Robur E 42, E 72, E 52, E 43, E 32 Installation, Operation And Maintanance

Page 1
Page 2
Page 3
INDEX
SECTION 1 GENERAL SECTION..................................................................................................2
1.1 GENERAL WARNINGS......................................................................................................2
1.2 OVERVIEW OF OPERATION OF THE APPLIANCE.........................................................3
1.4 DIMENSIONS.....................................................................................................................6
SECTION 2 FOR THE USER............................................................................................................7
2.1 SWITCHING THE APPLIANCE ON AND OFF ..................................................................7
2.2 MAINTENANCE..................................................................................................................8
2.3 ASSISTANCE.....................................................................................................................9
SECTION 3 FOR THE INSTALLATION TECHNICIAN............................................................10
3.1 BUILD CHARACTERISTICS..............................................................................................10
3.2 CONTROL AND SAFETY COMPONENTS........................................................................10
3.3 INSTALLATION ..................................................................................................................11
3.3.1 GENERAL NORMS FOR INSTALLATION OF THE APPLIANCE.....................................11
3.3.2 ELECTRICAL CONNECTIONS..........................................................................................12
3.3.3 SIZING AND INSTALLATION OF COMBUSTION AIR AND EXHAUST GAS PIPES.......14
3.3.4 WALL INSTALLATION .......................................................................................................18
3.3.5 PROCEDURE FOR CHECKING & ADJUSTING CALIBRATION OF THE
NOVAMIX VALVE SIT 822.................................................................................................19
3.3.6 GAS CHANGE....................................................................................................................21
3.3.7 FUNCTIONAL WIRING DIAGRAM.....................................................................................22
3.3.8 ASSEMBLY WIRING DIAGRAM........................................................................................23
3.3.9 WIRING DIAGRAMS FOR THE INSTALLATION OF SEVERAL HEATERS.....................24
3.4 SERVICE............................................................................................................................25
3.4.1 POSSIBLE OPERATING ANOMALIES.............................................................................. 25
26
3.5 LIST OF ACCESSORIES...................................................................................................27
3.5.1 CONTROL UNITS...............................................................................................................27
3.5.2 MOUNTING BRACKETS....................................................................................................28
3.5.3 OTHER ACCESSORIES....................................................................................................29
Please read the warnings contained in this manual; they give important instructions regarding safe installation, operation and maintenance of the appliance. Keep this manual safe for all further consultation. The manufacturer may not be held responsible for any damage arising from improper, incorrect or unreasonable use of the appliance.
NOTE
Page 4
2 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
1 GENERAL SECTION
1.1 GENERAL WARNINGS
This manual forms an integral and essential part of the product and must be delivered to the u s er as such. This appliance must be used only for the purposes for which it has been expressly designed. All other uses
are considered inappropriate and therefore dangerous. The manufacturer does not accept any contractual or extracontractual liability for damage caused by errors in
installation or use and in any case by failure to observe the instructions supplied by the manufacturer. Do not obstruct the inlet vent of the fan or the outlet grille. In the case of failure and/or poor operation of the appliance, deactivate it (disconnect the power supply and
close the gas valve), and refrain from any attempt to repair or intervene directly upon the appliance. Contact only professionally qualified personnel. Professionally qualified personnel means personnel that have specific technical expertise in the sector of
heating plant components for civil use. In any case the user may obtain all necessary information by
contacting ROBUR S.p.A.’s Customer Service Department (tel. 035/888111).
Any product repairs must only be carried out by a Technical Assistance Centre authorised by the manufacturer, and using only genuine parts.
Failure to observe the instructions above may compromise the safety of the appliance. To guarantee the efficiency and correct operation of the appliance it is essential to have annual maintenance
carried out by professionally qualified personnel, observing the manufacturer’s instructions. If the appliance is sold or transferred to a different owner, ensure that this manual accompanies the appliance
so that so that it may be consulted by the new owner and/or installation technician.
Have professionally qualified personnel check that:
the electricity and gas supply network data correspond to the data on the plate
the exhaust air duct and combustion air intake are functioning correctly
combustion air is supplied and exhaust fumes are discharged correctly, in accordance with current
norms
the fuel supply piping is correctly sealed internally and externally
the rate of fuel supply is adjusted in accordance with the power demanded by the heater
the appliance is supplied with the type of fuel for which it is designed
the fuel supply pressure is within the ranges indicated on the data plate
the fuel supply plant is sized for the flow required by the heater and that it is equipped with all the safety
and control devices required by current norms
Do not use gas pipes to earth electrical appliances. Do not leave the heater connected to the power supply unnecessarily when it is not used for a long period of
time, and close the gas valve.
do not use electrical switches, telephones or any other object or device that can cause sparks
open doors and windows in order to create an air current to ventilate the room
close the gas valves
contact professionally qualified personnel for assistance
IF YOU SMELL GAS …
BEFORE STARTING THE APPLIANCE
Page 5
Installation, Operation and Maintenance Manual– Ed.07/2005 3
EVOLUZIONE series natural gas/LPG heaters
1.2 OVERVIEW OF OPERATION OF THE APPLIANCE
The warm air heaters in the Evoluzione range are independent heating appliances of the sealed circuit and forced draught type.
They have been designed to be installed inside the room to be heated. They may be set up to run on natural gas (G20) and L.P.G. (G30/G31) (the appliance belongs to category
II
2H3B/P
in accordance with the EN 1020 norm).
The combustion circuit is sealed off from the environment to be heated and complies with the requirements of norm EN 1020 for type C appliances: intake of combustion air and outlet of exhaust gases occur outside and are ensured by the operation of a blower which is located in the combustion circuit. The appliances are approved also as type B appliances for installations where combustion air intake is permitted directly from the room to be heated.
The operation of the heater is controlled by an ambient thermostat (not supplied as standard). When the thermostat is activated, the electronic control unit, after a pre-wash time of about 30 seconds, ignites the burner.
An electrode detects when ignition has occurred. If there is no flame, the electronic control unit halts operation of the appliance.
A green ON light located on the right-hand side of the appliance indicates that ignition of the burner has occurred (see item 5, Figure 2).
The combustion products pass through the heat exchangers internally. The heat exchangers receive the current of air produced by the helicoidal fan, thus introducing warm air into the room.
The direction of the airflow can be adjusted up or down and/or from side to side by applying on the inlet grille the (optional) adjustable fins (see “List of accessories” on page 27).
The helicoidal fan starts automatically only when it receives the command from the ventilation thermostat, that is, only when the exchangers are warm, in order to prevent cold air from being introduced into the room. Likewise, it stops when the exchangers are cold.
If the heat exchangers should overheat, because of abnormal operation, a limit thermostat is fitted which, if required, cuts off power to the gas valve, which in turn cuts off the flow of fuel and makes the burner switch off.
Resetting the limit thermostat is an operation for professionally qualified personnel only, which restores operation of the appliance after having identified the cause of overheating.
