage is monitored E300 Electronic Overload Relay. Select the connection type for the appropriate power system.
Table 16 - Voltage Mode (Parameter 352)
Default Value 0 = Delta direct or with PTs
0 = Delta direct or with PTs
1 = Wye direct or with PTs
Range
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units
2 = Delta with Delta to Wye PTs
3 = Wye with D elta to Wye PTs
4 = Delta with Wye to Delta PTs
5 = Wye with Wye to Delta PTs
Potential (Voltage) Transformer Ratio
The E300 Electronic Overload Relay sensing module catalog number 193-ESM-VIG-30A-CT can be used with step down potential (voltage) transformers. PT Primary (Parameter 353) and PT Secondary (Parameter 354) allows you to identify the turns ratio of the step down potential (voltage) transformers in use. The E300 Electronic Overload Relay will automatically adjust the measured voltage based on these two configuration parameters. Use the primary voltage for your voltage protection settings.
Table 17 - PT Primary (Parameter 353)
Default Value 480
Minimum Value 1
Maximum Value 65535
Param eter Type UINT
Size (Bytes) 2
Scaling Factor 1
Units Amps
Table 18 - PT Secondary (Parameter 354)
Default Value 480
Minimum Value 165535
Maximum Value
Param eter Type UINT
Size (Bytes) 2
Scaling Factor 1
Units Amps
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 51
Page 52
Chapter 2 Installation and Wiring

Control Circuits

ATT EN TI ON : Do not exceed the ratings of the E300 Electronic Overload Relay’s
output and trip relay. If the coil current or voltage of the contactor exceeds the overload relay’s ratings, an interposing relay must be used.
ATT EN TI ON : When the power is applied to the E300 Electronic Overload Relay’s A1 and A2 terminals, the N.O. relay contact that is assigned as a Trip Relay closes after approximately 2 seconds if no trip condition exists.
ATT EN TI ON : More control circuit protection may be required. See the applicable electrical codes.
The E300 Electronic Overload Relay can provide motor control logic for many different types of motor starters (see Chapter 5 Operating Modes). By default, the E300 is configured for the Overload-Network operating mode. The following wiring diagrams are typical control circuits for Non-Reversing and Reversing Motor starters that use the Overload-Network operating mode when Relay 0 (terminals R03 and R04) is configured to be a normally closed Trip Relay.
for more information on

Full-Voltage Non-Reversing Starter (with Network Control)

Figure 38 - NEMA Nomenclature
Relay 0
Relay 1
R13 R14
1
Contact shown with supply voltage applied.
A1
M
Configured as a
Trip Relay
A2
R03
R04
1
52 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 53
Figure 39 - CENELEC Nomenclature
Relay 1
REV
Relay 2
FOR
FOR
REV
Relay 0 Configured as a
Trip Relay
1
1
Contact shown with supply voltage applied.
R13 R14
R23 R24
A1 A2
A1 A2
95 96
Installation and Wiring Chapter 2
L1
Relay 1
R13
R14
Relay 0 Configured
as a Trip Relay
R03
2
R04
A1
K
A2
N
2
Contact shown with supply voltage applied.

Full-Voltage Reversing Starter (with Network Control)

Figure 40 - NEMA Nomenclature
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 53
Page 54
Chapter 2 Installation and Wiring
Figure 41 - CENELEC Nomenclature
L1
Relay 0
Configured as a
Trip Relay
R03
2
R04
Relay 1
K2
R13
R14
Relay 2
R23
R24
K1
A1 A1
K1
A2
N
K2
A2
2
Contact shown with supply voltage applied.
54 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 55
Diagnostic Station
Chapter 3

Introduction

Navigation Keys

Key Name Description
The E300 Electronic Overload Relay supports a Diagnostic Station on the E300 Expansion Bus (requires Control Module firmware v3.000 and higher). The Diagnostic Station allows you to view any E300 parameter and edit any configuration parameter. This chapter explains the Diagnostic Station’s navigation keys, how to view a parameter, how to edit a configuration parameter, and the Diagnostic Station’s programmable display sequence.
The E300 Diagnostic Station has five navigation keys that are used to navigate through the Diagnostic Station’s display menu system and edit configuration parameters.
Up Arrow Down Arrow
Escape
Select
Enter
Scroll through the display parameters or groups. Increment or decrement values.
Back one step in the navigation menu. Cancel a change to a configuration parameter value
Select the next bit when viewing a bit enumerated parameter. Select the next digit when editing a configuration value. Select the next bit when editing a bit enumerated parameter.
Start the navigation menu. Advance one step in the navigation menu. Display the description for a bit enumerated parameter. Edit a configuration parameter value. Save the change to the configuration parameter value.

Displaying a Parameter

The E300 Diagnostic Station allows you to view parameters using a group menu system or by a linear list. To start the navigation menu, press the key. The
menu prompts you to view parameters by groups, parameters in a linear list, or E300 system information.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 55
Page 56
Chapter 3 Diagnostic Station

Parameter Group Navigation

To start the navigation menu, press the key. Use the or keys to select the Groups navigation method and press .
Use the or keys to select the parameter group to display and press
.
Use the or keys to view the parameters that are associated with that group.
When viewing a bit enumerated parameter, press to view the description of each bit. Press to view the next bit. Press to return to the parameter.
Press to return to the parameter group navigation system.
56 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 57
Diagnostic Station Chapter 3
If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically returns to its programmable display sequence.

Linear List Navigation

To start the navigation menu, press the key. Use the or keys to select the Linear List navigation method and press .
Use the or and keys to select the parameter number to display and press .
Use the or keys to view the next sequential parameter.
When viewing a bit enumerated parameter, press to view the description of each bit. Press to view the next bit. Press to return to the parameter.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 57
Page 58
Chapter 3 Diagnostic Station
Press to return to the linear list navigation system.
If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically returns to its programmable display sequence.

System Info

The E300 Diagnostic Station can display firmware revision information, view the time and date of the E300 virtual clock, and edit the time and date of the E300 virtual clock. To view E300 system information, start the navigation menu by
pressing key. Use the or keys to select System Info and press
.
Use the or keys to view the E300 system information.
To edit the system date or time, press to modify the value. Use the or
keys to select the new value. Press to select the next system value. Press to save the new system values or press to cancel the modification and
restore the previous system values.
58 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 59
Diagnostic Station Chapter 3
Press to return to the navigation menu.
If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically cancels the modification, restores the previous value, and returns to its programmable display sequence.

Editing Parameters

Editing a Configuration Parameter

The E300 Diagnostic Station allows you to edit configuration parameters using a group menu system or by a linear list. To start the navigation menu, press the
key. You will be prompted to view parameters by groups, parameters in a linear list, or E300 system information. Choose the appropriate method and navigate to the parameter to be modified.

Editing a Numeric Parameter

To edit a configuration parameter, press the key to modify the value. Use
the or keys to select the new value. Press to save the new system values or press to cancel the modification and restore the previous value.
Press to return to the navigation menu.
If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically cancels the modification, restores the previous value, and returns to its programmable display sequence.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 59
Page 60
Chapter 3 Diagnostic Station

Editing a Bit Enumerated Parameter

When editing a bit enumerated parameter, press the key to view the
description of each bit. Use the or keys to select the new bit value. Press to edit the next bit. Press to save the new value or press to
cancel the modification and restore the previous value.
Press to return to the navigation menu.
If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically cancels the modification, restores the previous value, and returns to its programmable display sequence.

Programmable Display Sequence

Display Sequence

The E300 Diagnostic Station sequentially displays up to seven screens every five seconds.
Three-phase current
Three-phase voltage
To ta l p ow er
User-defined screen 1
User-defined screen 2
User-defined screen 3
User-defined screen 4
The three-phase voltage and total power screens are only included in the sequence when the E300 Electronic Overload Relay has a voltage, current, and ground fault current (VIG)-based Sensing Module.
60 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 61
Diagnostic Station Chapter 3
The user-defined screens allow you to select up to two parameters per screen. Refer to Diagnostic Station User-defined Screens on page 86
to configure the
Screen# and Parameter# (Parameters 428…435).
If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the Diagnostic Station will automatically cancel any editing modifications, restore the previous value, and return to its programmable display sequence.

