Roca BCH-7, BCH-10, BCH-12, BCH-15, BCH-20 Technical Information

...
Page 1
1
Model BCH horizontal packaged air to air heat pump
Technical information
Ref.: N-26844 0700
Clima Roca York S.L. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products, in the program
AC1, AC2 and AC3.
EUROVENT
CERTIFIED PERFORMANCE
CGM-97/013
ACCORDING TO ISO 14001 STANDARDS
ER-028/1/91
ACCORDING TO ISO 9001 STANDARDS
Page 2
Page 3
Index
General 5
- General description 5
- Nomenclature 5
- Control 5
Technical specifications 5
- Mechanical specifications 5
- Physical data 6
- Nominal features 7
- Test conditions 7
- Correction factors 7
- Nominal flow-rates 7
- Sensitive cooling capacities 8 - 9
- Outdoor fan performance 10
- Indoor fan performance 10
Installation instructions 11
- General 11
- Protection of the environment 11
- Warning signs 11
- Transport 11
- Location 11
- Attaching unit 12
- Drain connections 12
- Clearances 12
- Air ducts 12
- Air intake and discharge orientations 13
- Variations to be performed at jobsite 13
Electrical installation 14
- Start-up procedure 14
- Electrical characteristics 14
- Utilization limits 1 5
- Balance point adjustment 15
- Logic module 15
- Discharge sensor 15
- Outdoor sensor 15
- Liquid sensor 15
- Balance point 15
- Timer 15
- Stoppage of inferior fan during defrost 15
- Delayed switch-off interior fan 16
- Other 16
Operation 16
- Summer cycle 16
- Winter cycle 16
- Detail module internal connections with exits to the connector 16
- Function of the pins 16
- Actions according to state of the probe 16
- Module 17
- Indications led autodiagnosis 17
- Operating sequences 18 - 19
- Defrost cycle (timer) 20
- Operating at -15°C 20
-
Operation on emergency heat 20
- Other safety features of the electric circuit 20
- Compressor crankcase oil heater 20
- Before finalising the installation 20
Operating instructions 21
- General instroduction 21
- DSL ambient thermostat for 610 heat pump 21
- Operation and start up 21
- Graphic information 24
Maintenance 24
- Cleaning of filters 24
- Cleaning outdoor coil 24
- Priming the dreinage siphon 24
- Indoor unit discharge ducts 24
General dimensions 25 - 27 Wiring diagrams 28 - 41
Optional accessories 42
- Filter rack with filter 43
- Air filter 44
- Indoor electric heaters RH 45
- Duct electric heaters RC-220 46
Page
Page
Page 4
Page 5
5
Design level
Voltage:
21 = 230.1.50 22 = 230.3.50 38 = 400.3.50
General
General description
The model BCH heat pump is an air to air type of equipment that provides air conditioning in summer and in winter by reversion of its operating cycle. It can be located either indoors or outdoors since it is protected to withstand weathering and the centrifugal fans allow the connection of ductwork. It is delivered totally equipped, factory tested and ready for the incorporation of the electric heater accessory, indoor or for ductwork. Designed to achieve an important energy saving and a long operating life by the incorporation of an electronic control module. Temperature adjustment is achieved by means of the 24 VAC ambient thermostat.
Nomenclature
Balance point
Since the heat pump operates by extracting heat from the outdoor air, it is possible that sometimes this temperature is so low that the extracted heat is insufficient to satisfy the heating demand. For these conditions the electronic module has six balance points (between - 4 and 14 °C), one of which will be adjusted during the start-up. Below this temperature the supplementary electric heater will come into operation. The heat pump will nevertheless continue to operate with a COP greater than that of the electric heaters until the outdoor temperature drops below -20°C. Below this temperature the heat pump will automatically stop operating and will only use the electric heaters to warm the space. This prevents the compressor from operating with very high compression ratios that will shorten its operating life.
Compressor safeties
A temperature sensing element protects the compressor against too high discharge temperatures. A pressure cutout stops the compressor when the discharge pressure is too high. It also actuates in case of a refrigerant leak or because of an insufficient air flow across the coils.
Defrost control
The defrost cycle starts after a period, set at will, of 30, 60 or 90 minutes after start or last defrost cycle and the liquid line temperature is -5°C or less.
Start timer
It prevents frequent stops and starts. After stopping, the unit does not start again until 2 or 5 minutes, set at will, have elapsed.
Control panel
The control of the BCH heat pump operation is done by means of thermostat that allows the following: 1- Setting of the desired temperature. 2- Automatic availability of heating or cooling as desired. 3- Control that the operation of the indoor fan be continuous
or intermittent depending on the operation of the com­pressor.
4- Operate the electric heaters shutting down the rest of the
unit.
Technical specifications
Mechanical specifications
Compressor
Of the vertical hermetic type, mounted on shock absorbent blocks, equipped with a low consumption motor. It is delivered with a charge of a special oil that prevents foam formation and with an electric oil heater.
Compressor oil heater
Keeps the crankcase oil hot to ease starts and prevent the oil from being carried away from compressor.
Suction accumulator
Connected to the suction tube of the compressor it protects it against liquid strokes, preventing the oil from coming out of the compressor.
Suction exchanger
Formed by the suction and liquid tubes of the circuit, protects the compressor by preventing the liquid refrigerant from
Horizontal packaged heat pump
Nominal power: Cooling Heating 7 = 6 400 W / 7 100 W 10 = 9 200 W / 10 800 W 12 = 11 600 W / 12 700 W 15 = 14 000 W / 14 300 W 20 = 17 900 W / 18 000 W 25 = 21 700 W / 22 500 W 30 = 27 000 W / 28 500 W
Control
To achieve maximum energy saving and a perfect operation of the equipment, that will avoid breakdowns and prolong its operating life, the BCH heat pump incorporates the following features:
BCH 7 21 A
Page 6
6
reaching it. Also it increases the efficiency of the system.
Coils
Of large heat transfer area, made of copper tubes and aluminum fins. They are located inside the casing and are therefore pro­tected from being damaged during transport and installation.
Fans indoor and outdoor fan
Centrifugal type with direct drive motor. These fans develop sufficient pressure for the installation of
ducts and optional accessories.
Casing
Built of steel sheet with aluminum-zinc protection, with primer and powder epoxy finish to allow its installation out­doors.
Supplementary electric heaters
Of the air exposed wires type that allow a rapid heat dissipa­tion, avoiding the thermal inertia that could affect com­ponents.
BCH-7 BCH-10 BCH-12 BCH-15 BCH-20 BCH-25 BCH-30
Quantity 1 1 1 1 1 1 1
Nominal power kW 2.8 4.3 4.7 5.3 6.9 9 10
Power supply V.ph.Hz. 230.1.50
Quantity 1 1 1 1 1 1 1
Tubes length x height 5 x 18 5 x 21 5 x 21 5 x 21 5 x 27 5 x 24 5 x 24
Fins per inch 12 12 14 12 14 14 14
Face area m
2
0.32 0.41 0.51 0.51 0.65 0.7 0.89
Tubes diameter mm (Inch) 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8")
Quantity 1 1 1 1 1 1 1
Tubes length x height 3 x 18 4 x 21 4 x 21 4 x 21 4 x 27 3 x 24 4 x 24
Fins per inch 12 12 12 12 12 12 12
Face area m
2
0.22 0.25 0.37 0.37 0.47 0.61 0.61
Tubes diameter mm (Inch) 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8") 9.52 (3/8")
Quantity 1 1 1 1 1 1 1
Turbine diameter m m 270 320 320 320 320 320 320
Turbine width mm 270 240 240 240 320 240 320
Nominal power kW 0.58 0.99 0.99 0.99 1.1 1.1 1.5
Nominal motor rpm 950 950 950 950 950 950 1 420
Power supply V.ph.Hz. 230.1.50 230.1.50 230.1.50 230.1.50
Quantity 1 1 1 1 1 1 1
Turbine diameter m m 240 270 320 320 320 320 320
Turbine width mm 240 200 240 240 240 240 240
Nominal power kW 0.38 0.54 0.95 0.95 0.99 1.1 1.1
Nominal motor rpm 950 950 950 950 950 1 410 1 410
Power supply V.ph.Hz. 230.1.50 230.1.50 230.1.50 230.1.50
R-22 refrigerant charge kg 2.95 4.2 4.5 4.75 7.5 5.9 7
Approximation nett weight kg 193 223 271 275 340 355 412
Approximation gross weight kg 219 257 311 315 370 395 462
Dimensions with standard packing cm 132x132x65 136x139x71 155x160x71 155x160x71 155x160x87 176x180x78 176x220x78
Indoor fan motor
Model
Compressor
Outdoor coil
Indoor coil
Outdoor fan motor
230.3.50
400.3.50
Physical data
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
Page 7
7
BCH-7 6 400 3 800 7 100 3 700 BCH-10 9 200 5 000 10 800 4 000 BCH-12 11 600 6 700 12 700 5 000 BCH-15 14 000 6 900 14 300 5 420 BCH-20 17 900 8 900 18 000 7 780 BCH-25 21 700 10 000 22 500 7 500 BCH-30 27 000 14 600 28 500 13 500
BCH-7 BCH-10 BCH-12 BCH-15 BCH-20 BCH-25 BCH-30
2 175 2 780 3 900 3 900 4 675 4 900 5 800
2 100 3 350 3 410 3 410 4 675 5 200 6 400
Model
Unit
Nominal features
Summer Winter
Cooling capacity W Consumption W
Heating capacity W
Consumption W
DB WB DB WB DB WB DB WB
35 24 27 19 7 6 20 12
Indoor temperature °C
14 10 6 0 -8 23 1.20 1.04 0.96 0.77 0.58 20 1.25 1.10 1.00 0.80 0.69 17 1.30 1.13 1.04 0.83 0.63
Summer
Winter
Outdoor unit air
intake temperature °C WB
Test conditions
Correction factors
Correction factors for the cooling capacities
Correction factors for the cooling capacity with regard indoor and outdoor temperatures.
Correction factors for the heating capacities
19 25 30 35 40 46 23 - 1.20 1.15 1.11 1.06 1 19 1.10 1.08 1.04 1 0.96 0.90 14 0.88 0.86 0.84 0.82 0.79 0.74
Outdoor unit air
intake temperature °C DB
Note:
Indoor unit air intake DB temperatures, between 21 & 32 °C. WB = Wet bulb. DB = Dry bulb.
Correction factors for the cooling capacity for flow-rates different from the nominal ones in the indoor coil.
130
1.046
1.118
1.025
120
1.032
1.075
1.017
100
1
1
1
110
1.016
1.038
1.009
80
0.960
0.945
0.980
90
0.980
0.973
0.990
Flow %
Total capacity
Sensitive capacity
Absorb. comp. poten.
Correction of the real temperature of the air entering the outdoor coil for flow-rates different from the nominal ones.
Flow % 70 80 90 100 110 120 130
Correction in °C over the real air intake temperature at the outdoor battery unit
5 3 1.5 0 -1 -2 -2.5
Correction of the real temperature of the air entering the outdoor coil for flow-rates different from the nominal ones.
Correction in °C over the real air intake temperature at the outdoor battery unit
-2 -1.5 -0.5 0 0.5 1 1.2
Outdoor temperature °C Indoor temperature °C Outdoor temperature °C
25 37 50 50 50 62 62
50 50 50 50 50 50 50
Indoor unit
air intake
temperature
°C WB
Indoor unit
air intake
temperature
°C DB
Nominal flow-rates
The cooling and heating capacities in the corresponding tables are valid for the following nominal flow-rates.