Upstream from the burner, a blower ensures the correct air-gas mixture and the forced expulsion to the outside of the exhaust fumes deriving from combustion.
If the inlet or exhaust pipes are obstructed, or if the blower is operating inefficiently, the differential “air-gas valve” control system interrupts the flow of combustion air to the burner.
The diagram in Figure 1 summarises winter operation of the heater. The heating output and ventilation of the Evoluzione warm air heater are modulating: they can be reduced by
approximately 20% (see “TECHNICAL DATA” on page 5). Operation on reduced power and ventilation allow ambient temperature to be kept constant, reducing gas consumption and further lowering noise emissions into the environment. Operation with automatic or manual modulation depends on the type of control units chosen (for further information, see the paragraph “Other accessories” on page 29).
In the summer period, it is possible to operate the fan only, producing a pleasant movement of indoor air (for further information see Section “For the User”, paragraph entitled “Summer”).
NOTE
Page 6
4 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
Figure 1 – DIAGRAM FOR WINTER OPERATION
Ambient thermostat
closes contact
Blower switches on
After 30 seconds of pre-
wash the electronic
control unit opens the
valve: the green
operation light and the
blower switch on
The detector electrode
determines whether
there is a flame
The combustion
products pass through
the exchangers
internally
The blower ensures
that combustion
products are forcibly
expelled
The differential “air-
gas” valve control system for combustion air flow checks that the
blower is functioning
correctly
When the exchangers
are hot, the fan,
controlled by the
ventilation thermostat,
comes on
The flow of air
produced by the fan
strikes the exchangers
externally and is
heated
Have the exchangers
overheated?
The heater works until
the ambient
temperature is reached
The limit thermostat
interrupts the operation
of the burner
Identify cause of
stoppage and reset
heate
r
Arrest
YES
NO
NO
YES
Page 7
Installation, Operation and Maintenance Manual– Ed.07/2005 5
EVOLUZIONE series natural gas/LPG heaters
1.3 TECHNICAL DATA
MODEL U.M. E 32 E 42 E 43 E 52 E 72
CATEGORY OF APPLIANCE II
2H3B/P
TYPE OF APPLIANCE C13 - C
33
- B
23
- C53 - C
63
GAS TYPE NATURAL GAS - L.P.G. NOMINAL HEAT INPUT (AT Ist SPEED) kW 26 34.75 37.15 48.35 69 kcal/h 22360 29890 31950 41580 59340 NOMINAL HEAT OUTPUT (AT Ist SPEED) kW 24.2 32 34.2 44.5 62.8 kcal/h 20790 27520 29410 38270 54010 REDUCED HEAT INPUT (AT 2nd SPEED) kW 20.8 27.8 29.8 38.7 55.2 kcal/h 17900 23910 25630 33280 47470 REDUCED HEAT OUTPUT (AT 2nd SPEED) KW 19.35 25.6 27.4 35.6 50.25 kcal/h 16640 22020 23560 30610 43210 NOMINAL EFFICIENCY % 93 92 92 92 91 AIR FLOW RATE AT Ist SPEED 2300 2900 3400 4200 6000 AT 2nd SPEED
m
3
/h
1900 2500 2700 3400 5100 THERMAL HEAD AT Ist SPEED 31.2 32.5 29.4 31.0 31.0 AT 2nd SPEED
K
30.2 30.0 29.8 30.7 29.2 NOMINAL GAS CONSUMPTION NATURAL GAS m3/h 2.75 3.68 3.93 5.11 7.30 (15°C - 1013 mbar) L.P.G. G30 2.05 2.74 2.93 3.81 5.44 L.P.G. G31
kg/h
2.01 2.69 2.90 3.74 5.34 REDUCED GAS CONSUMPTION NATURAL GAS m3/h 2.20 2.94 3.15 4.09 5.84 (15°C - 1013 mbar) L.P.G. G30 1.64 2.19 2.34 3.05 4.35 L.P.G. G31
kg/h
1.61 2.15 2.30 2.99 4.28 FUEL SUPPLY PRESSURE NATURAL GAS 20 L.P.G. G30
30
L.P.G. G31
mbar
30 GAS INLET DIAMETER 3/4 PIPE DIAMETER INTAKE EXHAUST
mm 80
ELECTRICITY SUPPLY VOLTAGE 230V - 50Hz INSTALLED ELECTRICAL POWER W 250 300 350 420 800 FUSE A 4 AIR THROW AT 1st SPEED
(RESIDUAL SPEED >1m/s)
m 14 18 20 22 26
SOUND PRESSURE AT 6 m (Ist SPEED) IN FREE-FIELD CONDITIONS
dB(A)
38
39
40
42
43 IN TYPICAL INSTALLATION dB(A) 48 51 52 56 57 SOUND PRESSURE AT 6 m (2nd SPEED)
IN TYPICAL INSTALLATION
dB(A)
45
46
47
51
54 WEIGHT kg 60 66 66 74 86
Table 1 – TECHNICAL DATA, EVOLUZIONE SERIES
Page 8
6 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
1.4 DIMENSIONS
1 EXHAUST OUTLET E32 E42/43 E52 E72 2 COMBUSTION AIR INTAKE A 474 591 709 944 3 POWER SUPPLY SOCKET B 755 872 990 1225 4 CONNECTION C 418 477 536 -- 5 ON LIGHT D 460 520 520 460 6 PASSTHROUGH HOLE FOR
E 197 256 315 432
MANOMETER TUBE
Figure 2 – DIMENSIONS
835
165
535
400 15
615 220
5
SIDE VIEW
26
777
26
829
130
B
290
=
A
=
FRONT VIEW
472
238,5
= =
120
80 80
290
12
EE
TOP VIEW
400
15
155
142
146
441
465
4
3
6
REAR VIEW E 72
597
411
460
C
146
142
3
4
6
REAR VIEW E 32/42/43/52
D
465
411
597
Page 9
Installation, Operation and Maintenance Manual– Ed.07/2005 7
EVOLUZIONE series natural gas/LPG heaters
2 FOR THE USER
2.1 SWITCHING THE APPLIANCE ON AND OFF
The first switching on of the appliance must be carried out by professionally qualified personnel. Before starting the heater, have professionally qualified personnel check that:
the data on the plate correspond to the data from the electricity and gas supply grids
the calibration is compatible with the power of the heater
the exhaust gas pipe is operating correctly
the intake of combustion air and outlet of exhaust gases occur correctly in accordance with the
specifications of current legislation
WINTER
1. Set the index of the ambient thermostat to maximum.
2. Check that the gas valve is open.
3. Supply current to the appliance by closing the omnipolar switch (provided by the electrical installation technician).
4. Set the summer/winter switch to the winter position (indicated by the snowflake symbol ).
5. After a pre-wash time of approximately 30 seconds, the gas electrovalve opens and the burner switches on.
6. When a flame is present, the central control unit keeps the gas valve open.
7. If no flame is present, the central control unit arrests operation of the appliance, and the arrest light illuminates on the reset button.
