Rockwell Automation Allen-Bradley CENTERLINE 2500 Installation Instructions Manual

Page 1
Installation Instructions
Original Instructions
CENTERLINE 2500 Low Voltage Motor Control Centers
Bulletin Number 2500
Page 2

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Page 3

Table of Contents

Preface
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Purchased Components and Additional Instruction Sheets . . . . . . . 8
Chapter 1
System Overview ArcShield Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
IntelliCENTER Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
IntelliCENTER Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
IntelliCENTER Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Typical Column Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Nameplate Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
MCC Column-number Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
ArcShield Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Chapter 2
Receiving, Handling, and Storage Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 3
Install Columns Location Planning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
ArcShield™ Clearance Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Remove Packing Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Locate Bus Splice Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Removing the Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Position the Motor Control Center . . . . . . . . . . . . . . . . . . . . . . . . 26
Secure a Motor Control Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Securing Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Seal IP42 and IP54 Enclosures Before Connection . . . . . . . . . . 28
Secure Single-front, One-column-wide Shipping Blocks. . . . . . 29
Secure Single-front, Two-column-wide Shipping Blocks . . . . . 30
Secure Double-front, One-column-wide Shipping Blocks . . . . 31
Secure Multiple-column Shipping Blocks . . . . . . . . . . . . . . . . . . . 32
Join Columns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Seismic Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Splice the Power Bus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Access the Power Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Splicing The Power Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Splice the Protective Earth (PE) Conductor . . . . . . . . . . . . . . . . 47
Control and Network Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 3
Page 4
Table of Contents
Chapter 4
Install Cable Install ArcShield Protection After Wiring . . . . . . . . . . . . . . . . . . . . . . 50
Lugs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Incoming Line Lug Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Main Disconnecting Means . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Cable Bracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Secure Load Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Chapter 5
Door Latches, Operator Handles, and Unit Interlocks
Height Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Door Latches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Quarter-turn Door Latches. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
ArcShield Door Latches. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Rotary-operator Handles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Small Rotary-operator Handles
(Cat. Nos. 140M-SB and 140M-SY) . . . . . . . . . . . . . . . . . . . . . . . 55
Medium Rotary-operator Handles
(Cat. Nos. 140U-PB and 140U-PY). . . . . . . . . . . . . . . . . . . . . . . . 58
Large Rotary-operator Handles
(Cat. Nos. 140U-HM4 and 140U-HM4E) . . . . . . . . . . . . . . . . . 62
Unit Interlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Chapter 6
Install and Remove Units Unit Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Withdrawable Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Operating Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Safety Guidelines to Install and Remove Withdrawable Units . . . . 72
Insert a Withdrawable Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Remove a Withdrawable Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Remove the Unit Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Multiple Module Unit Doors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
One Module Unit Doors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Chapter 7
Commissioning Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Pre-commissioning Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Commissioning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Chapter 8
Maintenance Establish a Maintenance Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Suggested Maintenance Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
4 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 5
Table of Contents
Chapter 9
IntelliCENTER Options EtherNet/IP Motor Control Centers . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Connection Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Cable Length Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Cable Routing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Add a MCC Unit to an EtherNet/IP System . . . . . . . . . . . . . . . 87
Ethernet Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Connect Power Supplies–Remote or in the MCC Lineup. . . . 88
Network Power Supply and the Protective Earth Circuit. . . . . 88
Connecting Two Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . 88
System Design Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . 89
EtherNet/IP Software Installation Checklist. . . . . . . . . . . . . . . . 90
DeviceNet Motor Control Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Preparing a DeviceNet System for Commission . . . . . . . . . . . . . 90
Terminating Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Joining DeviceNet Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
DeviceNet Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Connect Power Supplies–Remote or in the MCC Lineup. . . . 94
Network Power Supply and the Protective Earth Circuit. . . . . 94
Connecting Two Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Electronic Data Sheets (EDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Where to Find EDS Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Installing EDS Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Finding EDS Files for Other Devices . . . . . . . . . . . . . . . . . . . . . . . 96
Uploading EDS Files from the Device . . . . . . . . . . . . . . . . . . . . . . 96
Appendix A
Worksheets Sample MCC Layout Worksheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Appendix B
Cable Entry and Exit Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Glossary
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 5
Page 6
Table of Contents
Notes:
6 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 7
This publication provides procedures to the following:
• How to receive and handle a CENTERLINE® 2500 shipment.
• How to install the received columns.
•How to install cables.
• How to access internal components.
• How to install and remove units.
• How to start up (commission) a newly installed motor control center.
• How to maintain the motor control center.

Preface

Summary of Changes

This publication contains new and updated information as indicated in the following table.
Topic Page
Updated product photos to reflect Series D features. Throughout
Added introductory paragraph to Preface section. 7
Updated artwork and table 2, and added tables 4 and 6 in Figure 2. 12
Updated artwork, and added both notes in Figure 5. 14
Updated table information in Technical Data section. 15
Added bullet-pointed text about cable entry and exit points in Location Planning section. 21
Added Important table about column air gap requirements. 26, 27
Added table row for 500 mm column width in Figure 10. 27
Updated Seal IP42 and IP54 Enclosures Before Connection section to include IP42 enclosures. 28
Converted step 5 to Attention table i n Seal IP42 and IP54 Enclosures Before Connection section. 28
Updated table information in Seismic Information section. 36
Added content to Access the Power Bus section for main and withdrawable units. 37
Added Figures 14 and 15, and revised artwork in Figure 16 (formerly Figure 14). 38
Expanded Figure 17, and added Figure 18 for power bus splicing configurations. 42
Increased number of PE conductors that can be present from three to four. 46
Updated horizontal PE photograph in step 1 of Splice the PE Conductor subsection. 46
Added the second paragraph in Control and Network Cables subsection. 48
Added label examples and expanded table footnote in Torque Specifications section. 48
Added last sentence to third paragraph about cable strain on the termination blocks. 49
Added Important table to Cable Bracing section. 51
Added last paragraph, Table 5, and Important table in Secure Load Wires section. 52
Added Type 5 to Form 4b in first bullet point and to corresponding picture. 52
Added Rotary-operator Handle Sizes section. 55
Revised artwork in Figure 20 with newer handle design. 55
Revised steps 2…4 and the corresponding artwork in Open the Unit Door in the ON/I Position subsection.
Revised step 2 and the photograph in Lock Units in the OFF/O Position subsection. 57
Added Lock Units in the ON/I Position subsection and Figure 18. 57
Added Medium Rotary-operator Handles subsection. 58
Revised Figure 21 to remove the medium rotary-operator handle art. 65
Updated both photographs and their callouts in Figure 21. 67
Updated photograph and callouts in Figure 22. 68
Updated photograph in Figure 24 to show an Ethernet network connection. 69
Switched ‘withdraw lever’ and ‘locking mechanism’ in step 2 and in graphic. 70
Consolidated separate withdrawable position graphics into new Figure 26. 71
Added ‘Clean ventilation mesh’ to step 13 of Suggested Maintenance Guidelines. 83
Changed Stratix switch model to 5700 in first sentence of Cable Routing subsection. 86
Added Appendix B. 101
56
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 7
Page 8
Preface

Additional Resources

These documents contain additional information about related products from Rockwell Automation.
Resource Description
Receiving, Handling, and Storing CENTERLINE 2500 motor control centers, publication 2500-IN002
CENTERLINE 2500 EtherNet/IP™ Motor Control Centers, publication 2500-TD003
EtherNet/IP Network Configuration User Manual, publication ENET-UM001
CENTERLINE 2500 DeviceNet™ Motor Control Centers, publication 2500-TD002
DeviceNet Media Design User Manual, publication
DNET-UM072
IntelliCENTER® Software User Guide, publication
MCC-UM001
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Safety Guidelines for the Application, Installation and Maintenance of Solid-state Controls, publication SGI-1.1
Product Certifications website, rok.auto/certifications Provides declarations of conformity, certificates,
Provides information to receive, handle, and store CENTERLINE 2500 Motor Control Centers (MCCs).
Provides information about EtherNet/IP MCCs.
Provides information to design, install, and troubleshoot an EtherNet/IP network system.
Provides information about DeviceNet MCCs.
Provides information to design, install, and troubleshoot a DeviceNet cable system.
Provides information to install and use IntelliCENTER software on CENTERLINE MCCs.
Provides general guidelines for installing a Rockwell Automation™ industrial system.
Provides general guidelines to install and maintain solid-state control components.
and other certification details.
You can view or download publications at
https://www.rockwellautomation.com/en_NA/literature-library/ overview.page. To order paper copies of technical documentation, contact
your local Allen-Bradley™ distributor or Rockwell Automation sales representative.

Purchased Components and Additional Instruction Sheets

Documentation and data sheets for specific components (for example, transformers, metering devices, electronic overloads, PLCs, soft starters, and drives) are shipped inside the motor control center. All documentation and data sheets must be read and understood before you install and operate the motor control center. Keep these manuals and other documentation for future reference.
8 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 9
Chapter 1
System Overview
CENTERLINE® 2500 motor control centers (MCCs) are designed for applications low-voltage motor for tough required.
The CENTERLINE power bus structure distributes line power throughout the MCC via an isolated bus work structure. A standard, center-fed, 300 A vertical bus supplies power to units above and below the horizontal bus, which results in an effective 600 A capacity and unrestricted unit arrangement. An optional 600 A vertical bus provides an effective rating of 1200 A.
that must comply with international standards and practices for
control centers. The CENTERLINE 2500 MCC is ideal
industrial applications where uptime and ease of maintenance is

ArcShield Rating

The CENTERLINE MCC is also available with an ArcShield™ rating. This rating includes arc-resistant features for enhanced protection if internal arcing faults happen.
With the standard safety features of the CENTERLINE 2500 MCC, the ArcShield option provides the following:
•Spring latches
• Reinforced structure
• Pressure relief vent system through the top of the enclosure
• Protection up 300 ms at 480V/65 kA
Table 1 - Conformity Ratings for CENTERLINE 2500 MCC with ArcShield
Value Description
Ratings:
Ue lp arc tarc lpc arc
Protection Personal and assembly protection suitable for limited continued operation; assembly
Requirements IEC/TR 61641 Ed. 3.0, 2014-1, parts 1…7
480V 65 kA 300 ms 65 kA
protection is limited to outgoing units tested for conditional current under arcing conditions.
An ArcShield label is provided on the MCC with information about the accessibility level and arc fault ratings. See Figure 8 on page 18
for an example
of this rating label and its location.
See Figure 4 on page 14 and page 54
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 9
for ArcShield door latches.
for the location of ArcShield structure protection
Page 10
Chapter 1 System Overview

IntelliCENTER Software

CENTERLINE 2500 MCCs with IntelliCENTER® software provide an integrated hardware, software, and communication solution. Its preconfigured software provides real-time data, trending, component history, wiring diagrams, user manuals, and spare parts. IntelliCENTER offers plug and play setup, troubleshooting, hardware configuration changes without opening enclosure doors, and convenient change tracking. It also provides intelligent diagnostic and predictive failure information.
IntelliCENTER technolog y improves the intelligence of your MCC by using built-in networking to capture information used for predictive maintenance, process monitoring, and advanced diagnostics.

IntelliCENTER Features

• Built-in networking – EtherNet/IP ™ or DeviceNet™ – Media helps protected behind barriers – Access ports in wireways – Topology lets you add and remove devices without interrupting any
other device on the network
• Intelligent motor controls – PowerFlex® drives – SMC™-3 and SMC-Flex soft starters – E300™, E1 Plus™, and E3 Plus™ Electronic Overload Relays
• IntelliCENTER software –Distributed I/O –POINT I/O™ system/DSA –Virtual MCC – Parameter editor –Status dashboards – Documentation management – Spare parts information
• Factory configuration – IP address network media validation – IP address node configuration – Communication check – Network commissioning
10 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 11
System Overview Chapter 1

IntelliCENTER Software

IntelliCENTER MCCs can be provided with preconfigured IntelliCENTER software. This software views, manages, and configures multiple MCC lineups. The IntelliCENTER software communication driver lets the software be installed and operated on EtherNet/IP or DeviceNet. The IntelliCENTER software can function as a standalone software package or as an ActiveX control in a Human Machine Interface (HMI).

Structure

CENTERLINE 2500 MCCs offer units with a full complement of AC drives, soft starters, and other devices. Pluggable power connections on the back of the unit plug into the vertical bus. A mechanical interlock helps prevent the unit door from being opened while the main switch is in the ON/I position. An additional mechanical interlock helps prevent the unit from being withdrawn or inserted when the unit main switch is closed. Separate vertical wireways isolate control and network cables from power wiring. Units are available as fixed or fully withdrawable.
Figure 1 - CENTERLINE 2500 MCC
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 11
Page 12
Chapter 1 System Overview
Table 2 - Widths
Column
with Wireway
Column without
Wireway
Fixed or
Withdrawab le
Unit Width
(1)
Verti cal Wireway Width
(2)
Tot al
Column
Width
Fixed
Unit
Width
(3)
Tot al
Column
Width
500 200 700 500 500
300 800 600 600
400 900 700 700
500 1000 800 800
900 900
1000 1000
(1) Available from 1…24 modules. (2) Recommended minimum wireway widths
for the various forms of separation:
• For 3B, 300 mm wide
• For 4B Type 5, 400 mm wide
• For 4B Type 7, 500 mm wide
(3) Applies to a full column (24 modules).
Table 3 - Depth
Single-front Double-front
600 1200
800
(1)
(1) Single-front IP42 configurations with a
3200 A bus (air circuit breaker units only) or 4000 A bus (all unit types) require a 100 mm air gap behind the column. In these instances, the overall depth is 900 mm.
1600
(2)
(2) Double-front IP42 configurations with
a 3200 A bus (air circuit breaker units only) or 4000 A bus (all unit types) require a 400 mm air gap between the rear of the columns. In these instances, the overall depth is 2000 mm.
Table 4 - Thickness, Nominal
Description Measurement
Side plates (all depths) 2
Back plates (all widths) 2.5
Bottom mounting channel
(1)
(1) Front and re ar.
3.5
Top plates (all widths) 2
Bottom plates 2
Horizontal wireway covers 2
Wireway doors 2
Doors
(2)
(2) 2 mm for 1…22 modules, 2.5 mm for 24 modules.
2, 2.5
ArcShield 480V doors
(3)
(3) 2.5 mm for 1…22 modules, 3 mm for 24 modules.
2.5, 3
Table 5 - Weight, kg
(1)
Column Depth
Column Width 600 mm 800 mm
600, 700 350 450
800 400 525
900 450 575
1000 500 650
(1) Weights that are shown are for an MCC column with
six units. Many factors (number of units, horizontal power bus, wireway width, column depth, and shipment packaging) affect the ac tual weight. The packing slip shipped with an MCC unit shows the exact shipping weights.
Table 6 - He ight
Dimension Measurement
Total unit height
• With top gland plate
• With ventilation hood
•With lift angle
• With lift angle on gland plate
2300 2306 2370 2375 2387
Available unit height 1980
Top horizontal wireway 170
Bottom horizontal wireway 115
External mounting channel 35
All measurements are in mm unless otherwise specified.
600 mm Deep Withdrawable Column with a 200 mm Wireway Shown
170
1980
35
1
1
5
500…1000
600 or 800
2300
200…500
500