For other flow-rates, apply the correction factor from the corresponding table.
Flow % 70 80 90 100 110 120 130
Indoor fan
nominal
m3/h
Static pres.
nominal
Pa
Out. fan nominal
m3/h
Static pres.
nominal
Pa
Page 8
8
Dry temperature of air °C (DB)
Sensitive cooling capacities
Compressor
power
absorbed
kW
WWWWW
24
22 27 29
Sensitive capacity (W)
Model
Outside
air dry
temperature
°C (DB)
Air intake
humid
temperature
°C (WB)
22 9 300 2 600 3 700 4 900 6 000 2.18
19.5 8 300 3 500 4 600 5 700 6 800 2.08
17 7 200 4 300 5 400 6 500 7 200 1.92
22 8 200 2 200 3 300 4 500 5 600 2.51
19.5 7 500 3 200 4 300 5 400 6 500 2.38
17 6 800 4 100 5 200 6 300 6 800 2.22
22 7 800 2 100 3 200 4 300 5 400 2.88
19.5 6 700 2 800 4 000 5 100 6 200 2.75
17 5 700 3 600 4 800 5 700 5 700 2.48
22 13 600 3 700 5 500 7 200 9 000 3.25
19.5 12 200 5 200 7 000 8 700 10 500 3.10
17 10 600 6 400 8 200 10 000 10 600 2.85
22 12 000 3 200 8 000 6 700 8 500 3.75
19.5 11 000 4 700 6 500 8 200 10 000 3.58
17 10 000 6 200 8 000 9 700 10 000 3.20
22 11 400 3 000 4 700 6 500 8 300 4.30
19.5 9 800 4 200 6 000 7 800 9 000 4.10
17 8 400 5 500 7 200 8 400 8 400 3.65
22 17 600 4 600 7 300 10 000 12 700 4.15
19.5 16 400 7 000 9 700 12 400 15 100 3.90
17 14 800 9 200 11 900 14 600 14 800 3.75
22 16 500 4 200 6 900 9 600 12 300 4.65
19.5 14 900 6 400 9 100 11 800 14 500 4.45
17 13 400 8 600 11 300 13 400 13 400 4.25
22 14 700 3 500 6 200 8 900 11 600 5.30
19.5 13 700 6 000 8 700 11 400 13 700 4.95
17 12 200 8 100 10 800 12 200 12 200 4.70
25
35
45
25
35
45
25
35
45
BCH-7
BCH-10
BCH-12
Total
capacity
Page 9
9
Dry temperature of air °C (DB)
Sensitive cooling capacities
Compressor
power
absorbed
kW
WWWWW
24
22 27 29
Sensitive capacity (W)
Model
Outside
air dry
temperature
°C (DB)
Air intake
humid
temperature
°C (WB)
22 19 400 - 8 300 11 700 15 200 4.70
19.5 17 800 7 700 11 100 14 600 17 800 4.60 17 16 300 10 700 14 100 16 300 16 300 4.40 22 17 600 - 7 600 11 100 14 500 5.50
19.5 16 300 7 100 10 600 14 000 16 300 5.10 17 14 900 10 100 13 500 14 900 14 900 4.90 22 15 800 - 7 100 10 500 13 900 6.20
19.5 14 500 6 600 10 000 13 400 14 500 5.80 17 13 300 9 500 13 000 13 400 13 400 5.50 22 24 410 - 10 200 14 150 19 180 6.30
19.5 22 670 9 620 13 600 17 440 22 600 6.20 14 18 830 19 200 18 800 18 830 18 830 5.90 22 23 480 - 9 400 14 500 18 400 7.20
19.5 20 930 8 370 12 600 17 600 21 600 7.00 14 18 480 15 530 17 090 18 300 18 300 6.60 22 21 160 - 8 820 13 900 17 900 8.00
19.5 19 340 7 870 11 690 16 900 19 600 7.80 14 16 290 14 730 16 310 16 500 16 270 7.30 22 26 040 8 005 10 791 14 971 17 761 6.64
19.5 23 436 11 466 14 253 18 432 21 223 6.95 17 21 700 15 181 17 968 21 700 21 700 7.27 22 24 087 7 330 10 116 14 296 17 082 7.51
19.5 21 700 10 812 13 599 17 778 20 564 7.90 17 19 964 12 957 15 743 19 923 19 964 8.30 22 21 700 6 580 9 366 13 545 16 332 8.69
19.5 19 530 10 067 12 853 17 033 19 530 9.09 17 17 794 13 585 16 371 17 794 17 794 9.48 22 26 040 7 777 11 304 16 594 20 126 8.23
19.5 23 436 12 200 15 727 21 018 23 436 8.62 17 21 700 16 866 20 393 21 700 21 700 9.02 22 24 087 7 133 10 660 15 950 19 477 9.31
19.5 21 700 11 573 15 100 20 391 21 700 9.80 17 19 964 15 207 18 735 19 964 19 964 10.29 22 21 700 6 414 9 941 15 232 18 759 10.78
19.5 19 530 10 856 14 383 19 530 19 530 11.27 17 17 794 15 327 17 794 17 794 17 794 11.76
25
35
45
25
35
45
25
35
45
BCH-15
BCH-20
BCH-25
Total
capacity
25
35
45
BCH-30
Page 10
10
BCH-30
2 000 2 200 2 410 2 550
3 100 3 200 3 300 3 400 3 500 3 600
3 100 3 250 3 370 3 450 3 560 3 700
4 050 4 400 4 600 4 750 4 900 5 100 4 500 4 800 4 910 5 050 5 200 5 250 5 350 5 450 5 490 5 980 6 200 6 400 6 480 6 600 6 700
540 560 580 590
900 920 940 960 970 990
880 920 930 940 970 980
1 050 1 070 1 120 1 150 1 180 1 230 1 130 1 200 1 250 1 275 1 295 1 320 1 335 1 388 1 355 1 440 1 500 1 555 1 585 1 600 1 665
6 4 2 0
10
8 6 4 2 0
10
8 6 4 2 0
10
8 6 4 2
0 14 10
8
6
5.1 4 2 0
14 10
8
5.1 4 2 0
350 365 370 380 390 480 495 510 525 540 875 890 910 930 950 970 990
1 020
900 1 000 1 020 1 050 1 100 1 120 1 180 1 230 1 270
940 1 050 1 100 1 160 1 220 1 290 1 345 1 390 1 220 1 365 1 430 1 585 1 680 1 750 1 810
58.8
39.2
19.6
0.0
98.0
78.4
58.8
39.2
19.6
0.0
98.0
78.4
58.8
39.2
19.6
0.0
98.0
78.2
58.7
39.1
19.6
0.0
137.2 98
78.4
58.8
49.98
39.2
19.6 0
137.2 98
78.4
49.98
39.2
19.6 0
0.47
0.52
0.58
0.61
0.65
0.69
0.75
0.77
0.82
0.86
0.91
0.96
1.00
1.02
1.07
1.10
1.13
1.16
1.06
1.11
1.15
1.19
1.25
1.28
1.32
1.36
1.39
1.10
1.22
1.25
1.31
1.36
1.43
1.50
1.52
1.30
1.44
1.48
1.61
1.68
1.74
1.77
Power
absorbed
m3/smm WG Pa m3/h
78.4
58.8
39.2
19.6 0
78.4
58.8
39.2
19.6 0
137.2
117.6 98
78.4
58.8
39.2
19.6 0
156.8
137.2
117.6
98.0
78.2
58.7
39.1
19.6
0.0
156.8
117.6 98
78.4
61.7
39.2
19.6 0
156.8
117.6 98
61.7
39.2
19.6 0
1 700 1 900 2 100 2 200 2 350 2 500 2 700 2 800 2 950 3 100 3 300 3 450 3 600 3 700 3 850 3 960 4 100 4 200 3 800 4 000 4 150 4 300 4 500 4 600 4 750 4 900 5 000 3 980 4 400 4 520 4 750 4 900 5 180 5 420 5 500 4 700 5 200 5 350 5 800 6 050 6 280 6 400
Note: Performance calculated with wet coil including filters, except in models 25 and 30.
BCH -12 BCH -15
BCH -7
BCH-20
BCH -12 BCH -15
BCH -10
BCH -7
mm WG
Pa
m3/sm3/h
W
Power
absorbed
BCH -10
BCH-25
Air flow
Static pressure
available
Model
Static pressure
available
Air flow
Model
Outdoor fan performance
8 6 4 2 0 8 6 4 2
0 14 12 10
8
6
4
2
0 16 14 12 10
8
6
4
2
0 16 12 10
8
6.3 4 2 0
16 12 10
6.3 4 2 0
BCH -20
BCH-30
BCH-25
0.56
0.61
0.67
0.71
0.86
0.89
0.92
0.94
0.97
1.00
0.86
0.90
0.94
0.96
0.99
1.03
1.12
1.22
1.28
1.32
1.36
1.42
1.25
1.33
1.36
1.40
1.44
1.45
1.48
1.51
1.52
1.66
1.72
1.77
1.8
1.83
1.86
W
Indoor fan performance
Page 11
11
Installation instructions
General
The BCH heat pumps are delivered as factory charged and tested packaged units. Designed to be installed with ducts, on terraces, rooftops, in lofts or basements.
Protection of the environment
Packing
Packing is made of recyclable material. The disposal of same should be carried out in accordance with the regulations on selective residue disposal established by the local authori­ties.
Disposal of the unit
When dismantling after a long service life, its components should be ecologically salvaged. The cooling circuit is full of HCFC-22 refrigerant which should be salvaged and, finally, returned to the gas manufacturer for recycling. Oil will remain in the airtight compressor so, it will be returned along with the sealed circuit. The air conditioning unit will be deposited wherever estab­lished by the local authorities for its selective disposal.
Warning signs
The following signs indicate the presence of potentially dangerous conditions for the users or service personnel. Whenever found on the unit itself, keep in mind the warning indicated by each one.
Transport
The units should always be transported in a vertical position to prevent oil from leaking out of the compressor. If for some reason the unit must be temporarily moved from this position, the time that it rests in a different position should be kept to a minimum.
Location
The unit should be placed in a location that leaves a perma­nent access for maintenance service, either through the side panels, or top cover. They can be installed in any outdoor location. If installed indoors in basements, lofts, etc., the ducts for outdoor air intake and exhaust should be connected. When the unit is installed indoors, consideration should be given to the great quantity of water condensed by the outdoor coil during winter operation, that must be drained through the drain pipe. Occasionally, when the operating cycle is reversed in winter to remove the frost that forms on the coil, the air could carry water droplets. This should therefore be kept in mind when selecting the place of installation and also the possibility of
Attention: It is compulsory to read the instructions prior to any handling.
This sing indicates an electrical risk or danger.
Attention: Not to touch the hot surfaces.
Attention: The unit has remote control system and can start automatically. Two minutes prior to having access to the interior, the power supply should be disconnected so as to avoid any contact with the fan turbine in operation.
Attention: Fan in operation.
Page 12
12
the drain pipe becoming clogged by dust, dirt or some other material should be foreseen.
Attaching unit
From the roof
The unit will be fastened to the roof by four M-10 bolts as shown in figure. For this type of installation the use of vibration isolators is recommended. When fastening unit care should be taken that it is completely horizontal or slightly tilted towards the drain to avoid the dripping of condensed water (use an air bubble level).
