The appliance and all its accessories must be disposed of separately in accordance with the regulations in force.
Use of the WEEE symbol (Waste Electrical and Electronic Equipment) indicates that this product cannot be disposed of as household waste.
Proper disposal of this product helps to prevent potential negative consequences for the environment and human health.
Revision: B
Code: D-LBR749EN
This Installation, use and maintenance manual has been drawn up and printed by Robur S.p.A.; whole or partial
reproduction of this Installation, use and maintenance manual is prohibited.
The original is led at Robur S.p.A.
Any use of this Installation, use and maintenance manual other than for personal consultation must be previously
authorised by Robur S.p.A.
The rights of those who have legitimately led the registered trademarks contained within this publication are not
aected.
With the aim of continuously improving the quality of its products, Robur S.p.A. reserves the right to modify the
data and contents of this Installation, use and maintenance manual without prior notice.
INDEX OF CONTENTS
I Introduction .............................................................................
Installation, use and maintenance manual – Caldaia 35 Tech
3
Introduction
I INTRODUCTION
I
Manual
This Manual is an integral part of the Caldaia 35 Tech
unit and must be handed to the end user together with
the appliance.
II SYMBOLS AND DEFINITIONS
II.1 KEY TO SYMBOLS
DANGER
WARNING
NOTE
PROCEDURE
REFERENCE (to other document)
I.1 RECIPIENTS
This Manual is intended for:
▶
End user, for appropriate and safe use of the appliance.
▶
Qualied installer, for correct appliance installation.
▶
Planner, for specic information on the appliance.
Caldaia 35 Tech.
Boiler/External module = equivalent terms, both used to designate the part of the appliance to be installed outside the room
to be heated.
TAC = Technical Assistance Centre authorised by Robur.
Remote control = optional control device with chronothermo-
stat function.
External request = generic control device (e.g. thermostat, timer or any other system) equipped with a voltage-free NO contact
and used as control to start/stop the Caldaia 35 Tech unit.
First start-up = appliance commissioning operation which may
only and exclusively be carried out by a TAC.
II.2 TERMS AND DEFINITIONS
Appliance/Unit = equivalent terms, both used to refer to the
III WARNINGS
III.1 GENERAL AND SAFETY WARNINGS
Installer's qualications
Installation must exclusively be performed by a qualied rm and by skilled personnel, with specic knowledge on heating, electrical systems and gas appliances,
in compliance with the laws in force in the Country of
installation.
Declaration of conformity
Upon completing installation, the installing rm shall
issue to the owner/client the appliance's workmanlike
conformity declaration, according to national/local regulations in force and the manufacturer's instructions/
provisions.
Packing
Packing items (plastic bags, polystyrene foam, nails, etc.)
must be kept out of the reach of children, as they are potentially dangerous.
Misuse
The appliance must only be used for the purposes for
which it has been designed. Any other use is deemed
hazardous. Incorrect use may aect operation, duration
and safety of the appliance. Adhere to the manufacturer's instructions.
Use of the appliance by children
The device can be used by children over 8 years old,
and by people with reduced physical, sensory or mental
capabilities, or lack of experience or knowledge, only if
they are under surveillance or after they have received
instructions regarding safe use of the appliance and understanding the dangers inherent in it. Children should
not play with the appliance. Cleaning and maintenance
that must be performed by the user must not be performed by unsupervised children.
Hazardous situations
Do not start the appliance in hazardous conditions, such
as: gas smell, problems with the plumbing/electrical/gas
system, parts of the appliance under water or damaged,
malfunctioning, disabling or bypassing control and safety devices.
In case of danger, request intervention by qualied per-
sonnel.
In case of danger, switch o the electrical power and gas
supplies only if this can be done in total safety.
4
III
Warnings
Do not entrust children, persons with physical, sensory
or mental disabilities or persons with poor knowledge
and experience with use of the appliance.
Gas component tightness
Before performing any operation on gas ducting compo-
nents, close the gas valve.
Upon completing any procedure, perform the tightness
test according to regulations in force.
Gas smell
If you smell gas:
Do not use electrical devices such as telephones, mul-
timeters or other equipment that may cause sparks next
to the appliance.
Shut o the gas supply by turning the valve o. Disconnect electrical power supply by means of the
external isolation switch in the power supply electrical
panel.
Use a telephone away from the appliance to ask for inter-
vention from qualied personnel.
Poisoning
Ensure the ue gas ducts are tightness and compliant
with the regulations in force.
Upon completing any procedure, ensure components
are tightness.
Moving parts
Switching the appliance o
Disconnecting the power supply while the appliance
is running may cause permanent damage to internal
components.
Except in the event of danger, do not disconnect the
power supply to switch o the appliance, but always and
exclusively act through the provided control device.
In the event of failure
Operations on internal components and repairs may
exclusively be carried out by a TAC, using only original
parts.
In the event of failure of the appliance and/or breakage
of any component, do not attempt to repair and/or restore and immediately contact the TAC.
Routine maintenance
Proper maintenance assures the eciency and good operation of the appliance over time.
Maintenance must be performed according to the man-
ufacturer's instructions (see Chapter 7
p. 28
) and in
compliance with current regulations.
Appliance maintenance and repairs may only be entrust-
ed to rms legally authorised to work on gas appliances
and systems.
Enter into a maintenance contract with an authorised
specialised rm for routine maintenance and for servicing in case of need.
Use only original parts.
The appliance contains moving parts.
Do not remove guards during operation, and in any case
prior to disconnecting the power supply.
Burn hazard
The appliance contains very hot parts.
Do not open the appliance and do not touch internal
components before the appliance has cooled down.
Do not touch the ue gas exhaust before it has cooled
down.
Electrocution hazard
Disconnect the electrical power supply before any oper-
ation on appliance components.
For electrical connections exclusively use compliant
components and according to the specications provid-
ed by the manufacturer.
Ensure the appliance cannot be accidentally switched
back on.
Earthing
Electrical safety depends on eective earthing system,
correctly connected to the appliance and installed ac-
cording to the regulations in force.
Acid ue gas condensate
Discharge the acid condensate of combustion ue gas in
compliance with current exhaust regulations.
Decommissioning and disposal
If the appliance is to be disposed of, contact the manufacturer for its disposal.
Keep the Manual
This Installation, use and maintenance manual must always accompany the appliance and must be handed to
the new owner or installer in the event of sale or removal.
III.2 CONFORMITY
EU Directives and standards
The appliance is certied in accordance with European regulation GAR 426/2016/EU and meet the essential requirements of
the following Directives:
▶
Eciency Directive 92/42/EEC and subsequent modications and additions.
▶
2016/426/EU "Gas Appliances Regulation" as amended and
added.
▶
2014/30/EC "Electromagnetic Compatibility Directive" as
amended and added.
▶
2014/35/EC "Low Voltage Directive" as amended and added.
▶
2006/42/EC "Machine Directive" as amended and added.
Furthermore, they comply with the requirements of the following standards:
▶
EN 677 Specic requirements for condensing boilers with
nominal heat input up to 70 kW.
▶
EN 483 Type C boilers of nominal heat input not exceeding
70 kW.
▶
EN 15502 Gas-red central heating boilers.
Installation, use and maintenance manual – Caldaia 35 Tech
5
Warnings
III
Other applicable provisions and standards
The design, installation, operation and maintenance of the systems shall be carried out in compliance with current applicable
regulations, depending on the Country and location, and in accordance with the manufacturer's instructions. In particular, regulations regarding the following shall be complied with:
▶
Gas systems and equipment.
▶
Electrical systems and equipment.
▶
Heating systems employing condensing boilers.
▶
Environmental protection and combustion products exhaust.
▶
Fire safety and prevention.
▶
Any other applicable law, standard and regulation.
III.3 EXCLUSIONS OF LIABILITY AND
WARRANTY
Any contractual or extra-contractual liability of the
manufacturer for any damage caused by incorrect installation and/or improper use and/or failure to comply
with regulations and with the manufacturer's directions/
instructions shall be disclaimed.
In particular, the warranty on the appliance may be rendered void by the following conditions:
Incorrect installation. Misuse. Failure to comply with the manufacturer's indications on
installation, use and maintenance.
