Roberts Gorden VANTAGE CTH3-80, VANTAGE CTH3-150, Vantage Modulating CTH3-80, VANTAGE CTH3-115, Vantage Modulating CTH3-150 Installation, Operation & Service Manual

...
Page 1
FOR YOUR SAFETY
WARNING
Installation must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and Service Manual thoroughly before installing or servicing this equipment.
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
6. Leave the building.
7. Immediately call your local gas supplier after leaving the building. Follow the gas supplier’s instructions.
8. If you cannot reach your gas supplier, call the Fire Department.
Gas-Fired, Low Intensity
WARNING
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clear­ances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
Unitary Heater
Installation, Operation &
Service Manual
CTH3-80 CTH3-115 CTH3-150 CTH3-200
© 2012 Roberts-Gordon LLC
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
Roberts-Gordon LLC
1250 William Street P. O. Bo x 4 4 Buffalo, New York 14240-0044 Telephone: +1.716.852.4400 Fax: +1.716.852.0854 Toll Free: 800.828.7450
www.rg-inc.com www.radiantheaters.com
P/N 134100NA Rev K 02/12
Page 2
Page 3
© 2012
Roberts-Gordon LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon LLC.
TABLE OF CONTENTS
SECTION 1: Heater Safety...................................................... 1
1.1 Manpower Requirements ............................................. 1
1.2 Safety Labels and Their Placement ............................. 1
1.3 California Proposition 65 .............................................. 1
SECTION 2: Installer Responsibility ..................................... 4
2.1 Wall Tag .......................................................................4
2.2 Corrosive Chemicals.................................................... 4
2.3 National Standards and Applicable Codes ..................4
SECTION 3: Clearances to Combustibles............................. 5
3.1 Required Clearances to Combustibles.........................5
SECTION 4: National Standards and Applicable Codes .....9
4.1 Gas Codes................................................................... 9
4.2 Aircraft Hangars ........................................................... 9
4.3 Public Garages ............................................................9
4.4 Electrical ...................................................................... 9
4.5 Venting.........................................................................9
4.6 High Altitude ................................................................ 9
SECTION 5: Major Components .......................................... 10
5.1 Standard Parts List .................................................... 11
SECTION 6: Heater Installation............................................ 12
6.1 Burner Tube Installation ............................................ 16
6.2 Tube Clamp Package Installation..............................16
6.3 Coupling and Tube Assembly....................................17
6.4 Turbulator Installation ................................................18
6.5 Reflector Installation .................................................. 19
6.6 Burner Installation...................................................... 21
SECTION 7: Optional Heater Accessories.......................... 22
7. 1 U - Tube Configuration..................................................22
7.2 Elbow Package Configuration.....................................25
7.3 Reflector Side Extension ............................................27
7. 4 L o wer Clearance Shield Installation ...........................28
7. 5 Two-Foot Decorative Grille Installation .......................28
7.6 Protective Grille Installation ........................................30
SECTION 8: Venting.............................................................. 31
8.1 Venting.......................................................................31
8.2 Unvented Operation................................................... 31
8.3 Horizontal Venting......................................................32
8.4 Vertical Venting..........................................................32
8.5 Unvented Operation Tube Termination ......................32
8.6 Length Requirements ................................................32
8.7 Horizontal Ventilation 4" (10 cm) Pipe........................32
8.8 Vertical Ventilation 4" (10 cm) Pipe ............................33
8.9 Common Side Wall Venting ....................................... 33
8.10 Common Vertical Venting ........................................34
8.11 Outside Combustion Air Supply ...............................35
SECTION 9: Gas Piping........................................................ 37
SECTION 10: Wiring.............................................................. 39
10.1 Standard Heater Configuration ................................ 39
10.2 Central and Satellite Heaters (Zoning Capability).... 40
10.3 Communication Wiring within a Zone of Heaters..... 42
10.3 Communication Wiring within a Zone of Heaters
(continued).............................................................. 43
10.4 Heat Demand Control Wiring................................... 44
10.5 Internal Wiring.......................................................... 52
10.6 Ladder Diagram ....................................................... 53
10.7 Line Voltage Power Wiring....................................... 54
10.8 Electrical Connection to the Burner ......................... 54
10.9 Low Voltage Control Wiring Installation.................... 55
SECTION 11: Operation and Maintenance.......................... 56
11.1 S e q uence of Operation ............................................ 56
11.2 To Shut Off Heater.................................................... 56
11.3 To Start Heater ......................................................... 56
11.4 Pre-Season Maintenance and Annual Inspection..... 56
SECTION 12: Troubleshooting............................................. 59
12.1 Control LED ............................................................. 60
12.2 General LED Codes ................................................ 60
12.3 Troubleshooting Flow Chart ..................................... 62
12.4 Manifold Gas Pressure Measurement...................... 64
12.5 Pneumatic Connections........................................... 65
SECTION 13: Replacement Parts ........................................ 66
SECTION 14: General Specifications .................................. 69
14.1 Material Specifications............................................. 69
14.2 Heater Specifications............................................... 69
14.3 Suspension Specifications....................................... 69
14.4 Controls Specifications ............................................ 69
SECTION 15: The ROBERTS GORDON
MODULATING Warranty................................ 71
®
VANTAGE®
There are references in this manual to various trademarks. All trademarks mentioned herein, whether registered or not, are the property of their respective owners. Roberts-Gordon LLC is not sponsored by or affiliated with any of the trademark or regis­tered trademark owners, and make no representations about them, their owners, their products or services. Roberts-Gordon LLC is not sponsored by or affiliated with BACnet® or LonWorks®.
Prin ted in U.S.A.
Page 4
Page 5
TABLE OF FIGURES
Figure 1: Top and Bottom Panel Label Placement ....................2
Figure 2: Side and Back Panel Label Placement...................... 3
Figure 3: Standard Reflector .....................................................5
Figure 4: One Side Reflector.....................................................6
Figure 5: Two Side Reflectors ................................................... 6
Figure 6: 45° Tilt Reflector ........................................................ 6
Figure 7: U-Tube, Standard Reflector........................................ 7
Figure 8: U-Tube, 45°................................................................ 7
Figure 9: U-Tube, Opposite 45° Reflector .................................7
Figure 10: 2-Foot Deco Grille and Protective Grille ................... 8
Figure 11: Lower Clearance Shield ........................................... 8
Figure 12: Venting ..................................................................... 8
Figure 13: Major Component Descriptions.............................. 10
Figure 14: Critical Hanger Placement ..................................... 13
Figure 15: Linear Heater Assembly Overview ........................ 14
Figure 16: Linear Heater Layout Overview.............................. 15
Figure 17: U-Tube Heater Assembly Overview ......................23
Figure 18: U-Tube Heater Layout O
Figure 19: Reflector Joint Detail ..............................................26
Figure 20: Tube Termination................................................... 32
Figure 21: Gas Connection with Flexible Gas Hose ...............38
Figure 22: Zone Sensor Wiring Diagram.................................39
Figure 23: Central Heater Jumper Settings.............................40
Figure 24: Satellite Heater Jumper Setting..............................41
Figure 25: Communication Wiring within a Zone of Heaters ... 42 Figure 25: Communication Wiring within a Zone of Heaters
(continued)............................................................. 43
Figure 26: Thermostat Control Wiring Diagram....................... 44
Figure 27: Analog Control Signal Wiring Diagram................... 47
Figure 28: Potentiometer Control Wiring Diagram...................48
Figure 29: Modulating Thermostat Wiring Diagram
(LonWorks
®
[4-20 mA] optional).............................49
Figure 30: Modulating Thermostat Wiring Diagram
(LonWorks® [2-10Vdc with 500 Ohm resistor]
optional).................................................................50
Figure 31: Modulating Thermostat Wiring Diagram
with BACnet
®
(optional) .........................................51
verview ........................... 24
LIST OF TABLES
Table 1: Contents of Burner Carton........................................ 11
Table 2: Contents of Core and Extension Packages .............. 11
Table 3: CTH3-Series Component Package Guide ................11
Table 4: Cable Requirements ................................................. 46
Page 6
Page 7
SECTION 1: HEATER S AFETY
SECTION 1: HEATER SAFETY
Yo ur Safety is Important to Us! This symbol is used throughout the manual to notify you of possi­ble fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
Installation, Service and Annual Inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
Read this manual carefully before installation, operation or service of this equipment.
