INSTRUCTION MANUAL
10W SMD LED RETROFIT TRAY
MICROWAVE SENSOR
R100LEDRETS
PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.
! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or
use of this product, consult a competent electrician
Note:
Product technical information and specification may change over time without prior notification
For the latest technical information please visit our web site www.ledgrouprobus.com or robusdirect.com
Specifications
Model No: R100LEDRETS
Voltage: 220-240V~50/60Hz
Power: 10W
Lumen: 900lm
CCT: 4000K
Beam Angle: 110°
CRI: 80
PF: 0.75
Ta Range: -10°C ~ +30°C
Safety Class: Class I
Detection Range: Max.Ø12m range,
Mounting Height: Max 3m
Delay Time: Adjustable time delay 5
seconds ~ 20minutes
Sensor Load: 100W, (Max. 9 fittings)
Diameter: Ø254mm
Depth: 38mm
Weight: 0.63kg
Warranty: 5 Years
Suitable for mounting on a normally flammable surface
This fitting is not suitable for installation where ambient air
temperature is above 30°C
Light output will typically be reduced by 25% when installed
in a fitting with opaque diffuser (e.g. ROBUS 2D housing).
Installation
1. Ensure mains supply is switched off before commencing work
2. Installation instructions as per existing conventional
fitting
3. Remove existing conventional tray
4. Ensure that there is sufficient room in the fitting
housing for the R100LEDRETS
5. Connect supply cables to the fitting terminals, connect
Brown/ Live to Lin, Blue/Neutral to N, Green /Yellow to
Earth and Brown/ Live out to Lout (if required).
Note: It is not possible to control more than 100W of LED
load or 9 additional fittings. It is not possible to have more
than one fitting with microwave sensor on a circuit (no parallel
sensor to sensor wiring)
6. Attach LED tray to fitting base using existing mounting
posts and screws. Ensure that the tray is secure.
Walk testing can then be carried out to determine detection
area with slow walking pace. When the sensor detects
movement, the load will be switched on for the preset time.
For the walk test set detection range to 100 or 50 or 10%, set
delay time to 5s and disable daylight sensor. When finished,
set controls to desired levels.
Note: Once sensor has been triggered, subsequent detection
restarts timing period from beginning, so light stays on until
set time elapses after last triggering
Seting sensor table
1:on, 0:off
Detection range
S1 S2
1
I
II
III
1
0
0 0
100%
50%
1
10%
Delay time
II
III
IV
V
VI
S3
1I
0
1
0
1
0
S4 S5
1
1
1
1
0
1
0
1
1
0
0
0
5s
30s
180s
300s
15min
20min
Daylight sensor
S6
I
II
III
IV
V
S7 S8
1 1 1 5Lux
0 1 1
1 0 1
0 1 0
0 0 0
10Lux
20Lux
30Lux
Disable
Information for the Product user:
1. Please note the requirement to dispose of Waste Electrical & Electronic Equipment separately from household waste (WEEE marked with
crossed out wheelie bin symbol).
2. Please consider your role in contributing to re-use and recycling by returning this product at end of life to a collection centre for waste electrical
equipment or a Civic Amenity site, or to a retail outlet from which you are purchasing a replacement.
3. This equipment may contain substances that are hazardous to health and the environment if disposed of carelessly. It is important that it is
separated from normal household waste and recycled in the WEEE chain
4. The “crossed out wheelie bin symbol” on a product indicates this equipment must not be disposed of in normal household waste, but should be
disposed of according to local WEEE regulations
The Installation must be carried out by an electrician
LED Group
Western Retail Park Tel: +353 1 7099000
Nangor Road Fax: +353 1 7099060
Dublin 12 Email: info@led.ie
Ireland Website: www.led.ie
Issue 1 280415
ISO 9001:2008
QUAL IT Y ASSU RE D CO MPANY
1

Installation diagram
Ø254mm
1
3
2
out in
4
L L N
The Installation must be carried out by an electrician
LED Group
Western Retail Park Tel: +353 1 7099000
Nangor Road Fax: +353 1 7099060
Dublin 12 Email: info@led.ie
Ireland Website: www.led.ie
5
6
ISO 9001:2008
QUAL IT Y ASSU RE D CO MPANY
2