Stopping the Display Sequence

To stop the display sequence, press . Use the or keys to manually sequence through the displays. Press to return to the automatic display
sequence.
If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically returns to its programmable display sequence.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 61
Page 62
Chapter 3 Diagnostic Station

Automatic Trip and Warning Screens

When the E300 Electronic Overload Relay is in a trip or warning state, the E300 Diagnostic Station automatically displays the trip or warning event.
Press any of the navigation keys ( , , , , or ) to return to the automatic display sequence.
When the trip or warning event clears, the E300 Diagnostic Station automatically returns to its programmable display sequence.
If a different parameter is displayed and you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station will automatically return to the trip or warning screen if the trip or warning event is not cleared.
62 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 63
System Operation and Configuration
Chapter 4

Introduction

Device Modes

This chapter provides instructions for operating and configuring an E300 Electronic Overload Relay system. Settings for Device Modes, Option Match, Security Policy, I/O Assignments, Expansion Bus Fault, Emergency Start, and an introduction to Operating Modes are included in this chapter.
The E300 Electronic Overload Relay has five device modes to validate configuration of the device and limit when you can configure the E300 Electronic Overload Relay, perform a firmware update, and issue commands.
Administration Mode
Operation Mode
Run Mode
Te st Mo de
Invalid Configuration Mode

Administration Mode

Administration Mode is a maintenance mode for the E300 Electronic Overload Relay, which allows you to configure parameters, modify security policies, enable web servers (see page 382 firmware updates, and issue commands.
to enable the EtherNet/IP web server), perform
Follow these steps to enter into Administration Mode:
1. Set the rotary dials on the E300 Communication Module to the following values
For EtherNet/IP set the rotary dials to 0-0-0For DeviceNet set the rotary dials to 7-7
2. Cycle power on the E300 Electronic Overload Relay
After commissioning activities and maintenance tasks are completed, return the E300 Electronic Overload Relay back to Operation or Run Mode by setting the rotary dials of the E300 communication module back to its previous positions and cycle power.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 63
Page 64
Chapter 4 System Operation and Configuration
Bit
1514131211109876543210 Function

Operation Mode

Operation Mode is a standby mode for the E300 Electronic Overload Relay in which the E300 is ready to help protect an electric motor and no electrical current has been detected. You can modify configuration parameters, update firmware, and issue commands if the appropriate security policies are enabled. The Power LED on the Communication Module and Operator Stations will be flashing green and bit 14 in Device Status 0 (Parameter 20) is set to 1 when the device is in Operation Mode.
Table 19 - Operation Mode Bit Function Detail — Device Status 0 (Parameter 20)
X Trip Present
X Warning Present
X Invalid Configuration
X Current Present
X GFCurrent Present
X Voltage Present
X Emergency Start Enabled
X DeviceLogix Enabled
X Feedback Timeout Enabled
X Operator Station Present
X Voltage Sensing Present
X Intern Ground Fault Sensing Present
X Extern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved

Run Mode

Run Mode is an active mode for the E300 Electronic Overload Relay in which the E300 is sensing electrical current and is actively protecting an electric motor. Only non-motor protection configuration parameters can be modified if the appropriate security policies are enabled. The Power LED on the Communication Module and Operator Stations will be solid green and bits 3, 4, and/or 5 in Device Status 0 (Parameter 20) are set to 1 when the device is in Run Mode.
64 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 65
System Operation and Configuration Chapter 4
Table 20 - Run Mode Bit Function Detail — Device Status 0 (Parameter 20)
Bit
1514131211109876543210 Function
X Trip Present
X Warning Present
X Invalid Configuration
X Current Present
X GFCurrent Present
X Voltage Present
X Emergency Start Enabled
X DeviceLogix Enabled
X Feedback Timeout Enabled
X Operator Station Present
X Voltage Sensing Present
X Intern Ground Fault Sensing Present
X Extern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved

Test Mode

Test Mode is used by installers of motor control centers who are testing and commissioning motor starters with an automation system. A digital input of the E300 Electronic Overload Relay is assigned to monitor the motor control center enclosure’s Test Position. The Input Assignments (Parameters 196…201) are described later in this chapter.
Anyone commissioning motor starters in an automation system can put their motor control center enclosure into the Test Position to activate Test Mode and verify that the digital inputs and relay outputs of the E300 Electronic Overload Relay are operating properly with the motor starter without energizing power to
the motor. If the E300
Electronic Overload Relay senses current or voltage in Test
Mode, the E300 Electronic Overload Relay will generate a Test Mode Trip.

Invalid Configuration Mode

Invalid Configuration Mode is an active mode for the E300 Electronic Overload Relay in which the E300 is in a tripped state due to invalid configuration data. Invalid Configuration Parameter (Parameter 38) indicates the parameter number that is causing the fault. Invalid Configuration Cause (Parameter 39) identifies the reason for Invalid Configuration Mode.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 65
Page 66
Chapter 4 System Operation and Configuration
Bit
1514131211109876543210 Function
Table 21 - Invalid Configuration Cause (Parameter 39)
Code Description
0No Error
1 Value over maximum value
2 Value under minimum value
3 Illegal value
4 L3 Current detected (for single-phase applications)
5 CopyCat error
The Trip/Warn LED on the Communication Module and Operator Stations will be flashing a pattern of red, 3 long and 8 short blinks, and bits 0 and 2 in Device Status 0 (Parameter 20) are set to 1 when the device is in Invalid Configuration Mode.
Table 22 - Invalid Configuration Mode Bit Function Detail — Device Status 0 (Parameter 20)
X Trip Present
X Warning Present
X Invalid Configuration
X Current Present
X GFCurrent Present
X Voltage Present
X Emergency Start Enabled
X DeviceLogix Enabled
X Feedback Timeout Enabled
X Operator Station Present
X Voltage Sensing Present
X Intern Ground Fault Sensing Present
X Extern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved
To return to Operation/Run Mode, place a valid configuration value in the parameter identified by Invalid Configuration Parameter (Parameter 38) and Invalid Configuration Cause (Parameter 39). Reset the trip state of the E300 Electronic Overload Relay by pressing the blue reset button on the Communication Module, via network communications, with the internal web server of the EtherNet/IP communications module, or by an assigned digital input.

Option Match

Due to the modular nature of the E300 Electronic Overload Relay, you can enable the Option Match feature to ensure that the options that were expected for the motor protection application are the ones that are present on the E300
66 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 67
System Operation and Configuration Chapter 4
Electronic Overload Relay system. You can configure an option mismatch to cause a protection trip or provide a warning within the E300.

Enable Option Match Protection Trip (Parameter 186)

To enable the E300 Electronic Overload Relay’s Option Match feature to cause a protection trip in the event of an option mismatch, place a (1) in bit position 8 of Parameter 186 (Control Trip Enable). You can select the specific option match features to cause a protection trip in Parameter 233 (Option Match Action).
Table 23 - Enable Option Match Protection Trip Bit Function Detail— Control Trip Enable (Parameter 186)
Bit
1514131211109876543210 Function
X Test Trip Enable
XPTC Trip Enable
X DeviceLogix Trip Enable
X Operator Station Trip Enable
X Remote Trip Enable
X Blocked Start Trip Enable
X Hardware Fault Trip Enable
X Configuration Trip Enable
X Option Match Trip Enable
X Feedback Timeout Trip Enable
X Expansion Bus Trip Enable
Reserved
Reserved
X Nonvolatile Memory Trip Enable
XReady
Reserved
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 67
Page 68
Chapter 4 System Operation and Configuration
Bit
1514131211109876543210 Function

Enable Option Match Protection Warning (Parameter 192)

To enable the E300 Electronic Overload Relay’s Option Match feature to cause a warning in the event of an option mismatch, place a (1) in bit position 8 of Parameter 192 (Control Warning Enable). You can select the specific option match features to cause a warning in Parameter 233 (Option Match Action).
Table 24 - Enable Option Match Protection Warning Bit Function Detail— Control Warning Enable (Parameter 192)
Reserved
Reserved
X DeviceLogix Warning Enable
Reserved
Reserved
Reserved
Reserved
Reserved
X Option Match Warning Enable
X Feedback Timeout Warning Enable
X Expansion Bus Warning Enable
X Number Of Starts Warning Enable
X Operating Hours Warning Enable
Reserved

Control Module Type (Parameter 221)

The E300 Electronic Overload Relay offers six different control modules. Place the value of the expected control module into Parameter 221. A value of (0) disables the Option Match feature for the control module.
Table 25 - Control Module Type (Parameter 221)
Code Description Control Module Cat. No.
0Ignore
1 6 Inputs, 24V DC / 3 Relay Outputs 193-EIO-63-24D
2 4 Inputs, 110-120V AC 50/60Hz / 3 Relay Outputs 193-EIO-43-120
3 4 Inputs, 220-240V AC 50/60Hz / 3 Relay Outputs 193-EIO-43-240
4 4 Inputs, 24V DC / 2 Relay Outputs / External Ground Fault / PTC 193-EIOGP-42-24D
5 2 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs / External Ground Fault / PTC 193-EIOGP-22-120
6 2 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs / External Ground Fault / PTC 193-EIOGP-22-240
68 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 69
System Operation and Configuration Chapter 4

Sensing Module Type (Parameter 222)