This heater is designed for heating nonresidential indoor spaces. Do not install in residential spaces. These instructions, the layout drawing, local codes and ordinances, and applicable standards that apply to gas piping, electrical wiring, venting, etc. must be thoroughly understood before proceeding with the installation.
Protective gear is to be worn during installation, operation and service. Thin sheet metal parts, including the aluminum reflector portion of the heater and the various
venting components, have sharp edges. To prevent injury, the use of work gloves is recommended. The use of gloves will also prevent the transfer of body oils from the hands to the surface of the reflector.
Before installation, check that the local distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
This heater must be applied and operated under the general concepts of reasonable use and installed using best building practices. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do no play with the appliance.
For additional copies of the Installation, Operation and Service Manual, please contact Roberts-Gordon LLC.
1. 1 M an p o we r R e
quirements
To p revent personal injury and damage to the heater, two persons will be required for installation.
1.2 Safety Labels and Their Placement
the product user when they are no longer legible. Please contact Roberts-Gordon LLC or your ROB-
®
ERTS GORDON
independent distributor to obtain replacement signs or labels. See Page 2, Figure 1 through Page 3, Figure 2.
1.3 California Proposition 65
In accordance with California Proposition 65 require- ments, a warning label must be placed in a highly visible location on the outside of the equipment (i.e., near equipment’s serial plate). See label placement drawing on Page 2, Figure 1 for label location. Avoid placing label on areas with extreme heat, cold, corro­sive chemicals or other elements. To order additional labels, please contact Roberts-Gordon LLC or your ROBERTS GORDON
®
independent distributor.
Product safety signs or labels should be replaced by
1 of 71
Page 8
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Logo Label
Rating Plate Label
Bottom Panel
Top Panel
Gas Connection Label
Proposition 65 Label
Description Part Number
Logo Label 91013212 Rating Plate Label 91010401 Gas Connection Label 91018122 Proposition 65 Label 91070015
FIGURE 1: Top and Bottom Panel Label Placement
2 of 71
Page 9
FIGURE 2: Side and Back Panel Label Placement
Lighting Instruction Plate Label
Vent Length Label
Carbon Monoxide Hazard Label
Back Panel
Inside Bottom Panel
Low Voltage Connection Label
COM
N.O.
Description Part Number
Clearances to Combustibles Label 91013415 Wiring Label 91013303 Carbon Monoxide Hazard Label 91039501 Low Voltage Connection Label 91039700 Vent Length Label 91039500 Lighting Instruction Plate Label 91029602
Control Side Panel
SECTION 1: HEATER S AFETY
Clearances to Combustibles Label
Control Side Panel (Inside) Wiring Label
3 of 71
Page 10
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
CAUTION
Product Damage Hazard
Do not use heater in area containing corrosive chemicals.
Refer to appropriate Material Safety Data Sheets (MSDS).
Failure to follow these instructions can result in product damage.
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To install the heater, as well as the gas and electrical supplies, in accordance with applicable specifications and codes. Roberts-Gordon LLC recommends the installer contact a local Building Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing and in the manual together with the cited codes and regulations to perform the installation.
• To install the heater in accordance with the clearances to combustibles.
• To furnish all needed materials not furnished as standard equipment.
• To plan location of supports.
• To provide access to burners for servicing on all sides, for burner removal.
• To provide the owner with a copy of this installation, operation and service manual.
on the burner and in the Installation, Operation and Service Manual. See Page 5, Figure 3 through Page 8, Figure 12. Write the proper clearance dimensions in permanent ink according to your model number and configuration in the open spaces on the tag.
2.2 Corrosive Chemicals
• To never use heater as support for a ladder or other access equipment and never hang or sus- pend anything from heater.
• To ensure there is adequate air circulation arou the heater and to supply air for combustion, venti- lation and distribution in accordance with local codes.
• To safely and adequately install heater using materials with a minimal working load of 75 lbs (33 kg).
• To ensure the heater is placed in a approved application.
2.1 Wall Tag
A laminated wall tag is available for the heater as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Please contact Roberts-Gordon LLC or your ROBERTS GORDON
®
independent distributor to obtain the wall tag. Affix the tag by peeling off the backing of the adhesive strips on the rear surface and position the tag on a wall near the heater (e.g. thermostat or ROBERTS GORDON Controller).
A copy of the wall tag (P/N 91037912) is illustrated on the back cover. For an immediate solution, you may affix this copy on the wall near the heater.
Know your model number and installed configuration. Model number and installed configuration are found
Roberts-Gordon LLC cannot be responsible for ensuring that all appropriate safety measures are
nd
undertaken prior to installation; this is entirely the responsibility of the installer. It is essential that the contractor, the sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen elements (fluorine, chlorine, bromine, etc.). These com­pounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the life span of the heater compo­nents will be greatly reduced. An outside air supply must be provided to the burners whenever the presence of these compounds is suspected. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with the latest revision of the applicable standards and
®
national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in Public Garages, Aircraft Hangars, etc. may be applicable.
4 of 71
Page 11
SECTION 3: CLEARANCES TO COMBUSTIBLES
WARNING
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
3.1 Required Clearances to Combustibles
Clearances are the required distances that combustible objects must be away from the heater to prevent serious fire hazards. Combustibles are materials, that may catch on fire and include common items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times for safety.
Clearances for all heater models are located on the burner of the heater and on Page 5, Figure 3 through Page 8, Figure 12 in this manual. Check the clearances on each burner for the model heater being installed to make sure the product is suitable for your application and the clearances are maintained. Read and follow the safety guidelines below:
• Keep gasoline or other combustible materials including flammable objects, liquids, dust or vapors away from this heater or any other appliance
• The stated clearance to combustible represents a surface temperature of 90° F (50°C) above room temperature. Building materials with a low heat tolerance (su vas,triply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibil- ity to assure that adjacent materials are protected from degradation.
• Maintain clearances from heat sensitive equipment and workstations.
• Maintain clearances from vehicles parked below the heater.
• Maintain clearances from swinging and overhead doors, overhead cranes, vehicle lifts, partitions, storage racks, hoists, building construction, etc.
ch as plastics, vinyl siding, can-
SECTION 3: CLEARANCES TO COMBUSTIBLES
• In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain required clearances from the heater to the combustibles. Signs must be posted adjacent to the heater thermostat. In the absence of a thermostat, signs must be posted in a conspicuous location.
• Consult local Fire Marshal, Fire Insurance Carrier or other authorities for approval of proposed installation when there is a possibility of exposure to combustible airborne materials or vapors.