8. If point 7 applies, press the reset button.
9. If ignition is trouble-free, set the ambient thermostat index (not supplied as standard) to the value desired.
If the appliance is switched on after a long period of disuse, or the first time the appliance is switched on, it may be necessary to repeat the operation several times, due to air being present in the gas pipes.
SWITCHING OFF
To switch off the appliance, set the ambient thermostat index to the minimum. The burner will switch off, while the fans will continue to operate until the appliance has fully cooled.
If the appliance is not used for a protracted period, after the operation described above and after waiting for the fans to cease operating, close the gas valve and cut off electrical current to the appliance via the omnipolar switch located on the power supply line.
In no circumstances must the appliance be switched off by removing the power supply from it directly. This can damage the appliance, as it causes the fans to stop immediately and the limit thermostat to be activated, which must be reset manually.
WARNING
WARNING
WARNING
WARNING
Page 10
8 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
SUMMER
1. Close the gas valve and check that electrical current reaches the appliance.
2. Set the summer/winter switch to the summer position (indicated by the sun symbol ); set thus, only the fans will operate.
SEASONAL ARREST
1. Switch off the appliance and wait for the fans to stop.
2. Close the gas valve upstream of the appliance.
3. If the SUMMER function is not to be used, remove electrical power from the appliance by means of the omnipolar switch located on the power line.
RESET OF THE LIMIT THERMOSTAT
The limit thermostat stops the burner if the appliance becomes too hot. Reset is carried out by pressing the button on the rear of the appliance, after having removed the protective cap (see Figure 3). Replace the protective cap after resetting the thermostat.
Figure 3 LIMIT THERMOSTAT RESET BUTTON POSITION
Activation of the limit thermostat ALWAYS indicates an abnormal condition. For this reason, reset of the limit thermostat is a task for professionally qualified personnel, who will restore operation of the appliance ONLY after identifying the cause of overheating.
2.2 MAINTENANCE
Careful maintenance is always at the basis of economy and safety. The maintenance of heating plants must be carried out on an annual basis, preferably at the beginning of the
winter season, by professionally qualified personnel. For prolonged, trouble-free operation, we recommend a general cleaning of the appliance (paying particular
attention to the heat exchangers and the fan grilles) and carrying out combustion tests in accordance with specific regulations.
WARNING
RESET BUTTON
LIMIT THERMOSTAT
Page 11
Installation, Operation and Maintenance Manual– Ed.07/2005 9
EVOLUZIONE series natural gas/LPG heaters
2.3 ASSISTANCE
Always entrust
professionally qualified personnel with all reinstallation, activation, maintenance, gas
change, and other operations
.
For this reason, ROBUR S.p.A. has a network of Technical Assistance Centres that can be contacted via the dealer, the area representative, or by calling ROBUR S.p.A.'s Customer Assistance directly on 035/888111.
Before calling Customer Assistance, make sure that you have the machine documentation to hand and, if possible:
- the registration number and model of the product, which may be found on the data plate and on the guarantee card
- a description - even if only brief - of the type of installation
WARNING
Page 12
10 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
A
C
B
3 FOR THE INSTALLATION TECHNICIAN
3.1 BUILD CHARACTERISTICS
- premixed burner in stainless steel
- high head blower
- cylindrical combustion chamber in stainless steel
- ROBUR-patented
heat exchanger, manufactured in special light alloy, with horizontal fins on the air side
and vertical fins on the exhaust gas side, with extremely high heat exchange capacity
-
external panelling manufactured in painted steel and anodised aluminium
- two-speed
axial fan
The Evoluzione heater is manufactured in compliance with the norms currently in force as applied to gas appliances and electromagnetic emissions.
3.2 CONTROL AND SAFETY COMPONENTS
- manually resettable 100°C limit thermostat, providing protection against overheating of the heat exchangers.
-
differential “air-gas valve” control system for combustion airflow. If the air intake or exhaust outlet
pipes are obstructed, this safety system is activated, bringing about the arrest of the appliance.
-
Gas electrovalve: if a safety device is activated (limit thermostat, central control unit, etc.) the gas valve
is de-energised electrically, with the consequent interruption of gas flow to the burner.
Power supply: 230 V - 50 Hz
Operating temperature range: 0°C to +60°C
-
central ignition and flame control unit which takes care of the operation of igniting the premixed burner
and detecting the flame; if a flame is not detected within the safety time, the electronic control unit arrests the machine, which must be restarted manually.
Safety time: 5 seconds
Pre-wash time: 30 seconds
Power supply: 230 V - 50 Hz
Figure 4
A) central flame control unit B) transformer C) relay
Page 13
Installation, Operation and Maintenance Manual– Ed.07/2005 11
EVOLUZIONE series natural gas/LPG heaters
3.3 INSTALLATION
3.3.1 GENERAL NORMS FOR INSTALLATION OF THE APPLIANCE
Installation must be carried out be professionally qualified personnel, following the manufacturer’s
instructions.
Professionally qualified personnel means personnel that have specific technical expertise in the sector of
components of heating plants. In any case you may obtain any information that you may require by calling ROBUR S.p.A.’s Pre-sales Office on 035/888111.
Erroneous installation may cause damage to persons, animals or things. The manufacturer may not be
held responsible for such damage.
Installation must be carried out in compliance with current national and local norms.
For installation purposes, the following regulations should be respected:
- The minimum distance of the appliance from the wall behind it should be enough to allow adequate air renewal (at least 350 mm). The minimum distance from the side walls is indicated in Figu re 5.
- The optimum height recommended from the ground to the base of the heater is 2.5 – 3.5 m (see Figure 5). The heater must NOT be installed at heights of less than 1.8 m from the ground (for models E 32 and E
42), or 2.5 m (for models E 43, E 52 and E 72).
- To obtain maximum comfort and performance from the plant, we recommend that the following rules are observed:
make sure that the flow of air from the appliance does not strike workers directly
take into account the presence of obstacles (pillars and suchlike).
for better heat distribution, if several machines are installed, create alternating flows of warm air (see
Figure 6).
in such cases it may also be a good idea to position the appliances near main doors so that they
perform the additional function of creating an “air barrier” at the moment these doors are opened.
- Do not install Evoluzione series heaters in greenhouses or environments with a high degree of humidity or other such climatic conditions, as they have not been designed for this type of use.
On the basis of the installation plan, set up the gas and electricity supply lines, as well as the holes for exhaust gas outlet and combustion air intake (together with the mounting brackets, ROBUR supplies an “installation template” on which the layout of the holes has been reproduced). A) Unpack the appliance, taking care to check that it has not been damaged during transport; each appliance
is tested in the factory before being dispatched. Therefore, damage has occurred, tell the transporter immediately.
