Note that in England and Wales the Building Regulations require a terminal guard to be fitted if the terminal is less than 2m
(6ft 6in) from the level of any ground, balcony, flat roof or place to which any person has access and which adjoins the wall
in which the outlet is situated. A suitable guard assembly is available from Robinson Willey Limited. The part number is
994371. In Scotland, although the Building Standards (Scotland) do not require a terminal guard to be fitted, the fitting of a
guard as detailed above is recommended.
INSIDE:
1. Allow 50mm access at each side of the heater for servicing.
2. Curtains must be 150mm clear at the top of the heater and 50mm at the sides and must not be closeable over the front
of the fire.
3. A wooden or combustible shelf may be fitted over the fire. The minimum height of the underside of the shelf of 125mm
depth must be 130mm . For shelves of greater depth, allow an additional clearance of 15mm for every 25mm additional
shelf depth.
4. A minimum clearance to combustible material of 500mm is required around the heater.
4.0 PREPARATION OF WALL
NOTE: The following instructions relate to normal brick walls. If the wall is wholly or partly of combustible material, a
combustible wall kit (optional extra) must be used. Refer to Section 4.4.
Check the wall thickness. Three different sizes of flue available for wall thickness up to 508mm as shown below. The
medium flue is packed with the heater, the other lengths must be ordered specially.
Short - 75mm to 203mm
Medium - 203mm to 357mm
Long - 357mm to 508mm
4.1 Place the template against the wall ensuring the top is level. For hearth mounting, ensure that the centre of the flue is
351mm above the hearth. Mark the positions of the flue and four fixing holes and remove the template.
4.2 Cut the hole for the flue making sure that it is straight and level. This can be done with either a 135mm diameter core
drill or hammer and chisel. If neatly drilled no making good is necessary. If not it will be necessary to make good the
hole especially at the terminal end where the flue seal will be located and the inside wall face to achieve a good seal.
4.3 Use the template to mark the fixing holes if necessary. Drill the four fixing holes to a minimum depth of 57mm using
6mm diameter masonry drill and insert the plugs.
4.4 COMBUSTIBLE WALLS
1. For installation on walls constructed or comprising combustible materials, reference should be made to the
requirements of BS 5440 and the Building Regulations.
2. Timber Framed Housing: For a timber framed house, the fire can be installed as directed in The Institute of Gas
Engineers Utilization Procedure IGE/UP/7 GAS INSTALLATIONS IN TIMBER FRAME BUILDINGS.
3. The combustible wall kit is suitable for walls in which the combustible part is not more than 195 mm thick measured
from the inside of the building.
4. The combustible wall kit required is ÿ No. 994530, GC No. 154 759. If the whole of the wall is of combustible material,
the outer wall plate must be used, requiring access to the outside of the building.
5. If the screws and the wall plugs supplied are not suitable for a particular application, proprietary cavity wall fixings may
be used.
6. Proceed as detailed in Section 4 for brick walls, EXCEPT for the following points: -
(a) Cut the hole for the flue to a diameter of 178 mm through the plaster board taking care not to damage the Vapour
Control Layer (VCL).
(b) Cut the VCL 10 mm less in diameter than the hole just cut in the plasterboard. This will ensure a seal around the
flue liner.
(c) Continue the 178 mm diameter hole through the remainder of the combustible material. If the outer leave of the wall
is constructed of non-combustible material then cut the hole 135 mm diameter making allowances for the shrinkage
†
of the timber frame.
(d) Measure the thickness of the combustible part of the wall and cut the flue liner to this length, cutting off the end
without the fixing brackets. Fit the liner to the sealing plate using the screws provided.
(e) Push the liner through the VCL taking care not to damage the VCL, and ensuring that the liner DOES NOT protrude
into the cavity by more than 10 mm.
(f) If the wall is wholly of combustible material, install the outer wall plate centrally over the hole from the outside as
shown in the diagram below. It is recommended that a silicone sealing compound is applied to the inner face of the
wall plate to provide a watertight installation.
(g) Fit the flue, see the Fit Flue section in the Installation Instructions provided with the appliance. NOTE: When
determining the flue length, measure the wall thickness from the face of the outer wall plate.
(h) Slide the rope seal over the flue, until it touches the back of the heater, prior to removing the tape from the flue
foam sealing strip.
(i) Before installing the flue into the wall is necessary to provide a moisture barrier around the flue at the point which
will be in the centre of the cavity. Either of the following methods are acceptable: -
(i) Wrap a wire which will not cause corrosion tightly around the flue.
(ii) Form a bead of mastic or silicone around the flue.
† Note: It is not necessary to allow for shrinkage of timber frames in existing buildings where the necessary length of
time has elapsed to allow for any contraction of the timber frame.
5