• Hang heater in accordance to the minimum sus- pension requirements
• If the radiant tubes must pass through the building structure, be sure that adequate sleeving and fire stop is installed to prevent scorching and/or fire hazard.
on Page 13, Figure 14.
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect.
FIGURE 3: STANDARD REFLECTOR
Model A B C D A B C D
CTH3-80 6 38 66 38 16 97 168 97
CTH3-115 6 46 77 46 16 117 196 117
CTH3-150 6 50 80 50 16 127 204 127
CTH3-200 8 52 82 52 21 133 209 133
(inches) (centimeters)
5 of 71
Page 12
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
A
C
D
B
A
C
D
B
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect.
FIGURE 4: ONE SIDE REFLECTOR
Model ABCDABCD
CTH3-80 6 9 70 54 16 23 178 138
CTH3-115 6 9 83 65 16 23 211 166
CTH3-150 6 9 86 69 16 23 219 176
CTH3-200 8 9 88 73 21 23 224 186
(inches) (centimeters)
FIGURE 5: TWO SIDE REFLECTORS
Model ABCDABCD
CTH3-80 6 25 72 25 16 64 183 64
CTH3-115 6 32 84 32 16 82 214 82
CTH3-150 6 35 88 35 16 89 224 89
CTH3-200 8 40914021102232102
FIGURE 6: 45° TILT REFLECTOR
Model ABCDABCD
CTH3-80 8 8 66 60 21 21 168 153
CTH3-11510 8 78692621199176
CTH3-150 12 8 84 74 31 21 214 188
(inches) (centimeters)
(inches) (centimeters)
CTH3-20012 8 85793121216201
6 of 71
Page 13
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
A
C
D
B
B
C
D
A
A
C
D
B
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect.
FIGURE 7: U-TUBE, STANDARD REFLECTOR
Model ABCDABCD
CTH3-80 6 38 69 37 16 97 176 94
CTH3-115 6 46 79 43 16 117 201 110
CTH3-150 6 50 84 47 16 127 214 120
CTH3-200 8 54875121138221130
SECTION 3: CLEARANCES TO COMBUSTIBLES
(inches) (centimeters)
FIGURE 8: U-TUBE, 45°
Model ABCDABCD
CTH3-80 8 8 66 46 21 21 168 11 7
CTH3-115 8 8 78 61 21 21 199 155
CTH3-150 8 8 84 66 21 21 214 168
CTH3-200 8 8 85 70 21 21 216 178
FIGURE 9: U-TUBE, OPPOSITE 45° REFLECTOR
Model ABCDABCD
CTH3-80 8 60 66 22 21 153 168 56
CTH3-115 10 70 78 22 26 178 199 56
CTH3-150 12 74 84 22 31 188 214 56
(inches) (centimeters)
(inches) (centimeters)
CTH3-200 12 76 85 22 31 194 216 56
7 of 71
Page 14
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
A
C
D
B
A
C
D
B
Radiant Tubes
Vent Pipes
Unvented
Vented
A
E
F
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect.
FIGURE 10: 2-FOOT DECO GRILLE AND PROTECTIVE GRILLE
(inches) (centimeters)
Model ABCDABCD
CTH3-80 6 38 66 38 16 97 168 97
CTH3-115 6 46 77 46 16 117 196 117
CTH3-150 6 50 80 50 16 127 204 127
CTH3-200 8 52825221133209133
FIGURE 11: LOWER CLEARANCE SHIELD*
Model ABCDABCD
CTH3-80 6 40 38 40 16 102 97 102
CTH3-115 6 54 48 54 16 138 122 138
CTH3-150 6 55 50 55 16 140 127 140
CTH3-200
*When installed in the first 10' (3 m).
FIGURE 12: VENTING
Model A E F A E F
CTH3-80 20 24 18 51 61 46
CTH3-115 20 24 18 51 61 46
CTH3-150 20 30 18 51 77 46
(inches) (centimeters)
- UNAPPROVED -
- UNAPPROVED -
(inches) (centimeters)
CTH3-200 20 30 18 51 77 46
8 of 71
Page 15
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
SECTION 4: NATIONAL STANDARDS AND APPLICABLE C ODES
4.1 Gas Codes
The type of gas appearing on the nameplate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company.
United States: Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in accordance with the following codes:
United States: Refer to Standard for Aircraft Hangars, NFPA 409 - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.
In aircraft storage and servicing areas, heaters shall be installed at least 10' (3 m) above the upper surface of wings or of engine enclosures of the highest aircraft which may be housed in the hangar. The measurement shall be made from the wing or engine enclosure (whichever is higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft hangars communicating with aircraft storage or servicing areas, heaters shall be installed not less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so located in all spaces of aircraft hangars that they shall not be subject to injury by aircraft, cranes, movable scaffolding or other objects. Provisions shall be made to assure accessibility to suspended heaters for recurrent maintenance purposes.
4.3 Public Garages
Installation in garages must be in accordance with the following codes:
United States: Refer to Standard for Parking Structures NFPA 88A - latest revision or the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision. Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.
• Heaters must not be installed less than 8' (2.4 m) above the floor. Minimum clearances to combustibles must be maintained from vehicles parked below the heater.
• When installed over hoists, minimum clearances to combustibles must be maintained from the upper most point of objects on the hoist.
4.4 Electrical
The heater must be electrically grounded in accordance with the following codes:
United States: Refer to National Electrical Code NFPA 70 - latest revision. Wiring must conform to the most current National Electrical Code
®
, local
ordinances and any special diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance with the requirements within this manual and the following codes:
United States: Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.
®
,
4.6 High Altitude
These heaters are approved for installations up to 2000' (610 m)(US), 4500' (1370 m)(Canada) without modification. Consult factory if US installation is above 2000' (610 m) or Canadian installation is above 4500' (1370 m).
9 of 71
Page 16
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Burner with Tube Gasket
Must be installed with the
flame observation window facing down.
Reflector (Aluminum or Stainless Steel)
Alternate overlap as shown on overview and on Page 15, Figure 16. Minimum overlap is 6" (16 cm).
Tube and Reflector Hanger with Clamp Package
Position this hanger no more than 4" (10 cm) away from the burner.
Coupling Assembly with Lock
Reflector End Cap
Punch out center section to accommodate tube.
Tube and Reflector Hanger
Suspend system from these hangers.
Flex Gas Line with Shut Off Cock
Tube
Heat treated aluminized tube supplied in 10' (3 m) lengths.
Burner Tube
Supplied in 10
'
(3 m) lengths. Burner tube is always the first tube after the burner.
Reflector Support Strap & Wire Form
Turbulator
Turbulator must be installed in the last standard section of tube. Turbulator is not required on the CTH3-200. For installation see Page 18, Section 6.4.
Vent Adapter
SECTION 5: MAJOR COMPONENTS FIGURE 13: Major Component Descriptions
10 of 71
Page 17
SECTION 5: MAJOR COMPONENTS
5.1 Standard Parts List Table 1:
*Canadian Models: Rubber (Type 1) Gas Hoses available as an accessory.