Dimensions

CENTERLINE 2500 MCCs are designed in widths between 500…1000 mm. Each column is 2300 mm high and either 600 mm or 800 mm deep. Double-front in Figure 2
Unit size is described in terms of modules. Each module is approximately 80 mm high. Columns can accommodate 24 modules of different unit combinations.
Figure 2 - Typical Column Dimensions
columns are also available. For additional options, see the tables
.
12 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 13
System Overview Chapter 1
Lifting Angle
Network Wireway
Top Wi rew ay End Plates
Left Side Plate
Center End Closing Plate
Bottom Wireway End Plates
Mounting Channels
Bottom Plates
Bottom Wireway Cover
Right Unit Support and Vertical Wireway Assembly
Ver tic al W irew ay Doo r
Top Wi re way C ove r
Top Wi rew ay Pa n
Top Wi re way B ar ri er
Top Plate
Optional ArcShield Center End Closing Plate Insulator
Horizontal Power Bus
Single Unit Support Pan

Typical Column Construction

Columns are rigid, free-standing structures with heavy-duty, external mounting channels. Columns are secured at the installation site by bolting through clearance holes in the mounting channel or by welding.
The standard for internal sheet metal parts is Z275 galvanized metal for Series D CENTERLINE 2500 motor control centers.
Figure 3 - Typical Column
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 13
Page 14
Chapter 1 System Overview
Door Latch Brackets
See page 50
for more information.
Pressure Relief Plate
See page 21
for more information.
Detail A
Detail B
Detail C
A
B
C
Detail D
D
Center End Closing
Plate with Insulator
Only on end-of-lineup
columns.
See Figure 3 on page 13
for more details.
Frame-mounted Brackets
See page 50
for more
information.
Columns Installed in a Single-front Configuration Columns Installed in a Double-front Configuration
NOTE: Double-front IP42 configurations with a 3200 A bus (air circuit breaker units only) or 4000 A bus (all unit types) require a 400 mm air gap between the rear of the columns.
NOTE: Single-front IP42 configurations with a 3200 A bus (air circuit breaker units only) or 4000 A bus (all unit types) require a 100 mm air gap behind the column.
Additional bracing is provided for ArcShield columns.
Figure 4 - ArcShield Column Protection Hardware
Figure 5 - Column Configuration
14 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 15
System Overview Chapter 1

Technical Data

This table provides the technical specifications for the 2500 MCC.
The following certifications (2500-CT0xx) can be found at the Rockwell Automation Literature Library: https://www.rockwellautomation.com/
global/literature-library/overview.page.
Standards EN 60204-1:2006 + A1:2009 Safety of machinery – Electrical equipment of machines; Part 1: General requirements
IEC 61439-1 Low-voltage switchgear and controlgear assemblies; Part 1: General requirements
IEC 61439-2 Low-voltage switchgear and controlgear assemblies; Pa rt 2: Powe r switchgear an d controlgear as sembli es
IEC/TR 61641 Ed. 3.0, 2014-1, parts 1…7
EC Directives 2011/65/EU RoHS Directive
2004/108/EC EMC Directive
2006/95/EEC Low Voltage Directive
Certifications and Markings
ABS and ABS shipboard 2500-CT015
CE Conformance Marked 2500-CT008 and 2500-CT009
China Compu lsory Cer tificate (CCC) 2500-CT010, 2500-CT011, 2500-CT012, 2500-CT013, and 2500-CT022
DEKRA 2500-CT018, 2500-CT019, 2500-CT020, and 2500-CT021
EAC MCC-CT001
SII Approval 2500-CT014
Rated Voltages Rated operating voltage, U
Rated frequency, f
Rated insulation voltage, U
Rated Currents Continuous current rating, I
Short circuit peak withstand, I
Short time withstand rating, I
e
n
i
e
pk
cw
Neutral (N) Full or half-rated
Creepage Distances and Clearances
Bus Material and Plating
Rated impulse withstand voltage, U
Material group (overvoltage category) IIIa (175 </= CTI < 400)
Pollution degree 3
Horizontal power bus Copper (optional tin plating)
Vertical distribution bus Copper with tin plating
Protective earth conductor (PE) Copper (optional tin plating)
Degrees of
IEC 60529 IP20, IP42, or IP54
Protection
Forms o f
IEC 61439-2 Forms 2b, 3b, 4b, or 4b Type 7
Separation
Column
Height, width, and depth See page 12
Dimensions
Units Module size (approx) 80 mm high x 500 mm wide = 1 module
Modules per column, max 24 of varied unit combinations
Withdrawable unit sizes 1, 2, 4, 6, 8, 10, and 12 modules
Structural Surf ace Treatments
Interior Z275 galvanized metal (painted interior available as custom option)
Exterior RAL 7032 Pebble Grey paint (additional colors available by request)
Environment Storage temperature -25…+55 °C
Operating (ambient) temperature -5…+40 °C
Altitude Up to 1000 m without derating: derating over 1000 m
(1) Up to 600 A top and bottom, effective 1200 A per column. (2) The average temperature over a 24-hour period must not exceed 35 °C.
Enclosed low-voltage switchgear and controlgear assemblies; Guide for testing under conditions of arcing due to internal fault
, 2500-CT016, and 2500-CT017
Up to 690V, 3-phase
50…60 Hz
1000V, 3-phase
Horizontal bus up to 4000 A; vertical bus up to 1200 A per column
(1)
Horizontal bus up to 210 kA
Horizontal bus up to 100 kA for 1 second
6 kV, 8 kV, or 12 kV
imp
(2)
with up to 95% noncondensing humidity
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 15
Page 16
Chapter 1 System Overview
Catalog Number/Serial Number
Power Bus Voltage and Current Rating
Enclosure Typ e
Series Letter
Identifies Column Sequence Numbering
Catalog Number/Serial Number Unit LocationDevice Type and Rating
Vol tage Rati ngOrder Number

Nameplate Data

In compliance with EN 61439-1, each CENTERLINE 2500 MCC column is supplied with a nameplate on the enclosure or vertical wireway door.
Figure 6 - Column Nameplate
Each unit also has an identification label. On withdrawable units, the unit identification label is on the interior of the bottom plate of the unit. On fixed units, the unit identification label is on the interior right side plate.
Figure 7 - Unit Identification Label
TIP The catalog number or serial number and series letter are required to
identify the equipment properly to sales or factory personnel.
16 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 17
System Overview Chapter 1

MCC Column-number Sequence

IMPORTANT CENTERLINE 2500 MCCs are designed to function in any column-number
sequence. However, we recommend that columns be installed in sequential order.
Each CENTERLINE 2500 MCC column nameplate identifies column­number sequence, for example, MCC column 1 of 1 or 1 of 5. See
Figure 6 on page 16
Columns are numbered to match factory-supplied MCC elevation drawings and to easily identify MCC columns and units. If there are questions about column numbering during field installation, inspection, or operation, the following instructions can provide guidance.
IMPORTANT Leftmost column must be installed in the proper location for the bus to
The most important criteria for additions of columns to existing MCCs is matching the horizontal bus, enclosure type, and network capabilities for the complete MCC line up. The voltage, current rating, short circuit withstand, and IP rating for all columns must be consistent.
for where to find column-number sequence information.
splice. (Both ends of double-front MCCs must be installed as ends for splicing.)
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 17
Page 18
Chapter 1 System Overview
C
D
E
A
B
Detail D
Detail E
Detail C
Top Vi ew
Front View – Frame Mount Front View – Withdrawabl e
Detail B
Detail A
NOTE: All labels
are external except
for horizontal
locations of “D.”

ArcShield Labels

MCC columns with arc proof assembly have a rating label (Detail E in
Figure 8
be in place before operating an MCC with ArcShield; see Figure 8
) below the nameplate. There are also labels on other parts that must
.
At the end of a lineup, CENTERLINE 2500 MCCs with ArcShield have a back-corner baffle and insulation on the center side closing-plate; see
Figure 4 on page 14
for more details. They also have external vertical support
angles at each end of the lineup.
Figure 8 - ArcShield Label Locations
18 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 19
Chapter 2
Receiving, Handling, and Storage
See Receiving, Handling, and Storing CENTERLINE® 2500 Motor Control Centers Instructions, publication 2500-IN002 This publication is shipped with each MCC, attached to the outside of the MCC within the layer of clear polyethylene encasement (polywrap).
ATT EN TI ON : MCCs are top and front heavy. To avoid personal injury or structural damage, lift or move the MCC by only the methods outlined in Receiving, Handling, and Storing CENTERLINE 2500 Motor Control Centers, publication 2500-IN002
.
, for additional instructions.

Receiving

CENTERLINE 2500 MCCs are shipped upright as one or two column shipping blocks or two or four double-front column shipping blocks. Each CENTERLINE 2500 MCC shipping block is provided with a lifting angle. Each column in a shipping block is bolted to the shipping skid with removable shipping angles and covered with clear plastic wrap. Protection is for upright shipping and is not waterproof or water-resistant. Equipment that extends from the structures is also protected.
Heavy-duty export packaging is similar to standard packaging, but uses a polywrap suitable for occasional water spray. In addition, wood framing and sheeting surround the columns. The heavy-duty export packaging is not water-resistant, waterproof, or intended for long-term storage.
Upon delivery of the MCC, see the packing slip shipped with your MCC for sizes and exact shipping weights. Inspect the shipment for lost or damaged items. If lost or damaged items are detected, see the steps that are described in publication 2500-IN002
.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 19
Page 20
Chapter 2 Receiving, Handling, and Storage

Handling

Storage

The following are acceptable methods of handling MCC columns within the receiving facility. These methods are described in publication 2500-IN002
• Use of a forklift
• Overhead lifting (crane or hoist)
•Sling lifting
MCC columns must be handled in the upright vertical position. Failure to comply with this method can lead to busbar, unit, and enclosure damage.
The MCC must remain bolted to the shipping skid until delivered to its final installation area.
ATT EN TI ON : MCCs are top and front heavy. To avoid personal injury or structural damage, never attempt to lift or move the MCC by any means other than the methods outlined in Receiving, Handling, and Storing CENTERLINE 2500 Motor Control Centers, publication 2500-IN002
Store CENTERLINE 2500 MCCs, units, and related equipment in dry environment with ambient temperatures ranging from -25…+55 °C (-13…131 °F). For short periods (<24 hours), temperatures of up to 70 °C (158 °F) are allowed. Take care to help prevent damage from exposure to excessive humidity, vibration, and shock.
.
.
a clean,
Store MCCs with the plastic covering in place to help prevent dirt and dust from entering the structure. Check periodically for condensation build-up and, if necessary, install space heaters. To order space heaters, Rockwell Automation representative
.
contact your
20 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 21
Install Columns
300 mm Minimum Clearance
ArcShield pressure relief plate on top of column.
Chapter 3

Location Planning

When you plan the location for your CENTERLINE® 2500 MCC, consider the following:
• Cable entry and exit points (see Appendix B
•Busways
• Overall height of installation area
•Alignmen39
•t with other equipment
• Future needs
•Environment
The area must be level and the environment must be compatible with the degree of protection that is provided by the enclosure.
)

ArcShield™ Clearance Space

Provide a minimum 300 mm of clearance space above the MCC to vent the pressure relief plates if there is an arc flash.
ATT EN TI ON : Do not step on the pressure relief plate, which can cause it not to work properly during arc flash.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 21
Page 22
Chapter 3 Install Columns

Environment

CENTERLINE 2500 MCCs are designed to operate under the service conditions described in IEC 61439-1. Variations in temperature and relative humidity can potentially cause occasional condensation.
Temperature
When you operate an MCC, ambient air temperature must remain in the range of -5…+40 °C ( period must not exceed 35 °C
23…104 °F)
Humidity
Noncondensing humidity is permissible up to 95% at the maximum temperature of 40 °C (104 °F), with the average temperature not to exceed 35 °C
(95 °F)
over a 24-hour period
Altitude
. The average temperature over a 24-hour
(95 °F)
.
.
The CENTERLINE 2500 MCC is designed to operate at installation sites at altitudes up to 1000 m (3281 ft) above sea level without derating. If the altitude at your installation site exceeds 1000 m (3281 ft) above sea level, contact your Rockwell Automation™ representative for derating information.
Pollution Degree
CENTERLINE 2500 MCCs are designed for use in a pollution degree 3 environment. IEC 61439-1 defines pollution degree 3 as, “conductive pollution occurs or dry, non-conductive pollution occurs that become conductive due to condensation.”
22 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 23
Install Columns Chapter 3
Shipping Angle (
4 places)
Pack ing Box Bracket s (4 places)
Detail A
Detail B
B
A

Remove Packing Materials

When the MCC has been delivered to the site of installation, remove the packaging material. Save any manuals and data sheets for future reference.
ATT EN TI ON : To avoid personal injury, use caution when the motor control center is not secured. Motor control centers are top and front heavy.
1. Remove the packing box around the horizontal bus if present r
emove the four brackets as shown (Detail A).
and
2. Remove the bolts that secure each shipping angle (Detail B) from the shipping skid.
ATTENTION:
Once the bolts are removed from the shipping angles,
the MCC is no longer secured on the skid.
3. Remove the shipping angles from the MCC.
You can now remove the MCC from the shipping skid.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 23
Page 24
Chapter 3 Install Columns

Locate Bus Splice Kits

A fluorescent pink, removable label (on the outside of the column) designates where provided power bus splice kits are stored. PE splice kits are in the bottom horizontal wireway, which is fastened to the horizontal PE conductor.
Locate the splice kits and set aside for later use.
Figure 9 - Splice Kit Label
24 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 25
Install Columns Chapter 3
Top En d
Closing Plates
Horizontal
Wireway Cov ers
Center End Closing Plate
Insulator (optional)
Bottom End
Closing Plates
Center End
Closing Plates
Horizontal
Wirew ay Covers

Removing the Covers

Follow these procedures for removing the covers on the MCC.
1. Remove the top and bottom horizontal wireway covers from th MCC.
2. I
f present, remove the top, bottom, and center end closing plates, on
the sides of the two columns that are to be joined.
e
3. If ArcShield is present, remove the center end closing plate insulators.
IMPORTANT When you plan MCC cable routing, consider cable replacement in
your plans.
For more information about cable installation, see Chapter 4
.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 25
Page 26
Chapter 3 Install Columns

Position the Motor Control Center

Follow these procedures to position your MCC.
IMPORTANT See Figure 5 on page 14
for column air gap requirements on certain IP42
configurations.
1. Documentation packages that are shipped with assembled MCCs include an MCC elevation drawing with a floor plan layout. Lo
use this floor plan layout to position your MCC columns.
and
2. Identify the leftmost column.
cate
TIP The horizontal power bus does not extend past the leftmost MCC
column. For sequential columns, the horizontal power bus extends past the MCC.
3. Position the MCC in the location where it is to be installed.
IMPORTANT The floor surface must be level.
4. Depending on the installation site, begin with the leftmost or right­most column and install one shipping block at a time.
See Receiving, Handling, and Storing CENTERLINE 2500 Moto
ontrol Centers Instructions, publication 2500-IN002
C
, for handling
guidelines.
r
26 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 27
Install Columns Chapter 3
A
B
68
35
Mounting bolt holes (4), 18 mm dia.
Mounting bolt holes (4), 18 mm dia.
A
B
Front of Column
C
D
C
D
68
35
Standard Mounting Channels (2 installed per column) Optional Mounting Frame (1 per column)
NOTE: Neither mounting method is flush with any side of the MCC column.