B) Fit the mounting brackets, chosen from the three available types (for further information see the paragraph
entitled “Wall installation” on page 18), following the instructions supplied with the accessory.
C) Fix the heater to the bracket, using the screws supplied with the bracket. D) On the gas supply pipe, provide a gas shut-off valve and a three-piece joint. E) Check that an adequate gas distribution network exists. In particu lar, if the appliance is fuelle d by:
Natural gas
Make sure that the gas supply pressure from the distribution network, when the appliance is in operation, is set to the value of 20 mbar (204 mm H
2
O) (with a tolerance from 17 mbar to 25 mbar).
L.P.G. (Propane-Butane mix)
It is essential to fit a first-stage pressure reducer in proximity to the liquid gas tank to reduce pressure to
1.5 bar, and a second-stage pressure reducer for a further reduction from 1.5 bar to 30 mbar (306 mm H
2
O) in proximity to the heater (with a tolerance from 20 mbar to 35 mbar).
L.P.G. (pure Propane)
It is essential to fit a first-stage pressure reducer in proximity to the liquid gas tank to reduce pressure to
1.5 bar, and a second-stage pressure reducer for a further reduction from 1.5 bar to 30 mbar (306 mm H
2
O) in proximity to the heater (with a tolerance from 25 mbar to 35 mbar).
WARNINGS
Page 14
12 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
If you are not sure what composition of L.P.G. is used, assume that it is a Propane-Butane mix and act accordingly.
3.3.2 ELECTRICAL CONNECTIONS
A) Connect the appliance electrically using the socket supplied as standard and a type H05 VVF 3x1.5 mm
2
cable, with a maximum external diameter of 8.4 mm.
For this operation, ensure that:
- power grid data corresponds to the data on the machine data plate (230 V/50 Hz single phase).
- when the connection is made, the ground wire is kept longer than the live wire, so that it will be the last cable to be pulled out if the power supply cable is accidentally pulled out, thus ensuring that it remains grounded.
Electrical safety of the appliance is achieved only when it is correctly connected to an efficiently grounding system, created in accordance with current safety legislation. Do not use gas pipes to ground electrical equipment.
B) Provide a bipolar switch on the power supply line with minimum contact clearance of 3 mm.
“Bipolar”
means that it may be opened on both phase and neutral
. This means that when it is opened, both contacts
are open.
C) The installation of an ambient thermostat
is obligatory, whenever the control used does not provide it.
The thermostat must be connected to the appliance as shown in the electrical assembly diagram (see Figure 22 on page 23). We recommend that the thermostat (or its sensor) is positioned approximately 1.5 m from the floor, away from draughts or direct sunlight and other direct heating sources (lights, warm flows of air from the appliance itself, etc.) and, if possible,
NOT on outside-facing walls, so as not to give false
temperature readings and therefore compromise operation of the plant.
IN THIS WAY, UNDESIRED SWITCHING ON AND OFF OF THE PLANT WILL BE AVOIDED AND OPTIMAL COMFORT WILL E ENSURED IN THE ROOM.
In addition to the ambient thermostat it is necessary to install one of the control units that ROBUR supplies
as optional accessories (for further information, see the paragraph entitled “List of accessories” on page
27.)
Control cables (in particular those connected to the control units and temperature sensors) must be
protected from interference created by power cables.
Such protection may be obtained, for example,
either by shielding the cables or by laying them in separate channels from the power cables.
D) If it is not intended to use one of these accessories, it is nonetheless necessary to install, as well as the
thermostat
:
- 1 switch to control summer/winter operation of the heater, to connect to poles 1, 2 and 3 of the
terminal board (see electrical assembly diagram on page 23)
- 1 switch to control operation at maximum and reduced power, to connect to poles 8 and 3 of the
terminal board (see electrical assembly diagram on page 23)
- 1 illuminated switch to signal arrest of the heater, to connect to poles 5, 6 & 7 of the terminal board
(see electrical assembly diagram on page 23)
NOTE
NOTE
NOTE
Page 15
Installation, Operation and Maintenance Manual– Ed.07/2005 13
EVOLUZIONE series natural gas/LPG heaters
Figure 5 – CLEARANCES
Figure 6 – EXAMPLES OF INSTALLATION
minimum 400 mm
350 mm
minimum: E32 – E42: 1.8 m E43 – E52 – E72: 2.5 m maximum: 3.5 m
min
200
A
A
Page 16
14 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
3.3.3 SIZING AND INSTALLATI ON OF COMBUSTION AIR AND EXHAUST GAS PIPES
The Evoluzione series of warm air heaters may be installed in one of the following ways:
- type
B
23
installation: in this type, combustion air intake occurs inside the room, while exhaust gas outlet takes place outside, via a special pipe, that may be either horizontal or vertical. In this type of installation, the appliance is not sealed off from the room (see Figure 7 and Figure 8)
- type
C
13
and C
33
installation: the outlet of exhaust gases and intake of combustion air occur outside,
through coaxial or separate pipes, on a wall (for C
13
see Figure 9 or Figure 10) or on the roof (for C
33
see
Figure 11). In this way the appliance is sealed from the room in which it is installed.
- type
C
53
installation: the outlet of combustion products and combustion air intake occur through separate pipes that exit on the outside of the building, on different walls. This type allows wall-based air intake and exhaust gas outlet far from the appliance, or via the roof (see Figure 12).
- type
C
63
installation: with this type, exhaust outlet/air intake systems can be created using commercially available tubes, bends and terminals, on condition that they are approved for this type of appliance. In addition, pipes with a diameter of more than 80 mm can be used: for example when it is necessary to create air/exhaust systems of considerable length. With this type, for the calculation of the air/exhaust system, reference should be made to the data supplied by the pipe manufacturer, as well as to the composition, flow rate and temperature of the exhaust gases (see Table 2).
In any case, use approved pipes according to the type of installation that is to be carried out. ROBUR S.p.A. can supply to order rigid pipes, coaxial pipes and approved terminals.
In order to size the pipe system, it is necessary to calculate the total pressure drop generated by the system itself.
The maximum and minimum admissible total pressure drop depend on the model of appliance (see Table 2). Table 3 gives the pressure drops, for Ø 80 and Ø 100, for the air pipes and coaxial pipes su ppl ied by ROBUR. The pressure drops of the external terminals, being extremely small, can be disregarded. In the design stage, it is necessary to verify that the sum of the pressure drops of the pipe system is higher
than the minimum admissible pressure drop and that it is lower that the maximum admissible pressure drop of the appliance (see Table 2). The following pages give an example of how to calculate pressure drops.
The maximum lengths of the air pipe and the exhaust gas pipe, in relation to the type of installation carried out, are given in Table 4. The lengths should be taken as APPROXIMATE, and in the case of standard installations in which the air pipe and the exhaust gas pipe are routed in a linear fashion as shown in Figure 7, Figure 8, Figure 9, Figure 10, Figure 11 and Figure 12.