Contents of Burner Carton
Part No. Description CTH3-80 CTH3-115 CTH3-150 CTH3-200
034XXXXX Burner Assembly (Rate and Fuel Varies) 1 1 1 1
02568200 Gasket (Burner to Burner Tube) 1 1 1 1
134100NA Installation, Operation and Service Manual 1 1 1 1
94273914 Hex Head Bolts 5/16-18 Rolok 4 4 4 4
96411600 Split Lock Washer 4 4 4 4
91201708 Pipe Nipple (Black) 1/2" NPT x 4" 1 1 1 1
*91412200 Flexible Stainless Steel Gas Hose - 1/2" NPT (US Models Only) 1 1 - -
*91412204 Flexible Stainless Steel Gas Hose - 3/4" NPT (US Models Only) - - 1 1
03051503 Turbulator Adapter 1 1 1 -
03051504 Turbulator, Aluminized Steel 3 3 1 -
91317310 Wire Terminal Receptacle.187 x.032 8 8 8 8
91309605 Cable Grommet with Tie 1 1 1 1
See Page 37, Section 9
.
Table 2: Contents of Core and Extension Packages
Core Packages (Aluminized) Extension Packages (Aluminized)
Part No. Description 10
91409408 Tube, HT Aluminized, 10' (3m) - 1 2 3 1 2 3 4
03051101
03051601
01312700 Coupling Assembly - 1 2 3 1 2 3 4
02750303 Standard Reflector, 8
02750800 End Cap 2 2 2 2 - - - -
03090100 Tube and Reflector Hanger 2 3 4 5 1 2 3 4
91907302 S-Hook 2 3 4 5 1 2 3 4
03050010 Reflector Support Package (Strap, Wire Form, Screws) 1 2 3 5 2 3 4 6
91107720 U-Clip Package 1 1 1 1 1 1 1 1
90502700 Vent Adapter 1 1 1 1 - - - -
01318901 Tube Clamp Package 1 1 1 1 - - - -
Burner Tube, ALUMI-THERM
Burner Tube, HT ALUMI-THERM
®
Steel, 10' (3m)
®
Steel, 10' (3m)
'
(2.6m) 2 3 4 6 2 3 4 6
' (3m)20' (6m)30' (9m)40' (12m)10' (3m)20' (6m)30' (9m)40' (12m)
--11--- -
11 - - - - - -
Part Number
Table 3: CTH3-Series Component Package Guide
Model Tubing Length Core Packages
Minimum Aluminized
CTH3-80 20' (6m) CP20ALUM
CTH3-115 30' (9m) CP30ALUM
CTH3-150 40' (12m) CP40ALUM
CTH3-200 50' (15m) CP30ALUM + EXP20ALUM
Additional tubing length may be added to heater. Tubing must be heat-treated, aluminized or porcelain coated. Any additional tubing lengths are considered as vent length for length determination. Maximum venting length for minimum heater length is 45' (13.7 m) total.
CP10ALUM
CP20ALUM
CP30ALUM
CP40ALUM
EXP10ALUM
EXP20ALUM
EXP30ALUM
EXP40ALUM
11 o f 7 1
Page 18
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
WARNING
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
Failure to follow these instructions can result in injury.
SECTION 6: HEATER INSTALLATION
WARNING
Severe Injury Hazard
Secure burner to burner tube with bolts and lockwashers.
Hang heater with materials with a minimum working load of 75 lbs (33 kg).
Failure to follow these instructions can result in death, injury or property damage.
Expansion and contraction of the tube dictates that the minimum suspension lengths in the table on Page 13, Figure 14 be maintained.
To ensure your safety, and comply with the terms of the warranty, all units must be installed in accordance with these instructions.
The gas or the electrical supply lines must not be used to support the heater.
Do not locate the gas or electric supply lines directly over the path of the flue products from the heater.
The heater must be installed in a location that it is readily accessible for servicing.
The heater must be installed in accordance with clearances to combustibles as indicated on the heater and in this instruction manual.
The gas inlet pressure must be maintained as indicated on the rating plate.
Typical installation configurations are shown on Page 13, Figure 14.
12 of 71
Page 19
FIGURE 14: Critical Hanger Placement
Hanger
Side View
Must Be Within 4" (10 cm) Front View
S-hooks
Reflector
Hanger
45° Angle
* Allows for thermal expansion of system
Typical Suspension Details
Rod 3/8"
Beam Clamp
Concrete Beam
Wood Beam
Washers
Locknut
Screw Hook
3/8"
24" min.*
(61 cm)
X*
Anchor
S-hooks
Chain Size
3/16"
Minimum
Turnbuckle
Not Included
Description Part Number
S-Hook 91907302 Tube/Reflector Hanger 03090100
Run Length Typical Expansion Minimum “X” Length
10' - 50' ±1" (3 cm) 12" 51' - 60' ±2" (5 cm) 18" 61' - 70' ±3" (8 cm) 24"
SECTION 6: HEATER I NSTALLATION
13 of 71
Page 20
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Tube
Reflector
Reflector End Cap
Reflector Support
Burner
Coupling
U-Clips
Burner Tube
Tube and Reflector Hanger
Tube Clamp
Package
Vent Adapter
Turbulator
(With Select Models)
FIGURE 15: Linear Heater Assembly Overview
14 of 71
Page 21
FIGURE 16: Linear Heater Layout Overview
Burner
Reflector
Tube
Tube/Reflector Hanger
Coupling Assembly
Vent Adapter
LEGEND
a = 14" (36 cm) reflector width (not shown)
b = 2" (5 cm) end cap to burner
c = 2" (5 cm) end cap to hanger
d = 7'6" (229 cm) distance first hanger
e = 10' (305 cm) distance between hangers
f = 9.5" (24 cm) burner height
g = 17.5" (44 cm) burner length
g
c
b
de
e e e e
f
g
c
b
de
e e e
f
g
c
b
de
e e
f
g
c
b
de
f
20' (6 m) Tube Length
g
c
b
de
e
f
30' (9 m) Tube Length
40' (12 m) Tube Length
50' (15 m) Tube Length
60' (18 m) Tube Length
b
f
g
c
de
e e e e e
70' (21 m) Tube Length
b
b
f
g
c
de
e e e e e
80' (24 m) Tube Length
b
e
SECTION 6: HEATER I NSTALLATION
15 of 71
Page 22
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
7' 6" ± 1'
(229 cm ± 25 cm)
NOTE:
Tubing requires a downward slope of 1/2" (1.3 cm) per 20' (6 m) away from burner.
S-hook
Burner Tube
Hanger
Offset mounting hole must be to the top.
Weld seam must be to the bottom of the tube.
Description Part Number
Burner Tube 03051XXX S-Hook 91907302 Tube/Reflector Hanger 03090100
Bolt
Tube Clamp
Flat
Washer
Nut
(Torque 120 in/lb
13.56 Nm)
Description Part Number Tube Clamp Package01318901
Tube Clamp 01396801 Bolt 97113940 Flat Washer 95211600 Nut 92113900
Step 6.1 Burner Tube Installation
Step 6.2 Tube Clamp Package Installation
16 of 71
Page 23
Step 6.3 Coupling and Tube Assembly
Tube
Tube
Orient coupling so that
the impact block is in the
2:00 or 10:00 oclock
positions.
Closed
Open
Tab
3" (8 cm) to 4" (10 cm)
Slide Bar/Coupling Lock
Coupling
Wide End
Coupling
Tube
Slide Bar/Coupling Lock
A
Close coupling with tab.
B
Start Slide bar/Coupling Lock.
C
Insert tubes into coupling.
D
Tighten coupling to join tubes.