Secure a Motor Control Center

Documentation packages that are shipped with assembled MCCs include an MCC elevation drawing that shows an MCC floor plan layout. To secure a column to the foundation, see the provided floor plan layout and the following procedures.
See Chapter 4
for cable and conduit routing instructions.
IMPORTANT See Figure 5 on page 14 for column air gap requirements on certain IP42
column configurations.

Securing Methods

MCC columns or shipping blocks can be bolted or welded to a foundation. Two mounting channels on the bottom of each MCC column are used for either securing method.
Weld Down Method
See Figure 12 on page 33 to weld an MCC column or shipping block to a foundation.
Bolt Down Method
Two mounting channels are provided for each MCC column. An optional mounting frame is also available. Both mounting methods can be fastened with up to four steel M12 bolts (minimum Property Class 8.8). For best results, pre-locate and embed the bolts in the foundation before you install each MCC column. For more information about mounting bolt locations, see page 29
Figure 10 - Mounting Channel Dimensions and Bolt Locations
All dimensions are mm.
MCC Column Width A B MCC Column Depth C D
(1) Available only with the optional welded frame.
through page 31.
(1)
500
600 597 461 800 712 782
700 697 561
800 797 661
900 897 761
1000 997 861
497 361 600 512 582
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 27
Page 28
Chapter 3 Install Columns
3 mm wide continuous bead of caulk sealer around outside edge of the sideplate being joined.
Do not allow ‘skin’ to form on the caulk before you join the sec tions.

Seal IP42 and IP54 Enclosures Before Connection

TIP The following steps do not apply to IP20 enclosures.
1. Remove the tube of caulk (mastic) sealer from the splice kit and read th
e application directions on the tube.
2. Cut the nozzle at the first notch, 3 mm from the end.
3. Apply a continuous bead of caulk, 3 mm wide, around the outside edge
of the sideplate of the fixed motor control center.
4. Slide the columns together
V
erify that the cabinets are level and joining holes are aligned.
.
IMPORTANT If you removed the lifting angles from the IP42 or IP54 enclosure, then you
must also seal the lifting angle bolt holes with the caulk sealer.
28 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 29
Install Columns Chapter 3
500…1000
360…860
70
442…942
44
512…712
600…800
438…638
29
81
FRONT
REAR
Dimensions are in mm.
Diagram shows top view of 600 mm and 800 mm column
A
B
Protective earth (PE) conductor

Secure Single-front, One-column-wide Shipping Blocks

The following instructions are to bolt down the MCC. See Figure 12 on
page 33 for weld down requirements.
IMPORTANT Verify that there is adequate clearance on the sides of columns to access
the rear mounting bolt locations.
Use steel M12 bolts (minimum Property Class 8.8) to secure columns to the foundation.
1. To locate the front mounting channel, remove the bottom wireway cover. See Figure 3 on page 13
2. Secure the front of the MCC to the foundation with the mounting dimensions in the following illustration and the mounting channel requirements on page 27
3. Reinstall the bottom wireway cover.
4. To locate the rear mounting channel, remove the bottom wireway end
plate near the back of the unit. See Figure 3 on page 13 lo
cation.
for cover location.
.
for end plate
5. Secure the rear of the MCC to the foundation with the mounti
imensions in the following illustration and the mounting channel
d requirements on page 27
einstall the bottom wireway end plate.
6. R
.
ng
Input
Power, A
Up to 1600 6 234 3200 18 222
2000…2500 12 228 4000 24 216
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 29
Thickness, mm
Material
AB AB
Distance,
mm
Input
Power, A
Material
Thickness, mm
Distance,
mm
Page 30
Chapter 3 Install Columns
1000…2000
442…942
58
A
B
360…860
44
512…712
600…800
438…638
70
81
29
Protective earth (PE) conductor
FRONT
REAR
442…942
First Column
= Mounting hole location not required.
Dimensions are in mm.
Diagram shows top view of 600 mm and 800 mm column depths.

Secure Single-front, Two-column-wide Shipping Blocks

The following instructions are to bolt down the MCC. See Figure 12 on
page 33 for weld down requirements.
IMPORTANT Verify that there is adequate clearance on the exposed sides of columns to
access the rear mounting bolt locations.
Use steel M12 bolts (minimum Property Class 8.8) to secure columns to the foundation. Not all bolt locations are used.
1. To locate the front mounting channel, remove the bottom wireway cover. See Figure 3 on page 13
2. Secure the front of the MCC to the foundation with the mounting dimensions in the following illustration and the mounting channel requirements on page 27
3. Reinstall the bottom wireway cover.
4. To locate the rear mounting channel, remove the bottom wireway end
plate near the back of the unit. See Figure 3 on page 13
cation.
lo
for cover location.
.
for end plate
5. Secure the rear of the MCC to the foundation with the mounti
imensions in the following illustration and the mounting channel
d requirements on page 27
.
6. Reinstall the bottom wireway end plate.
ng
Material
Input
30 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Power, A
Up to 1600 6 234 3200 18 222
2000…2500 12 228 4000 24 216
Thickness, mm
Distance,
mm
AB AB
Input
Power, A
Material
Thickness, mm
Distance,
mm
Page 31
Install Columns Chapter 3
500…1000
360…860
70
A
B
442…942
1196
438…638
29
81
438…638
A
B
FRONT OF UNIT 2
FRONT OF UNIT 1
Protective Earth (PE) Conductor
Protective Earth (PE) Conductor
Dimensions are in mm.
Diagram shows top view of 600 mm column depths.
158
= Mounting hole location not required.

Secure Double-front, One-column-wide Shipping Blocks

The following instructions are to bolt down the MCC. See Figure 12 on
page 33 for weld down requirements.
IMPORTANT Use steel M12 bolts (minimum Property Class 8.8) to secure columns to
the foundation. Not all bolt locations are used.
1. To locate the front mounting channel, remove the bottom wireway cover. See Figure 3 on page 13
2. Secure the front of the MCC to the foundation according to the dimensions in the following illustration and the mounting channel requirements on page 27
3. Reinstall the bottom wireway cover.
4. Repeat steps 1…3 for the other side of the double-front shipping block.
for cover location.
.
Material
Input
Power, A
Up to 1600 6 234 3200 18 222
2000…2500 12 228 4000 24 216
Thickness, mm
AB AB
Distance,
mm
Input
Power, A
Material
Thickness, mm
Distance,
mm
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 31
Page 32
Chapter 3 Install Columns
Front
First Column Last ColumnSecond Column
Installation sequence, left to right.
Installation sequence, right to left.
First Colum n
Last Column
Additional Columns
Second ColumnAdditional Column
Front
ATTENTION: The figure shows which bolts are required for multiple­column shipping blocks. Drawings with specific dimensions are supplied with each multiple-column shipping block.
= Mounting hole locations not required.
Top View
Top View

Secure Multiple-column Shipping Blocks

Figure 11 and Figure 12 are to bolt down a multiple-column shipping block.
For weld down requirements, see Figure 13 on page 34
IMPORTANT Verify that there is adequate clearance on the exposed sides of columns to
access the rear mounting bolt locations.
Use steel M12 bolts (minimum Property Class 8.8) to secure columns to the foundation. Not all bolt locations are used.
Figure 11 - Bolt-down Requirements for Single-front, Multiple-column-wide Shipping Blocks
.
32 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 33
Figure 12 - Bolt-down Requirements for Double-front, Multiple-column-wide Shipping
Front of Unit 1
Front of Unit 2
Installation sequence, left to right.
Installation sequence, right to left.
First Column Last ColumnSecond Column Additional Columns
First ColumnLast Co lumn Second Colu mnAdditional Columns
Front of U nit 1
Front of Unit 2
= Mounting hole locations not required.
Top View
Top View
ATTENTION: The figure shows which bolts are required for multiple-
column shipping blocks. Drawings with specific dimensions are supplied with each multiple-column shipping block.
Blocks
IMPORTANT Use steel M12 bolts (minimum Property Class 8.8) to secure columns to the
foundation. Not all bolt locations are used.
Install Columns Chapter 3
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 33
Page 34
Chapter 3 Install Columns
Front
First Column Last ColumnSecond and Additional
Columns
40 mm 40 mm
40 mm40 mm
40 mm40 mm
40 mm 40 mm
40 mm40 mm
40 mm40 mm
Wel ds
External Mounting Channel
First Colum n Last ColumnSecond and Additional
Columns
40 mm 40 mm
40 mm40 mm
40 mm40 mm
40 mm
40 mm
40 mm40 mm
40 mm
40 mm
Weld
Wel d
External Mounting Channel
Floor Lin e
Floor Line
Double-front Configurations
Single-front Configurations
Front
Front
Front
Front
Top Vi ew
Wel d
Front
End View
Top Vi ew
End View
Weld
Figure 13 - Weld-down Requirements for Various Configurations
34 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 35
Install Columns Chapter 3
89
336
353
336
353
744
547
573
165
Dimensions are in mm.
89
336
353
336
353
744
747
773
365
FRONT
FRONT
600 mm Deep Column 800 mm Deep Column
Step 1
Step 2
Step 1

Join Columns

ATTENTION: Join columns is done after all columns/shipping blocks
have been secured to a foundation.
Do not use the hardware to draw columns together.
1. Starting with the first column, use M6 x 1.0 hardware that is provided in the power bus splice kit to fasten the six joining holes together (step 1 in the figure
800 mm deep columns: use a M6 hex head bolt, washer, and nut that
2.
is provided in the power splice kit to fasten the two joining
gether (step 2 in the figure).
to
).
holes
3. Torque all fastened bolts to 5.6 N•m.
4.
Inspect the interior for dust and dirt. Vacuum cleaning is recommended.
IMPORTANT Do not clean with compressed air—it can contain moisture and
blow debris into the control equipment.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 35
Page 36
Chapter 3 Install Columns

Seismic Capabilities

Actual CENTERLINE 2500 MCC units have been seismically qualified by dynamic (triaxial multi-frequency testing) seismic tests by using ICC–ES AC156
(1)
acceptance criterion that covers general equipment and supports the seismic certification of electrical systems such as Motor Control Centers (MCCs). The testing was conducted in accordance with ICC–ES AC156 criteria and supports data for the following qualification requirements:
• 2006 and 2009 International Building Code, International
Code
Council 1997 Uniform Building Code, Structural Engineering Design
• Provisions, Zone
ASCE Standards SEI/ASCE 7-05 and SEI/ASCE 7-10, Minimu
n Loads for Buildings and Other Structures
Desig
The ICC–ES AC156 parameters for an S
4
DS level of 1.63 g at the roof level or
below is in the following table.
(1)
Test Criteria
ICC-ES-AC156 1.63 1.0 2.608 1.956 1.33 1.092 0.440 2.48 1.0
(1) Equipment is qualified for SDS and z/h values shown. Qualifications can be valid for higher SPS where z/h is less than 1.0.
SDS (g) z/h
(1)
CENTERLINE 2500 MCC units demonstrated compliance with th fol
lowing:
• 100% g level of Uniform Building Code 1997 (UBC) Zo (
the maximum UBC Zone)
• 100% g level of the International Building Code 2009 (IBC
EI/ASCE: S
(S
DS
Horizontal Vertical
(1)
ARIG
(1)
AFLEX/ARIG AFLEX
(1)
(1)
ARIG
AFLEX/ARIG
ne 4
),
1.5 g @ 5 Hz and SD1 2 g @ 1 Hz) when
e
subjected to a UBC Zone 4 earthquake or the IBC seismic event
m
Rp/IpAFLEX
Throughout the seismic testing, the MCC units were under power and operated before, during, and after the seismic tests.
To obtain an IBC or UBC seismic withstandability, each individual CENTERLINE
2500 MCC lineup (including any in double-front applications) must be mounted on an adequate seismic foundation. Installation must be conducted per the anchoring requirements as indicated in this instruction manual. All columns in the MCC lineup must also be bolted together per instructions in Join Columns
on page 35.
In the CENTERLINE 2500 MCC lineup, mounting channels are incorporated in the standard design. As an alternative to bolt down anchoring, these mounting channels can be welded to an adequate seismic foundation. For seismic weld down applications, see Figure 12 on page 33
.
(1) Acceptance Criteria for Seismic Certification by Shake-Table of Non-structural components (AC156), International Code of Council
Evaluation Service (ICC-ES), October 2010.
36 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 37
Install Columns Chapter 3

Splice the Power Bus

ATT EN TI ON : To help prevent severe injury or death, de-energize all power
sources to the MCC before you join and splice columns. Follow EN 50110 requirements, and local codes and guidelines.
IMPORTANT When you splice the horizontal power bus, always begin by splicing from
the lowest phase busbar and work from the bottom up.
IMPORTANT NO-OX-ID Use– Do not get any busbar corrosion inhibitor on the bus
splicing hardware. It keeps the hardware from being properly torqued and damage can occur.
Power bus consists of the main horizontal bus and neutral bus (if present). Based on the current rating of the power bus, the splice kit contains the appropriate splice bars and corresponding hardware. The following procedures describe methods for splicing power buses that are based on the ampere rating of the busbars.
For additional splicing information related to specific MCCs, see the elevation drawing that is shipped with the MCC in the documentation package.
TIP If necessary, remove units and unit support pans for the appropriate
access to splice the power bus.