The connections to the unit should be done with copper tube of 22 mm O.D.
Resting on the ground
If unit is placed outdoors on the ground, it should be raised on supports to avoid the possibility that snow accumulation
blocks the air intakes.
Drain connections
The pan drain lines of the indoor and outdoor units must be installed with a water trap with a minimum level difference of 75 mm between the connection to the unit and the line after the water trap (see figure). This is necessary to avoid the fan generated negative pressure preventing the drain pan from draining. The drain line should have a minimum slope of 20 cm per meter length.
Attention:
When the heat pump operates under outdoor temperatures below 5°C, the drain tube could become obstructed by ice formation. If the unit is located outdoors, the possibility of this happening should be prevented by installing an electric heater on the drain connection and wiring it according to the corresponding diagrams.
Clearances
Free space must be allowed for in the installation of each unit for: a) Air intake and discharge from the outdoor unit. b) Connecting the drainage and wiring pipes. c) Air ducts. d) Maintenance servicing. e) Connecting up of the electrical supply. The minimum distances, indicated in the overall dimensions diagrams, must always be respected with regard to possible obstacles to the free circulation of air, or the operator's work.
Air ducts
1) Air ducts should be connected to the unit isolated by a sleeve of a flexible, preferably non-combustible material, to prevent transmission of the unit's own vibration. If ducts are made from a flexible material they will not transmit vibration.
2) It is advisable to install a damper in every discharge duct, thus making possible a correct balance of the system.
3) Allow for an easy access to the air filters for replacement and cleaning.
4) If the air discharge of the outdoor coil is done through ducts, it is advisable that the first meter section be of galvanized sheet to avoid corrosion produced by water droplets carried by the air.
It is very important to take the maximum cara with the support of the internal unit when hanging it from a false ceiling. Make sure that the false ceiling is strong enough to withstand the weight of the unit. Before hanging the unit, check the strength of every suspension bolt installed.
Attention: It is essential to use all fixing points on the unit. The BCH-7, 10, 12, 15 and 20 have 4 fixing points. The BCH-25 and 30 have 6 fixing points.
CAUTION
2% SLOPE
75 mm
MINIMUM
PLUG
Page 13
13
Air intake and discharge orientations
Factory supplied orientation.
BCH-7,10,12,15 & 20
BCH-25 & 30
Variations to be performed at jobsite
Starting from the standard unit the orientations of the air intake and discharge of the condenser and evaporator fans can be changed to obtain any of the combinations shown in the figure below.
BCH-7,10,12,15 & 20
BCH-25 & 30
*) This variation of the air intake can be used only in those
installations in which the heat pump is protected from direct rainfall, since it does not allow the rain protection grille (optional accessory) to be fitted.
DISCHARGEINTAKE
INDOOR COIL
OUTDOOR COIL
DISCHARGE INTAKE
OUTDOOR SIDE
INDOOR SIDE
ELECTRIC PANEL
INTAKE
INTAKE DISCHARGE
INDOOR COIL
OUTDOOR COIL
DISCHARGE
OUTDOOR SIDE
INDOOR SIDE
ELECTRIC PANEL
INTAKE
(STANDARD)
DISCHARGE
(STANDARD)
OUTDOOR SIDE
INDOOR SIDE
INTAKE
(STANDARD)
DISCHARGE (STANDARD)
DISCHARGE
(OPTIONAL)
INTAKE
(OPTIONAL)
INTAKE
(OPTIONAL)
DISCHARGE
(OPTIONAL)
*
INTAKE
(STANDARD)
DISCHARGE (STANDARD)
DISCHARGE
(OPTIONAL)
INTAKE
(OPTIONAL)
DISCHARGE
(OPTIONAL)
INTAKE
(STANDARD)
DISCHARGE (STANDARD)
OUTDOOR SIDE
INDOOR SIDE
Page 14
14
230.1.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
32
32
20
40
32
40
32
50
32
50
32
63
32
Power supply V.ph.Hz.
Consumption A
CompressorFan
Indoor
fan
Outdoor
fan
Power supply cables
min.
cross
section
Automatic
circuit
breaker
Model
Electrical characteristics
Compressor
mm
2
Run
Run
Nominal
Outd.
-
BCH -7
14.3
10.9
6.3
12.6
7.3
13.3
7.7
21.1
12.2
29.3
14.2
36
16.5
2.8
5.1
5.1
5.2
5.2
5.2
5.2
4.2
2.4
5.5
3.2
5.5
3.2
4
4
2.5
6
4
6
4
10
4
10
6
16
10
1.7
2.6
2.6
5.2
5.2
5.2
5.2
4.2
2.4
4.5
2.6
6.0
3.5
230.3.50
400.3.50
230.3.50
400.3.50
230.3.50
400.3.50
BCH -20
BCH -15
BCH -12
BCH -10
230.1.50
Electrical installation
In every case the established national regulations should be applied. Each heat pump is delivered with a control box, to which the power supply will be connected across a fused main discon­nect switch or automatic circuit breaker. The electric heater, if available, should be installed with power supply line and switches independent from those of the heat pump.
Start-up procedure
a) Connect the power supply cable and earth to the
corresponding boards on the controls box. b) Give power to the auxiliary control line at 220/240.1.50. c) Connect the room thermostat line to 24 V on the boards
provided in the heat pump. d) Before start-up connect the main switch or automatic
circuit breaker to supply power to the electric oil heater in
the compressor crankcase.
Compressor should not be started before a minimum
of 8 hours have passed.
This is necessary to evaporate any liquid refrigerant that
could have mixed with the compressor oil.
Loose cables can cause overheating of the connectors or an inadequate operation of the unit. Fire risk could also exist. Fot this reason, make sure that all cables are properly connected.
Do not supply power to the unit and do not start up operations until the tubing and electrical connections with the outdoor unit have been completed. Make sure that the electrical supply is correctly connected to the units, as shown in the electrical diagrams.
BCH -25
BCH -30
A
Important: The size of the circuit breaker and the cross-section of the supply and control lines are only as a guide and should be corrected in accordance with the conditons at the jobsite, distance between units, and current legislation.
Indoor
Page 15
15
Balance point adjustment
The balance point is the lowest outdoor temperature at which the heat pump can heat the space without the use of the supplementary electric heaters. The balance point depends on the following:
1) Design outdoor temperature.
2) Building's heat loss.
3) Pump's capacity. The balance point is usually predetermined by the instal­lation's project, but if it has not been predetermined the factory's adjustment at 6°C can be kept.
Logic module
The control module responds to the thermostat's demand signal, it examines the values given by the sensors outdoor, discharge and liquid and determines if the heat pump and/or the supplementary electric heater must operate.
Discharge sensor
It is a thermistor located in the discharge line of the compressor, connected in series with a high pressure cutout. It protects the compressor against high discharge tempe­ratures (and pressures). It stops the compressor when the discharge temperature exceeds the set point or the pressure is greater than 28 kg/cm2. It protects the compressor when there is a refrigerant leak or a flow reduction through outdoor or indoor coils. It allows the reset of the compressor circuit after a lockout condition, by removing the power supply to the control module, or pressing the reset button.
Outdoor sensor
This is a thermistor located in the air intake of the outdoor coil, that registers the air temperature. It controls the heat pump operation, stopping it when the outdoor temperature nears -15 °C. This prevents the compressor from operating at a high compression ratio that could damage it. Allows the connection of the duct electric heater (optional) controlled by the 2nd stage of the room thermostat if the outdoor temperature is less than -15 °C. It allows by means of the balance point for the adjustment of the temperature at which the supplementary electric heater should come into operation.
Utilization limits
Liquid sensor
It is connected in the liquid line of the outdoor coil. This sensor starts the defrost cycle after 30, 60 or 90 minutes from start or last defrost cycle depending on selection, if the temperature it senses is -5 °C or less. Indicates the end of the defrost cycle when the liquid temperature reaches 13 °C or stays at a minimum of 7 °C during 1 minutes. Prevents the cycle from starting in mild climates since sufficiently low liquid temperatures are not detected. The initial time reading for defrosting of 30, 60 or 90 minutes is nominal. These times assume an exterior temperature of 2°C, a highly unfavourable level causing much frost formation. At lower temperatures the total humidity content of the ambi­ent air is lower, permitting prolongation of the defrost cycles, saving energy. For example: at -10°C exterior temperature the initial time readings for defrost will be 60, 90 and 120 minutes.
Balance point
Prevents the operation of the supplementary heating system when the outdoor temperature is above the balance point as adjusted on the plaque. This way the electric heater is not used as long ads the heat pump is capable of meeting the space heating demand. The balance point can be adjusted between 14 °C and -4 °C. This way an additional outdoor thermostat is not needed.
Timer
Delays start during 5 or 2 minutes to avoid repeated starting cycles. This way operating pressures are equalized before the compressor is started. If the thermostat or manipulation cause false contacts the heat pump is not affected. It delays the start after a power supply cut, thus allowing the line voltage to regain its normal level.
Stoppage of interior fan during defrost
This module allows the option of stopping the interior fan during the defrost cycles. This option is only for when it is not possible to instal an auxiliary electric heater.
- With the JP-19 bridge in position (factory standard) the interior fan continues to function during defrosting.
- With the JP-19 bridge open (modified at jobsite) the interior fan is deactivated.
Minimum Maximum Minimum Maximum Cool Heat Cool Heat Cool WB Heat DB Cool WB Heat DB
198 254 342 436 19 -20
(1)
46 24 15 10
(2)
23 27
Indoor coil inlet air
temperature
Voltage limits
Outdoor coil inlet air
temperature DB
Operating cycle
Operating cycle
Nom. 400 V Nom. 230 V
Minimum °C Maximum °C Maximum °C Minimum °C
Notes: WB - Wet bulb. DB - Dry bulb. (1) At an outdoor temperature of -20 °C only the emergency electric heater (optional) continues to operate. (2) The equipment can work for a short period at a temperature of less than 10°C in order to raise the air temperature in the conditioned space to
10 °C.
Page 16
16
Delayed switch-off of interior fan
The interior fan will continue to function for one minute after the stop order. This is to permit dissipation of the energy accumulated in the interior interchanger and represents an energy saving. Optionally, at the jobsite, this option can be deactivated, leaving the JP-20 option of the module open.
Other
- Connector for computer switching.
- Possibility of lowering timer to 2 minutes.
- Buttons: Test. Lowers delay.
Direction for communication.
Reset. Restarts the control. Filters. Delete dirty filter counter.
- Leds:
Standby. Indicates compressor delay. Filters. Dirty filters. Reset. Self-diagnosis and reset Led.
Operation
Summer cycle
In summer functioning the 4-way valve is energised. In the corresponding figure the circuit followed by the refrig­erant is shown.
Winter cycle
On winter cycle the discharge gas goes to the indoor coil which operates as the condenser. The outdoor coil becomes the evaporator. Reversing valve is deactivated. Refrigerant's circuit is shown in figure.
Detail module internal connections with exits to the connector
Function of the pins
Actions according to state of the probe
3
2
1
6 8
4
9
5
7
12
10
11
ENTRY
EXIT
(G) (Y)
11
2
9 3
10
8(R)
12
(B)
6
(W)
1
6
7
24V LINE
(G1) FAN
COMPRESSOR DISCHARGE RELAY
INTERIOR HEATER DUCT HEATER
NO
YES
INTERIOR FAN FUNCTION DURING DEFROST
JP19
DISCHARGE TEMPERATURE LOCK-OUT
130 C
110 C
JP21
- SCALE OF BALANCE: 14,10,6,4,2,0,-2 and -4 °C.