It is ALWAYS necessary to install a condensate separator (see detail D in Figure 8), available as an accessory (Code O-SCN000).
In the case of installations with horizontal pipes of more than 1 metre in length, in order to prevent drops of condensate reaching the appliance, it is necessary to install the exhaust gas pipe with a counterslope of 1 or 2 cm for each metre of length. In addition, for the correct installation of external terminals for outlet of combustion products and intake of combustion air, follow the indications given in Figure 13.
If the integrated upper mounting bracket is not used, to make connection of the heater and the air/exhaust gas pipes easier, ROBUR supplies as an accessory an “air/exhaust gas pipe connector kit” (Code O­SCR010) that includes 2 adaptors Ø 80 with element for drawing exhaust gases/air (see detail C of Figure 8) and gasket.
NOTE
NOTE
NOTE
Page 17
Installation, Operation and Maintenance Manual– Ed.07/2005 15
EVOLUZIONE series natural gas/LPG heaters
Figure 7 – TYPE B23 INSTALLATION WITH WALL-BASED EXHAUST
OUTLET
Figure 8 - TYPE B23 INSTALLATION WITH ROOF-BASED EXHAUST
OUTLET
DATA FOR CALCULATION OF AIR/EXHAUST GAS SYSTEM WITH COMMERCIALLY AVAILABLE PIPES
CO2 CONTENT IN EXHAUST GASES %
ADMISSIBLE PRESSURE
DROP
MOD.
TEMPERATURE
EXHAUST GASES
°C
FLOW RATE OF
EXHAUST GASES
IN MASS
kg/h
NATURAL GAS LPG
MIN (Pa) MAX (Pa)
E 32 150 43.3 5 30 E 42 170 57.5 7 40 E 43 170 62.5 8 40 E 52 170 79.1 10 50 E 72 175 116.2
9.0 9.5
10 80
Table 2
DATA FOR CALCULATION OF AIR/EXHAUST GAS SYSTEM WITH PIPES Ø 80 OR Ø 100 SUPPLIED BY ROBUR ON RE QUEST
PRESSURE DROP FOR COMPONENTS Ø 80 PRESSURE DROP FOR COMPONENTS Ø 100
PIPE
(Pa/m)
90°BEND
(Pa)
COAXIAL
(Pa)
PIPE
(Pa/m)
90°BEND
(Pa)
MOD.
EXH. AIR EXH. AIR WALL ROOF EXH. AIR EXH. AIR
COAXIAL
ROOF (Pa)
E 32 0.70 0.36 1.05 0.54 2.5 4.4 0.26 0.10 0.39 0.15 3.1 E 42 1.20 0.60 1.80 0.90 4.2 12.3 0.40 0.20 0.60 0.30 7.9 E 43 1.39 0.74 2.08 1.11 4.9 14.6 0.45 0.27 0.67 0.40 10.1 E 52 2.26 1.16 3.39 1.74 9.7 25.6 0.76 0.40 1.14 0.60 16.9 E 72 4.95 2.54 7.42 3.81 13.5 48.7 1.66 0.86 2.50 1.30 31.9
Table 3
A Adaptor Ø 80 B Condensate separator C 90° bend Ø 80 D Pipe Ø 80 E Lower mounting bracket
A
B
B
D
C
E
A Roof exhaust terminal B Pipe Ø 80 C Adaptor Ø 80 D Condensate separator E Upper mounting bracket
E
A
B
C
D
Page 18
16 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
For each “T”-shaped element, consider an increase in length of 2 metres. For each 45° bend, calculate an increase in length of 0.75 metres.
APPROXIMATE MAXIMUM LENGTHS ALLOWED FOR EACH TYPE OF INSTALLATION
TYPE OF INSTALLATION
B 23 C 13 C 33 C 53
COAXIAL ROOF
PIPE Ø 80
COAXIAL
WALL
Ø 80
Ø 80 Ø 100
HORIZONTAL VERTICAL
SEPARATE
PIPES
Ø 80
PIPES Ø 80 PIPES Ø 80 PIPES Ø 80 PIPES Ø 100
SEPARATE
PIPES
Ø 80
MOD.
EXHAUST GAS EXHAUST GAS AIR/EXH. AIR/EXH. AIR/EXH. AIR/EXH. AIR/EXH. AIR/EXH.
E 32 20 20 16+16 14+14 13+13 15+15 20+20 1+15
E 42 20 20 14+14 13+13 12+12 14+14 20+20 1+15 E 43 20 20 13+13 12+12 10+10 12+12 20+20 1+15 E 52 20 20 10+10 8+8 7+7 9+9 15+15 1+15 E 72 15 15 7+7 7+7 4+4 6+6 15+15 1+10
Table 4
If your installation does not correspond with the figures given in Table 4 above (e.g. type C13 installation of an E 52 with air pipe diameter Ø 80 length 10 m and exhaust gas pipe diameter Ø 80 length 16 m), it is necessary to calculate the pressure drop of the pipe system and verify that the sum is not greater than the admissible pressure drop, or alternatively to contact ROBUR’s Pre-sales service on 035/888111.
CALCULATION – AN EXAMPLE
Let us hypothesise that we are installing an E 43 heater. The air/exhaust gas system will be created from separate pipes, Ø 80, in the following way:
- 20 metres of exhaust gas pipe Ø 80
- Four 90
° bends, Ø 80, on the exhaust gas pipe
- 8 metres of air pipes, Ø 80 It is now possible to proceed with a test calculation, remembering that the minimum admissible pressure drop
is 8 Pa while the maximum admissible pressure drop is 40 Pa (see Table 2).
Quantity
Pressure drop
Exhaust gas pipe Ø 80 20 m x 1.39 Pa = 27.8 Pa + 90
° bends on exhaust gas pipe
4 x 2.08 Pa = 8.32 Pa +
Air pipe Ø 80 8 m x 0.74 Pa = 5.92 Pa =
Total pressure drop
42.04 Pa
The total pressure drop of the pipe system is higher than the maximum admissible pressure drop (42.04 Pa, HIGHER than 40 Pa). Therefore, the installation IS NOT PERMITTED.