Access the Power Bus

How to access the power bus depends on the column type. Follow the procedures that are specific to your MCC columns.
For Columns with Main Units (see Figure 14 and Figure 15 on page 38)
1. Open the main unit door.
2. Depending on your unit, there are one or two splice covers with
handles to the side of the main, as shown in Figure 14
3. Remove the four M6 screws that secure each splice cover (step1 in
Figure 14
4. For one splice cover, follow the removal sequence in Figure 14
For two splice covers, follow the removal sequence in Figure 15
5. Reinstall all M6 screws.
The power busbars are now accessible.
, or steps 1 and 2 in Figure 15).
and Figure 15.
.
.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 37
Page 38
Chapter 3 Install Columns
21 3
21
Figure 14 - Remove Splice Cover on Main Unit (Frames 1 and 2) With Two Splice Covers
Figure 15 - Remove Splice Covers on Main Unit (Frame 4) With One Splice Cover
For Withdrawable Unit Columns with Vertical Wireways (see Figure 16 on page 39)
1. Open the vertical wireway door.
2. Locate and loosen the four M6 screws that secure the secondary splice
cover, as shown in step 1 of Figure 16
3. Slide the secondary splice cover so the four loosened screws align with the entry hole of each keyhole slot, as shown in step 2 of Figure 16
4. Remove the secondary splice cover.
5. Locate the M6 screws for the primary splice cover, as shown in step
of Fi
gure 16
.
TIP For vertical wireways up to 300 mm wide, there are only two
screws with keyhole slots that secure the primary splice cover.
For vertical wireways wider than 300 mm, there are four screws that secure the primary splice cover. The two additional screws must be removed before you can remove the primary splice cover.
6. Slide the primary splice cover so the two loosened screws align with the entry hole of each keyhole slot, as shown in step 4 of Figure 16
7. Remove the primary splice cover.
.
.
3
.
38 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 39
Install Columns Chapter 3
NOTE: Gray arrows represent bolts only on vertical wireways wider than 300 mm.
21 3
4
You can temporarily store the two splice covers at the bottom of the vertical wireway.
8. Reinstall any removed screws for the primary splice cover.
TIP You can temporarily store the two splice covers in the bottom of
the vertical wireway, as shown in Figure 16
.
The power busbars are now accessible.
Figure 16 - Remove Splice Covers on Withdrawable Units With Air Circuit Breaker (ACB) and Vertical Wireways
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 39
Page 40
Chapter 3 Install Columns
For Withdrawable Unit Columns with Type 4b Vertical Wireways (see Figure 17 on page 41)
1. Open the vertical wireway door.
2. Locate and loosen the three M6 screws that secure the top splice cover,
as shown in step 1 of Figure 17
3. Remove the top splice cover.
TIP You can temporarily store the top splice cover in the top of the
vertical wireway, as shown in step 2 of Figure 17
4. Locate the three M6 screws for the bottom splice cover, as shown in step 3 of Figure 17
.
5. Remove the bottom splice cover.
TIP You can temporarily store the bottom splice cover in the bottom
of the vertical wireway, as shown in step 4 of Figure 17
6. Reinstall any removed screws for the two splice covers.
The power busbars are now accessible.
.
.
.
40 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 41
Install Columns Chapter 3
2
1
3
4
2
4
Figure 17 - Remove Splice Covers on Withdrawable Units With Type 4b Vertical Wireways

Splicing The Power Bus

Follow these procedures to splice the power bus.
1. Assemble splice bars and hardware. Depending on our configuration,
Figure 18 on page 42 or Figure 19 on page 44.
see,
Repeat for each phase of busbar and, if present, the neutral bar.
2. Tighten hardware to torque specifications.
See Torque Requirements for Hardware Connections on page 48
.
IMPORTANT Do not grease or lubricate hardware.
3. Reinstall the splice covers and check that the bolts and nuts are secure.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 41
Page 42
Chapter 3 Install Columns
Frame 1 - 800 A and 1250 A
2 hole, RT
Frame 1 - 800 A and 1250 A
2 hole, LT
Frame 1 - 800 A and 1250 A
4 hole, LT and RT
Frame 1 - 1600 A
4 hole, LT and RT
Frames 1 and 2 - 2500 A
4 hole, LT and RT
Frame 2 - 2000 A
4 hole, RT
Frame 1 - 2000 A
4 hole, LT and RT
= Front of Unit RT = Right side of ACB column LT = Left side of ACB column
Frame 2 - 800 A and 1250 A
2 hole, RT
Frame 2 - 800 A and 1250 A
2 hole, LT
Frame 2 - 800 A and 1250 A
4 hole, LT
Frame 2 - 800 A and 1250 A
4 hole, RT
Frame 2 - 1600 A and 2000 A
4 hole, LT
Frame 2 - 1600 A
4 hole, RT
4. Reinstall the units and unit support pans in their respective stations if
ey were removed.
th
Figure 18 - Power Bus Splicing Configurations With Straight Splice Bars
IMPORTANT Only for units with air circuit breaker (ACB). For other units, see page 46.
42 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 43
Install Columns Chapter 3
Frame 4 - 2000 A and 2500 A
4 hole, RT
Frame 4 - 2000 A and 2500 A
4 hole, LT
= Front of Unit RT = Right side of ACB column LT = Left side of ACB column
Frames 1, 2, and 4 - 3200 A
4 hole, LT and RT
Frames 1, 2, and 4 - 4000 A
4 hole, LT and RT
Figure 17 - Power Bus Splicing Configurations With Straight Splice Bars (continued)
IMPORTANT Only for units with ACB. For other units, see page 46.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 43
Page 44
Chapter 3 Install Columns
Frame 1 - 800 A and 1250 A
2 hole, LT
Frame 1 - 800 A and 1250 A
2 hole, RT
Frame 1 - 800 A and 1250 A
4 hole, RT
Frame 1 - 800 A and 1250 A
4 hole, LT
= Front of Unit RT = Right side of ACB column LT = Left side of ACB column
Frame 1 - 2000 A and 2500 A
4 hole, RT
Frame 1 - 1600 A…2500 A
4 hole, LT
Frame 1 - 1600 A
4 hole, RT
Frame 2 - 2000 A
4 hole, RT
Frame 2 - 800 A and 1250 A
4 hole, RT
Frame 2 - 1600 A and 2000 A
4 hole, LT
Frame 2 - 1600 A
4 hole, RT
Frame 2 - 800 A and 1250 A
2 hole, LT
Frame 2 - 800 A and 1250 A
2 hole, RT
Frame 2 - 800 A and 1250 A
4 hole, LT
Figure 19 - Power Bus Splicing Configurations With Z-splice Bars
IMPORTANT Only for units with ACB. For other units, see page 46.
44 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 45
Figure 18 - Power Bus Splicing Configurations With Z-splice Bars (continued)
Frame 2 - 2500 A
4 hole, LT
Frame 2 - 2500 A
4 hole, RT
= Front of Unit RT = Right side of ACB column LT = Left side of ACB column
Frame 4 - 2000 A and 2500 A
4 hole, LT
Frames 1, 2, and 4 - 3200 A
4 hole, LT
Use this hole to align the Z link plate.
Use this hole to align the Z link plate.
Use this hole to align the Z link plate.
Use this hole to align the Z link plate.
Frames 1, 2, and 4 - 4000 A
4 hole, LT
Frames 2 and 4 - 4000 A
4 hole, RT
Frame 1 - 4000 A
4 hole, RT
Frame 4 - 2000 A and 2500 A
4 hole, RT
Frames 2 and 4 - 3200 A
4 hole, RT
Frame 1 - 3200 A
4 hole, RT
Use this hole to align the Z link plate.
Use this hole to align the Z link plate.
Use this hole to align
the Z link plate.
Use this hole to align the Z link plate.
Use this hole to align
the Z link plate.
Use this hole to align the Z link plate.
IMPORTANT Only for units with ACB. For other units, see page 46.
Install Columns Chapter 3
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 45
Page 46
Chapter 3 Install Columns
All Frames - 800 A and 1250 A
2 hole
All Frames - 800 A and 1250 A
4 hole
All Frames - 1600…2500 A
4 hole
All Frames - 3200 A
4 hole
All Frames - 4000 A
4 hole
= Front of Unit
Figure 20 - Power Bus Splicing Configurations With Straight Splice Bars
IMPORTANT Not for units with ACB. For those units, see page 42.
46 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 47
Install Columns Chapter 3
Splice bars as shipped.
PE splice bars

Splice the Protective Earth (PE) Conductor

The PE conductor is in the bottom horizontal wireway of an MCC column. Up to four PE conductors can be present. To access the PE conductor, remove the bottom horizontal wireway cover.
Follow these procedures to splice the Protective Earth Conductor.
1. Locate the PE splice bars.
PE splice bars are secured to the end of the horizontal PE during shipping.
2. Use the PE splice bars to join the horizontal PE of each column
ssemble the splice bars and hardware as shown.
a
and
3. Tighten hardware to torque specifications. See Torque Specifications
on page 48.
IMPORTANT Do not grease or lubricate hardware.
4. Reinstall the horizontal wireway cover and check that the bolts ar
cure.
se
e
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 47
Page 48
Chapter 3 Install Columns
Example of an information label on the interior right side plate of a fixed unit.
Example of an information label inside a ver tical wireway door.

Control and Network Cables

After you finish joining and splicing columns, make sure to connect network and other control cables as necessary.

Torque Specifications

See Appendix B
for the cable entry and exit points of various unit
configurations.
See Chapter 9
for IntelliCENTER® options.
Tighten bus splice connections with a torque wrench according to the table. Torque values can be found on the information label inside a vertical wireway door or on the interior right side plate of fixed units.
48 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Hardware Description Hardware Size Torque
Incoming line lug attachment bolts M12 x 1.75 61 N•m
Horizontal power bus to vertical distribution bus connection
Horizontal power bus splice connection M10 x 1.5 38 N•m
Protective earth conductor (PE) splice connection M6 x 1.0 7.3 N•m
Column joining hardware M6 x 1.0 6.2 N•m
DeviceNet splice cable screws 0.55 N•m
I/O terminal blocks 0.45 N•m
(1) The factory-made power bus connections are tightened by a computer-controlled torquing system. The following
connections do not require retorquing:
• Vertical to horizontal bus connections
• Power conductor to horizontal bus connections These factory-made connections do not require servicing for the li fe of the MCC.
(1)
M10 x 1.5 38 N•m
Page 49
Chapter 4
Install Cable
When you install cable, verify that it is installed according to appropriate codes and standards. Multi-conductor cables, cable trays, cable ducts, and conduit are all acceptable methods of routing cable to your MCC.
IMPORTANT All installed cable is installed must be compatible with the enclosure
rating of the MCC. Cable entry and exit points must be properly sealed so water and moisture cannot enter or accumulate inside the enclosure.
Inside the MCC enclosure, route cable away from the PE conductor to avoid damage. Position cable so bends are minimized and relative vertical alignment to incoming connections is maintained. Final cable connections must not place any additional strain on the termination blocks.
See the documentation package shipped with your MCC for the following information:
• Approximate cable entry locations
• Space availability for incoming cables
•PE conductor locations
• Wiring schemes for main fusible disconnects, main circuit breake incoming line compartments
and
Install cable per supplied instructions. Size cable to appropriate codes and standards.
rs,
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 49
Page 50
Chapter 4 Install Cable
Detail
A
Frame Stiffener Bracket Wireway Latch Bracket
Detail
B
Detail
C
A
B
C

Install ArcShield Protection After Wiring

TIP You can temporarily remove ArcShield™ latch brackets to maker it easier
to connect load cables.
Consider removing a unit if you cannot access the screw on the left side of the bracket.
Follow these procedures to install the door latch bracket/frame stiffener in the wireway.
1. Open the door.
2.
Install door latch bracket and frame stiffener bracket (if latter was rem
oved).
Verify that the latch bracket is in the correct orientation before you install it. See Detail C in the following figure.
3. Torque all bracket screws to 3.6 N•m (32 lb•in).

Lugs

IMPORTANT Install lugs so proper spacing is used between phases. Hardware must be
tightened per the torque specifications.
See Chapter 3
for more information.
Verify that the compatibility of wire size, type, and stranding for the power lugs is furnished. Use correct lugs in all applications. Crimp compression lugs with manufacturer recommended tools.
TIP Use the MCC electrical schematics and wiring diagrams to verify field
wiring connection points.
50 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 51
Install Cable Chapter 4

Incoming Line Lug Compartment

Main Disconnecting Means

Cable Bracing

Top or bottom incoming line lug compartments are available. Base the lug selection on the size, number, and type of conductor.
The following guidelines to select lugs are based on incoming line available short circuit current, I
50,000 amperes RMS symmetrical use mechanical screw or
I
sc
crimp/compression type lugs.
> 50,000 amperes RMS symmetrical crimp/compression type lugs are
I
sc
recommended.
For information on incoming termination, see the documentation package that is shipped with your MCC.
For main disconnects or circuit breakers, use the lugs provided.
The CENTERLINE® 2500 MCC bus work system has been tested and is qualified to withstand forces that exceed the short circuit withstand ratings for the MCC. Incoming line cables and outgoing feeder cables must be supported to withstand the same short circuit forces. Follow appropriate codes and standards when bracing incoming and outgoing cables.
.
sc
There are many sizes and types of cables, and different means by which the cables can be supported. Cabling must be secured or braced for the weight of the cable and if there is a fault.
IMPORTANT Position cable so bends are minimized and relative vertical alignment to
incoming connections is maintained. Final cable connections must not place any additional strain on the termination blocks.
Follow the guidelines addressed in IEC Standard 60364-5-52.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 51
Page 52
Chapter 4 Install Cable
Form 3b Form 4b Type 5
Form 4b Type 7

Secure Load Wires

Standard internal separation within the MCC is IEC 61439-2 Form 3b. The following IEC 61439-2 separation forms are also available as options.
• Form 4b Type 5: Terminals for external conductors are enclosed in al or plastic frame within the vertical wireway. Terminals ar
met
eparated by insulated coverings.
s
a
e
• Form 4b Type 7: Terminals for external conductors are enclosed in
metallic partitions. The termination for each functional unit has it ow
n integral glanding facility.
s
Support each wire as you install it so a strong connection is made. Do not overtighten the screws to fasten the wires. Torque the screws to the values in
Ta b l e 7
Table 7 - Torque Values for Separation Forms
.
Cap Screw Size
M6 x 16 hex head socket 3.6 (32) 2.7…4.5 (24…40)
M8 x 20 hex head 5.6 (50) 4.2…7.0 (38…63)
Target Torque Acceptable Torque Range
IMPORTANT You can strip the holes if you over-torque the screws.
52 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
N•m (Lb•in)
Page 53
Chapter 5
C
en
t
e
r
o
f
H
an
d
l
e
o
n
T
o
p
U
n
i
t
2
0
0
0
m
m
,
m
a
x
F
l
o
o
r
L
i
n
e
Door Latches, Operator Handles, and Unit Interlocks

Height Considerations

In accordance with EN 61439-1, operating devices (push buttons and handles) must be no more than 2000 mm above floor level. If the MCC is mounted on an elevated surface, the height from the floor to the center of the top handles must be checked for compliance.
Figure 21 - Operator Handle Height
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 53
Page 54
Chapter 5 Door Latches, Operator Handles, and Unit Interlocks
Head Slot
Latch shown in vertical
(closed) position.