Description Part Number
Coupling 01329600 Slide bar/Coupling Lock 01329700 Tube 91409XXX
Incorrect slide bar
position
Correct slide bar
dimensions
± 2" (5 cm)
Drive slide bar until tight. End of slide bar should be within tolerance listed below.
• Repeat Step 6.3 A - D until all tubes are assembled. See Page 18, Section 6.3.2.
Tighten slide bar as shown below.
SECTION 6: HEATER I NSTALLATION
Step 6.3.1 Coupling and Tube Assembly (Continued)
17 of 71
Page 24
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
10' ± 1'
(3 m ± .25 m)
Total Overall Tube Length
7' 6" ± 1'
(2.3 m ± .25 m)
Model
Tube L e n gth
Minimum
CTH3-80 20' (6 m) CTH3-115 30' (9 m) CTH3-150 40' (12 m) CTH3-200 50' (15 m)
T
w
i
s
t
Pull String
Tab
Fold tab around outside of tube nearest to the vent to hold turbulator in place.
Turbulator Section
Turbulator Adapter
Description Part Number
Turbulator Adapter 03051503 Turbulator Section 03051504 Tube 91409XXX
Turbulator Installation
CTH3-80 2nd 10' Section CTH3-115 3rd 10' Section CTH3-150 4th 10' Section CTH3-200 N/A
Turbulator must be installed in the last standard section of tube. Turbulator is not required on the CTH3-200.
Step 6.3.2 Coupling and Tube Assembly (Continued)
Step 6.4 Turbulator Installation
18 of 71
Page 25
6.5 Reflector Installation
WARNING
Fire Hazard
Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Failure to follow these instructions can result in death, injury or property damage.
Hanger
Burner Tube
Reflector
Description Part Number
Tube/Reflector Hanger 03090100 Burner Tube 03051XXX Reflector 02750303
NOTE: All tube surfaces must be covered
by a reflector, except for a U-Tube.
SECTION 6: HEATER I NSTALLATION
19 of 71
Page 26
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
2. The overlap at the first and second reflector is a slip overlap.
Thereafter, every third reflector joint is a slip overlap. A slip overlap is achieved by either: a.) both reflectors lay inside a hanger.
(No reflector support needed.)
b.) using a reflector support with
loose screws at the reflector overlap.
3. The remaining reflector overlaps require a non-slip overlap connection. To affix the reflectors together in a non-slip overlap either: a.) use reflector support and tight screws. b.) if both reflectors lay inside a hanger, u-clips or
sheet metal screws may be used.
This section of three reflectors joined together must be affixed to the tube with at least one reflector support with tight screws.
Reflector End Cap
U-clips
1. The first reflector after the burner must be affixed in the middle of the reflector with a reflector support and tight screws.
First Reflector
6"
(16 cm)
Overlap must be a
minimum of 6" (16 cm).
Loose screws loosened 1/16" (.16 cm) to allow slippage.
2 A
Slip Overlap
Reflector
Support
2 B
Slip Overlap
Reflector
Tight
Screws
3 B
Non-Slip Overlap
U-clip
(2 Clips per Non-slip Overlap Inside a Hanger)
Reflector
3 A
Non-Slip Overlap
Wire Form
Reflector Support
Strap
Tight
Sheet Metal
Screw
Description Part Number Reflector Suppor t Package 03050010
Wire Form 91908004 Reflector Support Strap 03050000 Screw #8 x 3/4 94320812 U-Clip Package 91107720 Reflector End Cap 027508XX
Step 6.5.1 Reflector, U-Clip and Reflector Support Installation
The pictorial drawings of the heater construction in Section 6 are schematic only and provide a general guideline of where hangers, reflector supports and U-clips are to be installed.
To ensure proper expansion and contraction movement of the reflectors, a combination of U-clips and reflector supports are used. The positioning of
reflector supports and U-clips depends on the individual installation. Use either pop rivets or sheet metal screws instead of u-clips when installing end caps and joint pieces in areas where impact and high wind may be a factor. The following rules must be observed.
20 of 71
Page 27
Step 6.6 Burner Installation
Lock Washer
Gasket
Burner
Bolt (Torque 120 in/lb
13.56 Nm)
S-hook
Burner Tube
Burner must be installed
with the flame observation
window facing down.
Description Part Number
Bolt 94273914 Burner 034XXXXX Lock Washer 96411600 Gasket 02568200
SECTION 6: HEATER I NSTALLATION
21 of 71
Page 28
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
WARNING
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
Failure to follow these instructions can result in injury.
SECTION 7: OPTIONAL HEATER ACCESSORIES
7.1 U-Tube Configuration
Heaters are approved for optional U-Tu be configurations.
The U-Tube may be installed in either a standard horizontal position, a 45° position or in an opposite 45° position as shown on Page 7, Figure 7 through Figure 9. When using a U-Tube configuration, the following additional rules must be adhered to:
• A minimum of 10' (3 m) on CTH3-80 and a mini­mum of 15' (4.5 m) on CTH3-115/150/200 is required between the burner and the U-Tube.
• The correct turbulator (See Page 18, Figure 6.4) must be installed in the last standard section of tube.
• The burner must never be operated in a tilted position.
• The heater must be properly supported at all loca­tions. See Page 24, Figure 18.
22 of 71
Page 29
FIGURE 17: U-Tube Heater Assembly Overview
SECTION 7: OPTIONAL H EATER ACCES SORIES
23 of 71
Page 30
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
LEGEND
a = 14" (36 cm) reflector width (not shown)
b = 2" (5 cm) end cap to burner
c = 2" (5 cm) end cap to hanger
d = 7'6" (229 cm) distance first hanger
e = 10' (305 cm) distance between hangers
f = 5' (153 cm) distance between last full tube hanger and half tube hanger
g = 17.5" (44 cm) burner length
h = 9.5" (24 cm) burner height
*Requires the last reflector before the u-tube to be cut in half for use on both sides.
**Requires the last tube before the u-tube to be cut in half for use on both sides.
U-tube
Burner
Reflector
Tube 10' (3 m)
Tube/Reflector Hanger
Coupling Assembly
c
b
de
e
g
60' (18 m) Tube Length
c
b
de
g
h
40' (12 m) Tube Length
c
b
de
f
g
h
50' (15 m) Tube Length* **
g
c
b
20' (6 m) Tube Length*
h
e
Tube 5' (1.5 m)**
c
b
d
f
g
h
30' (9 m) Tube Length**
c
b
de
e
f
g
h
70' (21 m) Tube Length**
c
b
de
e
g
h
80' (24 m) Tube Length
e
h
FIGURE 18: U-Tube Heater Layout Overview
24 of 71
Page 31
7. 2 E l b ow P a c k a ge Configuration
Tube
90° Elbow
Coupling
Description Part Number Elbow Package 02718702
90° Elbow 01335801 Coupling 01312700 Reflector End Cap 02750800 Reflector Joint Piece 02750900
U-Clip Package 91107720
Minimum Distance Required Between Burner and Elbow
Model
Minimum
Distance
CTH3-80 10' (3m) CTH3-115 CTH3-150 15' (4.5m) CTH3-200
Tube
Coupling
Step 7.2.1 Elbow Installation
Step 7.2.2 Elbow Installation
SECTION 7: OPTIONAL H EATER ACCES SORIES
Step 7.2.3 Reflector Joint Installation
25 of 71
Page 32
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 7.2.4 Reflector Joint Installation
Step 7.2.5 Reflector Joint Detail
FIGURE 19: Reflector Joint Detail
26 of 71
Page 33
7.3 Reflector Side Extension
Reflector Side
Extension Bracket
(2 per Reflector)
Use additional supports
in high air movement
applications.