Installation will be possible if one of the following measures is adopted:
- reducing the length of the air/exhaust gas pipes;
- reducing the number of bends in the exhaust gas pipe;
- increasing the diameter of the pipes to 100mm
NOTE
NOTE
Page 19
Installation, Operation and Maintenance Manual– Ed.07/2005 17
EVOLUZIONE series natural gas/LPG heaters
Figure 9 – TYPE C13 INSTALLATION WITH SEPARATE WALL-
MOUNTED PIPES
Figure 10 – TYPE C13 INSTALLATION WITH WALL-MOUNTED
COAXIAL PIPES
Figure 11 – TYPE C53 INSTALLATION WITH ROOF-MOUNTED
COAXIAL PIPE
Figure 12 TYPE C53 INSTALLATION WITH ROOF-MOUNTED
EXHAUST GAS OUTLET AND WALL-MOUNTED AIR INTAKE
A
B
A Wall-based terminal B Integrated upper mounting
bracket with separate wall­mounted air intake and exhaust
g
as outlet
A Wall-mounted
coaxial pipe
Ø 150 B 90° bend Ø 80 C Adaptor Ø 80
D Lower mounting
bracket E Condensate
separator
A Roof-mounted coaxial
exhaust gas outlet B Pipe Ø 80 C Adaptor Ø 80 D Lower mounting bracket
A Roof-mounted
terminal B Pipe Ø 80 C 90° bend Ø 80 D Adaptor Ø 80 E Upper mounting
bracket F Wall-mounted
terminal G Condensate
separator
A
B
C
D
E
G
F
B
D
C
E
B
A
A
B
E C
D
Page 20
18 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
Figure 13 – POSITIONS OF WALL-MOUNTED TERMINAL
3.3.4 WALL INSTALLATION
For the installation of its Evoluzione heaters, ROBUR S.p.A. supplies various types of mounting brackets (as optional extras) from which to choose according to the type of exhaust outlet to be created. In particular:
- upper mounting bracket. This supports the heater from above, and is supplied complete with condensate drain and air/exhaust gas pipe connection kit with elements for drawing air/exhaust ga s (see Figure 31).
- upper mounting bracket with integrated wall-mounted outlets (see Figure 32). This bracket performs two functions: supporting the heater from above, and intake and outlet of combustion products. It is supplied complete with an external dual wind-protected terminal.
- Adjustable lower mounting bracket. This supports the heater from below and allows it to adjusted by ± 30°
in relation to the wall used for installation; it is supplied complete with condensate drain and air/exhaust gas pipe connection kit with elements for drawing air/exhaust gas (see Figure 33).
- tubular support bracket. This supports the heater from below, and is supplied complete condensate drain and air/exhaust gas pipe connection kit with elements for drawing air/exhaust gas (see Figure 34).
If it is not intended to use these accessories, refer to the diagram below. As regards fixing the appliance to the support shelf, fix the latter with 4 M10 bolts.
Figure 14
1 = EXHAUST GAS OUTLET 2 = COMBUSTION AIR INTAKE
290
FRONT VIEW
POSITION RECOMMENDED
2
1
POSITION ALLOWED
2
1
POSITION NOT ALLOWED
2
1
25
790
400
Page 21
Installation, Operation and Maintenance Manual– Ed.07/2005 19
EVOLUZIONE series natural gas/LPG heaters
3.3.5 PROCEDURE FOR CHECKING & ADJUSTING CALIBRATION OF THE NOVAMIX VALVE SIT 822
These operations must be carried out by qualified personnel. Wrong or careless assembly or fitting of the gas circuit can cause dangerous gas leaks and in particular in areas that are tampered with. Use, too, adequate sealants on all connections.
Each heater is tested and approved in the factory for operation with G20 natural gas. The calibration of the valve must be carried out
ONLY if the gas valve is replaced.
After calibration is completed, the valve’s adjusting screws, A and B, must be sealed. After calibration, check the sealing of the screws of the pressure intakes with soapy water or other suitable means.
A) Completely unscrew the air/gas ratio adjustment screw A (Figure 15), turning it anticlo ckwise. B) Tighten screw B (Figure 15) until flush, turning it clockwise. C) Connect a differential manometer, with a resolution of at least 5 Pascal, in the following way:
- the positive connector (+) to the blower gas pressure intake D (Figure 15) on the gas valve;
- The negative connector (-) in parallel to the silicon tube that connects the blower (connector “G”, Figure 18) to the open valve signal input F (this operation is made possible by inserting a “T” connector between the silicon tube and the input (connector “F”) to the valve as indicated in Figure 1 7.
D) Start the heater and select minimum operating power. E) Check that the difference in pressure read on the differential manometer corresponds to the OFFSET
value (pressure at the burner – pressure at the blower) indicated in Table 5.
F) If the OFFSET value detected is more than +/- 0,1 mbar off of the valued indicated in Table 5, adjust the
valve by turning OFFSET adjustment screw C.
If the readout of the differential manometer is not sufficiently stable to carry out a correct calibration of the offset, we suggest inserting a damping nozzle (ROBUR optional accessory Code B-GLL103) in the silicone tube connected to the positive connector (pressure at the burner).
G) Switch operation of the heater to maximum power and check that the offset value does not change from
that indicated at minimum power (tolerance +/- 0.1 mbar). H) Visually check that the burner does not show signs of reddening at either minimum or maximum power. I) Switch the heater off and on, and check the offset calibration again at minimum and maximum power. J) Switch off the heater, disconnect the differential manometer from the valve’s gas pressure intake “F” and
the burner’s “G”, restore the connection of the silicone tube to the gas valve’s connector “F” and tighten
until flush screw “D” (Figure 15) of the gas pressure intake.
Figure 15 – Novamix SIT 822 gas valve
WARNING
WARNING
A) Air-gas ratio adjustment screw B) Pilot gas flow adjustment screw C) OFFSET adjustment screw D) Burner pressure intake E) Pressure intake at valve entrance
Page 22
20 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
Figure 16 – Novamix SIT 822 gas valve
Figure 17
OFFSET VALUES
MODEL E 32 E 42 E 43 E 52 E 72 OFFSET [mbar] 0 0 -0,3 0 0
Table 5 – OFFSET VALUES
F) Valve opening signal input
F
Offset adjustment screw (C)
Pressure on blower signal input (G)
Blower
Gas pipe
Gas valve
Signal input (E)
T connector
Open valve command signal tube
Burner pressure intake (D)
Gas intake
Differential manometer
OFFSET=burner pressure minus blower pressure
Page 23
Installation, Operation and Maintenance Manual– Ed.07/2005 21
EVOLUZIONE series natural gas/LPG heaters
3.3.6 GAS CHANGE
These operations must be carried out by professionally qualified personnel. Wrong or careless fitting and installation of the gas circuit may cause dangerous gas leaks in the whole circuit and in particular in areas that are tampered with. In addition, adequate sealants must be used on all connections.
If the type of gas indicated on the label does not correspond to that which is to be used, the appliance must be converted and adapted to the type of gas that is going to be used.
To carry out this operation, proceed as follows: A) Remove both the gas and electricity supply.
B) Unscrew the hexagonal nut that connects the gas pipe to the connector of the nozzle base (Figure 18).
Take care not to lose or damage the round internal seal.
Figure 18 – USCITA DEL SEGNALE DI PRESSIONE GENERATO
DAL SOFFIATORE
Figure 19
C) Loosen, without removing, the 4 screws that fix
the gas supply pipe to the valve (Figure 19).
D) Move the gas pipe and extract the nozzle, with
the help of a screwdriver for leverage if necessary (see Figure 20).
