1. Ensure mains supply is switched off before commencing work.
3. Ensure the area above the fitting is free from obstacle pipes cable tray etc.
4. Connect plug to AC supply
5. Ensure the connections going to and from the driver are secure.
6. Place connector, drivers and cable into the ceiling void.
7. Offer luminaire up to the ceiling void and manoeuvre into final position similar to standard ceiling tile.
8.This product has no user serviceable parts. If any part is damaged, disconnect from mains and discontinue use.
Page 1
The Installation must be carried out by an electrician
INSTRUCTION MANUAL
PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES. ! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or use of this product, consult a competent electrician Note: Product technical information and specification may change over time without prior notification. For the latest technical information please visit our web site www.ledgrouprobus.com.au
LED Group ROBUS Australia 9/210 Queensport Road North Tel: +61 73893 1488 Murarrie Fax: +61 73112 1927 QLD 4172 Email: purchases@ledgrouprobus.com.au Australia Website: www.ledgrouprobus.com.au
Model No. Voltage: Power: Lumen: CCT: CRI: Beam Angle: PF: Ta Range: IP Rating: IK Rating: Safety Class: Dimensions: Depth: Weight: Warranty: Installation:
Complete with flex and AU plug Suitable for mounting on normally flammable surface Minimum distance from illuminated object is 0.5 metre Driver must never be “hot-plugged” or connected to the fitting when live. Doing this may damage the fitting and will void the warranty. Complies with EN 60598-1, EN 60598-2-2, IEC 62471-2, IEC 62778, IEC 62493, IEC 61347-1, 61347-2-13
R1230LEDCW-01 220-240V~50/60Hz 30W 2800lm 4000K 80 110
o
0.9
-20°C < ta < +45°C 20 06 Class II for the driver 295mm X 1195mm 9mm
3.8Kg 5 year Recessed mounted, Box mounted, Suspended
R1230LEDDW-01 220-240V~50/60Hz 30W 3150lm 5000K 80 110
o
0.9
-20°C < ta < +45°C 20 06 Class II for the driver 295mm X 1195mm 9mm
3.8Kg 5 year Recessed mounted, Box mounted, Suspended
Specifications
Installation
ISO 9001:2008
QUAL IT Y ASSU RE D CO MPANY
Warning:
Luminaire marked as NON-IC according to ASNZS60598-2.2. Not suitable for use on residential properties. DO NOT COVER OR ABUT. Any insulation material must be positioned at a minimum distance of 100 mm from the fitting.
Caution:
Recessed Luminaires may pose an increased risk of fire or property damage if not installed according to the instructions provided.
Safety Instructions
Luminaires not suitable for covering with thermally insulating material.
Joist
Driver
SCB
HCB
MIC
SCI
DANGER - RISK OF FIRE
- Shall not be installed in residential premises
SCI = 100mm MIC = 100mm SCB = 50mm HCB = 25mm
1195mm
Remove 300 x 1200 tile from ceiling.
295mm
9mm
Page 2
1 2
3 4
5
ISO 9001:2008
QUAL IT Y ASSU RE D CO MPANY
The Installation must be carried out by an electrician
LED Group ROBUS Australia 9/210 Queensport Road North Tel: +61 73893 1488 Murarrie Fax: +61 73112 1927 QLD 4172 Email: purchases@ledgrouprobus.com.au Australia Website: www.ledgrouprobus.com.au
Installation diagram
2m
580mm
400mm
Loading...