Alteration or modication of the product or any part
thereof.
Extreme operational conditions or however outside of
the operational ranges set forth by the manufacturer.
Damages caused by external agents such as salts, chlo-
rine, sulphur or other chemical substances contained in
the installation water or present in the air of the installation site.
Abnormal actions transmitted to the appliance by the
The Caldaia 35 Tech units have been designed and built to meet
the needs of space heating. These boilers (external modules) can
also be installed outdoors.
The boiler casing is made of ABS, and is approved to resist
weathering with particular regard to the action of UV rays.
The appliance operation will be controlled by an external request (chronothermostat, room thermostat or another operation request) or by the remote control to be installed inside the
heated room.
When the heating service is requested, detected by the external
request or by the remote control, the electronic board starts the
circulation pump, the blower and then the burner.
When the burner starts up, the ame detector checks that the
burner has ignited; in the event of a lack of ame, the electronic
control unit stops the appliance and indicates the block. Resetting is manual.
1.2 DIMENSIONS
Figure1.1 Boiler dimensions
140
In the event of abnormal overheating of the delivery, the boiler
is switched o. The limit thermostat has manual reset.
Mechanical and thermo-hydraulic components
▶
Integrated spiral single tube stainless steel heat exchanger.
▶
Premix modulating burner with 1:9 ratio.
▶
Automatic air vent valve.
▶
High eciency modulating water pump.
▶
System drain tap.
▶
Water temperature probe.
▶
Condensate drain siphon.
Control and safety devices
▶
Flue safety thermal fuse.
▶
3 bar safety valve.
▶
Gas solenoid valve.
▶
Safety thermostat.
▶
Expansion tank.
▶
Water dierential pressure switch.
420
R Water inlet connection Ø 3/4" M
G Gas connection Ø 3/4" M
F System lling connection Ø 1/2"
370
710
B
110
53
RGFA
A Water outlet connection Ø 3/4" M
B Flue gas outlet Ø 80 mm
1488010237
Installation, use and maintenance manual – Caldaia 35 Tech
7
Features and technical data
10
11
12
R
G
1
2
3
4
6
7
8
9
10
11
12
13
14
15
17
18
16
1.3 COMPONENTS
Figure1.2 Boiler internal front view
2
3
4
5
6
7
8
13
14
15
16
17
18
19
20
1
1 SYstem lling tap
2 Heat exchanger
3 Burner unit
4 Flame detector
5 Heating return probe
6 Blower
7 Safety valve
8 Air vent valve
9 Modulating circulator
10 Gas valve
11 System drain tap
12 Heating delivery probe
13 Safety thermostat
14 Ignition electrode
15 Expansion tank
16 Ignition transformer
17 Air intake pipe
18 Venturi
19 Water pressure switch
20 Condensate drain siphon
9
1
Figure1.3 Hydraulic plan of boiler inside
6
5
sc
FA
R Heating return
G Gas inlet
SC Condensate drain
F Cold water inlet
A Heating delivery
1 Flue safety thermal fuse
2 Heat exchanger
3 Burner unit
4 Blower
5 Gas valve
6 Air vent valve
7 Modulating circulator
8 Safety valve
9 System drain tap
10 Heating delivery probe
11 Safety thermostat
12 Expansion tank
13 Air intake pipe
14 Venturi
15 Water pressure switch
16 Condensate drain siphon
17 Bypass
18 SYstem lling tap
8
1
Features and technical data
1.4 TECHNICAL CHARACTERISTICS
Table1.1 Technical characteristics
Caldaia 35 Tech
Heating mode
seasonal space heating energy eciency class (ErP)A
Heat input
Operating point 80/60Nominal heat input
Operating point 50/30Nominal heat inputeciency%106,4
Operating point Tr = 30 °CHeat input 30%eciency%108,6
Operating point Tr = 47 °CHeat input 30%eciency%102,1
Heat loss
Hot water delivery temperature maximum°C80
Ambient air temperature (dry
bulb)
eciency class****
Electrical specications
Power supply
Electrical power absorptionnominalkW0,08
Degree of protectionIP-X5D
Installation data
Gas consumption
Water tting
Gas connection
Flue gas exhaust
CO2 percentage in fumes
Flue temperatureNominal heat inputG20°C69,4
Fumes ow rate
CO emissionppm75,0
NOx emission class-6
Circulating pump data
type of installation-B23P, B33
maximum equivalent length of exhaust ductm15
maximum water pressure in operationbar3,0
maximum ow ue condensatel/h3,4
Water content inside the apparatusl6
expansion tank volumel8
ER Flame detector
EA Ignition electrode
PM Modulating circulator
VG Gas valve
Tra Ignition transformer
TS Safety thermostat
Pacq Water pressure switch
SR Heating delivery probe
EV Blower
EV
TF
TS
SR
Pacq
TF Flue gas thermofuse
SRi Heating return probe
MP Control panel terminal block
Se Connector for optional outdoor temperature
probe
Ta Connector for optional room thermostat
CS Standby contact
ne Black
ce Light blue
ma Brown
ar Orange
gi Yellow
bi White
gr Grey
L Line
N Neutral
Installation, use and maintenance manual – Caldaia 35 Tech
11
Transport and positioning
2 TRANSPORT AND POSITIONING
2
2.1 WARNINGS
Damage from transport or installation
The manufacturer shall not be liable for any damage during appliance transport and installation.
On-site inspection
Upon arrival at the site, ensure there is no transport dam-
age on packing or boiler panels.
After removing the packing materials, ensure the appli-
ance is intact and complete.
Packing
Only remove the packing after placing the appliance on
site.
Do not leave parts of the packing within the reach of
children (plastic, polystyrene, nails...) since they are potentially dangerous.
Weight
The lifting equipment must be suitable for the load. Do not stand under suspended loads.
2.3 MINIMUM CLEARANCE DISTANCES
Keep the appliance away from combustible or ammable materials or components, in compliance with applicable regulations.
In order to allow periodic maintenance of the boiler, the
installation must take place outside, respecting the distances indicated in Figure 2.1
height from the oor of no more than 3 metres.
Figure2.1 Clearances
p.12
and in any case at a
A
H
X
Y
2.2 HANDLING
Handling and lifting
▶
Always handle the appliance in its packing, as delivered by
the factory.
▶
Comply with safety regulations at the installation site.
In the event of handling with forklift or pallet truck,
comply with the handling instructions shown on the
packing.
3 HEATING ENGINEER
3.1 WARNINGS
3.1.1 General warnings
Read the warnings in Chapter III.1
portant information on regulations and on safety.
Compliance with installation standards
Installation must comply with applicable regulations in
force, based on the installation Country and site, in matters of safety, design, implementation and maintenance
of:
heating systems gas systems ue gas exhaust
p. 4
, providing im-
B
A 250 mm
B min 300 mm, max 3000 mm
X 60 mm
ue gas condensate discharge
Installation must also comply with the manufacturer's
provisions.
3.2 BOILER INSTALLATION
1. Fix the mounting jig of the external module to the instal-
lation wall, matching, if already present, the Ø 80 mm hole
for the passage of water pipes and electrical cables with the
shape of the relative hole (Ø 80 mm) indicated on the jig.
At this point, in correspondence with the relative shapes of
the holes indicated on the jig, trace the following points for
drilling on the wall: 3 xing holes (Ø 10 mm) and 1 lower hole
(moved to the right) Ø 10 mm.
2. Remove the mounting jig from the wall and drill the holes
marked out in the previous point: for the 3 upper holes (Ø
Y 60 mm
H 1000 mm
12
3
A
R
Heating engineer
10 mm) for xing the support bracket and the one for the
frame of the external module, a depth of 90 mm is sucient;
the hole (Ø 80 mm) must be drilled for the entire thickness
of the wall.
3. Insert a plastic pipe through the wall into the hole (Ø 80
mm), cut to size.
4. Position the support bracket of the external module in corre-
spondence with the upper holes made (Ø 10 mm, depth 90
mm) and secure it with the supplied wall plugs.
5. Lift the boiler and hook it to the support bracket.
6. Secure the boiler permanently to the wall, fastening the rear
panel by means of the third wall plug supplied.