Door Latches

There are two types of door latches available for the 2500 MCC: quarter-turn door latches and ArcShield™ door latches.

Quarter-turn Door Latches

Latches are provided on each unit door to hold the door closed and isolate the column. You can rotate the door latches by using a standard slotted screwdriver in the head slot.
Open the door latches as follows.
1. Rotate each door latch a quarter turn (90°) until its head slot is horizontal.
2.
Open the door once all latches are in the open position.
Close and lock the door latches as follows.
1. Close the door.
2. Use a slotted screwdriver to rotate each door latch a quarter turn (90°
ntil all slots are vertical.
u
)

ArcShield Door Latches

The sleeved ArcShield door latches are specialized spring­loaded latches. They are designed to manage the pressure generated during an arc blast.
Follow the same procedures in the Quarter-turn Door Latches to open or close a door with ArcShield door latches.
IMPORTANT ArcShield door latches are spring-loaded. When you close a door, push in
each latch as you turn it so it locks correctly for ArcShield protection.
54 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 55
Door Latches, Operator Handles, and Unit Interlocks Chapter 5
Handle in ON/I Position Handle in TRIP/+ Position
Handle in OFF/O Position

Rotary-operator Handles

Rotary-operator handles are available in three sizes for CENTERLINE 2500 MCCs. Because of their design and functionality, each size can require different instructions to modify or to lock in different positions.
The following table details the different rotary-operator handle sizes.
Handle Size
Small • 140M-SB
Medium • 140U-PB
Large • 140U-HM4
(1)
Cat. No. Color
• 140M-SY
• 140U-PY
• 140U-HM4E
•Black
• Red/yellow
•Black
• Red/yellow
•Black
• Red/yellow
(1) Handle pictures are not to scale.

Small Rotary-operator Handles (Cat. Nos. 140M-SB and 140M-SY)

The following is a brief summary of operating instructions for small rotary­operator handles. For additional information, see publication 140M-IN022, which is available online at https://www.rockwellautomation.com/global/
literature-library/overview.page.
Figure 22 - Small Rotary-operator Handle Positions
Open the Unit Door
1. Turn the small rotary-operator handle to the OFF/O position.
2. Release the door latches.
3. Grasp the small rotary-operator handle and pull the unit door toward
you to open.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 55
Page 56
Chapter 5 Door Latches, Operator Handles, and Unit Interlocks
A
B
C
10°, max
3.5 mm (0.14 in.), max
Close the Unit Door
Open the Unit Door in the ON/I Position
When the unit door is closed and the small rotary-operator handle is in the ON/I or TRIP/+ position, a defeater screw must be deliberately operated to open the unit door.
1. Verify that the small rotary-operator handle is in the OFF/O position.
2. Close the unit door.
3. Secure the door latches.
ATTENTION: Follow local codes and guidelines with requirements of EN 50110 when you work on energized equipment.
1. Release the door latches.
2. Locate the defeater screw on the side of the small rotary-operato
h
andle near the OFF/O position (A).
3. Use a screwdriver to turn the defeater screw 10° (max) clockwise
arefully open the unit door (C).
4. C
r
(B).
Operator Handles for Circuit Breakers
If there is a circuit breaker fault, the circuit breaker operator handle moves to the TRIP/+ position. Only reset the circuit breaker after the cause of the fault has been determined and corrected.
Follow these procedures to reset the circuit breaker.
1. Turn the small rotary-operator handle to the OFF/O position.
2.
After the fault has been corrected, verify that it is safe to re-energize the
nit and turn the small rotary-operator handle to the ON/I position.
u
56 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 57
Door Latches, Operator Handles, and Unit Interlocks Chapter 5
Lock Units in the OFF/O Position
ATTENTION: Follow all company safety and lockout procedures, and local codes when you perform this procedure.
Follow these procedures to lock a unit in the OFF/O position.
1. Turn the small rotary-operator handle to the OFF/O position.
2. Push and hold the middle section of the operator handle
he lock opening is now visible.
T
.
3. Insert and secure the lock
p to three 8 mm (shack
U
er) locks can be inserted
diamet
.
le
.
Lock Units in the ON/I Position
Locking units in the ON/I position requires user modification.
ATTENTION: Locking a small rotary-operator handle in the ON/I position can conflict with local codes and emergency shutdown requirements.
To modify the operator handle so it remains locked in the ON/I position, perform the following steps.
WARNING: To help prevent electrical shock, disconnect from the power source before you modify any small rotary-operator handle.
1. Verify that the small rotary-operator handle to be modified is in the ON/I position.
2. Release the door latches.
3. Open the door to access the locking nut that secures the small rotary-
operator handle to the door.
4. With the appropriate tool, remove the locking nut from the small rotary-operator handle body (A in Figure 23 on page 58
).
5. Remove the small rotary-operator handle from the door (B).
6. Slide the provided defeater plug into the slot to prohibit access to th
defea
ter screw (C).
e
7. Reinstall the small rotary-operator handle into the door (D).
For proper installation, align the notch on the back of the small rotary­operator handle with the corresponding slot in the door (E).
8. With the appropriate tool, reinstall the locking nut on the smal
ary-operator handle (F).
rot
l
9. Torque the locking nut to 3.95 N•m (G).
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 57
Page 58
Chapter 5 Door Latches, Operator Handles, and Unit Interlocks
3.95 N•m (35 lb•in)
800T-N245
A
B
C
D
E
F
G
10. Close the door.
11. Secure the door latches.
Figure 23 - Lock Small Rotary-operator Handles in the ON/I Position

Medium Rotary-operator Handles (Cat. Nos. 140U-PB and 140U-PY)

The following is a brief summary of operating instructions for medium
operator handles.
rotary-
Open the Unit Door
1. Turn the medium rotary-operator handle to the OFF/O position.
2. Release the door latches.
3. Grasp the medium rotary-operator handle and pull the unit door
toward you to open.
Close the Unit Door
1. Verify that the medium rotary-operator handle is in the OFF/O position.
2. Close the unit door.
3. Secure the door latches.
58 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 59
Door Latches, Operator Handles, and Unit Interlocks Chapter 5
A
B
C
10°, max
3.5 mm (0.14 in.), max
Lock Units in the OFF/O Position
ATT EN TI ON : Follow all company safety and lockout procedures and local codes when you perform this procedure.
Follow these procedures to lock a unit in the OFF/O position.
1. The medium rotary-operator handle must be in the OF
ition.
pos
2. Push and hold the middle section of the operator handle.
The lock opening is now visible.
F/O
3. Insert and secure a lock
p to three 8 mm (shack
U
er) locks can be inserted.
diamet
.
le
Open the Unit Door in the ON/I Position
ATTENTION: Follow local codes and guidelines with requirements of EN 50110 when you work on energized equipment.
When the unit door is closed and the small rotary-operator handle is in the ON/I or TRIP/+ position, a defeater screw must be deliberately operated to open the unit door.
1. Release the door latches.
2. Locate the defeater screw on the side of the small rotary-operato
andle near the OFF/O position (A).
h
3. Use a screwdriver to turn the defeater screw 10° (max) clockwise
r
(B).
arefully open the unit door (C).
4. C
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 59
Page 60
Chapter 5 Door Latches, Operator Handles, and Unit Interlocks
Lock Units in the ON/I Position
With medium rotary-operator handles, there are two ways to lock units in the ON/I position. Both ways require user modification.
To modify the operator handle so it remains locked in the ON/I position, perform either of the following ways.
Lock the Unit in the ON/I Position With a Defeater Plug
ATTENTION: Locking a medium rotary-operator handle in the ON/I
position can conflict with local codes and emergency shutdown requirements.
WARNING: To help prevent electrical shock, disconnect from the power source before you modify any medium rotary-operator handle.
1. Verify that the medium rotary-operator handle to be modified is in the ON/I position.
2. Release the door latches.
3. Open the door to access the backside of the medium rotary-operato
ha
ndle.
4. With a screwdriver, remove the two screws that secure the medium rotary-operator handle body to the door (A in Figure 24 on page 61
5. Remove the small rotary-operator handle from the door.
6. Slide the provided defeater plug into the defeater screw slot to help
prevent access to the defeater screw.
7. With the two screws that you previously removed, reinstall the medium rotary-operator handle into the door (C in Figure 24 on
page 61).
r
).
8. Close the door.
60 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 61
Door Latches, Operator Handles, and Unit Interlocks Chapter 5
BA & C
1
1
2
2
D
Screw Hole
Screw
Hole
5…8 mm
(0.2…0.3 in.)
Lock the Unit in the ON/I Position With Locks
1. Verify that the medium rotary-operator handle to be modified is in the ON/I position.
2. Release the door latches.
3. Open the door to access the backside of the medium rotary-operato
ha
ndle.
4. With a screwdriver, remove the two screws that secure the medium rotary-operator handle body to the door (A in Figure 24
).
5. Remove the small rotary-operator handle from the door.
6. With the screwdriver, remove the two tabs (B in Figure 24
).
7. With the two screws that you previously removed, reinstall the medium rotary-operator handle into the door (C in Figure 24
8. Close the door.
9. Push and hold the middle section of the operator hand
he lock opening is now visible (1 in D of Figure 24
T
10. Insert and secure a lock (2 in D of Figure 24
p to three 8 mm (shackle diameter) locks can be inserted.
U
Figure 24 - Lock Medium Rotary-operator Handles in the ON/I Position
).
le.
).
r
).
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 61
Page 62
Chapter 5 Door Latches, Operator Handles, and Unit Interlocks
Release Mechanism
Circuit Breaker Style
Disconnect Style
Release Mechanism

Large Rotary-operator Handles (Cat. Nos. 140U-HM4 and 140U-HM4E)

The following is a brief summary of operating instructions for large rotary­operator handles available for disconnects or circuit breakers.
For additional disconnect handle information, see publication 190-IN007, which is available online at https://www.rockwellautomation.com/global/
literature-library/overview.page.
Figure 25 - Large Rotary-operator Handle Styles
Open the Unit Door
Follow these procedures to open the unit door.
1. Verify that the large rotary­operator handle is in the OFF/O position.
2. Release the door latches.
3. Hold the large rotary-
operator handle in the OFF/O position while you push the release mechanis
n.
dow
m
4. Carefully open the unit door.
Close the Unit Door
1. Verify that the large rotary-operator handle is in the OFF/O position.
2. Slowly close the door until contact with the large rotary-operato
ha
ndle is made.
r
62 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
3. Hold the large rotary-operator handle in the OFF/O position while you close the door.
4. Close the door and secure the door latches.
Page 63
Door Latches, Operator Handles, and Unit Interlocks Chapter 5
Defeater
Mechanism
Open the Unit Door in the ON/I Position
ATTENTION: Follow local codes and guidelines, and the requirements of EN 50110 when you work on energized equipment.
When the unit door is closed and the large rotary-operator handle is in the ON/I position, a defeater mechanism must be deliberately operated to open the unit door (for example, to open the door of an energized unit).
Follow these procedures to open a door with the large rotary-operator handle in the ON/I position.
1. Release the door latches.
2. Locate the defeater
mechanism on the right of t
he handle.
side
3. Use a screwdriver to push th
ter mechanism in th
defea
rection of the arrow.
di
e
e
4. Carefully open the unit door.
Operator Handles for Circuit Breakers
If there is a circuit breaker fault, the circuit breaker operator handle moves to the TRIP/+ position. Only reset the circuit breaker after the cause of the fault has been determined and corrected.
Follow these procedures to reset the circuit breaker.
1. Turn the circuit breaker handle from the TRIP/+ position to th OF
F/O position.
2. Turn the circuit breaker handle from the OFF/O position to th
SET position.
RE
3. Locate and correct the fault.
e
e
4. Verify that it is safe to re-energize the unit.
5. Turn the handle from the RESET position to the ON/I position.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 63
Page 64
Chapter 5 Door Latches, Operator Handles, and Unit Interlocks
Lock Units in the OFF/O Position
ATT EN TI ON : Follow all company safety and lockout procedures and local codes when performing this procedure.
1. The large rotary-operator handle must be in the OFF/O position.
2. Pull the middle section of the operator handle toward you.
The lock opening is now visible.
3. Insert and secure the lock
p to three 8 mm (shackle diameter) locks can be inserted.
U
.
Lock Units in the ON/I Position
Locking units in the ON/I position requires user modification.
ATTENTION: Locking an operating handle in the ON/I position can conflict with local codes and emergency shutdown requirements.
1. Verify that the large rotary-operator handle to be modified is in the ON/I position.
2. Release the door latches.
3. Open the door to access the backside of the large rotary-operato
ha
ndle.
4. With a screwdriver, remove the four screws that secure the large rotary­operator handle body to the door (A in Figure 26 on page 65
5. Remove the large rotary-operator handle from the door.
).
r
IMPORTANT Place the four screws and the five O-rings aside so they can be
reinstalled.
6. With a sharp blade, cut the three stems that anchor the locking ta (B in Fi
gure 26
).
7. With a long nose plier, remove the locking tab from the large rotary­operator handle (C in Figure 26
).
8. Reinstall the five O-rings in the appropriate locations on the backside of the large rotary-handle (A in Figure 26
).
9. With the flour screws that you previously removed, reinstall the large rotary-operator handle into the door (D in Figure 26
).
10. Close the door.
11. Push and hold the middle section of the operator hand
he lock opening is now visible (1 in E of Figure 26
T
12. Insert and secure an 8 mm lock (2 in E of Figure 26
p to three 8 mm (shackle diameter) locks can be inserted.
U
le.
).
).
b
64 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 65
B
1
1
2
2
3
C E
A & D
O-ring Locations
5…8 mm
(0.2…0.3 in.)
Door Latches, Operator Handles, and Unit Interlocks Chapter 5
Figure 26 - Lock Large Rotary-operator Handles in the ON/I Position