- DELAY TIME START-UP: 2´,5´.
- TIME BETWEEN TWO DEFROSTS: 60´,30´,90´.
- LOW TEMPERATURE DISCONNECTION SCALE: -5,-10,-15,-20 °C.
THIS PLAQUE IS DELIVERED WITH 7 BRIDGES (PIN) AS FOLLOWS: CLOSING CIRCUIT: 5´,60´,6 °C,-15 C,JP19, JP20 and NTC.
WITHOUT CLOSING CIRCUIT: JP21.
STOPPAGE INTERIOR FAN DELAYED 1 MINUTE AFTER COMPRESSOR, WITH THERMOSTAT G TERMINAL DISCONNECTED
NO
YES
JP20
MICRO-93 PROBE (CODIGO 3785028 . 3785030 . 3785032)
NTC
MICRO-97 PROBE (CODIGO 3785050 . 3785052 . 3785054)
LIQUID PROBE OPEN - REPEATS DEFROST
CYCLES ACCORDING TO TIME
DISCHARGE PROBE CLOSED
- STOPPAGE OF COM­ PRESSOR (LOCK OUT)
EXTERIOR PROBE
OPEN - CONNECTS THE
EMERGENCY HEATER
- STOP THE COMPRESSOR
DEFROST CLOSED
( )
FOR 12 SECONDS WITH LIQUID TEMPERATURE < 4 °C
- BEGINS DEFROST
-
Page 17
17
Module
Indications led autodiagnosis
INPUT Y
INPUT G
INPUT W
INPUT O
STANDBY FILTERS RESET
TEST
RESET FILTERS
JP19
JP20
JP21
NTC
2
5
3060901410
642
0
-2
-4
-5
-10
-15
-20
BUTTONS TEST.- DIMINISHES TIMER/DIRECTOR PLATE COMMUNICATION
RESET.- RESTARTS CONTROL FILTERS.-DIRTY FILTERS CONTACTOR DELETE
LEDS STANDBY.- INDICATES COMPRESSOR DELAY
FILTERS.- DIRTY FILTERS RESET.- SELF-DIAGNOSIS/RESET LED
006791024
BCH/BCV-97/A
321 6 8 4 9
5 7
121011
CONTROL CABLE CONNECTOR
COMMUNICATION CONNECTOR BY COMPUTER
B4
LIQUIDO
LIQUID
B3
DESHIELO
DEFROST
B2
DESCARGA
DISCHARGE
B1
EXTERIOR OUTDOOR
BCH/AVO
ROCA CODE
SERIAL
NUMBER
VALIDITY PLATE
CORRECT FUNCTIONING AS PROGRAMMED
LOCK OUT DUE TO COMPRESSOR DISCHARGE TEMPERATURE ABOVE 130 °C
LOCK OUT DUE TO PRESSURE EXCEEDING 28 bar OR FAN THERMIC RELAY
LOCK OUT DUE TO TWO OR MORE DEFROST AT TEMPTS IN LESS THAN 5 MINUTES (ONLY IF THERE IS NO BRIDGE IN 30, 60 OR 90 MINUTES)
IMPULSES 01234567
0
1
0
1
0
1
0
1
0 = LED SWITCHED OFF
1 = LED ILLUMINATED
×
Page 18
18
Summer cycle diagram
Operating sequences
See relevant electrical diagrams. Summer cycle: Thermostat in COOL position
1) The 4-way valve is activated through the thermostat.
2) If the fan operating mode in the ambient thermostat is in
CONTINUOUS, the contactor is activated and the fan functions continuously.
3) With the logic module timing, the unit will start ip after 5
minutes.
4) When the thermostat contact connects, it activates the
contactor and starts the compressor. If the fan operating mode is set to «AUTO», the fan starts simultaneously with the compressor.
5) The unit will function intermittently in response to the
corresponding signal from the ambient thermostat to satisfy the cooling demand.
6) When the unit stops at the end of an operating cycle, or through a power failure, the logic module will not allow it to start up again until 5 minutes have elapsed. This is to protect the compressor by allowing the operating voltages to even up.
7) If the diescharge pressure exceeds 28 kg/cm2, or the discharge temperature is over 130°C, the logic module will switch off the unit, leaving the system in lock-out.
8) To reset after a lock-out, turn the power supply to the unit off, or set «OFF» on the thermostat and then reset «HEAT» or «COOL». The system will re-set and the unit will start up after 5 minutes.
CHECK VALVE
SUCTION ACCUMULATOR
CAPILLARY TUBE
INDOOR COIL
CHECK VALVE
4 WAY REVERSING VALVE
COMPRESSOR
CONTACT EXCHANGER
FILTER
CAPILLARY TUBE
OUTDOOR COIL
Page 19
19
Winter cycle diagram
Winter cycle: Thermostat in HEAT position
1) The 4-way valve is deactivated, allowing the position for the heating circuit, which means that the indoor coil acts as condenser and the outdoor one as evaporator.
2) If the fan operating mode in the ambient thermostat is in the CONTINUOUS position, the contactor is activated and the fan functions continuously.
3) With the logic module timing, the unit will start up after 5 minutes.
4) When the first stage of the thermostat connects, it activates the contactor and starts the compressor. If the fan operating mode is set to «AUTO», the fan starts simultaneously with the compressor.
5) The unit will function intermittently in response to the appropriate signals from the ambient thermostat to satisfy the demand for heating.
6) If the unit stops, after an operating cycle, or through a power failure, the logic module will not allow it to start up again until 5 minutes have elapsed. This is to protect the compressor by allowing the
operating voltages to even up.
7) If the discharge pressure exceeds 28 kg/cm2, or the discharge pressure is over 130°C, the logic module will stop the unit, leaving the system in lockout.
8) To reset after a lock-out, turn the power supply to the unit off, or set «OFF» on the thermostat and then reset «HEAT» or «COOL». The systen will re-set and the unit start up after 5 minutes.
9) The auxiliary heater is activated when the auxiliary heating stage of the thermostat is connected. The logic module allows the indoor auxiliary heater to function if the outdoor temperature is below the balance point. If the outdoor temperature is above that set as the balance point, the indoor heater does not function.
10) The emergency heater (complementary) is connected when the outdoor temperature is lower than that preselected as the operating limit (-15°C, logic module), and the ambient thermostat demands the second heating stage.
CAPILLARY TUBE
INDOOR COIL
CHECK VALVE
4 WAY REVERSING VALVE
COMPRESSOR
CONTACT EXCHANGER
FILTRE
CAPILLARY TUBE
SUCTION ACCUMULATOR
CHECK VALVE
OUTDOOR COIL
Page 20
20
Defrost cycle (timed)
The ice which is produced on the outdoor coil during the heating cycle must be eliminated when it begins to block the coil. The defrost cycle begins after a period selected between 30, 60 & 90 minutes from the start-up or the last defrosting, and when the evaporation temperature drops to -5 °C or less. The logic module activates the defrost relay, which:
- Activates the 4-way valve to go into the cooling cycle.
- Switches off the outdoor fan. The defrost cycle finishes when the liquid temperature is sufficiently high, measured by a thermistor 13 °C, or when, if it does not heat up, it reaches a minimum of 7 °C for a 1 minute period; also after 12 minutes from its beginning. When the defrost cycle finishes, the logic module disconnects the defrost relay, reestablishing normal operating conditions of the heating cycle. If the unit triess to go into another defrost cycle in less than 5 minutes, the logic module switches it off, leaving the system in lock-out.
Operating at -15°C (optionally -5, -10, -20)
When the outdoor temperature is less than -15°C there is no justification for running the compressor with the limited amount of heat it generates. If the logic module detects, through a thermitor in the exterior air entry, a temperature lower than -15°C, it acts as follows:
- It disconnects the compressor.
- It switches on the emergency heater (if there is one installed) controlled by the thermostat's second stage. (The auxiliary heater will also continue to function, governed by
the thermostat's second stage).
- It leaves the indoor fan functioning under the first heating stage of the thermostat.
Operation on emergency heat
When the thermostat operation mode is in the emergency heat position.
- Compressor will be in lockout.
- The supplementary and emergency electric heaters, if installed, will be controlled by the first stage of the thermo­stat.
Other safety features of the electric circuit
- The compressor is protected against overheating and the failure of a phase by a solid state protector with three sensors embedded in the windings.
- The control circuit is protected by a fuse.
- In general all the casing and components are protected by an earth circuit.
Compressor crankcase oil heater
The compressor is equipped with an electric heater in the crankcase, which heats the oil to prevent an excessive concentration of refrigerant in it during the periods when it does not operate. If the main disconnect switch has been off for some time, before heat pump is started switch should have been on for at least 8 hours. This is necessary to drive out any refrigerant that may be accumulated inside the compressor.
Before finalising the installation
Verify that:
- The voltage is always between 198­254 V or 342-436 V.
- The gauge of the supply cable is at least that which is recommended in the corresponding electrical dia­grams.
- Instructions have been given to the users on how to operate the system.
- The condensation drainage is perfectly assembled and their are no leaks in the water circuit.
- The need to clean the air filter has been communicated.
- The guarantee split has been filled in.
- Maintenance instructions have been given or a contract has been made for periodic servicing.
Page 21
21
Operating instructions
General introduction
Start up and automatic temperature regulation are imple­mented by the ambient thermostat. Locate the thermostat approximately 1.5 m. above floor level, where no object prevents it from registering the true tempera­ture of the room. Do not place it on a wall where it will be exposed to direct sunlight, or next to windows, air vents, etc. Before start up connect the mains switch in order to eliminate the electrical resistance of the compressor sump.
The compressor must not be started up until at least eight hours have passed.
DSL ambient thermostat for 610 heat pump
This thermostat has been designed to proportion a precise control of the ambient temperature and to give graphic information of the mode in which the heat pump is opera­ting.
It is a control with a Proportional-Differential-Integral re­sponse which, in relation to the difference between the programmed and the ambient temperatures, varies the on/off cycles between 3 and 7.5 cycles per hour.
The liquid crytal display (LCD) normally indicates the ambient temperature, mode of operation, and whether the heating or cooling system is connected.
It allows for the selection of different set points for heating and cooling, as well as the choice of °C or °F.
The operation of the fan can be set in continuous mode, or automatic, switching off and operating in unison with the compressor.
The controls are located underneath a cover which prevents their manipulation by unauthorised personnel.
Operation and start up
Start up is implemented by the controls located on the thermostat.
1.- MODE
The operational mode of the heat pump is selected by pressing this button. When the button is pressed the following
1.- Operational mode selection.
2.- Fan speed selection.
3.- Day/Night selection.
Controls and indicators
Connection: The electrical supply must be connected for at least 8 hours before operational start up of the conditioner in order to warm up the system. Leave the supply connected, except when the conditioner is going to be out of use for long periods of time.
ON
ELECTRICAL
SUPPLY
CAUTION
Mode
Fan Day/Night
1
2
SET TEMPERATURE SELECTION
3
Page 22
22
operational modes appear on the liquid crystal display panel:
- Controls the system in the cooling mode. (The word is displayed on the panel for 5 seconds).
- Controls the system in the heating mode. (The word is displayed on the panel for 5 seconds).
- Controls the system in cooling or heating according to requirements. (The word is displayed on the panel for 5 seconds).