3.3 HYDRAULIC CONNECTIONS
The hydraulic installer must make the hydraulic connection circuit to the heating system.
To facilitate mounting, the boiler is equipped with a kit of hydronic ttings (Figure 3.1
after removing the tting cover (Figure 5.1
Figure3.1 Hydronic tting kit
p.13
) to be connected to the boiler
p.21
).
weathering and freezing, insulated for thermal dispersion.
Sizing of the pipes, according to the standard circulator,
must grant the nominal water ow required for the correct operation of the heating system.
B. of the following data:
nominal ow at the maximum available head = 1400 l/h Residual pressure head at nominal ow rate = 1,5 m w.c.
3.3.1 System connections
Connect the water pipes between the boiler and the
system as follows:
1. After having removed the tting cover (Figure 5.1
connect the copper 90° ttings supplied to the hydraulic
connections of the boiler service plate, taking care to orient
them towards the wall hole (hole Ø 80 mm, made during the
installation phases of the boiler on the wall).
2. Connect the hydraulic hoses to the water delivery and return
connections (Figure 1.1
gaskets on each connection and taking care to avoid the entry of foreign bodies.
3. Connect a hose connected to a system test pump to the sys-
tem lling tap (Figure 3.3
hydraulic circuit with water; the air in the circuit and in the
pipes will be automatically vented by the venting device on
the boiler.
p. 7
), interposing appropriate
p.14
) on the boiler and ll the
p. 21
),
For the calculation of the total water content to be
loaded in the system it is necessary to add the water
content of the boiler (Table 1.1
A Delivery
R Return
The installer must provide for the construction of a suitably sized
hydraulic connection circuit, taking into account:
A. of the following indications:
Use pipes for heating/cooling systems, protected from
Table3.1 % of glycol, correction factor for pressure drop
% of antifreeze glycolProtection temperature (°C)Correction factor for pressure dropCorrection factor for pressure drop
Connect the boiler safety drains (heating circuit safety
valve) to a drain funnel. The manufacturer is not responsible for any damage due to the opening of the safety
valve in case of overpressure of the system.
3.3.2 System lling
Proceed with the lling of the system as follows.
1. Slightly loosen the cap of the jolly valve on the circulator to
release the air from the system (Figure 3.2
2. Slightly loosen the cap of the jolly valve placed on the top of
the condensing block (Figure 3.4
p.14
).
p. 14
) to release the air
bution terminals to the water content in the pipes.
In order to ensure correct operation of the unit and avoid
freezing of the water during the winter periods (with
possible damage to the unit and the system), it is necessary to add antifreeze glycol to the water in a quantity
proportional to the minimum winter temperatures of
the installation site (see Table 3.1
Low roughness pipes
(copper, stainless steel and plastic)
from the top of the boiler.
3. Open the lling tap (Figure 3.3
4. Check with pressure gauge (Figure 3.3
pressure reaches 1,2 bar (Figure 3.5
5. Open the automatic air purging valves on the system, if any,
and check the air purging process.
6. Make sure that the unit is energized.
7. Send an operating request to the unit for a few seconds. The
circulating pump will be immediately activated.
8. Remove the request before the burner is activated. The cir-
culating pump will continue to circulate the water for the
post-circulation time.
9. If, after the above operations, a decrease in system water
pressure is observed, open again the system lling valve
p. 9
) and of the distri-
p.13
).
Medium roughness pipes
(black and galvanized steel)
p.14
) and let out all the air.
p. 14
) that system
p.14
).
Installation, use and maintenance manual – Caldaia 35 Tech
13
Heating engineer
R
3
until the system pressure reaches 1,2 bar.
10. Repeat steps 7, 8 and 9 until the pressure has stabilised (at
least 1,2 bar).
11. After the operation, make sure that the system lling tap
(Figure 3.3
p.14
) is tightly closed.
Once the lling operation has been completed, re-
member to close the cap of the jolly valve on the circula-
tion pump, to avoid water leaks.
To start the circulation pump only, with the boiler pow-
ered, press the button (Figure 6.1
symbol will appear on the display; after a few sec-
onds turn o the boiler by pressing the button
again (the symbol will appear on the display). The
circulation pump will remain in operation for a few min-
utes. Repeat the operation several times until the pres-
sure of the circuit remains unchanged.
The rst time the unit is switched on, an automatic
system venting cycle is activated (see note in Paragraph
5.6
p.25
).
p. 26
): the
Figure3.3 Pressure gauge and system lling tap
M
Figure3.2 Cap of the jolly valve on ciculating pump
1 Cap of the jolly valve
M Pressure gauge
R System lling tap
1
Figure3.4 Cap of the jolly valve on condensing block
Figure3.5 Pressure gauge
14
3
Heating engineer
3.3.2.1 System water characteristics
Responsibility of the user/operator/installer
The installer, operator and user must assure system water quality (Table 3.2
manufacturer's guidelines may aect operation, integrity and life of the appliance, voiding the warranty.
In order to avoid any scale or deposits on the primary
exchanger, the water in the system must be treated in accordance with the applicable standards. This treatment
is absolutely essential in cases where there are frequent
episodes of water supply or partial or total emptying of
the system.
The hardness of the lling and top-up water brings a certain
amount of calcium into the system. This is attached to the hot
parts including the heat exchanger, thus creating pressure losses and thermal insulation on the active parts. This can lead to
damage.
If the lling and top-up water of the system is outside the values
indicated below, it must be softened. Additives may also be added to keep the calcium in solution. Hardness should be checked
regularly and recorded.
If the above limits are exceeded, a water chemical treatment
must be carried out.
The choice of the type of treatment must be made according to
the characteristics of the water to be treated, the type of plant
and the limits of purity required.
Adhere to the chemical-physical parameters in Table 3.2
and the regulations on water treatment for residential and industrial heating systems.
Table3.2 Chemical and physical parameters of water
When switching on for the rst time, the condensate siphon
must be lled to prevent the combustion gases from backowing through the siphon.
It is advisable, after the rst few months of operation of the appliance, to clean the siphon, which collects also any deposits resulting from the rst passage of the condensate inside the components of the boiler. These deposits could cause the siphon
itself to malfunction.
For charging the siphon proceed as follows (Figure 3.6
1. Unscrew screw P, remove the siphon and ll it with water to
the top point T.
2. Replace the siphon and fasten it with the screw P.
3. Connect the specically designed exible condensate drain
hose to a drainage system.
p.15
):
Figure3.6 Condensate drain siphon
T
P
P Fastening screw
T Top point
3.4 COMBUSTION PRODUCTS EXHAUST
Installation types
For this type of boiler the ue gas exhaust conguration
B23P, B33 can be used.
3.4.1 Flue gas exhaust connection
▶
Ø 80 mm, on the upper side of the boiler (Figure 1.1
The Caldaia 35 Tech is supplied with a anged socket, equipped
with a socket for ue gas analysis (detail PF in Figure 5.6
which must be connected to the combustion chamber after having interposed the silicone gasket, supplied, for the protection
against weathering.
After installing the anged socket, it is important to
check the correct positioning of the gasket G positioned
on the combustion chamber (Figure 3.7
Incorrect positioning of the gasket G can compromise
the correct discharge of the ue gas outside and consequently damage the appliance.
Figure3.7 Correct gasket positioning
p.15
).
G Gasket
G
p.7
).
p.24
),
The combustion air is drawn from the outside of the casing by
Installation, use and maintenance manual – Caldaia 35 Tech
15
Heating engineer
3
means of special louvres located in the lower part of the casing.
3.4.2 How to realize the ue gas exhaust
For the ue gas exhaust without a chimney, the special rainproof
terminal (code OTRM031) is available as an option.
It is not recommended to install the ue terminal near
the boiler if it is close to a wall. This condition could cause
condensation to form on the terminal and on the wall
that would fall on the boiler.
To avoid this type of problem, it is recommended to
take the ue terminal beyond the roof of the building
as shown in Figure 3.8
exhaust horizontally as shown in Figure 3.9
specting the indications given in Paragraph 3.4.3
Figure3.8 Roof vertical ue gas exhaust
p. 16
or to carry out the ue
p. 16
p.16
, re-
.