Tube and Reflector Hanger
ReflectorTube
Reflector Support
Description Part Number Reflector Side Extension Package 02712700
Reflector Side Extension 01368000 Retainer Clips 02751200 Sheet Metal Screws 94118106
Order Separately
Reflector Side Extension Bracket 01329910
Retainer Clip (2 per Side)
Cut relief notches for supports and hangers.
Reflector Side Extension
#8 x 3/8 (3.9 x 9.5 mm) Sheet Metal Screw
Step 7.3.1 Bracket Installation
SECTION 7: OPTIONAL H EATER ACCES SORIES
Step 7.3.2 Side Reflector Installation
27 of 71
Page 34
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
12"
(30 cm)
Reflector
Lower Clearance Shield
17"
(43 cm)
Washers
Screws
Locknuts
Align Pilot Holes
Description Part Number Lower Clearance Shield Package 01397501
Shield Support Strap 01397500 Lower Clearance Shield 8' 02793000 Locknut #8 92311400 Flat Washer #8 95310800 Screw #8 x 3/8" 93511406
Description Part Number
Aluminum Grille 2’ x 4’ 91407000
7.4 Lower Clearance Shield Installation Step 7.4.1 Shield Support Strap Assembly
7.5 Two-Foot Decorative Grille Installation Step 7.5.1 Grille Installation
28 of 71
Page 35
Step 7.5.2 Frame Shield Installation
Description Part Number
Deco Grille Shield 01365900
Distance "A" Extension
Minimum Maximum Part No. Width
2" (4 cm) 6" (15 cm) 01370408 8" (20 cm) 6" (15 cm) 10" (26 cm) 01370412 12" (30 cm) 10" (26 cm) 14" (37 cm) 01370416 16" (40 cm)
Description Part Number
Reflector Side Extension 01370412
SECTION 7: OPTIONAL H EATER ACCES SORIES
Step 7.5.3 Reflector Side Extension Installation for Decorative Grilles
29 of 71
Page 36
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Silicone Cap
Grille Finger
Description Part Number
Grille Section 08050001 Grille End Cap 08050002 Silicone Cap 91915951-6P
Bend up 90°.
Pull outward.
Grille
Grille End Cap
A
B
C
D
Grille
Grille
End Cap
Reflector
Final Grille Section
40"
(101 cm)
7.6 Protective Grille Installation Step 7.6.1 Silicone Cap Installation
Step 7.6.2 Grille End Cap Installation
Step 7.6.3 Grille Installation
30 of 71
Page 37
SECTION 8: VENTING
WARNING
Carbon Monoxide Hazard
Heaters installed unvented must be interlocked with sufficient building exhaust.
Heaters must be installed according to the installation manual.
Failure to follow these instructions can result in death or injury.
WARNING
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
Failure to follow these instructions can result in injury.
SECTION 8: VENTING
Vent pipe must be sloped downward away from the burner 1/2'' (1 cm) for every 20' (6 m).
The heater may be individually vented or common vented. When venting horizontally, a maximum of two heaters can be commonly vented. See Page 33, Section 8.9. When venting vertically, a maximum of four heaters can be commonly vented. See Page 34, Section 8.10.
The heater may also be installed unvented in certain circumstances according to building Refer to the above codes and Page 31, Section 8.2 for further information. Unvented operation also requires compliance with the clearances to combustibles given on Page 8, Figure 12.
The bottom of the vent or air intake terminal shall not be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m) above grade where located adjacent to public walkways.
Vent terminal must be installed at a height sufficient to prevent blockage by snow and building materials protected from degradation by flue gasses.
Secure all joints with #8 x 3/8 sheet metal screws. Seal all joints with high temperature silicone sealant.
ventilation codes.
8.1 Venting
This heater must be vented in accordance with the rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply:
United States: Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.
Exhaust end of heater will accept a 4 pipe using the vent adapter (P/N 90502700). To prevent leakage of condensation, install the vent adapter with the seam on top and seal the joint using
a high temperature silicone sealant.
Any portion of vent pipe passing through a combustible wall must have an approved thimble to conform with the above listed codes.
" (10 cm) vent
Vent terminal must be beyond any combustible overhang.
8.1.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below, 4' (1.2 m) horizontally from, or 1' (.3 m) above any door, operable building.
8.1.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a mechanical air supply inlet to any building.
The vent shall not terminate within 3' (.9 m) of a window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.
8.2 Unvented Operation
Sufficient ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United States); 3 cfm per 1000 Btu/h firing rate (Canada).
Use of optional outside combustion air is not recommended with unvented heaters.
If exhaust fans are used to supply ventilation air, an interlock switch must be used to prevent the heater from coming on when the fans are off. This may be done using a pressure switch.
window, or gravity air inlet into any
31 of 71
Page 38
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
4" (10 cm)
Single Wall Pipe
Vent Adapter
Vent Terminal
Combustible or
Non-Combustible Wall
Vent Adapter
18" (46 cm)
Min.
Vent Terminal
4" (10 cm) Single Wall Pipe
Non-Combustible Wall Only
SIDE VIEW
Description Part Number
Vent Terminal (Comb. Wall) 90502100 Vent Terminal 02537801-XX
8.3 Horizontal Venting
In noncombustible walls only, vent terminal (P/N 02537801-1P) may be used.
For 4" (10 cm) vents in either combustible or noncombustible walls, use Tjernlund VH1-4 (P/N
90502100) or equivalent, insulated vent terminal. Follow the manufacturer's instructions for proper installation.
For 6" (15 cm) common vents in either combustible or noncombustible walls, use Tjernlund VH1-6 (P/N
90502101) or equivalent, insulated vent terminal. Follow the manufacturer's instructions for proper installation.
8.4 Vertical Venting
For 4" (10 cm), an approved vent cap (P/N 90502300) must be used. For 6" (15 cm) common vent, an approved vent cap (P/N 90502302) m
ust be used. For common vertical venting of more than two heaters, See Page 34, Section 8.10. A vent shall not extend less than 2' (.6m) above the highest point where it passes through a flat roof of a building.
8.5 Unvented Operation Tube Termination
Turndown type vent terminal with a screen must be installed at the exhaust end of the tube. Vent terminal design shall not incorporate backdraft flap.
FIGURE 20: Tube Termination
8.6 Length Requirements
The maximum vent length allowed is 45' (13.7 m). The maximum outside air supply duct length allowed is 45' (13.7 m).
The total vent length, plus outside air duct length and any extensions to minimum heat exchanger lengths, cannot exceed 65' (19.8 m).
Vent length should be limited to less than 20' (6 m). If using extended heater lengths or vent lengths greater than 20' (6 m), condensation will form in the vent pipe. Insulation and additional sealing measures (high temperature silicone at all seams) are required. Optional heat exchanger beyond minimum lengths are considered as vent length for length determination.
Subtract 15' (4.6 m) of maximum allowed vent or duct length per vent elbow if more than two are used.