- Controls the system in the emergency heat­ing mode (it is only active if the optional accessory electrical resistance heater has been installed).
- Disconnects the system.
a) Cooling
Press the button MODE repeatedly until the cooling symbol is displayed on the panel (at the same time the word is displayed for 5 seconds). The cooling symbol continues to be displayed on the panel.
After a few minutes have passed the cooling system will start up, and the cooling symbol, visible on the display, will start to flash.
b) Heating
Press the MODE button repeatedly until the heating symbol is isplayed on the panel (at the same time the word is displayed for 5 seconds). The heating symbol continues to be displayed on the panel.
After a few minutes have passed the heating system will start up, and the heating symbol, visible on the display will start to flash.
c) Automatic
Select a set temperature for the cooling mode and another for the heating mode, as described in paragraphs a and b. In this operational mode the set temperature for cooling
must be at least 1°C above the heating ,
Once the operational mode has been selected, continue to select the set temperature by pressing button or button , whether this be to select a higher or a lower temperature. The set temperature is displayed together with a small symbol which represents a thermometer, which is displayed on the panel for 5 seconds. After the set temperature has disappeared then the ambient tempera­ture will again be displayed.
Once the operational mode has been selecte, select the set temperature by pressing button or button , whether this be to select a higher or a lower temperature. The set temperature is displayed accompanied by a small symbol which represents a thermometer, and remains visible on the display panel for 5 seconds. Once the set temperature will again be displayed.
SELECTED MODE (DISPLAYED FOR 5 SECONDS)
AMBIENT TEMPERATURE
COOLING SYMBOL (SELECTED MODE)
COOLING SYMBOL (SELECTED MODE)
SET TEMPERATURE (DISPLAYED FOR 5 SECONDS)
MODE SELECTED (DISPLAYED FOR 5 SECONDS)
AMBIENT TEMPERATURE
HEATING SYMBOL (MODE SELECTED)
SET TEMPERATURE (DISPLAYED FOR 5 SECONDS)
HEATING SYMBOL (SELECTED MODE)
Page 23
23
temperature, this is the minimum differential allowed by the thermostat. Press the MODE button repeatedly until the heating symbol and cooling symbol are displayed on the panel (at the same time the word will be displayed for 5 seconds). The heating and cooling symbols
will continue to be displayed on the panel.
After a few minutes have passed the system will start up, automatically switching to the heating or cooling mode and maintaining the temperature between the selected margins. The symbol corresponding to the operational mode, heating or cooling, will start to flash.
d) Emergency heating
Repeatedly press the MODE button until the letters (displayed for 5 seconds) appears on the display panel, at the same time the heating symbol will be displayed; once a few minutes have passed the emergency heating will start up, and the heating symbol will start to flash. In this operational mode the compressor is always shut down and the (optional) auxiliary and emergency resistance heaters, if they are fitted, are used to supply the heat. This operational mode can also be used for heating in case of a compressor breakdown.
e) Off
Repeatedly press the MODE button until the word appears on the display. The heat pump will stop and on the thermostat display panel the word and the ambient temperature will be permanently displayed.
3.- Day/night selection
Different set temperatures can be selected by pressing the
DAY/NIGHT button, for day and night (in each of the
f) °C/°F scale
To change the scale of degress of temperature, press the
and buttons simultaneously.
2.- Fan
The Fan is started up in a continuous manner by pressing the FAN button (independently of the operational state of the unit), the fan and air-flow symbols will be displayed on the thermostat display panel, the fan symbol steadily and the flow symbol flashing.
The FAN symbol will disappear when the button is pressed again and the fan will be automatically controlled in unison with the compressor or the electrical resistance heater (should this be installed).
SELECTED MODE (DISPLAYED FOR 5 SECONDS)
AMBIENT TEMPERATURE
HEATING SYMBOL
SELECTED MODE
COOLING SYMBOL
SELECTED MODE (DISPLAYED FOR 5 SECONDS)
AMBIENT TEMPERATURE
HEATING SYMBOL
DISPLAY PANEL WHEN THE SYSTEM HAS BEEN COMPLETELY SHUT DOWN
AIR-FLOW SYMBOL (FLASHING DISPLAY)
DISPLAY PANEL WHEN THE FAN IS CONTINUALLY OPERATIONAL
FAN SYMBOL (CONSTANTLY DISPLAYED)
Page 24
24
operational modes). When installing the thermostat the symbol will be displayed, indicating that the temperature selected is set for the day. By pressing the DAY/NIGHT button the symbol is displayed on the panel, indicating that the temperature selected will be set for the night. Every time that we press this button we alternate the established set temperatures, whether they be for the day or the night .
should be cleaned as frequently as necessary with a brush vacuum cleaner or detergent.
Graphic information
The display panel permanently provides us with information concerning: the ambient temperature, operational mode, day/night, and fan operation. To receive information concerning the set temperatures it is only necessary to press one of the temperature selection buttons once, and the established set temperature for the operational mode which is being displayed at that time will appear on the panel for 5 seconds.
Maintenance
Cleaning of filters
Keep coil's air filters in good condition. Check them at least every 15 days.
Cleaning outdoor coil
Dirt accumulation on outdoor coil should not be allowed. Coil
In cases of unrestricted discharge installations for an indoor unit intended for ducting, the outlet must be protected with a grill. Failure to fit this protection could result in damages being caused by the fan turbine.
Priming the dreinage siphon
To avoid problems with water from condensation we recommend that the drainage siphon be primed when starting up and before the beginning of each season so as to avoid, from the very beginning, the intake of air into this pipe.
Indoor unit discharge ducts
The indoor unit discharge, intended for ducts, is supplied without a protective grill. When maintenance work is being done this must be taken into account.
Check the outdoor unit periodically to see whether either the outlet or the inlet are blocked up with dirt or leaves, etc. The internal coil and other components of the outdoor unit must also be periodically cleaned. Contact your concessionary or maintenance service.
For safety reasons make sure you swich off the air-conditioner, and disconnect it from the mains before cleaning.
DAY
NIGHT
CAUTION
CAUTION
CAUTION
Page 25
25
Model A B C D E F G H I J K L M N O P Q S T U V
BCH-7 471 1200 1250 1156 78 376 290 302 80 362 35 86 262 376 550 214 436 214 362 154 154
BCH-10 549 1250 1300 1206 78 376 396 268 78 362 75 109 293 461 517 291 442 192 362 132 143
General dimensions mm
Note:
1-The solid line arrows indicate the standard air inlets and outlets. The
dotted line arrows show inlet and outlet arrangements that can be performed on the jobsite.
2-If a filter with rack is to be fitted in the air intake, refer to the accessory's
brochure for the dimensions.
BCH-7, 10
EF G H U
B
A
POQ
22 O.D. DRAIN CONNECTIONS
OPTIONAL OUTDOOR
AIR OUTLET
OPTIONAL INDOOR
AIR INTAKE
OPTIONAL OUTDOOR AIR INTAKE
OPTIONAL INDOOR AIR OUTLET
B
D
B
C
INDOOR
AIR OUTLET
INDOOR AIR
INTAKE
OUTDOOR
AIR INTAKE
OUTDOOR
AIR OUTLET
DETAIL "Z"
IF S N V
T
K
T
K
J
K
20
D.12 (4)
22
DETAIL "Z"
MINIMUM CLEARANCE 300
MINIMUM
CLEARANCE
500
M
L
OUTDOOR SIDE VIEW
INDOOR SIDE VIEW
ELECTRICAL CONNECTIONS
Page 26
26
Model A B C D E F G H I J K L M N O P Q S T U V
BCH-12 & 15 555 1440 1384 1492 78 476 412 315 78 430 39 25 345 546 652 324 464 192 430 159 148
BCH-20 727 1440 1384 1492 78 476 412 315 78 430 52 121 345 546 652 324 464 192 596 159 148
General dimensions mm
BCH- 12, 15 & 20
Note:
1-The solid line arrows indicate the standard air inlets and outlets. The
dotted line arrows show inlet and outlet arrangements that can be performed on the jobsite.
2-If a filter with rack is to be fitted in the air intake, refer to the accessory's
brochure for the dimensions.
EF G HU
B
POQ
22 O.D. DRAIN CONNECTIONS
OPTIONAL OUTDOOR
AIR INTAKE
OPTIONAL INDOOR
AIR OUTLET
B
D
C
B
INDOOR AIR
OUTLET
INDOOR AIR
INTAKE
OUTDOOR
AIR INTAKE
OUTDOOR
AIR OUTLET
DETAIL "Z"
IF
S
NV
T
K
T
K
J
K
MINIMUM CLEARANCE 300
MINIMUM
CLEARANCE
500
OPTIONAL
OUTDOOR AIR OUTLET
OPTIONAL
INDOOR AIR INTAKE
OUTDOOR SIDE VIEW
M
L
A
ELECTRICAL CONNECTIONS
28
D.12 (4)
DETAIL "Z"
20
INDOOR SIDE VIEW
Page 27
27
General dimensions mm
BCH - 25 & 30
Note:
1-Always use the six fixing points to assemble to unit. 2-The solid line arrows indicate the standard air inlets and outlets. The
dotted line arrows show inlet and outlet arrangements that can be performed on the jobsite.
GF
E
M
P
H
K
ELECTRICAL
CONNECTIONS
OPTIONAL INDOOR
AIR OUTLET
OPTIONAL OUTDOOR AIR INTAKE
B
INDOOR
AIR INTAKE
OUTDOOR
AIR OUTLET
INDOOR
AIR INTAKE
INDOOR
AIR OUTLET
DETAIL "Z"
123 L D 898 C
346
554
346
69
DETAIL "Z"
MINIMUM CLEARANCE 300
MINIMUM
CLEARANCE
300
820I
J
22 DIAM. INDOOR
DRAINAGE
AIR FILTER
23
O
A
25
D.12 (6)
30
INDOOR SIDE VIEW
69
640
N
I 820
515 36
883
35
OPTIONAL OUTDOOR AIR OUTLET
OUTDOOR SIDE VIEW
50
60
225
63
225
22 DIAM.
OUTDOOR
DRAINAGE
210
93
Model A B C D E F G H I J K L M N O P
BCH-25 1 750 1 700 81 233 442 315 133 1 650 870 1 690 1 750 315 667 348 1 145 93
BCH-30 2 150 2 100 130 499 648 400 138 2 050 890 1 710 1 770 400 732 368 1 495 132
Page 28
28
Wiring diagram
BCH - 7, 230.1.50
I-1310/j
INPUT Y
INPUT G
INPUT W
INPUT O
STANDBY FILTERS RESET
TEST
RESET FILTERS
JP19
JP20
JP21
NTC
2
5
3060901410
642
0
-2
-4
-5
-10
-15
-20
006791024
BCH/BCV-97/A
3
2
1
6 8
4
9
5
7
12
10
11
B4
LIQUIDO
LIQUID
B3
DESHIELO DEFROST
B2
DESCARGA DISCHARGE
B1
EXTERIOR OUT DOOR
BCH/AVO
24V AMBIENT
THERMOSTAT
OWYGR B
SWITCH
ROBWYG
AMBIENT
THERMOSTAT
240V
24V
60VA
220V00
125NN
23 N21
BB1
AIR FLOW CONTROL
NL
220V
240V
Cod. 6791003
2A
F1
3
2
1
6
8
4
9
5
7
12
10
11
K4
INTERNAL
HEATER
DUCT
HEATER
K5 K1 K15
4A
F2
B2B1
72B 73 74 75 76 77 78 79
*
L1 N
AIR FLOW CONTROL
**
230V, 1 ~, 50 Hz,
L1 N
Q 2
32 A
Q 1
30 m A
CROSS SECTION 4 mm
2
F14
MINIMUM SECTION 1.5 mm
2
1 mm
2
Cu
RECOMMENDED SECTION
WHEN AN ELECTRIC HEATER IS INSTALLED, FIT AN F14 AIR FLOW CONTROL
ATTENTION: PUT THE 230V. SWITCH IN THE POSITION CORRESPONDING TO THE NOMINAL VOLTAGE OF THE NERWORK
*
**
THE COMPONENTS INCLUDED IN THESE BOXES ARE NOT SUPPLIED BY THE MANUFACTURER.