The E300 Electronic Overload Relay offers 12 different sensing modules. Place the value of the expected sensing module into Parameter 222. A value of (0) disables the Option Match feature for the sensing module.
Table 26 - Sensing Module Type (Parameter 222)
Code Description Sensing Module Cat. No.
0 Ignore
1 Voltage / Current 0.5…30 A / Ground Fault 193-ESM-VIG-30A-__ or 592-ESM-VIG-30A-__
2 Voltage / Current 6…60 A / Ground Fault 193-ESM-VIG-60A-__ or 592-ESM-VIG-60A-__
3 Voltage / Current 10…100 A / Ground Fault 193-ESM-VIG-100A-__ or 592-ESM-VIG-100A-__
4 Voltage / Current 20…200 A / Ground Fault 193-ESM-VIG-200A-__ or 592-ESM-VIG-200A-__
5 Current 0.5…30 A / Ground Fault 193-ESM-IG-30A-__ or 592-ESM-IG-30A-__
6 Current 6…60 A / Ground Fault 193-ESM-IG-60A-__ or 592-ESM-IG-60A-__
7 Current 10…100 A / Ground Fault 193-ESM-IG-100A-__ or 592-ESM-IG-100A-__
8 Current 20…200 A / Ground Fault 193-ESM-IG-200A-__ or 592-ESM-IG-200A-__
9 Current 0.5…30 A 193-ESM-I-30A-__ or 592--ESM-I-30A-__
10 Current 6…60 A 193-ESM-I-60A-__ or 592--ESM-I-60A-__
11 Current 10…100 A 193-ESM-I-100A-__ or 592--ESM-I-100A-__
12 Current 20…200 A 193-ESM-I-200A-__ or 592--ESM-I-200A-__

Communication Module Type (Parameter 223)

The E300 Electronic Overload Relay offers two different communication modules. Place the value of the expected communication module into Parameter
223. A value of (0) disables the Option Match feature for the communication module.
Table 27 - Communication Module Type (Parameter 223)
Code Description Communication Module Cat. No.
0Ignore
1 EtherNet/IP with Dual Port Switch supporting DLR 193-ECM-ETR
2 DeviceNet 193-ECM-DNT
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 69
Page 70
Chapter 4 System Operation and Configuration

Operator Station Type (Parameter 224)

The E300 Electronic Overload Relay offers two different types of operator stations. Place the value of the expected operator station into Parameter 224. A value of (0) disables the Option Match feature for the operator station. A value of (1), “No Operator Station”, makes the operator station not allowed on the Expansion Bus and prevents you from connecting an operator station to the E300 Electronic Overload Relay system.
Table 28 - Operator Station Type (Parameter 224)
Code Description Operator Station Cat. No.
0Ignore
1 No Operator Station (Operator Station Not Allowed)
2 Control Station 193-EOS-SCS
3 Diagnostic Station with LCD 193-EOS-SDS

Digital I/O Expansion Module 1 Type (Parameter 225)

The E300 Electronic Overload Relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Digital I/O expansion module set to Digital Module 1. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 1 into Parameter 225. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1), “No Digital I/O Expansion Module”, makes the Digital I/O expansion module set to Digital Module 1 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 1 to the E300 Electronic Overload Relay system.
Table 29 - Digital I/O Expansion Module 1 Type (Parameter 225)
Code Description Digital I/O Expansion Module Cat. No.
0 Ignore
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Allowed)
2 4 Inputs, 24V DC / 2 Relay Outputs 193-EXP-DIO-42-24D
3 4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
4 4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-240
70 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 71
System Operation and Configuration Chapter 4

Digital I/O Expansion Module 2 Type (Parameter 226)

The E300 Electronic Overload Relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Digital I/O expansion module set to Digital Module 2. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 2 into Parameter 226. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1),“No Digital I/O Expansion Module”, makes the Digital I/O expansion module set to Digital Module 2 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 2 to the E300 Electronic Overload Relay system.
Table 30 - Digital I/O Expansion Module 2 Type (Parameter 226)
Code Description Digital I/O Expansion Module Cat. No.
0Ignore
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Allowed)
2 4 Inputs, 24V DC / 2 Relay Outputs 193-EXP-DIO-42-24D
3 4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
4 4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-240

Digital I/O Expansion Module 3 Type (Parameter 227)

The E300 Electronic Overload Relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Digital I/O expansion module set to Digital Module 3. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 3 into Parameter 227. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1),“No Digital I/O Expansion Module”, makes the Digital I/O expansion module set to Digital Module 3 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 3 to the E300 Electronic Overload Relay system.
Table 31 - Digital I/O Expansion Module 3 Type (Parameter 227)
Code Description Digital I/O Expansion Module Cat. No.
0Ignore
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Allowed)
2 4 Inputs, 24V DC / 2 Relay Outputs 193-EXP-DIO-42-24D
3 4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
4 4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-240

Digital I/O Expansion Module 4 Type (Parameter 228)

The E300 Electronic Overload Relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 71
Page 72
Chapter 4 System Operation and Configuration
Digital I/O expansion module set to Digital Module 4. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 4 into Parameter 228. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1), “No Digital I/O Expansion Module ”, makes the Digital I/O expansion module set to Digital Module 4 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 4 to the E300 Electronic Overload Relay system.
Table 32 - Digital I/O Expansion Module 4 Type (Parameter 228)
Code Description Digital I/O Expansion Module Cat. No.
0Ignore
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Allowed)
2 4 Inputs, 24V DC / 2 Relay Outputs 193-EXP-DIO-42-24D
3 4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
4 4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-240

Analog I/O Expansion Module 1 Type (Parameter 229)

The E300 Electronic Overload Relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 1. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 1 into Parameter 229. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 1 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 1 to the E300 Electronic Overload Relay system.
Table 33 - Analog I/O Expansion Module 1 Type (Parameter 229)
Code Description Analog I/O Expansion Module Cat. No.
0 Ignore
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Allowed)
2 3 Universal Analog Inputs / 1 Analog Output 193-EXP-AIO-31
72 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 73
System Operation and Configuration Chapter 4

Analog I/O Expansion Module 2 Type (Parameter 230)

The E300 Electronic Overload Relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 2. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 2 into Parameter 230. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 2 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 2 to the E300 Electronic Overload Relay system.
Table 34 - Analog I/O Expansion Module 2 Type (Parameter 230)
Code Description Analog I/O Expansion Module Cat. No.
0 Ignore
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Allowed)
2 3 Universal Analog Inputs / 1 Analog Output 193-EXP-AIO-31

Analog I/O Expansion Module 3 Type (Parameter 231)

The E300 Electronic Overload Relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 3. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 3 into Parameter 231. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 3 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 3 to the E300 Electronic Overload Relay system.
Table 35 - Analog I/O Expansion Module 3 Type (Parameter 231)
Code Description Analog I/O Expansion Module Cat. No.
0 Ignore
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Allowed)
2 3 Universal Analog Inputs / 1 Analog Output 193-EXP-AIO-31
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 73
Page 74
Chapter 4 System Operation and Configuration

Analog I/O Expansion Module 4 Type (Parameter 232)

The E300 Electronic Overload Relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 4. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 4 into Parameter 232. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 4 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 4 to the E300 Electronic Overload Relay system.
Table 36 - Analog I/O Expansion Module 4 Type (Parameter 232)
Code Description Analog I/O Expansion Module Cat. No.
0Ignore
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Allowed)
2 3 Universal Analog Inputs / 1 Analog Output 193-EXP-AIO-31

Option Match Action (Parameter 233)

The Option Match feature for the E300 Electronic Overload Relay allows you to specify an action when there is an option mismatch – Protection Trip or Warning. Place a (0) in the appropriate bit position for a warning, and place a (1) in the appropriate bit position to cause a protection trip if there is an option mismatch.
Table 37 - Option Match Action (Parameter 233) Bit Function Detail
Bit
1514131211109876543210 Function
X Control Module Mismatch Action
X Sensing Module Mismatch Action
X
X Operator Station Mismatch Action
X Digital Module 1 Mismatch Action
X Digital Module 2 Mismatch Action
X Digital Module 3 Mismatch Action
X Digital Module 4 Mismatch Action
X Analog Module 1 Mismatch Action
X Analog Module 2 Mismatch Action
X Analog Module 3 Mismatch Action
X Analog Module 4 Mismatch Action
Communication Module Mismatch Action
74 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 75
System Operation and Configuration Chapter 4

Security Policy

The E300 Electronic Overload Relay has a security policy that can be used to prevent anyone with malicious intent to potentially damage a motor or piece of equipment. By default, you can only modify the security policy when the E300 Electronic Overload Relay is in Administration Mode (see page 63
to learn how
to enable Administration Mode).
Table 38 - Security Policy (Parameter 211) Bit Function Detail
Bit
1514131211109876543210 Function
X Device Configuration Enable
X Device Reset Enable
X Firmware Update Enable
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
X Security Policy Config Enable

Device Configuration Policy

The Device Configuration Policy allows you to send external message instructions via a communications network to write values to configuration parameters. When this policy is disabled, all external message instructions with configuration data will return a communications error when the E300 Electronic Overload Relay is in Operation Mode or Run Mode.

Device Reset Policy

The Device Reset Policy allows you to send external message instruction via a communications network to perform a soft device reset when the E300 Electronic Overload Relay is in Operation Mode. When this policy is disabled, all external reset message instructions will return a communications error when the E300 Electronic Overload Relay is in Operation Mode or Run Mode.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 75
Page 76
Chapter 4 System Operation and Configuration

Firmware Update Policy

The Firmware Update Policy allows you to update the internal firmware of the communication module and control module via ControlFlash when the E300 Electronic Overload Relay is in Operation Mode. When this policy is disabled, firmware updates will return a communications error when the E300 Electronic Overload Relay is in Operation Mode or Run Mode.