Unit Interlocks

ATTENTION: Do not attempt to install or remove a unit while the unit
main switch is in the ON/I position.
A unit interlock is provided with each plug-in unit. Unit interlocks help prevent units from being removed from or inserted into a column while the operator handle is in the ON/I position.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 65
Page 66
Chapter 5 Door Latches, Operator Handles, and Unit Interlocks
Notes:
66 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 67
Install and Remove Units
One Module, Withdrawable Unit Six Modules, Fixed Unit
Chapter 6

Unit Size

Unit size is described in terms of modules. One module is 80 mm high by 500 mm wide. Withdrawable units are available in 1, 2, 4, 6, 8, 10, and 12 modules. Fixed units are available in 2, 4, 6, 8, 10, 12, 14, and 16 modules.
Any unit size above one module must be in even increments. Therefore, you cannot have a unit that is 11 modules high.
CENTERLINE® 2500 MCCs are available with many combinations of withdrawable and fixed units. This table lists the maximum ampere rating of each unit size.
Number of Modules Ampere Rating (Max)
132 A
2…12 225 A
Figure 27 - Unit Types
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 67
Page 68
Chapter 6 Install and Remove Units
Protective Earth Condu ctor (PE)
ControlNetwork Unit Load
Conne ction
Unit Line
Connect ion
Customer Load
Connection
Isolated
Control and
Network Wireway
PE
Load
Line
Control
Network

Withdrawable Units

Withdrawable units are characterized by withdrawable line, load, control, network, and PE connections. Outgoing load and control connections from these units are made in the vertical wireway. Withdrawable units use a sliding track and a mechanical lever for ease of insertion and removal. Additional features include a separate unit door and optional door-mounted pilot devices. The unit door can be closed and latched, providing isolation when the unit is removed. Pilot devices are housed in removable control stations. An optional closing plate is available to help provide isolation if the control station is removed.
Figure 28 - Connections for Multiple Module Withdrawable Units
Figure 29 - Withdrawable Unit Connections – Two or More Modules
68 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 69
Figure 30 - Withdrawable Unit Connections – One Module
PE
Network
Control
Guide Pins (2)
Line and Load
Network
Control
PE
Guide Pin Guide Pin
Line and Load
Install and Remove Units Chapter 6
Figure 31 - Subplate Connections for One Module Withdrawable Units

Operating Positions

Withdrawable units have four operating positions:
Disconnected
, and
Released
. Detents are present to confirm that the unit is in one of the four positions. An interlock helps prevent the unit from being inserted or removed while the branch circuit device is in the ON/I position. Stabs are provided to make the line and load connections. A first make, last break PE contact is also provided. Control and network connections plug into an isolated vertical wireway on the left side of the column. See the following descriptions for additional information about the features of each position.
Connected, Te s t
,
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 69
Page 70
Chapter 6 Install and Remove Units
Locking MechanismWithdraw Lever
Select an Operating Position
1. Grasp the withdraw lever with one hand.
2. Slide the withdraw lever towards the locking mechanism.
3. Rotate the withdraw lever to the desired position.
Mechanical detents are used to confirm that a position is selected.
4. Release the locking mechanism and withdraw lever.
In the Connected position, the line, load, control, network, and PE connections are engaged. Closing the unit door helps to keep the withdraw lever in the connected position. To engage the interlock or turn the branch circuit device to the ON/I position, the unit door must be fully closed. See
Figure 32 on page 71
.
In the Te s t position, the control, network, and PE connections are engaged. Line and load connections are isolated, which helps to verify unit control and network wiring. Units can be locked in this position. See Figure 32 on
page 71.
In the Disconnected position, the unit remains in the column but connections are not present, which is an isolated position. Units can be locked in the disconnected position. See Figure 32 on page 71
.
70 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 71
Install and Remove Units Chapter 6
With draw lever i n Rele ased position (and locked out).
Withdraw lever in Disconnected position (and locked out).
Withdraw lever in Test position (and locked out).Withdraw lever in Test position (and locked out).
Withdraw lever in Connected position.
Withdrawable units can be removed from the columns. The lever must be moved out of the Disconnected position into the Released position before the unit can be withdrawn. When units are removed from the MCC, they are fully isolated from connections. See Figure 32
Figure 32 - Various Positions for Withdrawable Units
.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 71
Page 72
Chapter 6 Install and Remove Units
Bottom of unit support pan
Screw location on left side
Screw locations on right side

Safety Guidelines to Install and Remove Withdrawable Units

ATT EN TI ON : De-energize, lock out, and tag out all sources of power to the
MCC when you install or remove MCC units. If MCC units are installed or removed with power that is applied to the main power bus, follow established electrical safety work practices. For further information, see the publication, NFPA 70E: Standard for Electrical Safety in the Wor kpl ace® .
ATTENTION: If power sources are connected to the motor control center, use extreme caution when you insert units. All busbars and the line sides of the inserted units are energized and contact with these parts can cause injury or death.
ATT EN TI ON : To increase operator safety and help prevent equipment damage, we recommend that two people install or remove units that are in the upper six modules or over 1600 mm above floor level.
Units with door-mounted operator handles, switches, and disconnects must be in the OFF/O position before units are inserted or removed.
Do not attempt to install or remove a unit when the unit main switch is in the ON/I position.

Insert a Withdrawable Unit

IMPORTANT The unit support pan below the unit compartment must be in place
before you install the unit.
Follow these procedures to insert a withdrawable unit.
1. Fully open the unit door and verify that the unit support pan has been installed.
The unit support pan is secured with two screws on the right si
ne screw on the left side.
o
de and
72 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
For one module units, verify that the subplate is installed. The subplate is attached to the column with two mounting screws.
2. Rotate the unit withdraw lever to the Released position.
Page 73
Install and Remove Units Chapter 6
3. Slowly slide the unit into the column along the tracks on the unit
upport pan until it locks in the Disconnected position.
s
4. Slide the locking mechanism toward the withdraw lever, rotate the withdraw lever to the Te s t position, and continue to insert the un in
to the column.
The unit locks in the Te s t position.
it

Remove a Withdrawable Unit

5. Slide the locking mechanism toward the withdraw lever agai
tate the withdraw lever to the Connected position.
ro
Vertical bus shutters automatically opens as the unit is inserted.
6. Insert the unit until it locks in the Connected position
The
unit is now installed in the column.
7. Connect any door-mounted devices.
8. Close the unit door and secure the door latches.
Refer to
information on the withdraw lever.
1. Fully open the unit door.
2. Unplug or remove door mounted pilot devices.
3. Slide the locking mechanism on the withdraw lever to the left
ro
4. Slide the locking mechanism toward the withdraw lever and rotate th w
5. Slide the locking mechanism toward the withdraw lever again ro
Select an Operating Position on page 70 for additional
tate the withdraw lever to the Te s t position.
ithdraw lever to the Disconnected position.
tate the withdraw lever to the Released position.
n, and
.
and
and
e
Continue to slide the unit out of the column. The unit can now be removed from the column.
Shutters close automatically as the unit is removed.
6. Close the unit door and secure the door latches.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 73
Page 74
Chapter 6 Install and Remove Units

Remove the Unit Door

It is not necessary to remove the unit door to install or remove a unit from a column. However, if a unit door must be removed, use one of the following procedures.
If present, door-mounted control stations can be removed from the door and kept with the unit.
Before you perform work on units or unit doors, verify that the unit main switch is in the OFF/O position.

Multiple Module Unit Doors

Follow this procedure to remove multiple module unit doors.
1. Verify that the unit main switch is in the OFF/O position
elease each door latch.
2. R
3. Fully open the unit door.
4. Remove or disconnect door-mounted devices and wiring.
5. Slide the hinge pins upward to remove.
.
6. Swing door to near closed position and lift outward to remove.
7. To install the unit door, reverse this procedure.

One Module Unit Doors

Follow this procedure to remove one module unit doors.
IMPORTANT Remove the unit from the column before removing its door. Follow
unit removal procedures on page 73
1. Verify that the unit main switch is in the OFF/O position
2. R
elease each door latch.
3. Fully open the unit door.
4. If a control station is provided with a plug for control wires, unplug
this connection before removing the unit.
5. Remove or disconnect door-mounted devices and wiring.
6. Remove the two screws that fasten the hinge to the column.
.
.
7. Remove the unit door and hinge assembly from the column.
8. To install the unit door, reverse this procedure.
74 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 75
Commissioning
Chapter 7

Introduction

Pre-commissioning Checklist

This chapter provides guidance for the startup of a newly installed MCC.
We recommend that you make an itemized list that includes the following:
• Serial number
•Number of columns
• Number of units and their corresponding voltage
• Current ratings
•Kilowatt ratings
•Types of circuits
• Fuse sizes
• Circuit breaker ratings and trip settings
•Other important data
Save this itemized list in a file with other MCC data, such as component manuals, MCC manuals, overload relay instructions, and wiring diagrams.
ATT EN TI ON : Follow applicable company safety procedures.
ATT EN TI ON :
energizing check disconnected and locked in the OFF/O position. Follow EN 50110 requirements, and local codes and guidelines.
Use a voltmeter to verify that the remote MCC power sources are disconnected.
ATT EN TI ON : Power factor correction capacitors (PFCCs) must be applied correctly. Temporarily disconnect PFCCs when they are connected to the motor circuit, and the startup procedure requires the respective motors to be jogged, inched, or bumped (rotation direction check).
For additional assistance, contact your Rockwell Automation representative.
ATT EN TI ON : Verify that motor acceleration times are within specific application specifications.
Excessive start currents and/or acceleration times can cause inverse time circuit breakers, power fuses, overload relays, and other components to overheat and/or shut down equipment.
To help protect the safety of personnel who perform the pre-
, verify that the remote MCC power sources are
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 75
Page 76
Chapter 7 Commissioning
The following procedures shall be executed by only a ‘skilled person’ as defined by IEV 195-04-01 and 3.52 of IEC 60204-1, as follows:
‘Skilled person Person with relevant education and experience to enable him or her to perceive risks and to avoid hazards that operation or maintenance of a product can create.’
Follow these procedures to complete the pre-commissioning checklist.
1. Check and verify that the MCC is installed per instructions.
See Chapter 3, Install Columns
nspect and verify that the MCC is level and secured.
2. I
.
3. Inspect the enclosure and units for damage and verify that electrical clearances have been maintained based on the voltage and impuls
g of the equipment.
ratin
e
4. Remove all blocks or temporary holding means used for shipping component devices in the MCC.
5. Check the integrity of the bus splice connections.
For the recommended torque values, see Torque Specifications
on
page 48.
See Chapter 3, Install Columns
for splicing information.
TIP The factory-made horizontal power bus to vertical distribution
bus connections are tightened by a computer-controlled torquing system. Therefore, these components do not need torquing by the customer.
6. Check and verify that all PE connections are made according to applicable codes and standards.
If the PE conductor is not provided or has been removed, verify that the MCC columns are connected with joining hardware to prov
tinuous PE path. See
con
Join Columns on page 35 for more
ide a
information.
7. Perform the following for field wiring: a. Check the field wiring for proper conductor sizing. b. Verify that all incoming and outgoing power wiring is secure, well
supported, and braced to withstand the effects of a fault current as detailed in Chapter 4, Install Cable
F
or incoming line compartments of eight modules or less: firmly
secure incoming cables halfway between the top of the column
he incoming line compartment terminal
t
F
or full-line (24 modules) incoming line compartments:
Brace the cables every 300 mm if the available short circuit curren
<42,000 amperes RMS symmetrical.
is Brace the cables every 150 mm if the available short circuit curren
is
≥42,000 amperes RMS symmetrical,
76 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
.
and
s.
t
t
Page 77
Commissioning Chapter 7
c. Check the integrity of all field connections.
R
ecommended torque values that are not found on individual
devices can be found on wiring diagrams.
d. Check field wired connections that are made to th
ee wiring diagrams and verify that proper clearances betwee
S adjace
nt phases and/or phases to PE are being maintained.
e MCC.
n
8. Verify that the voltage and kilowatt ratings on the motor correspond
ith the MCC unit ratings.
w
9. Verify that proper overload relays are installed and/or adjusted
lative full load current shown on the motor rating nameplate.
re
10. For applications that require power fuses, install fuses in fusi sw
itches in accordance with application requirements
.
to
ble
IMPORTANT Do not apply grease or NO-OX-ID to fuse ferrules.
or circuit breaker applications, verify that the circuit breakers are in
11. F accordance with application requirements, and have correct amperage and trip settings.
TIP High efficiency motors can have higher locked rotor and inrush
currents, which require higher magnetic trip settings.
ATTENTION: Rockwell Automation™ AC drives and soft starter units are shipped with preset factory settings such as ramp speed, current limits, switch positions, and readouts. Preset factory settings are not suitable for some applications. For specific startup guidance, see the instruction manuals that are supplied with the MCC.
12. Set and verify adjustable current, voltage and other settings, accord to
device instructions or wiring diagrams.
ing
See the device instruction sheets or manuals supplied with the
specific startup guidance.
for
Component devices in MCC units (such as transfer switches, powe
actor correction capacitors, transducers, motor protectors, line
f monitors, over and undervoltage relays, and motor windings heater
quire unique startup procedures.
can re
13. Manually exercise all switches, control auxiliary switches, circ b
reakers, their respective operators, unit interlocks, trip mechanisms
(to test, push the Push to Trip button) and any other operat
chanisms to verify proper operation.
me
14. Check timing relay settings as required.
15. Verify that the vents are free from obstructions.
16. Check that fans that are used for forced air cooling have:
a. Shafts that rotate freely b. Blades with no dust or debris build-up
17. Check that all filters are in place and clean.
TIP We recommend that you establish an in-house program for
scheduled cleaning or replacement.
MCC
r
s)
uit
ing
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 77
Page 78
Chapter 7 Commissioning
18. Check all current transformers for proper polarity.
Verify that the transformer secondaries are NOT open, and are either connected to their respective devices or shorted. Reference individual unit wiring diagrams and schematics for proper installation.
ATTENTION: Current transformer secondaries shall not be ‘open.’ To avoid possible injury and electrical shock to personnel, do not energize a current transformer with its secondary open.
19. Veri fy th at all barriers and parts that are removed during th i
nstallation process have been reinstalled
W
e recommend that a barrier checklist is developed including su
ite
ms as, unit location, and barrier location. Save this checklist for
.
e
future reference.
20. Before you close the enclosure and/or individual units, remove a t
ools, metal chips, scrap wire, and other debris from the MCC interior.
If there is an accumulation of dust or dirt, clean out the MCC by using a brush, vacuum cleaner, or a clean, lint-free rag. DO NOT use
compressed air—it redistributes contaminates on other surfaces.
21. Verify that all withdrawable units are in the Connected position.
Before you close and latch unit and wireway doors, verify that wires are not pinched. Column closing plates must be in place.
ATTENTION: When you conduct an electrical insulation resistance test, isolate equipment sensitive to high test voltages, such as meters, solid-state devices, motor winding heaters, capacitor units, and transformers.
ch
ll
78 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 79
Commissioning Chapter 7
22. Conduct an electrical insulation resistance test to verify MCC wiring
egrity. Conduct this test with an insulation resistance tester with a
int potential of 500…1000 V.
ATTENTION: Verify that all switches or circuit breakers are in the OPEN/I or Off/O positions before an electrical resistance test is conducted.
Conduct this insulation resistance tester test phase-to-phase, phase-to­PE and, when applicable, phase-to-neutral on the MCC bus work. Typical insulation resistance values are 50 MΩ or greater.
Temperature, humidity, or dampness can affect insulation resistance values and considerably lower insulation resistance readings. If the insulation resistance values are less than 1 MΩ (due to dampness, temperature, or humidity) or the MCC has been stored in a damp or humid area, it is recommended the equipment be dried out. Dry out motor cables with a low voltage current or by using space heaters.
Once the equipment is dry, repeat the insulation resistance test. The minimum value for insulation resistance on a new installation at startup or energizing is 1 MΩ. These readings can be recorded in
Table 11 on page 100
.