Page 29
29
Wiring diagram
BCH - 10, 12, 15, 230.3.50 BCH - 10, 12, 15, 400.3.50
INPUT Y
INPUT G
INPUT W
INPUT O
STANDBY FILTERS RESET
TEST
RESET FILTERS
JP19
JP20
JP21
NTC
2
5
3060901410
642
0
-2
-4
-5
-10
-15
-20
006791024
BCH/BCV-97/A
3
2
1
6 8
4
9
5
7
12
10
11
B4
LIQUIDO
LIQUID
B3
DESHIELO DEFROST
B2
DESCARGA DISCHARGE
B1
EXTERIOR OUT DOOR
BCH/AVO
WHEN AN ELECTRIC HEATER IS INSTALLED, FIT AN F14 AIR FLOW CONTROL
ATTENTION: PUT THE 230V SWITCH IN THE POSITION CORRESPODING TO THE NOMINAL VOLTAGE OF THE NERWORK
*
**
AIR FLOW CONTROL
**
MODEL
Q2 (A)
SECTION B
mm
2
2.5 4 4
BCH-10 BCH-12 BCH-15
20 32 32
Q2 (A)
SECTION B
mm
2
4 6
6
32 40 40
400.3.50 230.3.50
I-1312/j
24V AMBIENT THERMOSTA T
SWITCH
L1 L3L2
OWYGR B
ROBWYG
AMBIENT
THERMOSTAT
240V
24V
60VA
220V00
125NN
23 N21
BB1
AIR FLOW CONTROL
NL
220V
240V
Cod. 6791003
2A
F1
3
2
1
6
8
4
9
5
7
12
10 11
N
B2B1
72B 73 74 75 76 77 78 79
4A
F2
K4
INTERNAL
HEATER
DUCT
HEATER
K5 K1 K15
*
Q 2
400V, 3 ~, 50 Hz,N,
Q 1
30 m A
L1L2 L3 N
CROSS SECTION B mm
2
F14
MINIMUM SECTION
1.5 mm
2
RECOMMENDED SECTION
1 mm
2
Cu
230V, 3 ~, 50 Hz,
ONLY UNIT
TO 400.3.50
THE COMPONENTS INCLUDED IN THESE BOXES ARE NOT SUPPLIED BY THE MANUFACTURER.
Page 30
30
Wiring diagram
BCH - 20, 230.3.50 BCH - 20, 400.3.50
24V AMBIENT THERMOSTA T
OWYGR B
SWITCH
ROBWYG
AMBIENT
THERMOSTAT
240V
24V
60VA
220V00
125NN
23 N21
BB1
AIR FLOW CONTROL
NL
220V
240V
Cod. 6791003
2A
F1
3
2
1
6
8
4
9
5
7
12
10
11
L1 L3L2 N
F4 F5
K3 K6K2
K4
INTERNAL
HEATER
DUCT
HEATER
K5 K1 K15
4A
F2
B2B1
72B 73 74 75 76 77 78 79
*
CROSS SECTION B mm
2
400V, 3 ~, 50 Hz,N,
Q 1
30 m A
L1 L2 L3
Q 2
N
AIR FLOW CONTROL
**
F7
MINIMUM SECTION
1.5 mm
2
SECCION ACONSEJADA
1 mm
2
Cu
ONLY UNIT
TO 400.3.50
230V, 3 ~, 50 Hz,
I-1307/j
INPUT Y
INPUT G
INPUT W
INPUT O
STANDBY FILTERS RESET
TEST
RESET FILTERS
JP19
JP20
JP21
NTC
2
5
3060901410
642
0
-2
-4
-5
-10
-15
-20
006791024
BCH/BCV-97/A
3
2
1
6 8
4
9
5
7
12
10
11
B4
LIQUIDO
LIQUID
B3
DESHIELO
DEFROST
B2
DESCARGA DISCHARGE
B1
EXTERIOR
OUT DOOR
BCH/AVO
WHEN AN ELECTRIC HEATER IS INSTALLED, FIT AN F14 AIR FLOW CONTROL
ATTENTION: PUT THE 230V. SWITCH IN THE POSITION CORRESPONDING TO THE NOMINAL VOLTAGE OF THE NERWORK
*
**
MODEL
Q2 (A)
SECTION B
BCH-20 32
4
Q2 (A)
SECTION B
mm
2
50 10
400.3.50 230.3.50
mm
2
THE COMPONENTS INCLUDED IN THESE BOXES ARE NOT SUPPLIED BY THE MANUFACTURER.
Page 31
31
Wiring diagram
BCH - 25 & 30, 230.3.50 BCH - 25 & 30, 400.3.50
24V AMBIENT THERMOSTA T
OWYGR B
SWITCH
ROBWYG
AMBIENT
THERMOSTAT
240V
24V
60VA
220V00
125NN
23 N21
BB1
AIR FLOW CONTROL
NL
220V
240V
Cod. 6791003
2A
F1
3
2
1
6
8
4
9
5
7
12
10 11
L1 L3L2 N
F3 F2
KM2
KM1
KM3
K4
INTERNAL
HEATER
DUCT
HEATER
K5 K1 K15
4A
F2
B2B1
72B 73 74 75 76 77 78 79
*
CROSS SECTION B mm
2
400V, 3 ~, 50 Hz,N,
Q 1
30 m A
L1 L2 L3
Q 2
N
AIR FLOW CONTROL
**
F7
MINIMUM SECTION
1.5 mm
2
RECOMMENDED SECTION
1 mm
2
Cu
ONLY UNIT TO 400.3.50
230V, 3 ~, 50 Hz,
I-1877/b
INPUT Y
INPUT G
INPUT W
INPUT O
STANDBY FILTERS RESET
TEST
RESET FILTERS
JP19
JP20
JP21
NTC
2
5
3060901410
642
0
-2
-4
-5
-10
-15
-20
006791024
BCH/BCV-97/A
3
2
1
6 8
4
9
5
7
12
10
11
B4
LIQUIDO
LIQUID
B3
DESHIELO
DEFROST
B2
DESCARGA DISCHARGE
B1
EXTERIOR OUT DOOR
BCH/AVO
WHEN AN ELECTRIC HEATER IS INSTALLED, FIT AN F7 AIR FLOW CONTROL
ATTENTION: PUT THE 230V. SWITCH IN THE POSITION CORRESPONDING TO THE NOMINAL VOLTAGE OF THE NERWORK
*
**
MODEL
Q2 (A)
SECTION B
BCH-25 32
40
6
10
Q2 (A)
SECTION B
mm
2
50 63
10 16
400.3.50 230.3.50
mm
2
BCH-30
THE COMPONENTS INCLUDED IN THESE BOXES ARE NOT SUPPLIED BY THE MANUFACTURER.
Page 32
32
Power diagram
BCH - 7, 230.1.50
IO:
M1:
M2:
M3:
R1:
R2:
I-1298/g
BCH-7, 230.1.50
SEE DIAGRAM
RC-10-220/15-220
230V, 1 , 50 Hz,N,
~
4 mm Cu
2
6/10 mm Cu
230 - 400V, 3 , 50 Hz,
L1
L2 L3
~
2
IO
R1
1
(4)
2
1
2
K12
3
4
5
6
K4
R2
Q6
32/50 A
L1
L2 L3
Q 5
30 m A
L1
L1
N
N
Q 1
30 m A
Q2
32 A
L1
L1
N
N
Q 3
30 m A
Q4
32 A
(01) (03) (04) (06)(02) (05) (07)
M1
1
2
3
4
(6)
L1 N
X1/...
4 mm
2
Cu.
K6
C1
1
2
M3
5
6
M
1 ~
K3
(13)
1
M2
M
1 ~
35
246
K2
(14)
F3
(8)
97 95
98 96
N
L1
(1)
(1)
(5)
THE COMPONENTS INCLUDED IN THESE BOXES
ARE NOT SUPPLIED BY THE MANUFACTURER.
THE COMPONENTS INCLUDED IN THESE BOXES ARE STANDARD
ACCESSORIES SUPPLIED BY THE MANUFACTURER.
JOBSITE
INSTALLATION
COMPRESSOR
INDOOR
FAN
OUTDOOR
FAN
INDOOR
HEATER
5 kW
DUCT ELECTRIC
HEATER
10/15 kW
Page 33
33
Power diagram
BCH - 10, 12, 15, 230.3.50
IO:
M1:
M2:
M3:
R1:
R2:
JOBSITE
INSTALLATION
COMPRESSOR
INDOOR
FAN
OUTDOOR
FAN
INDOOR
HEATER
10/15 kW
DUCT ELECTRIC
HEATER
10/15 kW
SEE DIAGRAM
RC-10-220/15-220
IO
(01) (03) (04) (06)(02) (05) (07)
1
2
M3
5
6
M
1 ~
K3
(13)
1
M2
M
1 ~
35
246
K2
(14)
F3
(8)
97 95
98 96
L3
L1
(1)
(1)
L1
L1
L3
L3
Q1
30 m A
Q2
L2
L2
M1
1
2
3
4
(6)
L1 L3
X1/...
B mm Cu.
2
K6
L2
5
6
230V,3 ~,50 Hz,
L1
L2 L3
1
2
K12
3
4
5
6
R2
Q6
10 kW-32A
15 kW-50A
L1
L2 L3
Q5
30 m A
10 kW-6
15 kW-10
mm Cu
2
L1
L2 L3
1
2
K4
3
4
5
6
R1
Q4
10 kW-32A
15 kW-50A
L1
L2 L3
Q3
30 m A
10 kW-6
15 kW-10
mm Cu
2
(4)
(5)
MODEL
Q2 (A)
SECTION B
mm
2
BCH-10
BCH-12
BCH-15
324040
4
6
6
I-1275/g
BCH-10,12,15, 230.3.50
THE COMPONENTS INCLUDED IN THESE BOXES
ARE NOT SUPPLIED BY THE MANUFACTURER.
THE COMPONENTS INCLUDED IN THESE BOXES ARE STANDARD
ACCESSORIES SUPPLIED BY THE MANUFACTURER.
Page 34
34
Power diagram
BCH - 10, 12, 15, 400.3.50
IO:
M1:
M2:
M3:
R1:
R2:
JOBSITE
INSTALLATION
COMPRESSOR
INDOOR
FAN
OUTDOOR
FAN
INDOOR
HEATER
10/15 kW
DUCT ELECTRIC
HEATER
10/15 kW
I-1274/g
BCH-10,12,15, 400.3.50
SEE DIAGRAM
RC-10-220/15-220
(01) (03) (04) (06)(02) (05) (07)
1
2
M3
5
6
M
1 ~
K3
(13)
1
M2
M
1 ~
35
246
K2
(14)
F3
(8)
97 95
98 96
N
L1
(1)
(1)
M1
1
2
3
4
(6)
L1 L3
X1/...