Security Configuration Policy

The Security Configuration Policy allows you to modify the Security Policy of the E300 Electronic Overload Relay in Operation Mode. When this policy is disabled, the Security Policy can only be modified when the E300 Electronic Overload Relay is in Administration Mode.

I/O Assignments

The E300 Electronic Overload Relay has native digital inputs and relay outputs in the Control Module. This I/O can be assign to dedicated functions. the following sections list the function assignments for the available Control Module I/O.

Input Pt00 Assignment (Parameter 196)

Input Pt00 Assignment (Parameter 196) allows you to assign this digital input for the following functions:
Table 39 - Input Pt00 Assignment (Parameter 196)
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E300 when it is in a tripped state
2 Remote Trip Force the E300 to go into a tripped state
3Activate FLA2
4 Force Snapshot Force the E300 to update its Snapshot log
5 Emergency Start Issue an Emergency Start command
6 Test Mode Enable Test Mode monitoring
7 L1 Line Loss Arm Activate L1 Line Loss Protection
8 L2 Line Loss Arm Activate L2 Line Loss Protection
9 L3 Line Loss Arm Activate L3 Line Loss Protection
10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection
11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection
12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection
13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms
76 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 77
System Operation and Configuration Chapter 4

Input Pt01 Assignment (Parameter 197)

Input Pt01 Assignment (Parameter 197) allows you to assign this digital input for the following functions:
Table 40 - Input Pt01 Assignment (Parameter 197)
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E300 when it is in a tripped state
2 Remote Trip Force the E300 to go into a tripped state
3Activate FLA2
4 Force Snapshot Force the E300 to update its Snapshot log
5 Emergency Start Issue an Emergency Start command
6 Test Mode Enable Test Mode monitoring
7 L1 Line Loss Arm Activate L1 Line Loss Protection
8 L2 Line Loss Arm Activate L2 Line Loss Protection
9 L3 Line Loss Arm Activate L3 Line Loss Protection
10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection
11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection
12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection
13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms

Input Pt02 Assignment (Parameter 198)

Input Pt02 Assignment (Parameter 198) allows you to assign this digital input for the following functions:
Table 41 - Input Pt02 Assignment (Parameter 198)
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E300 when it is in a tripped state
2 Remote Trip Force the E300 to go into a tripped state
3Activate FLA2
4 Force Snapshot Force the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6 Test Mode Enable Test Mode monitoring
7 L1 Line Loss Arm Activate L1 Line Loss Protection
8 L2 Line Loss Arm Activate L2 Line Loss Protection
9 L3 Line Loss Arm Activate L3 Line Loss Protection
10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection
11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection
12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection
13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 77
Page 78
Chapter 4 System Operation and Configuration

Input Pt03 Assignment (Parameter 199)

Input Pt03 Assignment (Parameter 199) allows you to assign this digital input for the following functions:
Table 42 - Input Pt03 Assignment (Parameter 199)
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E300 when it is in a tripped state
2 Remote Trip Force the E300 to go into a tripped state
3Activate FLA2
4 Force Snapshot Force the E300 to update its Snapshot log
5 Emergency Start Issue an Emergency Start command
6 Test Mode Enable Test Mode monitoring
7 L1 Line Loss Arm Activate L1 Line Loss Protection
8 L2 Line Loss Arm Activate L2 Line Loss Protection
9 L3 Line Loss Arm Activate L3 Line Loss Protection
10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection
11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection
12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection
13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms

Input Pt04 Assignment (Parameter 200)

Input Pt04 Assignment (Parameter 200) allows you to assign this digital input for the following functions:
Table 43 - Input Pt04 Assignment (Parameter 200)
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E300 when it is in a tripped state
2 Remote Trip Force the E300 to go into a tripped state
3Activate FLA2
4 Force Snapshot Force the E300 to update its Snapshot log
5 Emergency Start Issue an Emergency Start command
6 Test Mode Enable Test Mode monitoring
7 L1 Line Loss Arm Activate L1 Line Loss Protection
8 L2 Line Loss Arm Activate L2 Line Loss Protection
9 L3 Line Loss Arm Activate L3 Line Loss Protection
10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection
11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection
12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection
13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms
78 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 79
System Operation and Configuration Chapter 4

Input Pt05 Assignment (Parameter 201)

Input Pt05 Assignment (Parameter 201) allows you to assign this digital input for the following functions:
Table 44 - Input Pt05 Assignment (Parameter 201)
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E300 when it is in a tripped state
2 Remote Trip Force the E300 to go into a tripped state
3Activate FLA2
4 Force Snapshot Force the E300 to update its Snapshot log
5 Emergency Start Issue an Emergency Start command
6 Test Mode Enable Test Mode monitoring
7 L1 Line Loss Arm Activate L1 Line Loss Protection
8 L2 Line Loss Arm Activate L2 Line Loss Protection
9 L3 Line Loss Arm Activate L3 Line Loss Protection
10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection
11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection
12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection
13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 79
Page 80
Chapter 4 System Operation and Configuration

Output Pt00 Assignment (Parameter 202)

Output Pt00 Assignment (Parameter 202) allows you to assign this relay output for the following functions:
Table 45 - Output Pt00 Assignment (Parameter 202)
Value
Assignmen
t
Descripti
on
0 Normal Function as a relay output
1Trip Relay
Function as a normally closed contact until the E300 is in a tripped state in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
2Control Relay
commanded to close by communications or via a DeviceLogix program. When the E300 enters into a tripped state the Control Relay opens and remains open until a trip reset is issued.
3Trip Alarm
4 Warning Alarm
5 Monitor L1 Trip Relay
6 Monitor L2 Trip Relay
7 Monitor L3 Trip Relay
Function as a normally open contact until the E300 is in a tripped state in which the relay closes. The Trip Alarm remains closed until a trip reset is issued.
Function as a normally open contact until the E300 is in a protection warning state in which the relay closes. The Warning Alarm remains closed until the protection warning clears.
Function as a normally closed contact until the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or
(1)
L1 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or
(1)
L2 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or
(1)
L3 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L1
8Monitor L1 Control Relay
(1)
Under Current, L1 Over Current, or L1 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L2
9Monitor L2 Control Relay
(1)
Under Current, L2 Over Current, or L2 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L3
10 Monitor L3 Control Relay
(1)
Under Current, L3 Over Current, or L3 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued.
(1) Req uires Control M odule firmw are v3.000 or higher
80 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 81
System Operation and Configuration Chapter 4

Output Pt01 Assignment (Parameter 203)

Output Pt01 Assignment (Parameter 203) allows you to assign this relay output for the following functions:
Table 46 - Output Pt01 Assignment (Parameter 203)
Value
Assignmen
t
Descripti
on
0 Normal Function as a relay output
1Trip Relay
Function as a normally closed contact until the E300 is in a tripped state in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is
2Control Relay
commanded to close by communications or via a DeviceLogix program. When the E300 enters into a tripped state the Control Relay opens and remains open until a trip reset is issued.
3Trip Alarm
4 Warning Alarm
5 Monitor L1 Trip Relay
6 Monitor L2 Trip Relay
7 Monitor L3 Trip Relay
Function as a normally open contact until the E300 is in a tripped state in which the relay closes. The Trip Alarm remains closed until a trip reset is issued.
Function as a normally open contact until the E300 is in a protection warning state in which the relay closes. The Warning Alarm remains closed until the protection warning clears.
Function as a normally closed contact until the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or
(1)
L1 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or
(1)
L2 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or
(1)
L3 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L1
8Monitor L1 Control Relay
(1)
Under Current, L1 Over Current, or L1 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L2
9Monitor L2 Control Relay
(1)
Under Current, L2 Over Current, or L2 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L3
10 Monitor L3 Control Relay
(1)
Under Current, L3 Over Current, or L3 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued.
(1) Req uires Control M odule firmw are v3.000 or higher
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 81
Page 82
Chapter 4 System Operation and Configuration

Output Pt02 Assignment (Parameter 204)

Output Pt02 Assignment (Parameter 204) allows you to assign this relay output for the following functions:
Table 47 - Output Pt02 Assignment (Parameter 204)
Value
0 Normal Function as a relay output
1Trip Relay
2Control Relay
3Trip Alarm
4 Warning Alarm
5 Monitor L1 Trip Relay
6 Monitor L2 Trip Relay
7 Monitor L3 Trip Relay
8Monitor L1 Control Relay
9Monitor L2 Control Relay
10 Monitor L3 Control Relay
(1) Req uires Control M odule firmw are v3.000 or higher
Assignmen
t
Descripti
on
Function as a normally closed contact until the E300 is in a tripped state in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 enters into a tripped state the Control Relay opens and remains open until a trip reset is issued.
Function as a normally open contact until the E300 is in a tripped state in which the relay closes. The Trip Alarm remains closed until a trip reset is issued.
Function as a normally open contact until the E300 is in a protection warning state in which the relay closes. The Warning Alarm remains closed until the protection warning clears.
Function as a normally closed contact until the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or
(1)
L1 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or
(1)
L2 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a normally closed contact until the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or
(1)
L3 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L1
(1)
Under Current, L1 Over Current, or L1 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L2
(1)
Under Current, L2 Over Current, or L2 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L3
(1)
Under Current, L3 Over Current, or L3 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued.
Table 48 - Activate FLA2 with Output Relay (Parameter 209)
Activate FLA2 with Output Relay (Parameter 209) allows you to activate the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms when the assigned output relay is in an energized state.
Table 49 - Activate FLA2 with Output Relay (Parameter 209)
Value Description
0 Disable
1 Pt00 Output
2 Pt01 Output
3 Pt02 Output