3.4.3 Possible ue
In case of extension of the duct, follow the instructions below:
▶
Use ducts and terminals (Ø 80 mm) suitable for forced draft
condensing appliances.
▶
For vertical ducts longer than 1,5 m, a curve and a Tee (Figure
3.10
p. 16
) for condensate collection and drainage must
be provided. The condensate must then be evacuated in accordance with the regulations in force, at the same time as
that coming from inside the boiler.
Figure3.10 Flue gas condensate discharge
> 300 mm
Figure3.9 Horizontal ue gas exhaust
The connection of the discharge to the sewerage system
must be made at atmospheric pressure, i.e. by dripping
into a siphoned container connected to the sewerage
system.
Maximum exhaust length
▶
Pipe Ø 80 mm: 15 m
▶
Blower available head: 91 Pa
The maximum exhaust length (or equivalent linear length) is obtained by adding the length of the linear duct to the equivalent
length of each additional curve.
The equivalent lengths of the curves are given in Table
3.3
p.16
.
Table3.3
Elbow Ø 80 mm
90° elbow1,5 m
45° elbow1,2 m
3.5 PUMP ANTIFREEZE AND ANTILOCK
FUNCTION
Antifreeze function
If the delivery temperature detected by the temperature probe
falls below +12 ºC (antifreeze temperature ON), the control
board starts the circulation pump and the ignition of the burner
at the minimum power.
When the delivery water temperature reaches +30 ºC (antifreeze
temperature OFF), the control board will switch the burner o.
16
3
Heating engineer
Electrical and gas continuity
The antifreeze function is only eective if the power
on the bottom of the boiler (Figure 1.1
▶
Install an anti-vibration connection between the appliance
and the gas piping.
and gas supplies are assured. Otherwise, antifreeze uid
might be required.
Pump anti-lock function
In order to prevent the circulation pump from locking, the
Caldaia 35 Tech is equipped with an anti-lock function which,
every 24 hours of inactivity, operates the circulation pump for
30 seconds.
Mandatory shut-o valve
▶
Provide a gas shut-o valve (manual) on the gas supply line,
next to the appliance, to isolate it when required.
▶
Perform connection in compliance with applicable regula-
tions.
Gas pipes sizing
The gas pipes must not cause excessive pressure drops and, consequently, insucient gas pressure for the appliance.
Electrical continuity
Supply gas pressure
The pump anti-lock function is only eective if the power supply is guaranteed.
This appliance is equipped for a maximum gas supply
pressure of 50 mbar.
3.6 FUEL GAS SUPPLY
The appliance's gas supply pressure, both static and dynamic,
must comply with Table 3.4
Gas connection
▶
3/4" M
Table3.4 Gas network pressure
Product categoryCountries of destination
AL, AT, BG, CH, CY, CZ, DK, EE, FI, GR, HR, IT, LT, LV, MK, NO, RO, SE,
II
2H3B/P
II
2H3P
II
2ELL3B/P
II
2Esi3P
II
2E(R)3P
II
2E(S)3P
II
2E3P
II
2E3B/P
II
2L3B/P
II
2L3P
II
2EK3P
II
2EK3B/P
I
2EK
I
2ELL
I
2E(S)
I
2E(R)
I
2Esi
I
2H
I
2L
I
2E
I
3B/P
The appliance gas supply pressure, both static and dynamic, must comply with the values in the Table, with a tolerance of ± 15%.
Before proceeding with the construction of the system, the in-
G20G25G25.3G30G31
external temperatures.
staller must:
▶
Check that the gas used corresponds to that for which the
appliance has been designed (see nameplate).
▶
Check that the ow rate of the gas meter is such as to ensure
the simultaneous use of all the devices connected to it.
If it is necessary to change the type of gas supply to
the boiler, contact the TAC that will make the necessary
changes.
Although it is normal for the inlet pressure to decrease
during the operation of the appliance, it is important to
check that there are no excessive uctuations in the inlet
Under no circumstances shall the installer be authorised
to carry out such operations.
pressure. In order to limit the extent of these variations, it
is necessary to appropriately dene the diameter of the
gas inlet pipe to be adopted based on the length and
pressure drop of the pipe itself, from the gas meter to
the boiler.
If uctuations in the gas distribution pressure happen,
it is advisable to insert a special pressure stabiliser upstream of the gas inlet to the boiler. In case of LPG
supply, all necessary precautions must be taken to avoid
Vertical pipes and condensate
▶
Vertical gas pipes must be tted with siphon and discharge
of the condensate that may form inside the pipe.
▶
If necessary, insulate the piping.
LPG pressure reducers
With LPG the following must be installed:
▶
A rst stage pressure reducer, close to the liquid gas tank.
▶
A second stage pressure reducer, close to the appliance.
freezing of the combustible gas in case of very low
Gas supply pressure [mbar]
37
4 ELECTRICAL INSTALLER
Do not power and/or start the boiler before lling the
hydraulic system, as this may damage the internal hydraulic components.
4.1 WARNINGS
General warnings
Read the warnings in Chapter III.1
portant information on regulations and on safety.
Compliance with installation standards
Installation must comply with applicable regulations in
force, based on the installation Country and site, in matters of safety, design, implementation and maintenance
of electrical systems.
Installation must also comply with the manufacturer's
provisions.
Live components
After placing the appliance in the nal position, and pri-
or to making electrical connections, ensure not to work
on live components.
p. 4
, providing im-
Earthing
The appliance must be connected to an eective earth-
ing system, installed in compliance with regulations in
force.
It is forbidden to use gas pipes as earthing.
Cable segregation
Keep power cables physically separate from signal ones.
Do not use the power supply switch to turn the appliance on/o
Never use the external isolation switch to turn the appli-
ance on and o, since it may be damaged in the long run
(occasional blackouts are tolerated).
To switch the appliance on and o, use only the control
device provided for this purpose (remote control or external request).
4.2 ELECTRICAL POWER SUPPLY
The cables inside the boiler must be routed through the
P1 and P2 cable glands (Figure 4.2
make a hole in the cable gland, slightly smaller than the
cable, so that the air does not pass through.
p. 19
). To do this,
18
4
B
1
2
3
B
CR
Electrical installer
How to connect the power supply
1. Remove the ABS casing, the tting cover and the front panel
(Paragraph 5.2
2. Unscrew the two screws and remove the terminal block cov-
er plate (Figure 4.1
3. Perform connections as shown in Figure 4.1
4. The ground wire to the terminal marked with the ground
symbol.
5. The neutral cable to the terminal marked with the letter N.
6. The line cable to the terminal marked with the letter L.
Figure4.1 Electrical power supply
p.20
).
p.19
).
p.19
.
A
SeSe
TaTa
N
Figure4.2 Cable gland position and remote control connection detail
to the external module
P1 P2
A
SeSe
TaTa
N
L
A Plate
B Terminal block
1 Neutral
2 Yellow/Green
3 Line
4.3 CONTROL DEVICE
To make the electrical connections of the room thermostat (TA)
or of the remote control (optional OCDS006) or of an external
request, proceed as follows (Figure 4.2
1. Remove the bridge on the Ta-Ta contacts and then connect
the two non-polarized conductors on the Ta-Ta contacts.
2. After the operation, reassemble the plate, the front panel,
the tting cover and the ABS casing.
p.19
).
L
P1 - P2 Cable glands
A Plate
B Terminal block
CR Room thermostat or remote control (OCDS006)
4.4 CONTROL THROUGH OPTIONAL
OCDS006 REMOTE CONTROL
RECOMMENDED SOLUTION
The use of the remote control allows you to adjust the operation of the boiler to the desired temperature, in the time programming chosen, provides a series of information on the status
of operation and/or boiler lock and also allows the resetting of
some locks.
For the electrical connection of the remote control, follow the
instructions given in Paragraph 4.3
The remote control is electrically connected to the boiler
by means of two non-polarized conductors through
which it receives the power supply necessary for its operation and carries out communication between the two
devices.
p.19
.
4.5 POSITIONING THE CONTROL SYSTEM
Install the chosen thermostat/control system according to the
following guidelines:
▶
At about 1,5 m from the oor, protected against air draughts,
direct exposure to sun rays and direct heat sources (lamps,
hot air ow from the unit itself, etc.).