B mm Cu.
2
K6
L2
5
6
N
IO
L1
L1
L3
L3
Q1
30 m A
Q2
L2
L2
400V,3 ~ ,50Hz,N,
N
N
L1
L2 L3
1
2
K4
3
4
5
6
R1
Q4
10 kW-20A
15 kW-25A
L1
L2 L3
Q 3
30 mA
10 kW-2.5
15 kW-4
mm Cu
2
(4)
L1
L2 L3
1
2
K12
3
4
5
6
R2
Q6
10 kW-20A
15 kW-25A
L1
L2 L3
Q 5
30 mA
10 kW-2.5
15 kW-4
mm Cu
2
(5)
MODEL
Q2 (A)
SECTION B
mm
2
BCH-10
BCH-12
BCH-15
20
32
2.5
4
4
32
THE COMPONENTS INCLUDED IN THESE BOXES
ARE NOT SUPPLIED BY THE MANUFACTURER.
THE COMPONENTS INCLUDED IN THESE BOXES ARE STANDARD
ACCESSORIES SUPPLIED BY THE MANUFACTURER.
Page 35
35
Power diagram
BCH - 20, 230.3.50
IO:
M1:
M2:
M3:
R1:
R2:
JOBSITE
INSTALLATION
COMPRESSOR
INDOOR
FAN
OUTDOOR
FAN
INDOOR
HEATER
10/15 kW
DUCT ELECTRIC
HEATER
20/30 kW
I-1308/g
BCH-20, 230.3.50
SEE DIAGRAM
RC-20-220/30-220
(03) (04) (06)(05) (07)
L3
L1
(1)
(1)
230V,3 , 50 Hz,
~
IO
(01) (02)
L1
L1
L3
L3
Q1
30 m A
Q2
50 A
L2
L2
M1
1
2
3
4
(6)
L1 L3
X1/...
10 mm Cu.
2
K6
L2
5
6
M2
M
3
~
1L1
F4
(8)
13 21
14 22
OFF ON
3L2 5L3
K2
(14)
135
246
2L1 4L2 6L3
M3
M
3
~
1L1
F5
(15)
13 21
14 22
OFF ON
3L2 5L3
K3
(13)
135
246
2L1 4L2 6L3
10 kW-6
15 kW-10
mm Cu
2
L1
L2 L3
Q4
10 kW - 32 A
15 kW - 50 A
L1
L2 L3
Q 3
30 mA
K4
(4)
1
2
3
5
6 4
R1
10 kW-6
15 kW-10
mm Cu
2
10 kW-6
15 kW-10
mm Cu
2
L1
L2 L3
Q8
10 kW - 32A
15 kW - 50A
L1
L2 L3
Q 7
30 mA
K15
1
2
3
5
6 4
L1
L2 L3
L1
L2 L3
Q 5
30 mA
Q6
10 kW - 32 A
15 kW - 50 A
K12
(5)
1
2
3
5
6 4
R2
(5)
THE COMPONENTS INCLUDED IN THESE BOXES
ARE NOT SUPPLIED BY THE MANUFACTURER.
THE COMPONENTS INCLUDED IN THESE BOXES ARE STANDARD
ACCESSORIES SUPPLIED BY THE MANUFACTURER.
Page 36
36
Power diagram
BCH - 20, 400.3.50
IO:
M1:
M2:
M3:
R1:
R2:
JOBSITE
INSTALLATION
COMPRESSOR
INDOOR
FAN
OUTDOOR
FAN
INDOOR
HEATER
10/15 kW
DUCT ELECTRIC
HEATER
20/30 kW
I-1309/g
BCH-20, 400.3.50
RC-20-220/30-220
(03) (04) (06)(05) (07)
N
L1
(1)
(1)
400V,3 , 50 Hz,N,
~
IO
(01) (02)
L1
L1
L3
L3
Q1
30 m A
Q2
32 A
L2
L2
M1
1
2
3
4
(6)
L1 L3
X1/...
4 mm Cu.
2
K6
L2
5
6
M2
M
3
~
1L1
F4
(8)
13 21
14 22
OFF ON
3L2 5L3
K2
(14)
135
246
2L1 4L2 6L3
M3
M
3
~
1L1
F5
(15)
13 21
14 22
OFF ON
3L2 5L3
K3
(13)
135
246
2L1 4L2 6L3
10 kW - 2.5
15 kW - 4
mm Cu
2
L1
L2 L3
Q4
10 kW - 20 A
15 kW - 25 A
L1
L2 L3
Q3
30m A
K4
(4)
1
2
3
5
6 4
R1
L1
L2 L3
Q8
10 kW - 20A
15 kW - 25A
L1
L2 L3
Q7
30 m A
N
N
N
L1
L2 L3
L1
L2 L3
Q5
30m A
Q6
10 kW - 20 A
15 kW - 25 A
K15
1
2
3
5
6 4
K12
(5)
1
2
3
5
6 4
R2
(5)
10 kW - 2.5
15 kW - 4
mm Cu
2
10 kW - 2.5
15 kW - 4
mm Cu
2
SEE DIAGRAM
THE COMPONENTS INCLUDED IN THESE BOXES
ARE NOT SUPPLIED BY THE MANUFACTURER.
THE COMPONENTS INCLUDED IN THESE BOXES ARE STANDARD
ACCESSORIES SUPPLIED BY THE MANUFACTURER.
Page 37
37
Power diagram
BCH - 25 & 30, 230.3.50
IO:
M1:
M2:
M3:
R1:
JOBSITE
INSTALLATION
COMPRESSOR
INDOOR
FAN
OUTDOOR
FAN
DUCT ELECTRIC
HEATER
20/30 kW
I-1873/b
BCH-25,30, 230.3.50
SEE DIAGRAM
RC-20-220/30-220
(03) (04) (06) (07)
L3
L1
(1)
(1)
230V,3 , 50 Hz,
~
IO
(01) (02)
L1
L1
L3
L3
Q1
30 m A
Q2
L2
L2
M1
1
2
3
4
(6)
L1 L3
X1/...
B mm
2
Cu.
KM1
L2
5
6
M2
M
3
~
1
F2
(8)
13 21
14 22
OFF ON
35
KM2
(14)
135
246
246
M3
M
3
~
1
F3
(15)
13 21
14 22
OFF ON
35
KM3
(13)
135
246
246
10 kW-6
15 kW-10
mm Cu
2
10 kW-6
15 kW-10
mm Cu
2
L1
L2 L3
Q8
10 kW - 32A
15 kW - 50A
L1
L2 L3
Q 7
30 mA
K15
1
2
3
5
6 4
L1
L2 L3
L1
L2 L3
Q 5
30 mA
Q6
10 kW - 32 A
15 kW - 50 A
K12
(5)
1
2
3
5
6 4
R1
(5)
MODEL
Q2 (A)
SECTION B
BCH-25
50
63
10
16
mm
2
BCH-30
THE COMPONENTS INCLUDED IN THESE BOXES
ARE NOT SUPPLIED BY THE MANUFACTURER.
THE COMPONENTS INCLUDED IN THESE BOXES ARE STANDARD
ACCESSORIES SUPPLIED BY THE MANUFACTURER.
Page 38
38
Power diagram
BCH - 25 & 30, 400.3.50
IO:
M1:
M2:
M3:
R1:
JOBSITE
INSTALLATION
COMPRESSOR
INDOOR
FAN
OUTDOOR
FAN
DUCT ELECTRIC
HEATER
20/30 kW
I-1875/c
BCH-25,30, 400.3.50
RC-20-220/30-220
(03) (04) (06) (07)
N
L1
(1)
(1)
400V,3 , 50 Hz,N,
~
IO
(01) (02)
L1
L1
L3
L3
Q1
30 m A
Q2
L2
L2
M1
1
2
3
4
(6)
L1 L3
X1/...
B mm
2
Cu.
KM1
L2
5
6
M2
M
3
~
1
F2
(8)
13 21
14 22
OFF ON
35
KM2
(14)
135
246
246
M3
M
3
~
1
F3
(15)
13 21
14 22
OFF ON
35
KM3
(13)
135
246
246
L1
L2 L3
Q8
10 kW - 20A
15 kW - 25A
L1
L2 L3
Q7
30 m A
N
N
N
L1
L2 L3
L1
L2 L3
Q5
30m A
Q6
10 kW - 20 A
15 kW - 25 A
K15
1
2
3
5
6
4
K12
(5)
1
2
3
5
6 4
(5)
10 kW - 2.5
15 kW - 4
mm Cu
2
10 kW - 2.5
15 kW - 4
mm Cu
2
SEE DIAGRAM
R1
MODEL Q2 (A)
SECTION B
BCH-25
32
40
6
10
mm
2
BCH-30
THE COMPONENTS INCLUDED IN THESE BOXES
ARE NOT SUPPLIED BY THE MANUFACTURER.
THE COMPONENTS INCLUDED IN THESE BOXES ARE STANDARD
ACCESSORIES SUPPLIED BY THE MANUFACTURER.
Page 39
39
Control diagram
BCH - 7, 10, 12, 15, 230.3.50, 400.3.50
A3:
B1:
B2:
B3:
F3:
F5:
F6:
F14:
M1:
M2:
R1:
R2:
R3:
R4:
RD:
ELECTRONIC
PLAQUE
OUTDOOR
SENSOR
DISCHARGE
SENSOR
LIQUID
SENSOR
INDOOR FAN
THERMAL
RELAY
AUTOMATIC
PRESSURE
CUT-OUT 28 bar
24V AMBIENT
THERMOSTAT
AIR FLOW
RATE
CONTROL
COMPRESSOR
INDOOR FAN
MOTOR
INDOOR
HEATER
DUCT
HEATER
DRAIN PAN
HEATER
CASING
HEATER
DEFROSTING
RELAY
I-1313/e
BCH-7,10,12,15
230.3.50
400.3.50
WHEN AN ELECTRIC HEATER IS INSTALLED,
FIT AN F14 AIR FLOW CONTROL
*
Y1
A3
F2
4A
B
B1 72 BB1
K2
(14)
B2
13
14
K14
75
3
6
K5
(16)
K1
(14)
3
4
76
K3
74 73
K1
B
P
11 11
9 9
6 6
79 78
O R
B Y
W
G
O R
B Y
W
G
F6
B
K2
77
1
2
3
4
5
6
13 14
(02)
(10)
F3
95
96
(02)
10 10
2 2
K5
(16)
45
78
K5
(16)
K4a
12 12
1 1
7 7
3 3
4 4
8 8
K5
1
2
3
4
5
6
13 14
(03)
1
2
3
4
5
6
13 14
(01)
1
2
3
4
5
6
13 14
(06)
1
2
3
4
5
6
13 14
(05)
(2)
44
R4
K12
5
K 4
5
K 6
T1
63 VA
L
F1
2A
220 V
240 V
S1
L1
K4a
(9)
1
2
K14
(11)
1
2
K1
(14)
1
2
(L3)
N N
N 1 21
23 25
N
71R371
14
13
K4
(4)
17151491110876543 12 13
B1
B2
B3
16
F5
230V.1.50 Hz
21
A4
F14
24 V
*
R1 R2 M1
M3
M2
RD
THE COMPONENTS INCLUDED IN THESE BOXES
ARE NOT SUPPLIED BY THE MANUFACTURER.