Commissioning Procedure

Next, check the field wiring (for example, motor cables and/or incoming line cables).
ATT EN TI ON : Only skilled personnel with proper personal protective equipment can commission a motor control center. Energizing a MCC for the first time is potentially dangerous. Serious damage and/or personal injury can occur. Follow EN 50110 requirements, and local codes and guidelines.
ATT EN TI ON : This procedure is provided as a general guideline to energize a newly installed CENTERLINE® 2500 an MCC and be used only after the
pre-commissioning checklist has been completed.
Read this procedure in its entirety before beginning the commissioning procedure. If you have any questions or concerns, contact your Rockwell Automation representative.
1. Review other instructions that are supplied for the proper operation of special units such as AC drives and soft starters, with appropriat sk
illed personnel.
e and
2. Verify that main and unit main switches are in the OFF/O positi
here is no load on the MC
t
A
lso, verify that associated remote devices are de-energized.
3. Latch doors and secure covers.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 79
C.
on so
Page 80
Chapter 7 Commissioning
4. Energize the MCC remote power source.
If the MCC has a main circuit breaker or disconnect switch that can be operated from a remote location, energizing from the remote location is recommended.
If the MCC main circuit breaker or disconnect switch cannot be energized from a remote location, follow the procedure below.
• De-energize the remote power source
• Close MCC main disconnect or circuit breaker switch.
• Re-energize the MCC remote power source.
AT TE NT IO N: Main switch handles must be operated with a firm, direct motion into the closed (ON/I) position.
5. Energize from the source of the system, working toward the loads.
Energize one unit at a time, beginning with control units then feeder units.
6. Fully withdrawable units can be commissioned in the Test position
is position helps allow control and network connections to be
Th tested without engaging 3-phase power.
See Chapter 6, Install and Remove Units
for more information on
operating positions.
7. After the disconnect devices have been closed, loads such as lighting circuits, motor starters, and contactors can be energized.
a. When power factor correction capacitors are energized with the
motor windings and the startup procedure requires that th
espective motors be jogged or inched, temporarily disconnect the
r
e
power factor correction capacitors. For more information on power factor capacitors and MCC units, contact your local Rockwe
utomation representative.
A
ll
b. Verify that acceleration times are within application specifications.
TIP Excessive starting currents and/or acceleration times can
cause inverse time circuit breakers, power fuses, overload relays, and other components to overheat and/or shut down equipment.
8. Verify that meters are working properly, including voltmeters am
meters.
and
.
9. Reset device settings that were adjusted during installati
ommissioning to appropriate operational settings.
c
For commissioning MCCs with the DeviceNet networ
ntelliCENTER® software, see the CENTERLINE 2500 DeviceN
I M
otor Control Centers Technical Data, publication 2500-TD002
C
ENTERLINE 2500 Motor Control Centers with EtherNet/IP™
Network Technical Data, publication 2500-TD003
80 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
on and
k and/or
et
, or
.
Page 81
Maintenance
ATT EN TI ON : Only skilled personnel shall oversee the maintenance and
service of motor control centers.
De-energize all power sources before any maintenance or service work is performed on columns or units.
For work on energized equipment, follow EN 50110 requirements, and local codes and guidelines.
Replace and secure all barriers, covers, shields and doors, and perform the
Pre-commissioning Checklist
Chapter 8
on page 75 before re-energizing the equipment.

Establish a Maintenance Program

Establish a periodic maintenance program for MCCs to avoid unnecessary downtime. The frequency of service to the MCC depends on the equipment usage and the operating environment. Inspect MCCs once per year or per an established maintenance program. Use the following suggested maintenance guidelines to establish a maintenance program.
Keep a log of service and maintenance work performed on your MCC. Record the following information.
• Date test and maintenance work are performed
• List of checks and tests performed
• Condition of the equipment
• Any repairs or adjustments that are made to equipment
For maintenance regarding specific components, such as circuit breakers, contactors, AC drives, relays, and meters, reference the specific component instruction manual for each device.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 81
Page 82
Chapter 8 Maintenance
Suggested Maintenance
This table provides some suggested guidelines for maintaining your MCC.
Guidelines

Suggested Maintenance Guidelines Date Remarks Initials

1. Environment • Verify operating (ambient) conditions.
2. Enclosure Exterior • Clean surfaces. Retouch painted surfaces if necessary.
3. Contaminants
4. Bus System ATT EN TI ON : De-energize all power sources
– Room temperature range: -5…+40 °C – Noncondensing humidity, max: 95% at 40 °C
• Check that door latches are functioning and secure.
• Inspect for signs of excessive heat in the following locations: –Doors – Enclosure sides
If severe corrosion or discoloration is evident, replace the damaged components. Identify the cause of damage and
make necessary repairs.
ATTENTION:
equipment, follow EN 50110 requirements, and local codes and guidelines.
• Check for contaminants (moisture, dirt, dust) inside the enclosure. Remove any contaminants and their source.
• Check for contaminants in the following locations: – Cable entr y and exit points, seams, and openings – Devices (push buttons, relays, and disconnect switches)
Make sure the source or cause of wetness or moisture is identified and removed.
before any maintenance or service work on columns or units is performed.
For work on energized
(1)
(1)
• The factory-made power bus connections are tightened by a computer-controlled torquing system. The following connec tions do not require retorquing: – Vertical to horizontal bus connections – Power conductor to horizontal bus connections
These factory-made connections do not require servicing for the life of the MCC.
• Check the bus support and insulation for cracks or damage.
• Inspect bus splice connections for discoloration.
• Verify the integrity of bus splice connections. Retorque connections. See label inside vertical wireway door for recommended torque values.
• Use a vacuum or a lint free cloth to clean the bus and supports.
• Conduct an electrical insulation resistance test. Record and save the results.
Pre-commissioning Checklist on page 75.
See
5. Operating Handles • Verify that operator handles move freely (no sticking or
6. Locking Devices Check locking and interlocking devices for proper working
7. Current Carrying Components
8. Contacts • Check for excessive wear and dirt accumulation.
binding).
• Check function of the operator handles.
• Check the defeater mechanisms on operator handles.
• Replace broken, deformed, malfunctioning or badly worn parts/assemblies.
condition. Replace as necessary.
• Inspect for discoloration, corrosion, wear, excessive heat, and other signs of possible failure.
• Current carrying devices can include fuse clips, line, and load terminals.
Vacuum or wipe contacts with a soft cloth to remove dirt. Note: Applicable only for Allen-Bradley® 100-D size contactors (95-860A).
• Replace contacts in complete sets to avoid misalignment and uneven contact pressure.
• Discoloration or slight pitting of the contacts is normal.
• Do not file contacts or use spray cleaners.
82 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 83
Maintenance Chapter 8
Suggested Maintenance Guidelines Date Remarks Initials
9. Coils • Check contactor and relay coils for signs of overheating (cracking, melting, or burnt insulation). – If signs of overheating are present, replace the coil.
• Correct the overvoltage or undervoltage conditions that caused coil failure.
• Clean any residue of melted coil insulation from other parts of the device or replace such parts.
10.Terminals • Check for loose wire connections and tighten as necessary.
• Check schematics/component documentation for torque values. – Power terminals – Control circuit terminals
• Replace damaged parts or wiring.
11.Pilot Lights Replace damaged lamps and lenses.
12.Fuses • Check fuses and fuse clips. – When replacing fuses, install the same type and rated
fuse that was originally furnished with the MCC.
13.Fans and Cooling
Devices
• Inspect blowers and fans for operation and damage. – Replace blowers and fans that have bent, chipped, or
missing blades, or if the shaft does not turn freely.
• Clean or change air filters for fans.
• Clean heat exchanger fins.
• Clean ventilation mesh.
14.Solid-state Devices • Perform a visual inspection. Components or circuit boards must be replaced if the following are found: –Discoloration – Charred or burned components
• Check printed circuit boards for: – Proper seating in the edge board connectors – Locking tabs in place
15.Unit Stabs
• Inspect stabs for wear and corrosion. Replace if necessar y. – If the line stab assembly is severely pitted, inspect the
vertical bus for wear and pitting. Replace as necessary.
• Lightly lubricate line and load stabs with NO-OX-ID grease before installing the unit into the column.
16.Control and Network Plugs
• Inspect for bent or damaged pins. – If necessar y, clean the contacts.
• Verify that the connector mechanism is functioning properly.
17.Withdrawable Units • Remove dust and grease from the guide rail.
• Check that the withdraw lever and locking mechanism operate freely.
• Check for easy movement of withdrawable units within the column.
• Test the unit interlock function.
18.Final Check • Verify that all withdrawable units are in the correct operating position (Connected, Test, Disconnected, With drawn) .
• Verify that enclosure doors and wireway covers have been closed and are secure.
• After maintenance or repair is performed, test the control system for proper functioning under controlled conditions.
(1) The average temperature over a 24-hour period must not exceed 35 °C (95 °F).
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 83
Page 84
Chapter 8 Maintenance
Notes:
84 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 85
IntelliCENTER Options
Chapter 9

EtherNet/IP Motor Control Centers

Basic information is provided in the following sections. For additional information, see CENTERLINE® 2500 Motor Control Centers with EtherNet/IP™ Network, publication 2500-TD003
.

Connection Count

The EtherNet/IP network can accommodate a vast number of nodes. The EtherNet/IP network does not have a specific maximum number of nodes like other fieldbus networks. The limit is based on the number of connections the EtherNet/IP scanner can make.
To estimate the number of connections a network uses, visit
http://www.rockwellautomation.com/solutions/integrated architecture/ resources3.html for our EtherNet/IP Capacity Tool.

Cable Length Limitations

The EtherNet/IP network uses fiber or copper twisted-pair wiring. The maximum length of copper twisted-pair wiring is 100 m between devices. There is no cumulative length for the entire network. Fiber cable length varies by cable design. Inside the MCC, all cables are copper twisted pair.
IMPORTANT The 100 m maximum length must account for Ethernet cable inside the
column. To help determine cable lengths for your application, each MCC is shipped with documentation that identifies the cable length that is used within the MCC. This cable length must be added to the length between the GracePort® and the externally connected device.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 85
Page 86
Chapter 9 IntelliCENTER Options
Ethernet cable enters and leaves through wireways on each side of column.
Removable horizontal wireway cover at top of MCC column.
NOTE: The examples shown above depict typical 2500 MCC configurations with EtherNet/IP communication. See publication 2500-TD003
for more information on EtherNet/IP
communication for 2500 MCC units.
See publication 1783-UM004
for more information on Stratix 5700 Ethernet-managed switches.
Ethernet cable routing through
typical single MCC column.
Stratix 5700™
Ethernet Ports
(6-port
model shown)
Ethernet cable routing through typical two MCC columns.
Stratix 5700 switch behind top horizontal wireway cover.