Installation, use and maintenance manual – Caldaia 35 Tech
19
First start-up
▶
If possible, do not place the control system on walls bordering the outside, to avoid false temperature readings
and therefore aect system operation. If this is not possible,
shield the control system by placing a sheet of insulating
material (cork, polystyrene or other similar) between the
control system and the wall.
5
contact between the terminals must be closed. When
these are closed, the boiler will stop, while when they are
reopened, the boiler can be activated according to what
has been set on the other controls (room thermostat or
remote control).
By following the above guidelines, unwanted starting
and stopping of the system can be avoided and optimal
comfort in the heated space can be guaranteed.
4.6 OPERATION VIA CENTRALISED
EXTERNAL REQUEST
The unit's operation can also be controlled by means of an external request. This request, activated for example by a programmable timer or another system, can be used for the centralised
activation or deactivation of several boilers.
For the electrical connection of the external request, follow the
instructions below:
1. Remove the ABS casing, the tting cover and the front panel
(Paragraph 5.2
p.20
).
2. Access the CS terminal block on the left side of the control
panel (Figure 1.5
p.11
).
3. Connect the external request to the terminal block.
4. After the operation, reassemble the plate, the front panel,
the tting cover and the ABS casing.
The terminals have open contacts from the factory
(active request). If the boiler is to be switched o, the
5 FIRST START-UP
In the case of centralized management of several boilers,
each request must be connected through the interposition of a relay.
For further information on the operation and use of
boilers in this mode, please contact the Robur technical
service.
4.7 OPERATION WITH EXTERNAL
TEMPERATURE PROBE OPTIONAL
It is possible to operate the boiler with a variable water ow temperature depending on the outdoor temperature.
To do this, it is necessary to install an outdoor temperature
probe (available as OSND007 optional) and connect it to the SE
terminals of the boiler terminal block (Figure 1.5
The outdoor temperature probe provides the temperature value of the outdoor air and according to this the electronic board
of the boiler will change the water supply temperature. The extent of the temperature correction depends on the temperature
control value Kd set (using the board parameter P16 - see Figure
5.4
p.23
).
p.11
).
First start-up entails checking/setting up the combustion parameters and may exclusively be carried out by a
Robur TAC. NEITHER the user NOR the installation technician is authorised to perform such operations, under
penalty of voiding the warranty.
5.1 PRELIMINARY CHECKS
5.1.1 Preliminary checks for rst start-up
Upon completing installation, before contacting the TAC the installer must check:
▶
Water, electrical and gas systems suitable for the required
capacities and equipped with all safety and control devices
required by the regulations in force.
▶
Absence of leaks in the water and gas systems.
▶
Type of gas for which the appliance is designed (natural gas
or LPG).
▶
Supply gas pressure complying with the values of Table
3.4
p.17
.
▶
Power supply mains complying with the appliance's rating
plate data.
▶
Appliance correctly installed, according to the manufacturer's instructions.
▶
System installed in a workmanlike manner, according to national and local regulations.
5.1.2 Abnormal or hazardous installation situations
Should any abnormal or hazardous installation situations be
found, the TAC shall not perform rst start-up and the appliance
shall not be commissioned.
These situations may be:
▶
Failed compliance with minimum clearances.
▶
Insucient distance from combustible or ammable materials.
▶
Conditions that do not warrant access and maintenance in
safety.
▶
Appliance switched on/o with the main switch, instead of
the provided control device.
▶
Appliance defects or faults caused during transport or installation.
▶
Gas smell.
▶
Non-compliant mains gas pressure.
▶
Non-compliant ue gas exhaust.
▶
All situations that may involve operation abnormalities or
are potentially hazardous.
5.1.3 Non-compliant system and corrective actions
Should the TAC nd any non conformities, the user/installer is
bound to perform any corrective procedures required by the
TAC.
After performing the remedial actions (the installer's responsibility), if the TAC deems that safety and conformity conditions
are in place, rst start-up may be eected.
5.2 HOW TO ACCESS THE BOILER
For all check and maintenance operations it is necessary to remove the front panel of the boiler as follows (Figure 5.1
1. Remove the fastening screws 1 located to the side of the
casing ange, and pull it out as shown in Figure 5.1
p.21
p.21
):
.
20
5
3
2
4
First start-up
2. Remove the fastening screws 2 located on the upper and
lower side of the casing, grasp the ABS casing and pull it out
towards you.
3. Remove the fastening screws 3 located on the lower side of
the boiler and remove the tting cover.
To work on the front side of the boiler, proceed as follows:
1. Remove the fastening screws 4 located in front of the front
panel.
2. Grab the front panel and pull it out towards you.
To work on the side panels of the boiler, proceed as follows:
1. Remove the fastening screws 5 located in the front edge of
the side panel.
2. Grab the base of the panel and, after moving it sideways, pull
it out by lifting it up.
Figure5.1 Accessing the boiler
1
B
A
2
1
Figure5.2 Accessing the control panel
1
1
1
1
3
3
4
D
A ABS casing ange
B ABS casing
C Fitting cover
D Front panel
E Side panel
To work on the internal electrical connections of the control panel, proceed as follows (Figure 5.2
p.21
):
1. Simultaneously grab the control panel support brackets by
widening them and turn the panel upside down by rotating
it down.
2. Unscrew the four xing screws 1 and remove the cover
upwards.
5.3 ELECTRONIC BOARD PARAMETERS
SETTING
Before commissioning the operation of the device to the
user, the operating parameters must be set or simply
checked.
To access the parameters menu and adjust the value of the desired parameter, follow the procedure described below (refer to
Figure 5.3
1. Press key to select the OFF mode, displayed with the
2. Hold at the same time the and keys and wait until on
3. Use the keys and of the space heating circuit to
4. Press the and keys of the 'S' side to change the pa-
5. Press the key to conrm and wait for the display to
6. To exit the parameter menu, hold down the and keys
p.22
):
symbol.
the display appears the symbol with the message ‘P00’,
and release the and keys.
select the parameter to be edited.
rameter value.
stop blinking, to make the adjustment eective.
simultaneously and wait for the symbol to appear on the
Installation, use and maintenance manual – Caldaia 35 Tech
21
First start-up
5
display.
The operating parameters are shown in Table 5.1
p.22
and are
visible on the internal display of the boiler.
Figure5.3 Access and setting of boiler parameters
Table5.1 Electronic board parameters
Parameter DescriptionRangeDefaultSetting
P00Boiler model selection0 - 1099 = Caldaia 35 Tech
P01Boiler type selection0 - 555 = heating only
Gas type selection
P02
WARNING: before changing the parameter value, read the instructions in Paragraph 5.5
p.25
.
P03Heating temperature setting0 - 10
Heating run-up
P04
It is possible to set the time, during the start-up phase, that the boiler takes to
reach the maximum set power (for the space heating service).
Heating timing
P07
You can set the minimum time in which the burner is kept o once the heating
temperature has reached the setpoint.
Post-circulation heating timing
It is possible to set the operating time of the pump, in heating mode, after the
P08
main burner has been switched o due to the intervention of the room thermostat.
Heating blower minimum speed adjustment
It is possible to set the minimum speed of the fan for the heating service, which
P12
corresponds to the minimum power of the burner during a heating request (see
Figure 5.5
p.24
and the type of gas (parameter P02).
Heating blower maximum speed adjustment
It is possible to set the maximum speed of the fan for the heating service, which
P13
corresponds to the maximum power of the burner during a heating request (see
Figure 5.5
and the type of gas (parameter P02).
Starting step adjustment
P14
It is possible to set the fan speed during the start-up phases. The value is preset
according to the set power (parameter P00) and the type of gas (parameter P02).
Setting the climate curve (only with outdoor probe connected)
An outdoor temperature probe may be connected and acts by automatically
changing the delivery temperature according to the measured outdoor temperature. The extent of the correction depends on the set Kd heating control value
P16
(see Figure 5.4
delivery temperature Tm and the minimum outdoor temperature Te, taking into
account the degree of insulation of the house. The values of the delivery temperatures Tm refer to standard systems 30-80 °C or oor systems 25-45 °C. The type of
system can be set using parameter P03.