E) Remove the o-ring seal from the nozzle and fit
it to the new nozzle. For the type of nozzle suitable for the model of
heater refer to Table 6.
F) Insert the new nozzle in its seating.
Figure 20
G) Refit the gas pipe, checking that the round seal in the metal nut and the square seal on the valve exit are
firmly in place. Tighten the nut to a locking torque of 62±2 Nm; tighten the valve screws and carry out
calibration checks. H) Calibrate the appliance for the new gas type; adjusting the pressure to the burner as described in the
previous paragraph “Checking and adjusting operating gas pressure”. I) While the appliance is in operation, check the sealing of all gas connections with soapy water or by
another suitable means, including those that have not been handled during the operation. J) Replace the sticker indicating the type of gas applied on the appliance with one indicating the new type of
gas.
NATURAL GAS AND L.P.G. NOZZLES
E 32 E 42 E 43 E 52 E 72 Natural gas (G20) diameter (mm)
stamped code
4.60 108
5.50 119
5.90 074
7.20 120
10.3 121
LPG diameter (mm) stamped code
3.50 117
4.25 122
4.50 123
5.40 073
7.50 124
Table 6
WARNING
G
O-RING
NOZZLE
EXIT OF PRESSURE SIGNAL GENERATED BY BLOWER
Page 24
22 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
3.3.7 FUNCTIONAL WIRING DIAGRAM
Figure 21 – FUNCTIONAL WIRING DIAGRAM
1234567 89
10 11 12 13 14 J5 J616 17 18 19
~
230V 50Hz
L
M9
Z1
Z9
M1
M4
TR
RP8
Q1
S
P1
L1
GND
N
M2
J1 J2 J3 J4
CVCV VV
RLRL-1 RL-2
CR
Q2
MIN
M
A
X
M
I
N
MAX
MIN MAX
LMP
RP7
Z2
~
~
M9
Mains fuse - 5x20 4 A F
M2 Fan thermostat
Z1 Summer/winter switch (optional)
Z9
Ambient thermostat (optional)
M1
Limit thermostat
M4 Flame control equipment
L1 Arrest light (optional) P1 Restart button (optional)
CV Fan condenser (2 pcs for E72)
V
Fan motor 2 pcs for E72)
CR Condenser speed reduction blower
Z2
MAX/MIN switch (optional)
S Blower motor
TR Ignition transformer
RP7 Ignition electrode (2 pcs)
RP8 Flame detection electrode
Q1 Safety gas electrobvalve
L Power – phase
N Power – Neutral
GND Power – Ground
RL Relay + base
Q2 Modulating gas electrovalve
LMP Ignition light
SP
Panel plug (see Figure 25)
Page 25
Installation, Operation and Maintenance Manual– Ed.07/2005 23
EVOLUZIONE series natural gas/LPG heaters
3.3.8 ASSEMBLY WIRING DIAGRAM
Figure 22 – ASSEMBLY WIRING DIAGRAM (SEE KEY TO Figure 21)
Page 26
24 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
3.3.9 WIRING DIAGRAMS FOR THE INSTALLATION OF SEVERAL HEATERS
ROBUR has control units for the control and management of several heaters (see “List of accessories” on page 27). If these controls are not used, follow the diagrams below.
In these conditions, power and ventilation modulation will not occur.
Figure 23 – WIRING DIAGRAM FOR OPERATION OF SEVERAL HEATERS WITH A SINGLE TIMER AND SEVERAL THERMOSTATS
Figure 24 – WIRING DIAGRAM FOR OPERATION OF SEVERAL HEATERS WITH A SINGLE TIMER AND A SINGLE AMBIENT THERMOSTAT
(solution with several relays)
NOTE
HEATER HEATER HEATER
RL1 RL2 RL3
P
L N L N L N
Z9 Z9 Z9
TA TA TA
N L
I
230 V - 50 Hz
P = PROGRAMMABLE TIMER TA = AMBIENT THERMOSTAT RL1-2-3 = PROGRAMMED
CONTROL RELAY
HEATER HEATER HEATER
RL1 RL2 RL3
P
L N L N L N
Z9 Z9 Z9
N L
I
230 V - 50 Hz
P = PROGRAMMABLE TIMER TA = AMBIENT THERMOSTAT RL1-2-3 = PROGRAMMED
CONTROL RELAY
TA
Page 27
Installation, Operation and Maintenance Manual– Ed.07/2005 25
EVOLUZIONE series natural gas/LPG heaters
Figure 25 – WIRING DIAGRAM FOR OPERATION OF SEVERAL HEATERS WITH A SINGLE PROGRAMMABLE TIMER AND A SINGLE AMBIENT
THERMOSTAT (solution with single relay)
3.4 SERVICE
All maintenance and service operations must be carried out by an
Authorised Service Centre.
3.4.1 POSSIBLE OPERATING ANOMALIES
Before performing specific checks, make sure that: A) The appliance is powered (230 V ± 10% 50 Hz) and that it has an adequate gro unding system. B) There is a supply of gas. C) Pressures and flows fall within the limits specified by the manufacturer. A lower pressure reading than that
indicated by the manufacturer corresponds to insufficient gas supply. The causes may be: If the appliance runs on natural gas:
Inadequate meter
excessive length and/or number of bends in the gas piping for the diameter used
If the appliance runs on L.P.G.:
it may happen that after initial switch-off of the burner, upon switching on again, the appliance fails to
start. In this case it is possible that the reducer has insufficient flow capacity
if the indicated pressure is not reached it is possible that the pressure reducer on the tank does not
have sufficient flow capacity, or that the length and/or number of bends in the gas piping are excessive in relation to the diameter used
Only at this point should you proceed with checking for the specific failure.
Before opening the door on the side of the appliance to gain access to the electrical panel, REMOVE ELECTRICAL POWER from the appliance using the omnipolar switch located upstream of the appliance or by disconnecting the power plug.
NOTE
NOTE
HEATER HEATER HEATER
P
L N L N L N
Z9 Z9 Z9
N L
I
230 V - 50 Hz
P = PROGRAMMABLE TIMER TA = AMBIENT THERMOSTAT RL = PROGRAMMED
CONTROL RELAY
TA
RL
Page 28
26 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
3.4.2 TYPES OF FAILURE AND POSSIBLE COURSES OF ACTION
In case of failure contact your local Authorised Service Centre.
Case 1: The appliance fails to start during ignition phase
A) The correct phase connection has not been respected. B) The ignition electrodes are broken or incorrectly positioned. C) The flame detector electrode is broken, incorrectly positioned, or is touching the earth of the equipment. D) Damage to the ignition transformer or to its electrical connections. E) Damage to the gas valve or to its electrical connections. F) Inefficient grounding system. G) Air present in the gas piping. H) Incorrect calibration of gas pressure to burner.
Case 2: Arrest of the appliance during operation
A) Gas not supplied due to damage to gas plant; the central control unit repeats the ignition cycle, after which
it closes the gas valve, thereby arresting the appliance (accidental interruption to gas supply).