Expansion Bus Fault

The E300 Electronic Overload Relay’s expansion bus can be used to expand the I/O capabilities of the E300 Electronic Overload Relay with the addition of digital and analog expansion I/O modules. The Expansion Bus Fault allows you to have the E300 Electronic Overload Relay go into a Trip or Warning state when
82 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 83
System Operation and Configuration Chapter 4
established Expansion Bus communications is disrupted between the Control Module and any digital and analog expansion I/O modules.
The Expansion Bus Fault is used when the Option Match feature is not enabled for the digital and/or analog expansion I/O modules. The Expansion Bus Fault only monitors for communication disruptions between the Control Module and digital and/or analog expansion I/O modules. Expansion bus communication disruptions between the Control Module and Operator Station do not affect the Expansion Bus fault.

Expansion Bus Trip

Expansion Bus Trip is enabled by setting Control Trip Enable (Parameter 186) bit 10 to 1. When communications is disrupted between the Control Module and digital and/or analog expansion I/O modules, the E300 Electronic Overload Relay will go into a tripped state in which the Trip/Warn LED on the Communication Module and Operator station will blink a red 3 long and 11 short blinking pattern.
Table 50 - Expansion Bus Trip Bit Function Detail— Control Trip Enable (Parameter 186)
Bit
1514131211109876543210 Function
X Test Trip Enable
XPTC Trip Enable
X DeviceLogix Trip Enable
X Operator Station Trip Enable
X Remote Trip Enable
X Blocked Start Trip Enable
X Hardware Fault Trip Enable
X Configuration Trip Enable
X Option Match Trip Enable
X Feedback Timeout Trip Enable
X Expansion Bus Trip Enable
Reserved
Reserved
X Nonvolatile Memory Trip Enable
XReady
Reserved
To return to Operation/Run Mode, verify that the expansion bus cables are properly plugged into the Bus In and Bus Out ports of all of the expansion modules. When all of the expansion I/O modules’ status LEDs are solid green, reset the trip state of the E300 Electronic Overload Relay by pressing the blue reset button on the Communication Module, via network communications, with the internal web server of the EtherNet/IP communications module, or by an assigned digital input.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 83
Page 84
Chapter 4 System Operation and Configuration
IMPORTANT
Bit
1514131211109876543210 Function

Expansion Bus Warning

Expansion Bus Warning is enabled by setting Control Warning Enable (Parameter 192) bit 10 to 1. When communications is disrupted between the Control Module and digital and/or analog expansion I/O modules, the E300 Electronic Overload Relay will go into a warning state in which the Trip/Warn LED on the Communication Module and Operator station will blink a yellow 3 long and 11 short blinking pattern.
Table 51 - Expansion Bus Warning Bit Function Detail— Control Warning Enable (Parameter 192)
Reserved
X P TC Warni ng En able
X DeviceLogix Warning Enable
X Operator Station Warning Enable
Reserved
Reserved
Reserved
Reserved
X Option Match Warning Enable
X Feedback Timeout Warning Enable
X Expansion Bus Warning Enable
X Number Of Starts Warning Enable
X Operating Hours Warning Enable
Reserved

Emergency Start

To return to Operation/Run Mode, verify that the expansion bus cables are properly plugged into the Bus In and Bus Out ports of all of the expansion modules. When all of the expansion I/O modules’ status LEDs are solid green, the warning state of the E300 Electronic Overload Relay will automatically clear.
In an emergency, it may be necessary to start a motor even if a protection fault or a communication fault exists. The trip condition may be the result of a thermal overload condition or the number of starts exceeded its configuration. These conditions can be overridden using the Emergency Start feature of the E300 Electronic Overload Relay.
Activating Emergency Start inhibits overload and blocked start protection. Running in this mode can cause equipment overheating and fire.
To enable the Emergency Start feature in the E300 Electronic Overload Relay set the Emergency Start Enable (Parameter 216) to Enable.
84 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 85
System Operation and Configuration Chapter 4
Table 52 - Emergency Start (Parameter 216)
Value Description
0 Disable
1Enable
Configure one of the Ptxx Input Assignments (Parameters 196…201) to Emergency Start and activate the corresponding digital input.
Table 53 - Emergency Start Input PTXX Assignment (Parameters 196…201)
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E300 when it is in a tripped state
2 Remote Trip Force the E300 to go into a tripped state
3Activate FLA2
4 Force Snapshot Force the E300 to update its Snapshot log
5 Emergency Start Issue an Emergency Start command
Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms
You can also use a network command to activate the Emergency Start feature. For the EtherNet/IP communications module, you would set the Emergency Start bit to 1 in Output Assembly 144. See EtherNet/IP Communications on
page 373 for more information on EtherNet/IP communications.
When the Emergency Start feature is active, the following actions occur in the E300 Electronic Overload Relay:
Protection trips are ignored
Output relays configured as Trip Relays are put into closed state
Normal operation resumes with any Normal or Control Relay assigned
output relay
The Emergency Start Active bit is set to 1 in Device Status 0 (Parameter
20) bit 6
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 85
Page 86
Chapter 4 System Operation and Configuration
Bit
1514131211109876543210 Function
Table 54 - Emergency Start Bit Function Detail— Device Status 0 (Parameter 20)
X Trip Present
X Warning Present
X Invalid Configuration
X Current Present
X GFCurrent Present
X Voltage Present
X Emergency Start Enabled
X DeviceLogix Enabled
X Feedback Timeout Enabled
X Operator Station Present
X Voltage Sensing Present
X Intern Ground Fault Sensing Present
X Extern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved
Diagnostic Station User­defined Screens
The E300 Electronic Overload Relay’s Diagnostic Station has four user-defined screens that are part of the Diagnostic Station’s display sequence in which you can define up to two parameters per screen.

User-defined Screen 1

User-defined Screen 1 – Parameter 1
User-defined Screen 1 - Parameter 1 (Parameter 428) is the E300 parameter number to display for the first parameter in user-defined screen 1. You can select one of the 560 available E300 Electronic Overload Relay parameters.
Table 55 - Screen 1 - Parameter 1 (Parameter 428)
Default Value 1
Minimum Value 0
Maximum Value 560
Parameter Type UIN T
Size (Bytes) 2
Scaling Factor 1
Units
User-defined Screen 1 – Parameter 2
User-defined Screen 1 - Parameter 2 (Parameter 429) is the E300 parameter number to display for the second parameter in user-defined screen 1. You can select one of the 560 available E300 Electronic Overload Relay parameters.
86 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 87
System Operation and Configuration Chapter 4
Table 56 - Screen 1 - Parameter 2 (Parameter 429)
Default Value 50
Minimum Value 0
Maximum Value 560
Parameter Type UIN T
Size (Bytes) 2
Scaling Factor 1
Units

User-defined Screen 2

User-defined Screen 2 – Parameter 1
User-defined Screen 2 - Parameter 1 (Parameter 430) is the E300 parameter number to display for the first parameter in user-defined screen 2. You can select one of the 560 available E300 Electronic Overload Relay parameters.
Table 57 - Screen 2 - Parameter 1 (Parameter 430)
Default Value 2
Minimum Value 0
Maximum Value 560
Parameter Type UIN T
Size (Bytes) 2
Scaling Factor 1
Units
User-defined Screen 2 – Parameter 2
User-defined Screen 2 - Parameter 2 (Parameter 431) is the E300 parameter number to display for the second parameter in user-defined screen 2. You can select one of the 560 available E300 Electronic Overload Relay parameters.
Table 58 - Screen 2 - Parameter 2 (Parameter 431)
Default Value 3
Minimum Value 0
Maximum Value 560
Parameter Type UIN T
Size (Bytes) 2
Scaling Factor 1
Units
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 87
Page 88
Chapter 4 System Operation and Configuration

User-defined Screen 3

User-defined Screen 3 – Parameter 1
User-defined Screen 3 - Parameter 1 (Parameter 432) is the E300 parameter number to display for the first parameter in user-defined screen 3. You can select one of the 560 available E300 Electronic Overload Relay parameters.
Table 59 - Screen 3 - Parameter 1 (Parameter 432)
Default Value 51
Minimum Value 0
Maximum Value 560
Parameter Type UIN T
Size (Bytes) 2
Scaling Factor 1
Units
User-defined Screen 3 – Parameter 2
User-defined Screen 3 - Parameter 2 (Parameter 433) is the E300 parameter number to display for the second parameter in user-defined screen 3. You can select one of the 560 available E300 Electronic Overload Relay parameters.
Table 60 - Screen 3 - Parameter 2 (Parameter 433)
Default Value 52
Minimum Value 0
Maximum Value 560
Parameter Type UIN T
Size (Bytes) 2
Scaling Factor 1
Units