8.7 Horizontal Ventilation 4" (10 cm) Pipe
32 of 71
Page 39
8.8 Vertical Ventilation 4" (10 cm) Pipe
Description Part Number
Vent Cap 4" (10 cm) 90502300
4" (10 cm) Single Wall Pipe
Outside Wall
Vent Adapter
Sweeping 'T'
Connection
Sweeping 'Y'
Connection
Outside Wall
6" (15 cm) Single Wall Pipe
Vent Terminal
Tjernlund VH1-6 or Equivalent
Outside Wall
4" (10 cm) Single Wall Pipe
Vent Adapter
Vent Terminal
Tjernlund VH1-6 or Equivalent
Vent Adapter
Vent Adapter
TOP VIEW
4" (10 cm) Single Wall Pipe
6" (15 cm) Single Wall Pipe
Description Part Number
Vent Terminal 6" (15 cm) 90502101
SECTION 8: VENTING
8.9 Common Side Wall Venting
Requirements:
• Maximum of two heaters can be commonly vented through a side wall.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common thermostat.
33 of 71
Page 40
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
8.10 Common Vertical Venting
Requirements:
• Maximum of four heaters can be commonly vented through the roof.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common thermostat.
• Connections to a common stack must be positioned to avoid direct opposition between streams of combustion gases.
34 of 71
Page 41
8.11 Outside Combustion Air Supply
Description Part Number
Vent Cap 4" (10 cm) for 80,000 Btu/h and 115,000 Btu/h models
90502300
Vent Cap 5" (13 cm) for 150,000 Btu/h and 200,000 Btu/h models
90502301
SIDE VIEW
Band Clamp
(Recommended)
Flex Hose
(Recommended)
Vent Cap
Wall
For 80 and 115 models, 4" (10 cm) Single Wall Pipe. For 150 and 200 models, 5" (13 cm) Single Wall Pipe.
Burner
4"
(10 cm)
Min.
SIDE VIEW
Description Part Number
Vent Cap 4" (10 cm) for 80,000 Btu/h and 115,000 Btu/h models
90502300
Vent Cap 5" (13 cm) for 150,000 Btu/h and 200,000 Btu/h models
90502301
IMPORTANT: If the building has a slight negative pressure or corrosive contaminants such as
8.11.1 Length Requirements
Follow the constraints listed on Page 32, Section 8.6.
halogenated hydrocarbons are present in the air, an outside combustion air supply to the heater is required. Seal all combustion air pipe joints.
The air supply duct may have to be insulated to prevent condensation on the outer surface. The outside air terminal must not be more than 1' (31 cm) above the vent terminal.
Use of optional outside combustion air is not recommended with unvented heaters.
8.11.2 Vertical Outside Air Supply for Single Heater Installation
SECTION 8: VENTING
8.11.3 Horizontal Outside Air Supply for Single Heater Installation
35 of 71
Page 42
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Sweeping 'T'
Connection
For 80 and 115 models, 6" (15 cm) Single Wall Pipe. For 150 or 200 models, 7" (18 cm) Single Wall Pipe.
Vent Cap
Band Clamp
(Recommended)
BurnerBurner
Flex Hose
(Recommended)
Flex Hose
(Recommended)
Roof
For 80 and 115 models, 4" (10 cm) Single Wall Pipe. For 150 or 200 models, 5" (13 cm) Single Wall Pipe.
Description Part Number
Vent Cap 6" (15 cm) 90502302
SIDE VIEW
Sweeping 'Y' Connection
Vent Cap
Outside Wall
For 80 or 115 models, 4" (10 cm) Single Wall Pipe. For 150 and 200 models, 5" (13 cm) Single Wall Pipe.
Flex Hose
(Recommended)
Band Clamp
(Recommended)
Burner
Burner
4"
(10 cm)
Min.
For 80 or 115 models, 6" (15 cm) Single Wall Pipe. For 150 and 200 models, 7" (18 cm) Single Wall Pipe.
Description Part Number
Vent Cap 6" (15 cm) 90502302
TOP VIEW
8.11.4 Vertical Outside Air Supply for Double Heater Installation
Requirements:
• Heaters must be controlled by a common thermostat.
8.11.5 Horizontal Outside Air Supply for Double Heater Installation
Requirements:
• Heaters must be controlled by a common thermostat.
36 of 71
Page 43
SECTION 9: GAS P IPING
WARNING
Explosion Hazard
Leak test all components of gas piping before operation.
Gas can leak if piping is not installed properly.
Do not high pressure test gas piping with heater connected.
Failure to follow these instructions can result in death, injury or property damage.
SECTION 9: GAS PIPING
WARNING
Fire Hazard
Tighten gas hose fittings to connect gas supply according to Figure 21.
Gas hose can crack when twisted.
Gas hose moves during normal operation.
Use only 36" (91 cm) long connector of 1/2" or 3/4" nominal ID.
Connector supplied with heater for U.S. models (not with Canadian models).
Failure to follow these instructions can result in death, injury or property damage.
There is an expansion of the tube with each firing cycle. This will cause the burner to move with respect to the gas line. This can cause a gas leak resulting in an unsafe condition if the gas connection is not made in strict accordance with Figure 21.
Meter and service must be large enough to handle all the burners being installed plus any other connected load. The gas line which feeds the system must be large enough to supply the required gas with a maximum pressure drop of 1/2" wc When gas piping is not included in the layout drawing, the local gas supplier will u
Gas lines must meet applicable codes: United States: The Flexible Stainless Steel Gas Hose (US models) supplied with the heater is certified per the Standard for Connectors for Gas Appliances, ANSI Z21.24/CSA 6.10 - latest revision. Canada: The Rubber Type 1 Gas Hose (Canadian models) optional with the heater is certified as being in compliance with the Standard for Elastomeric Composite Hose and Hose Couplings for Conducting Propane and Natural Gas, CAN/CGA 8.1 - Latest revision.
• Check the pipe and tubing ends for leaks before placing heating equipment into ser­vice. When checking for gas leaks, use a soap and water solution; never use an open flame.
sually help in planning the gas piping.
Install the gas hose as shown in Figure 21. The gas hose accommodates expansion of the heating system and allows for easy installation and service of the burner. Before connecting the burners to the supply system, verify that all high pressure testing of the gas piping has been completed.
37 of 71
Page 44
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Shut-Off Valve (included with gas hose) must be parallel to burner gas inlet. The 3" (8 cm)
displacement shown is for the cold condition. This displacement may reduce when the system is fired.
CORRECT POSITIONS
Horizontal
45°
End View
Vertical
(as shown left)
Alternate positions okay
Flexible Gas Hose 36" (91 cm) length
3" (8 cm) max. displacement
Side View
Heater Movement
12"
(30 cm)
CAUTION
Product Damage Hazard
Hold gas nipple securely with pipe wrench when attaching gas hose.
Failure to follow these instructions can result in product damage.
INCORRECT POSITIONS (WRONG INSTALLATION)
Heater Movement
Heater Movement
Heater Movement Heater Movement
Description Part Number
1/2" Flexible Stainless Steel Gas Hose (US Models) 91412200 3/4" Flexible Stainless Steel Gas Hose (US Models) 91412204 1/2" Rubber Type 1 Gas Hose (Canadian Models) 91412206 3/4" Rubber Type 1 Gas Hose (Canadian Models) 91412207
FIGURE 21: Gas Connection with Flexible Gas Hose
38 of 71
Page 45
SECTION 10: WIRING
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.
Failure to follow these instructions can result in death or electrical shock.