B) Electrical power not received due to damage to the external electricity supply system; if electrical power is
absent for a prolonged period, the limit thermostat (M1) is activated, arresting the machine and preventing it from being switched on again. Wn power returns, it must be reset by pressing the button located on the
thermostat itself on the outside of the appliance under the black screw-cap (see Figure 3). C) The flame detector electrode touching the earth of the equipment or is interrupted. D) The gas valve closes because it or its electrical or pneumatic connections are damaged.
Case 3: The limit thermostat (M1) arrests the burner
A) The heat exchangers have overheated: check operation of the fan, the gas pressure and the n ozzle s. B) The heat exchangers overheat because of a build-up of dirt or obstruction of the air inlet vent. Clean the
exchangers or free the air inlet vent (clean the ventilation grille). C) Check that electrical power is always present during operation. To reset the thermostat, press the button located on the thermostat underneath the black screw cap (see
Figure 3 on page 8).
Case 4: The burner switches off and fails to restart, even if the ambient temperature requires it
A) Check the operation of the ambient thermostat, and the relative electrical connections. B) Re-examine the position of the ambient thermostat (check that it is not influenced by external sources of
heat). C) Check the signal from the blower that reaches the valve.
Case 5: The combustion air blower does not start
A) Check that the device’s protective fuse is intact. B) Check that the ambient thermostat requires heat and is correctly connected. C) Check the fuse on the power plug. D) Check that the limit thermostat has not activated. E) Check the power supply to the central control unit. F) Check that the central control unit’s fuse is intact. G) Check the electrical connections of the blower.
Case 6: The combustion air blower starts but the appliance does not switch on
A) The central ignition control unit does not begin the cycle: reeplace the internal fuse of the central control
unit or the unit itself. B) Check the voltage supplied to the ignition transformer and to the gas valve.
Page 29
Installation, Operation and Maintenance Manual– Ed.07/2005 27
EVOLUZIONE series natural gas/LPG heaters
3.5 LIST OF ACCESSORIES
The accessories listed below are specifically for Evoluzione series heaters.
3.5.1 CONTROL UNITS
- BASIC CONTROL UNIT (Code O-CTR001): summer/winter selection, selection of maximum/reduced power operation, illuminated arrest warning/manual reset button (see Figure 26).
- THERMOSTATED CONTROL UNIT
(Code O-CTR009): control of ambient temperature via remote sensor, automatic operation with modulation of maximum or reduced power according to temperature set, selection of reduced power operation, antifreeze function, summer/winter selection, arrest warning light, reset button, sound signal in the case of incorrect operation and/or wrong connections to the remote sensor (see Figure
27).
Figure 26 – BASIC CONTROL UNIT
Figure 27 – THERMOSTATED CONTROL UNIT
- INTEGRATED CONTROL UNIT (Code O-CTR010): daily and/or weekly timer programming, control of ambient temperature via remote sensor, automatic operation with modulation of maximum or reduced power according to temperature set, selection of reduced power operation, antifreeze function, summer/winter selection, arrest warning light, reset button, sound signal in the case of incorrect operation an/or wrong connections to the remote sensor (see Figure 28).
- STAGNO IP 55 INTEGRATED CONTROL UNIT
(Code O-CTR012): daily and/or weekly timer programming, control of ambient temperature via remote sensor, automatic operation with modulation of maximum or reduced power according to te mpera ture s et, selec tio n of red uced po wer op erat ion, a ntif reez e function, summer/winter selection, arrest warning light, reset button, sound signal in the case of incorrect operation an/or wrong connections to the remote sensor, lockable front cover (see Figure 29 ).
Figure 28 – INTEGRATED CONTROL UNIT
Figure 29 – STGNO IP55 INTEGRATED CONTROL UNIT
NOTE
Page 30
28 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
- EXPANSION MODULE (Code O-CTR007): in
conjunction with the use of a thermostated or integrated control, it allows up to a maximum of three heaters to be controlled simultaneously (see Figure 30)
Figure 30 – EXPANSION MODULE
3.5.2 MOUNTING BRACKETS
- UPPER MOUNTING BRACKET (Code O-STF003): supplied complete with condensate drain and air/exhaust gas pipe connection kit with elements for drawing air/exhaust gases (see Figure 31).
- UPPER MOUNTING BRACKET WITH INTEGRATED WALL-MOUNTED OUTLETS (Code O-STF000): supplied complete with double external terminal (Figure 32).
- ADJUSTABLE LOWER MOUNTING BRACKET (Code O-STF006): supplied complete with condensation drain and air/exhaust gas pipe connection kit with elements for drawing air/exhaust gase s (Figure 33).
- TUBULAR MOUNTING BRACKET: complete with condensation drain and air/exhaust gas pipes kit with elements for drawing air/exhaust gases (Code O-STF007 for models E32/E42/E43; Code O-STF008 for models E52/E72) (Figure 34).
Figure 31 – UPPER MOUNTING BRACKET
Figure 32 – UPPER MOUNTING BRACKET WITH INTEGRATED
OUTLETS
Page 31
Installation, Operation and Maintenance Manual– Ed.07/2005 29
EVOLUZIONE series natural gas/LPG heaters
Figure 33 – ADJUSTABLE LOWER MOUNTING BRACKET
Figure 34 – TUBULAR MOUNTING BRACKET
3.5.3 OTHER ACCESSORIES
- ADJUSTABLE ALUMINIUM FINS: these allow the direction of warm air flow to be adjusted horizontally and/or vertically. Each kit (Code O­LTT000) consists of 20 fins (see Figure 35).
- CONDENSATE SEPARATOR (Code O-
SCN000): this element allows any condensate that forms on the exhaust gas pipe to be collected and drained. It must be used when there is a vertical length of exhaust gas piping of 1 metre or longer and when ROBUR mounting brackets are not used (see Figure
36).
Figure 35 – ADJUSTABLE ALUMINIUM FIN
- AIR/EXHAUST PIPE CONNECTION WITH INTAKE ELEMENT (Code O-SCR010): consisting of 2 vertical connectors (see Figure 37) that allow the connection of the exhaust gas pipe and the air pipe to the heater. It is necessary when ROBUR mounting brackets are not used.
Figure 36 – CONDENSATE
SEPARATOR
Figure 37 – AIR/EXHAUST GAS PIPE
CONNECTOR
Page 32
30 Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
With the aim of continuously improving the quality of its products, ROBUR S.p.A. reserves the right to modify the data
and contents of this manual without prior notice.
ROBUR S.p.A.
Via Parigi, 4/6
24040 Verdellino/Zingonia (Bergamo)
Tel. 035- 888111 Fax 035 - 884165
INTERNET: www.ROBUR.it e-mail ROBUR@ROBUR.it
Page 33
Page 34
Codice: D-LBR345 05 MED SPV 042 28/07/2005
Loading...