). The value is preset according to the set power (parameter P00)
p.24
). The value is preset according to the set power (parameter P00)
p.23
). The choice of the curve is determined by the maximum
0 - 10
0 - 41
0 - 9036
0 - 9036
45 - P13--Value in hertz (1 Hz = 30 RPM)
P12 - 203--Value in hertz (1 Hz = 30 RPM)
P10 - 203--Value in hertz (1 Hz = 30 RPM)
0 - 3015
0 = G20, G25, G25.3
1 = LPG, G30, G31
0 = standard (30-80 °C)
1 = reduced (25-45 °C)
0 = disabled
1 = 50 s
2 = 100 s
3 = 200 s
4 = 400 s
Value in multiples of 5 s (default 36 x 5
= 180 s)
Value in multiples of 5 s (default 36 x 5
= 180 s)
The numbering of the value corresponds to the 'Kd' curves of the graph
(see Figure 5.4
p.23
)
22
5
Te (°C)
35
4
Tm (°C)
35
30
25
First start-up
0-10 V industrial bus drive enable
P18
The 0-10 V industrial bus input can be enabled or disabled to set burner power or
delivery temperature via the external bus.
Min heating setpoint
P19
It is possible to set the minimum user-adjustable heating temperature.
Max heating setpoint
P20
It is possible to set the maximum user-adjustable heating temperature.
Δt delivery-return setpoint
P22
It is possible to set the temperature dierence between delivery and return.
Modulating pump minimum speed
P23
It is possible to set the minimum speed value of the modulating pump during a
request for space heating operation.
Modulating pump maximum speed
P24
It is possible to set the maximum speed value of the modulating pump during a
request for space heating operation.
Modbus address
P26
Not used
Modbus communication baud rate
P27
Not used
Modbus mode
P28
Not used
Post-circulation heating Δt
P29
It is possible to set the temperature dierence from the main burner shutdown
due to the room thermostat, to the pump shutdown for the heating service.
Heating antifreeze temperature setting
P31
It is possible to set the temperature of the water in the heating system at which
the antifreeze protection is activated.
Flowmeter enable
P32
Not used
Minimum water ow setting
P33
Not used
0 - 20
20 - 4030Value in °C
40 - 9085Value in °C
0
10 - 40
50 - 7060Value in percentage
70 - 100100Value in percentage
0 - 2510Value in °C
5 -128Value in °C
0 = disabled
1 = temperature control mode
2 = power control mode
0 = disabled
20
Value in °C
Figure5.4 Climatic curves
5 MAX
80
75
70
65
60
55
50
45
40
35
30
MIN
Tm Delivery temperature
Te Outdoor temperature
Kd = 10
Kd = 5
Kd = 0
Kd = 25
-10
Kd = 20
-5
Kd = 15
-15-20
Kd = 30
0
5
Kd Heating control value
3025201510
Installation, use and maintenance manual – Caldaia 35 Tech
23
First start-up
G25.3
34
Ti (kW)
Freq (Hz)
A
Figure5.5 Heat input/blower frequency diagram
30
26
5
22
18
14
10
6
2
35557595115135155175
Ti Thermal inputFreq Frequency
Table5.2 Minimum and maximum blower frequencies in heating mode
Figure5.6 Socket for ue gas analysis and gas valve
G30
G20
G25
G31
PF
5.4 COMBUSTION PARAMETERS CHECK
The CO2 value should be checked with casing assembled, while the gas valve should be adjusted with the
casing open.
To check and calibrate the CO
power, proceed as follows, referring to Figure 5.6
▶
Power the boiler.
▶
Open the gas valve on the boiler and check that the valves
connecting to the system are open.
▶
Activate the heating request to the boiler, through the control devices provided, and provide an adequate thermal load
for carrying out the verication operations.
▶
Insert the ue gas analyser into the ue gas analyser socket
PF (Figure 5.6
p.24
value at maximum and minimum
2
) and turn it on.
p.24
.
1
2
PF Flue gas analysis socket
A Protection screw
1 Gas ow adjustment screw
2 Oset adjustment screw
5.4.1 Minimum heating power
1. Activate the chimney sweep function by pressing for 7 sec-
onds the
fore being forced out of the function is 15 minutes.
2. Check that the CO2 value complies with Table 1.1
otherwise unscrew protection screw A and adjust screw 2 of
key (Figure 6.1
p.26
). The maximum time be-
p. 9
,
24
5
D
First start-up
the oset regulator with a 4 hex key. To increase the value of
CO2 it is necessary to turn the screw clockwise and vice versa
if you want to decrease it.
3. Once completed the adjustment, tighten the protection
screw A on the oset adjuster.
5.4.2 Maximum heating power
1. Press the key of the heating side for the calibration of
the maximum heating power.
2. Check that the CO2 value complies to the value shown in Ta-
ble 1.1
p.9
.
3. If this is not the case, adjust the gas ow adjuster using the
screw 1 (Figure 5.6
the screw counterclockwise and vice versa if you want to decrease it.
4. After each adjustment on screw 1 of the gas ow adjuster,
you have to wait about 30 seconds for the boiler to stabilize
itself to the set value.
5. Press the key of the space heating circuit and check
that CO2 value at minimum power has not changed. If so,
repeat the calibration described in previous Paragraph
5.4.1
p.24
.
6. Deactivate the chimney sweep function by switching the
boiler to OFF mode using the button ( symbol
appears on the display).
7. Disconnect the ue gas analyzer and screw the cap of the
ue gas analysis socket back on.
8. Replace the boiler front panel.
p. 24
). To increase the CO2 value turn
Figure5.7 Gas changeover
1
3
2
G
V
2
2
C
C
3
5.5 GAS CHANGEOVER
Paragraph reserved exclusively to TACs.
The following instructions apply to both the conversion
from natural gas (G20) to any other gas and vice versa.
Check that the gas supply line is suitable for the new fuel
type used to supply the unit.
How to change gas (Figure 5.7
1. Loosen the two screws 1 from the xing bushing, and re-
move the air intake pipe.
2. Unscrew the pipe connection connecting the gas valve to
the venturi.
3. Unscrew the three xing screws 2 of the venturi V with a 10
mm wrench.
4. Unscrew the two screws 3 and press on the back side of the
venturi body C.
5. Replace the venturi with the one suitable for the type of gas
to be used and make sure that the orientation of tooth D is
downwards on the aluminium body.
6. Reassemble the components, proceeding in the opposite se-
quence to the disassembly operations, making sure that the
gasket G is reassembled.
7. Set the boiler to operate with the new type of gas, chang-
ing the value of parameter P02 (gas type selection) from the
control panel (Paragraph 5.3
8. Proceed to the adjustment of the CO2 value, as described in
Paragraph 5.4
p.24
.
9. Replace the sticker indicating the gas type on the appliance
1. Remove the ABS casing of the boiler (see Paragraph
5.2
p.20
).
2. Power the boiler.
The ignition system will automatically activate the
system venting cycle function shown in the display
with the code F33, which lasts 2 minutes (except the
rst time the appliance is switched on, where the duration is 5 minutes).
When function F33 is active, the pump is activated at intervals and the burner ignition request is disabled. The
regular operation of the boiler is allowed only when the
operation is completed.
3. Make sure that the circulator is not locked.
4. If it is locked, wait for the circulator to perform the automatic
unlocking function (duration 3 minutes).
5. If the circulator is still locked, reactivate the automatic un-
locking function of the circulator (a further 3 minutes) by
power cycling the boiler.
6. At the end of the above operations, open the gas tap.
7. To switch the boiler to the heating operating mode, press
the key; the xed symbol will appear on the dis-
play, indicating that the function has been activated.
Installation, use and maintenance manual – Caldaia 35 Tech
25
Normal operation
5
1
6
234
6
8. When the room thermostat contact or the remote control
enable is closed, the burner ignition will start.
9. In case of lack of ame, the board repeats the ignition opera-
tions again after the post-ventilation (20 seconds).
10. It may be necessary to repeat the ignition operation sever-
al times to remove any air in the gas pipe. Before repeating
the operation, wait about 5 seconds from the last ignition
attempt and unlock the boiler from error code E01 by pressing the reset key.