User-defined Screen 4

User-defined Screen 4 – Parameter 1
User-defined Screen 4 - Parameter 1 (Parameter 434) is the E300 parameter number to display for the first parameter in user-defined screen 4. You can select one of the 560 available E300 Electronic Overload Relay parameters.
Table 61 - Screen 4 - Parameter 1 (Parameter 434)
Default Value 38
Minimum Value 0
Maximum Value 560
Parameter Type UIN T
Size (Bytes) 2
Scaling Factor 1
Units
88 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 89
System Operation and Configuration Chapter 4
User-defined Screen 4 – Parameter 2
User-defined Screen 4 - Parameter 2 (Parameter 435) is the E300 parameter number to display for the second parameter in user-defined screen 4. You can select one of the 560 available E300 Electronic Overload Relay parameters.
Screen4‐Parameter2(Parameter435)
Default Value 39
Minimum Value 0
Maximum Value 560
Parameter Type UIN T
Size (Bytes) 2
Scaling Factor 1
Units

Display Timeout

Display Timeout (Parameter 436) defines the time duration in which there is no display navigation activity, and the E300 Diagnostic Station returns to its normal display sequence. Any configuration parameters that were left in an edit state will be canceled. A value of zero disables the display timeout function.
Table 62 - Display Timeout (Parameter 436)
Default Value 300
Minimum Value 0
Maximum Value 65535
Parameter Type UIN T
Size (Bytes) 2
Scaling Factor 1
Units Seconds
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 89
Page 90
Chapter 4 System Operation and Configuration

Analog I/O Expansion Modules

The E300 Electronic Overload Relay supports up to four Analog I/O Expansion Modules on the E300 Expansion Bus. The E300 Analog Expansion Module has three independent universal inputs and one analog output.

Analog Input Channels

The universal analog inputs can accept the following analog signals:
Current4…20 mA0…20 mA
Vo l t a g e0…10V DC1…5V DC0…5V DC
2-Wire or 3-Wire RTD Sensors100 Ω, 200 Ω, 500 Ω, 1000 Ω Pt 385100 Ω, 200 Ω, 500 Ω, 1000 Ω Pt 391610 Ω Cu 426100 Ω Ni 618120 Ω Ni 672604Ω NiFe 518
Resistance0…150 Ω0…750 Ω0…3000 Ω0…6000 Ω (PTC and NTC Sensors)
The analog inputs can report data in four different formats. Tab le 6 3 through
Tab le 66
display the data ranges for all of the available analog input types for the
four available data formats.
Table 63 - Analog Input Data Format for Current Input Type
Input Range Input Value Condition
21.00 mA High Limit 21000 2100 32767 17407
4…20 mA
0…20 mA
90 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
20.00 mA High Range 20000 2000 32767 16383
4.00 mA Low Range 4000 400 -32768 0
3.00 mA Low Limit 3000 300 -32768 -1024
21.00 mA High Limit 21000 2100 32767 17202
20.00 mA High Range 20000 2000 32767 16383
0.00 mA Low Range 0 0 -32768 0
0.00 mA Low Limit 0 0 -32768 0
Engineering Units
Engineering Units x 10
Raw / Proportional
PID
Page 91
System Operation and Configuration Chapter 4
Table 64 - Analog Input Data Format for Voltage Input Type
Input Range Input Value Condition
10.50V DC High Limit 10500 1050 32767 17202
0…10 V DC
1…5 V DC
0…5V DC
10.00V DC High Range 10000 1000 32767 16383
0.00V DC Low Range 0 0 -32768 0
0.00V DC Low Limit 0 0 -32768 0
5.25V DC High Limit 5250 525 32767 17407
5.00V DC High Range 5000 500 32767 16383
1.00V DC Low Range 1000 100 -32768 0
0.50V DC Low Limit 500 50 -32768 -2048
5.25V DC High Limit 5250 525 32767 17202
5.00V DC High Range 5000 500 32767 16383
0.00V DC Low Range 0 0 -32768 0
0.00V DC Low Limit 0 0 -32768 0
Engineering Units
Table 65 - Analog Input Data Format for RTD Input Type
Input Range Input Value Condition
850.0 °C High Limit 8500 850 32767 16383
850.0 °C High Range 8500 850 32767 16383
RTD 100 Ω, 200 Ω, 500 Ω, 1000 Ω Pt 385
RTD 100 Ω, 200 Ω, 500 Ω, 1000 Ω Pt 3916
RTD 10 Ω Cu 426
RTD 100 Ω Ni 618
-200.0 °C Low Range -2000 -200 -32768 0
-200.0 °C Low Limit -2000 -200 -32768 0
1562.0 °F High Limit 15620 1562 32767 16383
1562.0 °F High Range 15620 1562 32767 16383
-328.0 °F Low Range -3280 -328 -32768 0
-328.0 °F Low Limit -3280 -328 -32768 0
630.0 °C High Limit 6300 630 32767 16383
630.0 °C High Range 6300 630 32767 16383
-200.0 °C Low Range -2000 -200 -32768 0
-200.0 °C Low Limit -2000 -200 -32768 0
1166.0 °F High Limit 11660 1166 32767 16383
1166.0 °F High Range 11660 1166 32767 16383
-328.0 °F Low Range -3280 -328 -32768 0
-328.0 °F Low Limit -3280 -328 -32768 0
260.0 °C High Limit 2600 260 32767 16383
260.0 °C High Range 2600 260 32767 16383
-100.0 °C Low Range -1000 -100 -32768 0
-100.0 °C Low Limit -1000 -100 -32768 0
500.0 °F High Limit 5000 500 32767 16383
500.0 °F High Range 5000 500 32767 16383
-148.0 °F Low Range -1480 -148 -32768 0
-148.0 °F Low Limit -1480 -148 -32768 0
260.0 °C High Limit 2600 260 32767 16383
260.0 °C High Range 2600 260 32767 16383
-100.0 °C Low Range -1000 -100 -32768 0
-100.0 °C Low Limit -1000 -100 -32768 0
500.0 °F High Limit 5000 500 32767 16383
500.0 °F High Range 5000 500 32767 16383
-148.0 °F Low Range -1480 -148 -32768 0
-148.0 °F Low Limit -1480 -148 -32768 0
Engineering Units
Engineering Units x 10
Engineering Units x 10
Raw / Proportional
Raw / Proportional
PID
PID
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 91
Page 92
Chapter 4 System Operation and Configuration
Input Range Input Value Condition
260.0 °C High Limit 2600 260 32767 16383
260.0 °C High Range 2600 260 32767 16383
-80.0 °C Low Range -800 -80 -32768 0
RTD 120 Ω Ni 672
RTD 100 Ω NiFe 518
-80.0 °C Low Limit -800 -80 -32768 0
500.0 °F High Limit 5000 500 32767 16383
500.0 °F High Range 5000 500 32767 16383
-112.0 °F Low Range -1120 -112 -32768 0
-112.0 °F Low Limit -1120 -112 -32768 0
200.0 °C High Limit 2000 200 32767 16383
200.0 °C High Range 2000 200 32767 16383
-100.0 °C Low Range -1000 -100 -32768 0
-100.0 °C Low Limit -1000 -100 -32768 0
392.0 °F High Limit 3920 392 32767 16383
392.0 °F High Range 3920 392 32767 16383
-148.0 °F Low Range -1480 -148 -32768 0
-148.0 °F Low Limit -1480 -148 -32768 0
Engineering Units
Engineering Units x 10
Table 66 - Analog Input Data Format for Resistance Input Type
Input Range Input Value Condition
150.00 Ω High Limit 15000 1500 32767 16383
Resistance 0-150 Ω
Resistance 0-750 Ω
Resistance 0-3000 Ω
Resistance 0-6000 Ω (PTC / NTC)
150.00 Ω High Range 15000 1500 32767 16383
0.00 Ω Low Range 0 0 -32768 0
0.00 Ω Low Limit 0 0 -32768 0
750.0 Ω High Limit 7500 750 32767 16383
750.0 Ω High Range 7500 750 32767 16383
0.0 Ω Low Range 0 0 -32768 0
0.0 Ω Low Limit 0 0 -32768 0
3000.0 Ω High Limit 30000 3000 32767 16383
3000.0 Ω High Range 30000 3000 32767 16383
0.0 Ω Low Range 0 0 -32768 0
0.0 Ω Low Limit 0 0 -32768 0
6000 Ω High Limit 6000 600 32767 16383
6000 Ω High Range 6000 600 32767 16383
0 Ω Low Range 0 0 -32768 0
0 Ω Low Limit 0 0 -32768 0
Engineering Units
Engineering Units x 10
Raw / Proportional
Raw / Proportional
PID
PID