THE COMPONENTS INCLUDED IN THESE BOXES ARE STANDARD
ACCESSORIES SUPPLIED BY THE MANUFACTURER.
Page 40
40
Control diagram
BCH - 20, 230.3.50, 400.3.50
A1:
B1:
B2:
B3:
F3:
F4:
F5:
F6:
F7:
M1:
M2:
R1:
R2:
R3:
R4:
RD:
ELECTRONIC
PLAQUE
OUTDOOR
SENSOR
DISCHARGE
SENSOR
LIQUID
SENSOR
AUTOMATIC
PRESSURE
CUT-OUT 28 bar
INDOOR FAN
THERMAL
RELAY
OUTDOOR
FAN
THERMAL
24V AMBIENT
THERMOSTAT
AIR FLOW
RATE
CONTROL
COMPRESSOR
INDOOR FAN
MOTOR
INDOOR
HEATER
DUCT
HEATER
DRAIN PAN
HEATER
CASING
HEATER
DEFROSTING
RELAY
I-1301/e
BCH-20
230.3.50
400.3.50
WHEN AN ELECTRIC HEATER IS INSTALLED,
FIT AN F7 AIR FLOW CONTROL
*
Y1
A1
F2
4A
B
B1 72 BB1
K2
(14)
B2
13
14
K14
75
3
6
K5
(16)
K1
(14)
3
4
76
K3
74
K1
11 11
9 9
6 6
79 78
O
R
B Y
W
G
O R
B Y
W
G
F6
B
K2
77
1
2
3
4
5
6
13 14
(02)
(10)
F4
13
14
(02)
10 10
2 2
K5
(16)
45
78
K5
(16)
K4a
12 12
1 1
7 7
3 3
4 4
8 8
K5
1
2
3
4
5
6
13 14
(03)
1
2
3
4
5
6
13 14
(01)
1
2
3
4
5
6
13 14
(05)
(2)
24 V
T1
63 VA
L
F1
2A
220 V
240 V
S1
L1
K4a
(9)
1
2
K14
(12)
1
2
K1
(14)
1
2
(L3)
N N
N 1 N
R3
14
13
K4
(4)
17151491110876543 12 13
B1
B2
B3
A2
A1
16
73
B
P
A1
A2
F5
(03)
12
F3
230V.1.50 Hz
A2
A1
13
14
A2
*
F7
1
2
3
4
5
6
13 14
(07)
25
K12K4
21
23
A2
A1
A2
A1
K15
A2
A1
13
14
K12
X3/5 X2/5
X2/7
K6
A2
A1
X3/4
X2/4
RD
R4
R1 R2 M1
M3
M2
THE COMPONENTS INCLUDED IN THESE BOXES
ARE NOT SUPPLIED BY THE MANUFACTURER.
THE COMPONENTS INCLUDED IN THESE BOXES ARE STANDARD
ACCESSORIES SUPPLIED BY THE MANUFACTURER.
Page 41
41
Control diagram
BCH - 25 & 30, 230.3.50, 400.3.50
A1:
B1:
B2:
B3:
F2:
F3:
F5:
F6:
F7:
M1:
M2:
M3:
R2:
R3:
R4:
RD:
ELECTRONIC
PLAQUE
OUTDOOR
SENSOR
DISCHARGE
SENSOR
LIQUID
SENSOR
INDOOR FAN
THEMAL
RELAY
OUTDOOR
FAN THERMAL
RELAY
AUTOMATIC
PRESSURE
CUT-OUT28 bar
24V AMBIENT
THERMOSTAT
AIR FLOW
RATE
CONTROL
COMPRESSOR
INDOOR FAN
MOTOR
OUTDOOR
FAN
DUCT
HEATER
DRAIN PAN
HEATER
CASING
HEATER
DEFROSTING
RELAY
I-1876/a
BCH-25,30
230.3.50
400.3.50
WHEN AN ELECTRIC HEATER IS INSTALLED,
FIT AN F7 AIR FLOW CONTROL
*
Y1
A1
F2
4A
B
B1 72 BB1
KM2
(14)
B2
13
14
K14
75
3
6
K5
(16)
K1
(14)
3
4
76
KM3
74
K1
11 11
9 9
6 6
79 78
O R
B Y
W
G
O R
B Y
W
G
F6
B
KM2
77
1
2
3
4
5
6
13 14
(02)
(10)
F2
13
14
(02)
10 10
2 2
K5
(16)
45
78
K5
(16)
K4a
12 12
1 1
7 7
3 3
4 4
8 8
K5
1
2
3
4
5
6
13 14
(03)
1
2
3
4
5
6
13 14
(01)
1
2
3
4
5
6
13 14
(06)
(2)
24 V
T1
63 VA
L
F1
2A
220 V
240 V
S1
L1
K4a
(9)
1
2
K14
(12)
1
2
K1
(14)
1
2
(L3)
N N
N 1 N
R3
14
13
K12
(4)
17151491110876543 12 13
B1
B2
B3
A2
A1
16
73
B
P
A1
A2
F3
(03)
12
F5
230V.1.50 Hz
A2
A1
13
14
A2
*
F7
1
2
3
4
5
6
13 14
(07)
25
K15K12
21
23
A2
A1
A2
A1
X3/5 X2/5
X2/7
KM1
A2
A1
X3/4
X2/4
RD
R4
R1 R2 M1
M3
M2
K12
13
14
THE COMPONENTS INCLUDED IN THESE BOXES
ARE NOT SUPPLIED BY THE MANUFACTURER.
THE COMPONENTS INCLUDED IN THESE BOXES ARE STANDARD
ACCESSORIES SUPPLIED BY THE MANUFACTURER.
Page 42
42
Optional accessories
Filter rack with filter for
BCH-7, 10, 12, 15 & 20
Indoor electric heater RH
for BCH-7, 10, 12, 15 & 20
Duct electric heater RC -220
for BCH-7, 10, 12, 15, 20, 25 & 30
Air filter for BCH-7, 10, 12, 15 & 20,
(the 25 and 30 units are supplied with a
filter installed)
Page 43
43
BCH -12, 15 & 20
482
528
174
434
480
490
540
220
Due to the shape of the filter rack the access cover to the filter can be placed on any of the four sides of the rack or duct. When designing the air ducts consideration should be given to the fact that the use of this accessory, always implies a 90° rotation of the dimensions of the unit's air inlet port, as shown in the diagram below.
Positions and general dimensions mm
Filter rack with filter
Designed for installation in the air intakes of either the indoor or outdoor fans (only for the indoor one in the case of BCH-
20). The incorporated filter is of the cleanable type, with the filter mat made of open cell polyurethane foam.
Note: With the BCH-20 unit this accessory can be connected only in the indoor air return.
Filters pressure drop (mm WG)
Height A
Width B
Depth C
D
E
Height
Width
Depth
BCH -7 & 10
403
419
164
364
380
413
430
210
Model
Air inlet dimensions
Filter rack dimensions
8.0
10.3
13.0
16.0
19.6
22.5
26.4
29.4
0.82
1.06
1.35
1.65
2.00
2.30
2.70
3.00
Flow rate
m3/h
1 300 1 500
2 000 2 500
3 000
3 500 4 000
4 500 5 000
5 500 6 000
BCH -7 & 10
Pa
0.64
0.80
1.20
1.60
2.10
2.60
3.20
Pa
BCH -12, 15 & 20
-
-
-
-
--
-
-
--
-
-
-
-
mm WG mm WG
6.2
7.8
11.7
15.6
20.5
25.4
31.3
Shipping dimensions
E
D
E
D
A
C
B
FACE
X
FACE
Y
E
D
FACE
Y
FACE
X
E
D
FACEXFACE
Y
E
D
FACE
Y
FACE
X
C
A
B
Page 44
44
Height Width Depth Height Width Depth
356 370 100 375 450 110
Air filter
Of the cleanable type, with open cell polyurethane foam filter mat.
Can be adapted to either the evaporator or condenser side. Once attached the filter will exceed the conditoner's outer dimensions by 100 mm.
General dimensions mm
426 470 100 445 550 110
Model
BCH -7 & 10 BCH -12, 15 & 20
Shipping dimensions
Filter dimensions
A B C
Note: With the BCH-20 unit this accessory can be connected only in the indoor air return.
1 300
1 500
2 000
2 500
3 000
3 500
4 000
4 500
5 000
5 500
6 000
-
BCH -7 & 10 BCH -12, 15 & 20
Flow rate m3/h
mm WG
Pa mm WG
Pa
0.82
1.06
1.35
1.65
2.00
2.30
2.70
3.00
8.0
10.3
13.0
16.0
19.6
22.5
26.4
29.4
-
-
-
-
-
-
-
-
-
-
-
-
-
Filters pressure drop (mm WG)
0.64
0.80
1.20
1.60
2.10
2.60
3.20
6.20
7.80
11.70
15.60
20.50
25.40
31.30
A
C
B
Page 45
45
10
26/15
2
370 x 510 x 140
3.1
3.4
Indoor electric heaters RH
They are electric resistances made of air exposed wire elements and include the following components: Electric resistances of the air exposed wires type with chrome-nickel wires. High reliability contactors with 220 V coil. Safety thermal protector that disconnects control circuit when sensing an abnormally high temperature. Fan control to prevent the resistance from operating if the fan
has not been switched on. Star-triangle connection terminal strip for 230.3.50 &
400.3.50. Quick connector for the control wiring between the heater ans the air conditioner.
Attention:
A flow rate control should be installed together with every electric heater, to prevent the heater from operating if the fan has not been switched on.
General dimensions mm
15
39/23
2
370 x 510 x 140
3.8
4.2
kW
V.ph.Hz
A
mm WG
mm
kg
kg
BCH-7,10 BCH-7,10,12,15,20 BCH-10,12,15,20
For installation in heat pump size
Power
Power supply
Consumption
Pressure with nominal flow rate
Shipping dimensions
Nett weight
Gross weight
RH - 5.1
RH - 5.3 RH - 103 RH - 15.3
Model
BCH-7
5
230.1.50
22
1
370 x 510 x 140
2.3
2.7
5
13/7.5
1
370 x 510 x 140
2.3
2.7
Characteristics
230.3.50 or 400.3.50
70
85
410
495
123
350
310
Page 46
46
Duct electric heaters RC-220
For installation in the indoor fan outlet. Its intended function is to operate as an emergency heater. The charge loss calculated for these heaters in any functioning state is 1 mm WG
Attention:
A flow rate control should be installed together with every electric heater, to prevent the heater from operating if the fan has not been switched on.
kW
10 15 20 30
Nominal power
Resistance model
RC-10 - 220 RC-15 - 220 RC-20 - 220 RC-30 - 220
10, 15, 20 30
Resistance size
ABCDEFGH
582 562 330 408 376 345 542 321 823 803 435 517 482 451 783 351
General dimensions mm
Note: For more detailed information see the brochure for this accessory.
All data subject to change without notice.
Note: To connect electric heaters, see the wiring diagrams of each BCH.
PERFORATED SHEET COVER FOR FUNCTION BOX
104
187
31
C
23 DIAM. POWER CONNECTION BORINGS
CONNECTIONS BOX CAN BE MOUNTED AT JOBSITE ON THE LEFTSIDE
CONTROL LINES PLUG
65
30
33
1800 mm FLEXIBLE PLASTIC CONTROL LINES
D
H
G
E
F
A
B
Page 47