11. Check the system pressure. if a decrease is observed, open
the lling tap again until the pressure reaches 1,2 bar. When
done, close the lling tap again.
5.7 SWITCHING OFF
To switch o the unit, select the OFF mode using the
key (Figure 6.1
mode ( symbol appears on the display), ONLY the antifreeze
function (system water) and the boiler pump anti-lock function
remain active.
As it is harmful to the appliance, it is essential to avoid
p.26
). In this way the appliance is in standby
6 NORMAL OPERATION
switching o the appliance by removing the power
supply to the external module.
For the antifreeze and pump anti-lock functions to be
active, the boiler must be left powered.
5.8 PROLONGED PERIODS OF INACTIVITY
To switch o the unit, select the OFF mode using the key
(Figure 6.1
( symbol appears on the display).
Switch o the power using the main switch, outside the boiler,
and close the gas tap upstream of the appliance.
p.26
). In this way the appliance is in standby mode
By removing the power supply, the automatic antifreeze and pump anti-lock functions will be disabled.
If it is expected that during the period of inactivity
the external temperature may fall below zero, it is
therefore advisable NOT to cut o the electrical and
gas supply to the appliance.
This section is for the end user.
The use of the device by the end user is only permitted
Figure6.1 External module control panel
1 Heating temperature adjustment keys
2 INFO key: press once to view the temperatures and other informations - hold for 5 seconds, in o operating mode, to view the last 5 faults
3 Operating mode selection key: heating only / OFF
4 RESET key: faults reset - chimney sweep function activation (hold for 7 seconds)
5 Parameter value adjustment keys / hold the keys at the same time for 5 seconds to activate display backlighting for 10 minutes
6 Display
after the Robur authorised TAC has completed the
rst start-up.
26
6
4567
121314
15
Figure6.2 Boiler display icons
Normal operation
3
2
1
1 Parameter number indication or displayed info code
2 Parameter programming function active
3 Not used
4 Not used
5 Not used
6 Not used
7 Temperature display / setpoint / parameter value
8 OpenTherm communication present (remote control)
6.1 WARNINGS
General warnings
Prior to using the appliance carefully read the warnings
in Chapter III.1
on regulations and on safety.
First start-up by TAC
First start-up may exclusively be carried out by a Robur
TAC (Chapter 5
Never power the appliance o while it is running
p. 4
, providing important information
p.20
).
8
9
10
11
≤ 33%>33%<66% > 66% <100%
9 Insucient system water pressure signal
10 Flame presence signal / it also indicates, on 3 percentage levels, the
modulating power level of the boiler
11 Operation in DHW mode enabled (only for boilers having this function)
12 Resettable error signal
13 O operating mode
14 Non resettable error signal
15 Operation in heating mode enabled
ll the system according to the instructions in Paragraph
3.3.2
p.13
and 3.3.3
Check on the pressure gauge that the system pressure
is 1,2 bar.
If there is no water in the system or if the system pressure
is less than 1,2 bar, appears on the display of the control panel (Figure 6.2
the remote control (if any). When the correct pressure is
restored, the error code disappears.
p.15
.
p.27
), while error E04 appears on
6.3 OPERATION WITHOUT REMOTE
CONTROL
NEVER power the appliance o while it is running (except in the event of danger, Chapter III.1
the appliance or system might be damaged.
Routine switching on/o
The appliance may exclusively be switched on/o by
means of the suitably provided control device.
Do not switch on/o with the power supply switch
Do not switch the appliance on/o with the power supply switch. This may be harmful and dangerous for the
appliance and for the system.
6.2 PRELIMINARY CHECKS
Checks before switching on
Before switching on the appliance, ensue that:
Gas valve open. Appliance electrical power supply (main switch ON). The fumes exhaust duct is free and correctly connected
to the fumes exhaust system.
The hydraulic circuit has been lled. If this is not the case,
p. 4
), since
6.3.1 Turning the external boiler on and o
1. Open the gas tap and provide electrical power.
2. Switch on the appliance by closing the two-pole switch (to
be provided by the installer).
3. Press the key on the control panel of the boiler (Fig-
ure 6.1
p.26
) and select the desired operating mode.
4. The xed symbol that appears on the display, corresponding
to the operating mode, indicates that the function has been
activated.
6.3.2 Heating mode
In this operating mode the boiler provides heating:
1. Press the key (Figure 6.1
bol will appear on the display, indicating that the function
has been activated.
2. Whenever there is a demand for space heating, the auto-
matic ignition system will ignite the burner; the operation is
represented by the ignition of the symbol with an intermittent signal on the display.
After a long period of unit inactivity or at the rst start-up,
it may be necessary to repeat the ignition operation a
few times due to the presence of air in the gas piping.
p.26
), the xed sym-
Installation, use and maintenance manual – Caldaia 35 Tech
27
Maintenance
7
3. If the boiler does not start up, the relative error will be indi-
cated both on the remote control and on the internal panel
of the boiler. It will be possible to reset the boiler either remotely or directly on the boiler panel.
4. Program the operation according to your needs.
For operation of the remote control refer to the instructions supplied with it.
6.3.3 Adjust the heating temperature
The temperature is adjusted using the and keys of the
heating side (Figure 6.1
p.26
):
1. Pressing the key decreases the temperature.
2. Pressing the key increases the temperature.
3. The heating temperature control range is from a minimum
of 30 °C to a maximum of 80 °C.
6.3.4 OFF mode
In this operating mode the boiler no longer provides heating,
but the antifreeze and pump anti-lock systems remain active.
To switch the boiler to the OFF operating mode, press the
key; the xed symbol will appear on the display, indicating that the function has been activated.
If the boiler was previously in operation, it is switched o and
the post-ventilation and post-circulation functions are activated.
If you decide to shut down the boiler for a long period of time,
secure it by operating in one of the following two ways:
1. Call the TAC that will empty the water system, where there
is no provision for the use of antifreeze, and disconnect the
power supply, water and gas.
2. Leave the boiler in the OFF operating mode, keeping the
power and gas supply active, so that the antifreeze function
and the pump anti-lock function can be activated.
6.3.5 Pump antifreeze and anti-lock function
Refer to Paragraph 3.5
p.16
.
6.4 REMOTE CONTROL OPERATION
OPTIONAL
For switching on, adjusting and switching o the boiler,
refer to the instructions supplied with the remote control.
INFO MENU DISPLAY
To view the boiler data from Info menu you have to:
1. Press the key (Figure 6.1
displayed on the left side of the screen and its value will be
displayed on the centre of the screen.
2. To scroll through the list of displayable data, use the and
keys of the heating side .
3. Press the key to exit the Info menu.
Table 6.1
p.28
shows the list of Info menu displayable data.
Table6.1 List of displayable data from menu Info
Info codeDescription
d0Not used temperature
d1Outdoor probe temperature
d2Blower speed
d3Not used temperature
d4Return probe temperature
Maintenance operations described herein may exclu-
sively be performed by the TAC or skilled maintenance
technician.
Any operation on internal components may exclusively
be performed by the TAC.
Before performing any operation, switch o the appli-
ance by means of the control device and wait for the end
of the shutdown cycle, then disconnect power and gas
supply, by acting on the electrical disconnector and gas
valve.
It is recommended that the following operations and checks be
carried out each year:
▶
Combustion circuit functionality and heat exchange control:
Burner and ue exhaust duct inspection Cleaning of burner and water/ue exchanger (if applica-
ble)
Flame ignition/detection system control
▶
Hydraulic circuit and internal components functionality
check:
Hydraulic circuit control (pipes, gaskets) Expansion tank Control and safety devices Water temperature probe
▶
Periodic analysis of combustion, in accordance with regulations in force
7.1 HYDRAULIC BOILER EMPTYING
Whenever there is a need to empty the boiler, proceed as follows:
▶
Switch o the boiler by pressing the button.
▶
Turn o the main power switch.
▶
Wait until the boiler has cooled down.
▶
Connect a hose emptying point and connect the other end
of the hose to a suitable drain.
▶
Open the drain tap (Figure 7.1
▶
When all the water has drained o, close the drain tap.
p.29
).
28
8
Figure7.1 System drain tap position
RS Drain tap
Diagnostics
RS
8 DIAGNOSTICS
In the event of a malfunction of the appliance, before contacting
the TAC, make sure that:
▶
There is a full electricity supply.