Analog Output Channel

The isolated analog output can be programmed to provide one of the following analog output signal types:
Current4…20 mA0…20 mA
92 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 93
System Operation and Configuration Chapter 4
Vo l t a g e0…10V DC1…5V DC0…5V DC
The analog outputs can report data as a percent of range. Tab le 6 7 and Tabl e 6 8 display the data ranges for all of the available analog output types.
Table 67 - Analog Output Data Format for Current Output Type
Output Range Output Signal Condition % Range
21.000 mA High Limit 106.25%
4…20 mA
0…20 mA
20.000 mA High Range 100.00%
4.000 mA Low Range 0.00%
3.000 mA Low Limit -6.25%
21.00 mA High Limit 105.00%
20.00 mA High Range 100.00%
0.00 mA Low Range 0.00%
0.00 mA Low Limit 0.00%
Table 68 - Analog Output Data Format for Voltage Output Type
Output Range Output Value Condition % Range
10.50V DC High Limit 105.00%
0…10 V DC
1…5 V DC
0…5 V DC
10.00V DC High Range 100.00%
0.00V DC Low Range 0.00%
0.00V DC Low Limit 0.00%
5.25V DC High Limit 106.25%
5.00V DC High Range 100.00%
1.00V DC Low Range 0.00%
0.50V DC Low Limit -6.25%
5.25V DC High Limit 105.00%
5.00V DC High Range 100.00%
0.00V DC Low Range 0.00%
0.00V DC Low Limit 0.00%
The analog output can be used to communicate E300 diagnostic information via an analog signal to distributed control systems, programmable logic controllers, or panel-mounted analog meters. The analog output can represent one of the following E300 diagnostic parameters:
Average %FLA
%TCU
Ground Fault Current
Current Imbalance
Average L-L Voltage
Voltage Imbalance
To ta l kW
To ta l kVA R
To ta l kVA
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 93
Page 94
Chapter 4 System Operation and Configuration
Output Selection Low Range High Range
Average % FLA 0% 100%
Scaled Average % FLA 0% 200%
% TCU 0% 100%
Ground Fault Current
Internal, 0.50…5.00 A 0.50 A 5.00 A
External, 0.02…0.10 A 0.02 A 0.10 A
External, 0.10…0.50 A 0.10 A 0.50 A
External, 0.20…1.00 A 0.20 A 1.00 A
External, 1.00…5.00 A 1.00 A 5.00 A
Current Imbalance 0% 100%
Average L-L Voltage 0V (PT Primary) V
Voltage Imbalance 0% 100%
Total kW 0 kW (FLA1 x PT Primary x 1.732) V
Total kVAR 5.25V DC (FLA1 x PT Primary x 1.732) V
Total kVA 5.00V DC (FLA1 x PT Primary x 1.732) V
Total Power Factor -50% (Lagging) +50% (Leading)
User-defined Value -32768 32767
To ta l P ow er Fa c tor
User-defined Value
Table 69 - Analog Output Selection Type

Update Rate

Analog Input Channels
The performance for the input channels of the E300 Analog I/O Expansion Module is dependent on the filter setting for each channel. The total scan time for the input channels of the module is determined by adding the conversion time for all enabled input channels.
Table 70 - Analog Input Channel Conversion Time
Input Type Filter Frequency Conversion Time
17 Hz 153 ms
Current, Volta ge, 2-Wire RTD, Resistance
3-Wire RTD
Example:
Channel 00 is configured for a 3-wire RTD and 4 Hz filter (conversion time = 1024 ms).
Channel 01 is configured for 17Hz voltage (conversion time = 153 ms).
Channel 02 is configured for 62Hz current (conversion time = 65 ms).
4 Hz 512 ms
62 Hz 65 ms
470 Hz 37 ms
17 Hz 306 ms
4 Hz 1024 ms
62 Hz 130 ms
470 Hz 74 ms
94 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 95
System Operation and Configuration Chapter 4
The E300 Analog I/O Expansion Module input channel scan time will be 1242 ms (1024+153+65).
Analog Output Channel
The E300 Analog I/O Expansion Module output channel update rate is 10 ms.