Cable Routing

Each EtherNet/IP network has one or two Stratix 5700™ switches typically mounted in the top horizontal wireway in the standard configuration. The number of switches depends on the number of units in the column. Cables connected to the switch are then routed to EtherNet/IP devices in the column. Up to 24 EtherNet/IP ports can be provided in each CENTERLINE 2500 column.
In a standard MCC column, the vertical network wireway has EtherNet/IP connections equal to the number of units (up to 24) for that column. Devices that require 24V DC to power up must have it supplied through pins B4 and B5 in the control plug.
IMPORTANT Pins B4 and B5 in the control plug are reserved for 24V DC power; avoid
using for other reasons.
Connection to the EtherNet/IP network and the control plug is made when a unit is in the Connected or Test position.
Figure 33 - EtherNet/IP Network Connections in 2500 MCC Units
If you add or remove a unit from the EtherNet/IP system, it does not interrupt the operation of other units in the system.
86 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 87
IntelliCENTER Options Chapter 9
87654321
Determine Cable Lengths
To help determine cable lengths for your application, each MCC is shipped with documentation that identifies the cable lengths used within the MCC.
MCC Cable Types
ATT EN TI ON : Do not apply high voltage to any installed EtherNet/IP cable system or its connectors.
The CENTERLINE 2500 MCCs use a high-voltage 600V Ethernet cable designed to perform above TIA 568-B.2 and ODVA Ethernet standards. These cables have the following features:
• Foil and braided shield, PVC, eight conductor (four pair)
• 600V PVC cable designed to support high-voltage applications
• On-Machine™ rated cable for use in a cable tray shared with high­voltage power cables
• RJ45 insulation displacement connector available for field terminations
• Wide thermal operating range
Table 8 - EtherNet/IP Cable Specifications for MCCs
Certifications UL and c-UL Listed
Outside diameter 8.13 ± 0.38 mm
Operating temperature -20…+80 °C
Cable rating UL, c-UL TYPE CMG; UL PLTC or UL AWM 2570 80C 600V, TIA 568B
Figure 34 - EtherNet/IP Cable Pinout
Pin No. Cable Color Description
1 White/Orange TxData + 2 Orange TxData ­3 White/Green Recv Data + 4Blue Unused 5 White/Blue Unused 6Green Recv Data ­7White/BrownUnused 8Brown Unused

Add a MCC Unit to an EtherNet/IP System

Use this section to add 2500 MCC units to an EtherNet/IP MCC. Each EtherNet/IP component is factory wired within the unit and has a communication cable that plugs into the device on one end and generally into a vertical wireway EtherNet/IP port on the other end.
No. of Conductors
8 Teal 600V PVC Foil and
(1) Replace -2 (2 m) with -5 (5 m), or -10 (10 m) for additional standard cable lengths.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 87
Jacket Material Cable Type Cable Rating Cat. No.
Red 600V PVC 1585J-M8EBJM-2
braided shield
(UL) CMX, CMR; c(UL) CMG; (UL) PLTC or AWM 2570 80 °C 600V; TIA-568-B
(1)
1585J-M8HBJM-2
Page 88
Chapter 9 IntelliCENTER Options

Ethernet Power Supply

IMPORTANT Many EtherNet/IP components require 24V DC power source to operate.
The power supply must be EtherNet/IP compatible as specified in the ODVA requirements.
Power supplies that do not satisfy both preceding points can result in damage to the EtherNet/IP signal and components, and failure to comply with local codes and inspection.
A power supply unit that meets EtherNet/IP requirements can be supplied with the MCC. A cable connects the output of the power supply to pins C3 and C4 of the control plug in the network wireway. This cable is already connected when the power supply unit ships installed in the MCC. Redundant configurations are also available.

Connect Power Supplies–Remote or in the MCC Lineup

Connect power supplies according to guidelines to minimize voltage drops in the EtherNet/IP system while providing proper supply voltage to system devices. For detailed connection instruction, see the Converged Plantwide Ethernet Design and Implementation Guide, publication ENET-TD001
.

Network Power Supply and the Protective Earth Circuit

The EtherNet/IP network is grounded at the various components via the component ground. Therefore, no further grounding is needed for the Ethernet cables.
IMPORTANT Do not connect the 24V DC common in the power supply bucket to the PE.
Doing so violates the grounding guidelines for the various EtherNet/IP components.

Connecting Two Power Supplies

Install an additional 24V DC Class 1 power supply for MCC lineups with 14 or more columns. When using two supplies, provide a break between the two 24V DC networks. Locate the appropriate break for the two networks and verify that the terminal blocks are not connected between these two columns.
88 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 89
Figure 35 - Connecting Two Power Supplies
EtherNet/IP Network
24V DC Connection
-24V DC Connected +24V DC Not Connected
24V DC Connection
IntelliCENTER Options Chapter 9
Position each power supply so it feeds a maximum of seven columns to the left or right (see the sample lineup on page 95
).

System Design Installation Checklist

When you install an EtherNet/IP MCC, verify the following before you apply power to the network:
• Only one power supply is connected for every 14 sections of MCC.
• The power supply for the system is 24V DC.
• The PE is connected.
• Connections are inspected to detect and correct any loose wires, opens, or shorts.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 89
Page 90
Chapter 9 IntelliCENTER Options

EtherNet/IP Software Installation Checklist

The following steps, along with references for more information, are provided to assist with the EtherNet/IP software installation process.
1. Install the communication card in your personal computer.
2. Load the Windows hardware drivers for the communication card.
3. Load RSLinx® software.
4. Configure the RSLinx driver.
Within the RSWho function, make sure no unrecognized devices (the ‘?’ symbols) appear for any devices. If an unrecognized device appears, load the Electronic Data Sheet (EDS) file.

DeviceNet Motor Control Centers

For additional details, see Electronic Data Sheets (EDS)
IMPORTANT Do not leave the RSWho software so it constantly browses. Close
the RSWho screen or disable Autobrowse.
5. Use the device web pages or RSLogix 5000® software to progra con
figure devices (for example, full load current, acceleration rate).
6. Write the PLC program.
7. If IntelliCENTER® software is provided, load per the IntelliCENTER
Software User Guide, publication MCC-UM001
This section explains how to connect the terminating resistors and join the DeviceNet cables.
on page 95.
m and
.

Preparing a DeviceNet System for Commission

If your CENTERLINE 2500 MCC is equipped with DeviceNet, terminating resistors must be installed before commissioning. If your MCC consists of multiple shipping blocks, then DeviceNet splicing cables must be installed as columns are joined.
Basic information is provided in the following sections. For additional information, see DeviceNet Motor Control Centers (MCCs), publication
2500-TD002
90 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
.
Page 91
IntelliCENTER Options Chapter 9

Terminating Resistors

IMPORTANT The DeviceNet network only operates correctly when there are exactly
two terminating resistors, one at each end of the network trunk line.
Terminating resistors are necessary at the ends of trunk lines to reduce reflections of the communication signals on the network.
For more information, see Figure 36
.
Follow these procedures to install terminating resistors.
1. Locate the terminating resistor kit.
Terminating resistor kits are shipped in the top horizontal wireway. A removable white label indicates the location of the kit.
2. Remove the top horizontal wireway cover from each column in th
work.
net
3. Plug the first terminating resistor into the left port in the to ho
rizontal wireway of the left end column in the network and torq
t
he connector screws to 0.55 N•m.
p
4. Plug the second terminating resistor into the right port in the top horizontal wireway of the right end column of the network and torque the connector screws to 0.55 N•m.
5. Do not replace the horizontal wireway covers until all shipping blocks in the network have been spliced together.
Refer to
Joining DeviceNet Cables on page 93.
e
ue
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 91
Page 92
Chapter 9 IntelliCENTER Options
Ter m in at i ng
Resistor
DeviceNet cable is spliced between MCC columns.
Ter m in at i ng
Resistor
Removable horizontal wireway cover at top of MCC column.
DeviceNet Linking
3-phase Horizontal Power Bus
NOTE: Examples at right depict typical 2500 MCC configurations with one DeviceNet network.
See publication 2500-TD002
for examples of typical 2500
MCC configurations with two DeviceNet networks.
Tru nk l ine in t he control and network wireway.
DeviceNet ports are supplied for each required unit.
DeviceNet trunk cable routing
through typical MCC column.
DeviceNet
Scanner
DeviceNet
Scanner
Power
Flex
Drive
MCC configuration with a remote DeviceNet scanner.
Configuration with remote D eviceNet scanner and divided MCC lineup.
Each DeviceNet trunk line must start and end with a terminating resistor.
MCC configuration with DeviceNet scanner installed in a fixed unit.
MCC configuration with remote DeviceNet scanner and remote device.
DeviceNet port behind top horizontal wireway cover.
Remote
DeviceNet
Scanner
Figure 36 - Install Terminating Resistors and DeviceNet Splicing Cables
92 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 93
IntelliCENTER Options Chapter 9

Joining DeviceNet Cables

After the terminating resistors have been installed, DeviceNet cables in each column of the network must be spliced together.
Follow these procedures to join the DeviceNet cables.
1. Locate the DeviceNet splicing cable in the top horizontal wireway.
One end of the splicing cable is plugged into the right DeviceNet po i
n the column to the left of the splice.
2. Route the cable through the top horizontal wireway into the column to the right of the splice.
3. Plug the free end of the DeviceNet splicing cable into the left port
he top horizontal wireway of the column to the right of the splice.
t
4. Torque connector screws on the splicing cable plugs to 0.55 N•m.
5. Verify that the horizontal wireway is free of tools and debris.
6. Replace horizontal wireway covers.

DeviceNet Power Supply

IMPORTANT The DeviceNet cable system requires a 24V DC power source to operate.
The power supply must be DeviceNet compatible as specified in the ODVA requirements.
Power supplies that do not satisfy both points above can result in damage to the DeviceNet signal and components, and failure to comply with local codes and inspection.
rt
in
A power supply unit that meets DeviceNet requirements can be supplied with the MCC. A cable connects the output of the power supply to a DeviceNet port in the control and network wireway. This cable is already connected when the power supply unit ships installed in the MCC. Redundant configurations are also available.
Remote power supplies shall meet the following requirements, per ODVA:
• Rated 24V DC (±1%)
• Rise time of less than 250 milliseconds to within 5% of 24V DC at full load of 8 A
• Current limit protection of 8 Amps continuous and 10 Amps for th fi
rst 250 ms
• Sized correctly to provide each device with its required power—each device typically requires 90…165
Derated for temperature as specified by the manufacturer
mA
e
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 93
Page 94
Chapter 9 IntelliCENTER Options
Power Supply
Red V+
White CAN_H
Blue CAN_L
Black V- (common)
BREAK
Power Supply

Connect Power Supplies–Remote or in the MCC Lineup

Connect power supplies according to these guidelines to minimize voltage drops in the DeviceNet system and help achieve proper supply voltage to system devices. For detailed connection instructions, see the Media Design Installation Guide, publication DNET-UM072
.

Network Power Supply and the Protective Earth Circuit

The DeviceNet cable must be connected to the PE circuit at only one location. The ideal choice is at the power supply. Connect the power supply and 24V DC common (black wire) to the PE circuit by using #8 AWG wire.
Best PE Practice
• If the power supply comes installed in the MCC, the black 24V DC common terminal is connected to the PE within the un
To improve the connection, use #8 AWG green wire and ground the
• black 24V DC common terminal to a stable PE external to the MC
to an optional true earth (TE) connection inside the MCC.
or
• If the power supply is external, the same recommendations apply.
it.
C

Connecting Two Power Supplies

An additional 24V DC Class 1 power supply must be installed for MCC lineups with more than 14 columns. When using two supplies, the red conductor between the power supplies must be broken. Locate a linking connector between columns and disconnect the red conductor.
Connect only ONE of the two power supplies to the PE.
94 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 95
IntelliCENTER Options Chapter 9
Power Supply
MCC Lineup With More Than 14 Columns
Break Red Conductor Power Supply
Position each power supply so it feeds a maximum of seven columns to the left or right (see the following sample lineup).
MCC lineups with more than 14 columns could exceed the 75 m trunk length limit to support 500 Kbps communications. When the trunk length exceeds this limit, specify 250 Kbps communications.

Electronic Data Sheets (EDS)

This section applies to any MCC with IntelliCENTER software that is inst
alled on a DeviceNet or EtherNet/IP network.
After IntelliCENTER software is installed, an Electronic Data Sheet (EDS) must be registered for each unique device in the MCC. This section details how to perform that task.

Overview

EDS files are simple text files that are used by network configuration tools— such as RSNetWorx™, RSLogix 5000, or IntelliCENTER software—to help identify products and easily commission them on a network. EDS files describe device type, version, and configurable parameters on a DeviceNet or EtherNet/IP network.

Where to Find EDS Files

The IntelliCENTER data CD has a directory (<cdrom>:\<order>\<item>\EDS) that contains the EDS files necessary for the devices in your IntelliCENTER MCC. The installation program automatically registers the EDS files.
An ‘EDS file’ CD is provided with EDS files for all DeviceNet and EtherNet/IP products that are found in MCCs.
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 95
Page 96
Chapter 9 IntelliCENTER Options

Installing EDS Files

EDS files are installed with a program from Rockwell Software® called ‘RSHWare.exe’. This program is included on the IntelliCENTER data CD and in the same directory as the EDS files.
Follow these steps to install EDS files for a DeviceNet or EtherNet/IP network.
1. Ru n t he pr og r am ‘ RS H War e .e xe ’.
2. Click Add/Remove.
3. Select Register an EDS file and click Next.
4. Select Register a directory of EDS files.
5. Browse to the EDS directory on the data CD.
6. Click Next.
The Installer displays the test results.
7. Click Next to continue.
You can change the graphic image for each de
8. Click Next to continue.
The Installer displays the final task summary
lick Next to continue.
9. C
10. Click Finish when completed.
vice.
.

Finding EDS Files for Other Devices

EDS files can be obtained at
https://ab.rockwellautomation.com/Networks-and-Communications
.

Uploading EDS Files from the Device

RSNetWorx for EtherNet/IP or RSNetWorx for DeviceNet software can be used to upload an EDS file directly from a device. If an EDS file cannot be found by other methods, see the RSNetWorx help file for steps to upload an EDS file.
96 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 97
Worksheets
Ver tic al Wi reway
1A
1J
2A
2N
2S
80 mm
Bottom Horizontal Wireway
Ver tic al Wi reway
Top Hori zon tal Wi rew ay
Appendix A

Sample MCC Layout Worksheet

Figure 37 - Sample MCC Layout Worksheet
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 97
Page 98
Appendix A Wor ksh eets
Table 9 - Location of Sample Units within above MCC Layout
Unit Data
Serial Number Wiring Diagram
Unit Location
1A Y-359039 1200A MLUG
1J Y-359043 DOL 185
2A Y-359042 DOL 110
2N Y-359041 DOL 22
2S Y-359045 XFMR
Size or Amp Rating
Description
Full Load Current
Overload
Kilowatts
Circuit Breaker Trip Setting
Power Fuse Rating
98 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Page 99
Work she ets Appendix A
Table 10 - Motor Control Center Layout Worksheet
MCC Name / Number ___________________________________________________________
Unit Data
Serial Number Wiring Diagram
Unit Location
Size or Amp Rating
Description
Full Load Current
Overload
Kilowatts
Circuit Breaker Trip Setting
Power Fuse Rating
Rockwell Automation Publication 2500-IN001E-EN-P - April 2019 99
Page 100
Appendix A Wor ksh eets
Table 11 - Electrical Insulation Resistance Test Reading/Recording Table
MCC Name / Number ___________________________________________________________
Date
Circuit / Unit Name / Number
Phase-to-Phase Phase-to-PE Phase-to-Neutral
A - B B - C C - A A - PE B - PE C - PE A - Neut. B - Neut. C - Neut.
100 Rockwell Automation Publication 2500-IN001E-EN-P - April 2019
Loading...