▶
The gas is supplied.
▶
The gas pressure is within the indicated limits.
▶
The remote control (if any) is set so that the appliance is
switched on and the appliance does not signal a fault.
8.1 SYSTEM PRESSURE RESTORE
In case of malfunction of the appliance, with pressure inside the
hydraulic circuit lower than 0,3 bar, which can be seen through
the pressure gauge located on the instrument panel inside the
boiler, it is necessary, after having identied and solved any leaks
Table8.1 Error codes
CodeFaultPossible causeRemedial actionReset
Without ame ignition
No gas supplyCheck the gas supply network
Broken or badly positioned ignition electrodeReplace
Gas valve faultReplace
Slow ignition set too lowAdjust the minimum or slow ignition
Inlet pressure of gas valve too high (only for LPG
E01Flame lockout
Safety thermostat trip
E02
(95 °C)
Flue safety thermal
E03
fuse (102 °C)
supply)
With ame ignition
Power supply with phase and neutral invertedConnect the power supply correctly
Flame detector faultReplace
Detection electrode cable disconnectedCheck the electrical connection
Phase-to-phase electric current
Hydraulic circuit overheatingRemove the cause of the lack of heat exchange
Thermostat cable broken or disconnectedCheck the electrical connection
Thermostat faultReplace
Hydraulic circuit overheatingRemove the cause of the lack of heat exchange
Thermal fuse faultReplace
Thermal fuse cable disconnectedCheck the electrical connection
on the circuit, to proceed with the restoring the correct amount
of water (with glycol, if needed), as indicated in Paragraph
3.3
p.13
.
8.2 ERROR CODES
To display the last 5 fault codes, from the most recent in chronological order, activate the o mode using the key (Figure
6.1
p.26
) and press and hold the key for 5 seconds.
▶
To scroll through the list of stored faults, use the and
keys of the heating side .
▶
To reset the fault history, press the reset key .
▶
To exit the display press the key.
Manual reset (press
key) (1)
Check the maximum calibration pressure
If the voltage measured between neutral and
earth is almost the same as the one measured
between phase and earth, eliminate the
dispersions
Manual reset (press
key) (1)
Manual reset (press
key) (1)
Manual reset (press
key) (1)
Installation, use and maintenance manual – Caldaia 35 Tech
29
Diagnostics
CodeFaultPossible causeRemedial actionReset
Insucient water pressure in the system (less
Low system water
E04
pressure
E05Heating probe fault
E06 (2)DHW probe fault
E10 (4)False safety tripIncorrect setting of parameter P32 to value 1Set parameter P32 to 0Automatic
E14 (3)Air pressure switch
E15Return probe fault
E16Blower fault
E18Low water ow
Generic internal elec-
E21
tronic board error
Parameter program-
E22
ming request
Not compatible
E31
remote control
Communication error
E32
between boiler board
and Modbus board
E35Parasitic ame
Wrong power supply
E40
voltage
than 0,3 bar)
Water pressure cable disconnectedCheck the electrical connection
Water pressure switch faultReplace
Probe fault or out of calibration (nominal resistance 10 KΩ at 25 °C)
Probe connector wet or disconnectedCheck the electrical connection
Probe fault or out of calibration (nominal resistance 10 KΩ at 25 °C)
Exhaust duct obstructedCheck the ue exhaust duct
Pressure switch disconnectedCheck the electrical connection
Pressure switch faultReplace
Probe fault or out of calibration (nominal resistance 10 KΩ at 25 °C)
Probe connector wet or disconnectedCheck the electrical connection
Blower board faultReplace
Blower faultReplace
Power supply cable faultReplace
Clogged exchangerClean the heat exchanger or replace it
Circulator fault or dirty impellerClean the impeller or replace the circulator
Wrong recognition of a signal by the microprocessor of the modulation board
Microprocessor memory lossParameter reprogramming
The remote controller connected to the boiler is
not compatible with the electronic board
No electrical connectionCheck the electrical connection
Modbus board faultReplace
Flame detector faultClean or replace
Supply voltage out of operating range (≤160
Volts)
Load the system at the required pressure.
Automatic
Replace
ReplaceAutomatic
Replace
If the modulation board does not reset the error
automatically, replace it
Replace with a compatible oneAutomatic
Check the power supply (the error is automatically reset as soon as the power supply voltage
returns to the required limits)
Automatic
Manual reset (press
key) (1)
Automatic
Automatic
Automatic
Automatic
Manual reset (disconnect
the power supply)
Automatic
Manual reset (press
key) (1)
Automatic
8
1 For model 100.2 boilers, press the key on the master control panel.
2 Only for boilers with DHW production.
3 Only for 100.2 boiler.
4 Not applicable to 100.2 boilers.
Table8.2 Signalling codes (visible ONLY on the boiler display)
CodeFunctionDescription
F07
F08
F09 (1)
F33 (2)
FH (1)Fast H2O
1 Only for boilers with DHW production.
2 Not applicable to 100.2 boilers.
Chimney sweep
function active
Heating antifreeze
function
DHW antifreeze
function
System air purge cycle
in progress
It is activated by pressing the reset key for 7 seconds and it is deactivated by turning o the boiler.
Brings the boiler to the minimum and maximum power for 15 minutes by deactivating the modulation function. Generally used
for combustion and calibration tests.
It is automatically activated when the heating probe detects a temperature of 12 °C. The boiler operates at minimum power and is
deactivated when a temperature of 30 °C is detected.
It is automatically activated when the DHW probe detects a temperature of 4 °C. The boiler operates at minimum power with
diverter valve in summer position. It is deactivated when a temperature of 8 °C is detected.
It automatically starts when the boiler is rst turned on, running for 5 minutes a series of cycles in which the pump is turned on for a
period of 40 seconds and then turned o for a period of 20 seconds. Regular operation is only permitted at the end of the function.
It can also be activated during normal operation of the boiler, in the event that the enable of the water pressure switch is lacking,
when the contact is closed, a 2-minute venting cycle is performed.
It is activated or deactivated by holding down the reset and keys of the DHW side for 7 seconds.
30
9
Table 7
9 APPENDICES
9.1 PRODUCT FICHE
Figure9.1
COMMISSION DELEGATED REGULATION (EU) No 811/2013
Technical parameters for boiler space heaters, boiler combination heaters and cogeneration space heaters
Rated heat output
For boiler space heaters and boiler combination heaters:
Useful heat output
For boiler space heaters and boiler combination heaters:
Useful efficiency
s
92,81%
on:retaeh yratnemelppus a htiw deppiuqe ,sey fIon:retaeh ecaps noitarenegoC
tinUeulaVlobmySmetItinUeulaVlobmySmetI
At rated heat output and
high-temperature regime (*)
At 30 % of rated heat output
and low-temperature
regime (**)
P
4
P
1
33,4kWAt rated heat output and
high-temperature regime (*)
10,2kWAt 30 % of rated heat output
4
1
and low-temperature
regime (**)
smeti rehtOnoitpmusnoc yticirtcele yrailixuA
At full loadelmax0,038kWStandby heat lossP
At part loadelmin0,016kWIgnition burner power
stby
P
ign
consumption
In standby modeP
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return
temperature (at heater inlet).
SB
0,004
kWAnnual energy consumptionQ
Sound power level, indoors
HE
L
WA
- / 52,4dB
Additional information required by COMMISSION REGULATION (EU) No 813/2013, Table 1:
Emissions of nitrogen oxides:NO
x
55mg/
kWh
88,3%
97,8%
0,059kW
0kW
105,5GJ
Installation, use and maintenance manual – Caldaia 35 Tech
31
Robur mission
Robur is dedicated to dynamic progression
in research, development and promotion
of safe, environmentally-friendly, energy-eciency products,
through the commitment and caring
of its employees and partners.
23/07/2019
19 MCM SDC 022
Code: D-LBR749EN
Robur S.p.A.
advanced technologies
for climate conditioning
via Parigi 4/6
24040 Verdellino/Zingonia (BG) Italy
+39 035 888111 - F +39 035 884165
www.robur.it robur@robur.it
Revision: B
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.