Analog Module 1

Analog Module 1 – Input Channel 00 Type
Analog Module 1 – Input Channel 00 Type (Parameter 437) defines the type of analog signal that Input Channel 00 of Analog Module 1 will be monitoring.
Table 71 - Analog Module 1 – Input Channel 00 Type (Parameter 437)
Value Assignment Description
0 Disabled Disable the analog input
1 4To20mA Read an analog current signal from 4…20 mA
2 0To20mA Read an analog current signal from 0…20 mA
3 0To10Volts Read an analog voltage signal from 0…10 V DC
4 1To5Volts Read an analog voltage signal from 1…5 V DC
5 0To5Volts Read an analog voltage signal from 0…5 V DC
6 100Pt385 Read a 100 Ω Pt 385 RTD Sensor
7 200Pt385 Read a 200 Ω Pt 385 RTD Sensor
8 500Pt385 Read a 500 Ω Pt 385 RTD Sensor
9 1000Pt385 Read a 1000 Ω Pt 385 RTD Sensor
10 100Pt3916 Read a 100 Ω Pt 3916 RTD Sensor
11 200Pt3916 Read a 200 Ω Pt 3916 RTD Sensor
12 500Pt3916 Read a 500 Ω Pt 3916 RTD Sensor
13 1000Pt3916 Read a 1000 Ω Pt 3916 RTD Sensor
14 10Cu426 Read a 10 Ω Cu 426 RTD Sensor
15 100Ni618 Read a 100 Ω Ni 618 RTD Sensor
16 120Ni672 Read a 120 Ω Ni 672 RTD Sensor
17 604NiFe518 Read a 604Ω NiFe 518 RTD Sensor
18 150ohm Read a resistance signal from 0…150 Ω
19 750ohm Read a resistance signal from 0…750 Ω
20 3000ohm Read a resistance signal from 0…3000 Ω
21 6000ohm
Read a resistance signal from 0…6000 Ω. This setting can be used with PTC and NTC sensors.
Analog Module 1 – Input Channel 00 Format
Analog Module 1 – Input Channel 00 Format (Parameter 438) defines the data format for how the analog reading is reported.
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 95
Page 96
Chapter 4 System Operation and Configuration
Table 72 - Analog Module 1 – Input Channel 00 Format (Parameter 438)
Value Assignment Description
0 EngUnits Engineering Units (mA, V, °C, °F, or Ω)
1 EngUnitsTimes10 Engineering Units x 10 (mA, V, °C, °F, or Ω)
2 RawProportional Raw / Proportional (-32768…+32767)
3 ScaledForPID Scaled for PID (0…16383)
Analog Module 1 – Input Channel 00 Temperature Unit
Analog Module 1 – Input Channel 00 Temperature Unit (Parameter 439) defines the temperate unit for RTD sensor readings.
Table 73 - Analog Module 1 – Input Channel 00 Temperature Unit (Parameter 439)
Value Assignment Description
0 DegreesC Report RTD Temperature Data in °C
1 DegreesF Report RTD Temperature Data in °F
Analog Module 1 – Input Channel 00 Filter Frequency
Analog Module 1 – Input Channel 00 Filter Frequency (Parameter 440) defines update rate for the analog module’s input channels.
Table 74 - Analog Module 1 – Input Channel 00 Filter Frequency (Parameter 440)
Value Assignment Description
0 17 Hz Analog to D igital Conversion Update Frequency of 17 Hz
1 4 Hz Analog to Digital Conversion Update Frequency of 4 Hz
2 62 Hz Analog to D igital Conversion Update Frequency of 62 Hz
3 470 Hz Analog to Digital Conversion Update Frequency of 470Hz
Analog Module 1 – Input Channel 00 Open Circuit State
Analog Module 1 – Input Channel 00 Open Circuit State (Parameter 441) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel.
Table 75 - Analog Module 1 – Input Channel 00 Open Circuit State (Parameter 441)
Value Assignment Description
0 Upscale Repor ts the high limit of the input channel type
1 Downscale Reports the low limit of the input channel type
2 Zero Reports zero
Analog Module 1 – Input Channel 00 RTD Type Enable
Analog Module 1 – Input Channel 00 RTD Type Enable (Parameter 442) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor.
96 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 97
System Operation and Configuration Chapter 4
Table 76 - Analog Module 1 – Input Channel 00 RTD Type Enable (Parameter 442)
Value Assignment Description
0 3-Wire Scan a 3-wire RTD sensor
1 2-Wire Scan a 2-wire RTD sensor
Analog Module 1 – Input Channel 01 Type
Analog Module 1 – Input Channel 01 Type (Parameter 446) defines the type of analog signal that Input Channel 01 of Analog Module 1 will be monitoring.
Table 77 - Analog Module 1 – Input Channel 01 Type (Parameter 446)
Value Assignment Description
0 Disabled Disable the analog input
1 4To20mA Read an analog current signal from 4…20 mA
2 0To20mA Read an analog current signal from 0…20 mA
3 0To10Volts Read an analog voltage signal from 0…10 V DC
4 1To5Volts Read an analog voltage signal from 1…5 V DC
5 0To5Volts Read an analog voltage signal from 0…5 V DC
6 100Pt385 Read a 100 Ω Pt 385 RTD Sensor
7 200Pt385 Read a 200 Ω Pt 385 RTD Sensor
8 500Pt385 Read a 500 Ω Pt 385 RTD Sensor
9 1000Pt385 Read a 1000 Ω Pt 385 RTD Sensor
10 100Pt3916 Read a 100 Ω Pt 3916 RTD Sensor
11 200Pt3916 Read a 200 Ω Pt 3916 RTD Sensor
12 500Pt3916 Read a 500 Ω Pt 3916 RTD Sensor
13 1000Pt3916 Read a 1000 Ω Pt 3916 RTD Sensor
14 10Cu426 Read a 10 Ω Cu 426 RTD Sensor
15 100Ni618 Read a 100 Ω Ni 618 RTD Sensor
16 120Ni672 Read a 120 Ω Ni 672 RTD Sensor
17 604NiFe518 Read a 604Ω NiFe 518 RTD Sensor
18 150ohm Read a resistance signal from 0…150 Ω
19 750ohm Read a resistance signal from 0…750 Ω
20 3000ohm Read a resistance signal from 0…3000 Ω
21 6000ohm
Read a resistance signal from 0…6000 Ω. This setting can be used with PTC and NTC sensors.
Analog Module 1 – Input Channel 01 Format
Analog Module 1 – Input Channel 01 Format (Parameter 447) defines the data format for howthe analog reading is reported.
Table 78 - Analog Module 1 – Input Channel 01 Format (Parameter 447)
Value Assignment Description
0 EngUnits Engineering Units (mA, V, °C, °F, or Ω)
1 EngUnitsTimes10 Engineering Units x 10 (mA, V, °C, °F, or Ω)
2 RawProportional Raw / Proportional (-32768…+32767)
3 ScaledForPID Scaled for PID (0…16383)
AnalogModule1–InputChannel01TemperatureUnit
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 97
Page 98
Chapter 4 System Operation and Configuration
Analog Module 1 – Input Channel 01 Temperature Unit (Parameter 448) defines the temperate unit for RTD sensor readings.
Table 79 - Analog Module 1 – Input Channel 01 Temperature Unit (Parameter 448)
Value Assignment Description
0 DegreesC Report RTD Temperature Data in °C
1 DegreesF Report RTD Temperature Data in °F
Analog Module 1 – Input Channel 01 Filter Frequency
Analog Module 1 – Input Channel 01 Filter Frequency (Parameter 449) defines update rate for the analog module’s input channels.
Table 80 - Analog Module 1 – Input Channel 01 Filter Frequency (Parameter 449)
Value Assignment Description
0 17 Hz Analog to Digital Conversion Update Frequency of 17 Hz
1 4 Hz Analog to Digital Conversion Update Frequency of 4 Hz
2 62 Hz Analog to Digital Conversion Update Frequency of 62 Hz
3 470 Hz Analog to Digital Conversion Update Frequency of 470Hz
Analog Module 1 – Input Channel 01 Open Circuit State
Analog Module 1 – Input Channel 01 Open Circuit State (Parameter 450) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel.
Table 81 - Analog Module 1 – Input Channel 01 Open Circuit State (Parameter 450)
Value Assignment Description
0 Upscale Reports the high limit of the input channel type
1 Downscale Reports the low limit of the input channel type
2 Zero Reports zero
Analog Module 1 – Input Channel 01 RTD Type Enable
Analog Module 1 – Input Channel 01 RTD Type Enable (Parameter 451) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor.
Table 82 - Analog Module 1 – Input Channel 01 RTD Type Enable (Parameter 451)
Value Assignment Description
0 3-Wire Scan a 3-wire RTD sensor
1 2-Wire Scan a 2-wire RTD sensor
Analog Module 1 – Input Channel 02 Type
Analog Module 1 – Input Channel 02 Type (Parameter 455) defines the type of analog signal that Input Channel 02 of Analog Module 1 will be monitoring.
98 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Page 99
System Operation and Configuration Chapter 4
Table 83 - Analog Module 1 – Input Channel 02 Type (Parameter 455)
Value Assignment Description
0 Disabled Disable the analog input
1 4To20mA Read an analog current signal from 4…20 mA
2 0To20mA Read an analog current signal from 0…20 mA
3 0To10Volts Read an analog voltage signal from 0…10 V DC
4 1To5Volts Read an analog voltage signal from 1…5 V DC
5 0To5Volts Read an analog voltage signal from 0…5 V DC
6 100Pt385 Read a 100 Ω Pt 385 RTD Sensor
7 200Pt385 Read a 200 Ω Pt 385 RTD Sensor
8 500Pt385 Read a 500 Ω Pt 385 RTD Sensor
9 1000Pt385 Read a 1000 Ω Pt 385 RTD Sensor
10 100Pt3916 Read a 100 Ω Pt 3916 RTD Sensor
11 200Pt3916 Read a 200 Ω Pt 3916 RTD Sensor
12 500Pt3916 Read a 500 Ω Pt 3916 RTD Sensor
13 1000Pt3916 Read a 1000 Ω P t 3916 RTD Sensor
14 10Cu426 Read a 10 Ω Cu 426 RTD Sensor
15 100Ni618 Read a 100 Ω Ni 618 RTD Sensor
16 120Ni672 Read a 120 Ω Ni 672 RTD Sensor
17 604NiFe518 Read a 604Ω NiFe 518 RTD Sensor
18 150ohm Read a resistance signal from 0…150 Ω
19 750ohm Read a resistance signal from 0…750 Ω
20 3000ohm Read a resistance signal from 0…3000 Ω
21 6000ohm
Read a resistance signal from 0…6000 Ω. This setting can be used with PTC and NTC sensors.
Analog Module 1 – Input Channel 02 Format
Analog Module 1 – Input Channel 02 Format (Parameter 456) defines the data format for how the analog reading is reported.
Table 84 - Analog Module 1 – Input Channel 02 Format (Parameter 456)
Value Assignment Description
0 EngUnits Engineering Units (mA, V, °C, °F, or Ω)
1 EngUnitsTimes10 Engineering Units x 10 (mA, V, °C, °F, or Ω)
2 RawProportional Raw / Proportional (-32768…32767)
3 ScaledForPID Scaled for PID (0 …16383)
Analog Module 1 – Input Channel 02 Temperature Unit
Analog Module 1 – Input Channel 02 Temperature Unit (Parameter 457) defines the temperate unit for RTD sensor readings.
Table 85 - Analog Module 1 – Input Channel 02 Temperature Unit (Parameter 457)
Value Assignment Description
0 DegreesC Report RTD Temperature Data in °C
1 DegreesF Report RTD Temperature Data in °F
Rockwell Automation Publication 193-UM015D-EN-P - February 2015 99
Page 100
Chapter 4 System Operation and Configuration
Analog Module 1 – Input Channel 02 Filter Frequency
Analog Module 1 – Input Channel 02 Filter Frequency (Parameter 458) defines update rate for the analog module’s input channels.
Table 86 - Analog Module 1 – Input Channel 02 Filter Frequency (Parameter 458)
Value Assignment Description
0 17 Hz Analog to Digital Conversion Update Frequency of 17 Hz
1 4 Hz Analog to Digital Conversion Update Frequency of 4 Hz
2 62 Hz Analog to Digital Conversion Update Frequency of 62 Hz
3 470 Hz Analog to Digital Conversion Update Frequency of 470Hz
Analog Module 1 – Input Channel 02 Open Circuit State
Analog Module 1 – Input Channel 02 Open Circuit State (Parameter 459) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel.
Table 87 - Analog Module 1 – Input Channel 02 Open Circuit State (Parameter 459)
Value Assignment Description
0 Upscale Reports the high limit of the input channel type
1 Downscale Repor ts the low limit of the input channel type
2 Zero Repor ts zero
Analog Module 1 – Input Channel 02 RTD Type Enable
Analog Module 1 – Input Channel 02 RTD Type Enable (Parameter 460) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor.
Table 88 - Analog Module 1 – Input Channel 02 RTD Type Enable (Parameter 460)
Value Assignment Description
0 3-Wire Scan a 3-wire RTD sensor
1 2-Wire Scan a 2-wire RTD sensor
AnalogModule1OutputChannel00Type
Analog Module 1 – Output Channel 00 Type (Parameter 464) defines the type of analog signal that Output Channel 00 of Analog Module 1 will be providing.
Table 89 - Analog Module 1 – Output Channel 00 Type (Parameter 464)
Value Assignment Description
0 Disabled Disable the analog input
1 4To20mA Provide an analog current signal from 4…20 mA
2 0To20mA Provide an analog current signal from 0…20 mA
3 0To10Volts Provide an analog voltage signal from 0…10 V DC
4 1To5Volts Provide an analog voltage signal from 1…5 V DC
5 0To5Volts Provide an analog voltage signal from 0…5 V DC
100 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Loading...