MODULATION CONTROL WIRING TO SATELLITE HEATERS
CENTRAL HEATER CONTROL
OFF
ON
-LCD++FAN-SEN
ZONE SENSOR
SET
J10
W
R
-
+
-
+
-+
OUT
RATE
FIRING
IN
RATE
FIRING
EXT. POT
GND
WIPER
HIGH
GND
BAR
SLIDE
GND
THERMISTOR
INPUT
ANALOG
THERMOSTAT
T31
T29
T19
T18
T16
T14
T27
T25
T30
T28
T17
T15
T13
T26
T24
MODULATION CONTROL WIRING
TO ADDITIONAL SATELLITE
HEATERS CONTROL TERMINALS
T28 and T29.
*OPTIONAL
SWITCH
SATELLITE HEATER CONTROL
J10
W
R
-
+
-
+
-+
OUT
RATE
FIRING
IN
RATE
FIRING
EXT. POT
GND
WIPER
HIGH
GND
BAR
SLIDE
GND
THERMISTOR
INPUT
ANALOG
THERMOSTAT
T31
T29
T19
T18
T16
T14
T27
T25
T30
T28
T17
T15
T13
T26
T24
A
B
AB
* Separate on/off switch is optional for "satellite" heaters (install at user level). On/ Off switch is used to disable heater operation or reset a heater that is in "lockout" mode. If on/off switch is not desired, leave jumper wire between R and W terminals in place.
Description Part Number
Zone Sensor, 40° - 75° 10081530
SECTION 10: WIRING Heater must be grounded in accordance with
applicable codes: United States: refer to National Electrical Code
®
NFPA 70 - latest revision Canada: refer to Canadian Electrical Code, CSA C22.1 Part I - latest revision.
If any of the original internal wiring must be replaced, it must be replaced with wiring materials having a temperature rating of at least 105°C and 600 Volts.
10.1 Standard Heater Configuration
From the factory, the heater is configured for zone sensor control. Connect zone sensor to the heater control as shown on Page 39, Figure 22. If additional heaters are in the same heating zone, control wiring must be installed between the heaters’ controls as shown on Page 39, Figure 22. For additional details or for use with heat demand control devices other than the zone sensor, see Page 40, Section 10.2 through Page 48, Section 10.4.9.
FIGURE 22: Zone Sensor Wiring Diagram
39 of 71
Page 46
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
10.2 Central and Satellite Heaters (Zoning Capability)
The heater can be configured so that several heaters within the same heating zone will modulate
simultaneously with connection to a single heat demand control device. The heat demand control device (See Page 44, Section 10.4) will be wired directly to a single heater configured as the central heater. The remaining heaters in the zone will be configured as satellite heaters and will modulate based on control signaling from the central heater. Zoning capability allows any CTH3-Series heater (regardless of input) to modulate based on the signal from the central heater. During modulation, each satellite heater will operate at the same percentage
10.2.1 Central Heater Configuration
Central heater configuration is set by positioning of jumpers on pin blocks (J10 and J9) located on the control inside the heater compartment, See Page 40,
Figure 23. Jumper position on J10 shown in Figure 23, will configure heater as a central heater and at
the same time configure the heater for the desired heat demand device (zone sensor, thermostat, analog input, or 10K Ohm pot.). If j positioned for "analog", jumper on J9 must be positioned for either 0-10 Vdc or 4-20 mA. If jumpers on J10 are not positioned for "analog", the J9 jumper may be left alone.
of full rated input as the central heater.
FIGURE 23: Central Heater Jumper Settings
umpers on J10 are
40 of 71
Page 47
10.2.2 Satellite Heater Configuration
Satellite heater configuration is set by positioning of jumpers on pin block J10 located on the control board inside the heater compartment, See Page 41, Figure
24. Jumper position on J10, shown on Page 41, Figure 24 will configure heater as a satellite heater.
(The jumper position for satellite is the same as the jumper position of a central heater using a zone sensor). Jumper on J9 may be left alone.
FIGURE 24: Satellite Heater Jumper Setting
SECTION 10: WIRING
41 of 71
Page 48
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
CENTRAL HEATER CONTROL
10.3 Communication Wiring within a Zone of Heaters
Satellite heaters will be wired in series to the central heater via low voltage control wiring.
Communication wiring uses the T28-T31 terminals on the control, see Page 42, Figure 25.
FIGURE 25: Communication Wiring within a Zone of Heaters
42 of 71
Page 49
SECTION 10: WIRING
10.3 Communication Wiring within a Zone of Heaters (continued)
Satellite heaters will be wired in series to the central heater via low voltage control wiring. Communication wiring uses the T28-T31 terminals on the control, See Page 42 through Page 43, Figure 25.
FIGURE 25: Communication Wiring within a Zone of Heaters (continued)
43 of 71
Page 50
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
*OPTIONAL
SWITCH
SATELLITE HEATER CONTROL
J10 JUMPER POSITION SHOWS "SATELLITE" DESIGNATION.
MODULATION CONTROL WIRING TO ADDITIONAL SATELLITE HEATER CONTROL TERMINALS T28 AND T29.
MODULATION CONTROL WIRING TO SATELLITE HEATERS
CENTRAL HEATER CONTROL
T31
T29
T19
T18
T16
T14
T27
T25
T30
T28
T17
T15
T13
T26
T24
T31
T29
T19
T18
T16
T14
T27
T25
T30
T28
T17
T15
T13
T26
T24
RW
T
J10
W
R
-+
-
+
-+
OUT
RATE
FIRING
IN
RATE
FIRING
EXT. POT
GND
WIPER
HIGH
GND
BAR
SLIDE
GND
THERMISTOR
INPUT
ANALOG
THERMOSTAT
J10
W
R
-+
-
+
-+
OUT
RATE
FIRING
IN
RATE
FIRING
EXT. POT
GND
WIPER
HIGH
GND
BAR
SLIDE
GND
THERMISTOR
INPUT
ANALOG
THERMOSTAT
J10 JUMPER POSITION SHOWS "CENTRAL" DESIGNATION AND "THERMOSTAT" CONTROL METHOD.
* Separate on/off switch is optional for "satellite" heaters (install at user level). On/Off switch is used to disable heater operation or reset a heater that is in "lockout" mode. If on/off switch is not desired, leave jumper wire between R and W terminals in place.
10.4 Heat Demand Control Wiring
The heater input can be controlled by any one of the following heat demand control devices (control devices are wired to central heaters only):
10.4.1 Zone Sensor
The zone sensor (P/N 10081530) offers automatic control of heater input. Heater(s) modulates based on difference between sensed air temperature and the temperature setpoint. Heater modulation in response to air temperature changes is immediate. Setpoint is adjusted with the slide bar adjustment at the bottom of the sensor. ON/OFF switch (used to disable heater operation or reset heater from lockout) is located on the side of the sensor. See Page 39, Figure 22 for wiring details.
10.4.2 Thermostat
A thermostat offers automatic control of heater input. The heater control is designed for use with a standard 2-wire or 4-wire low voltage electronic thermostat (not for use with thermostats that have a heat anticipator). Typical wiring connects the R and
FIGURE 26: Thermostat Control Wiring Diagram
W wires to the heater control and does not connect the Y (cooling) and G (fan) wires to the heater control.
The heater can be used with thermostat, 24V (p/n
90425100) if set to 5 cycles per ho
ur. Any other electronic thermostat without heat anticipator can be used if set to 5 or 6 cycles per hour.
On the control, the T24 and T25 (R and W) terminals supply 24 V to power an electronic thermostat. See Page 44, Figure 26 for wiring details. Consult the factory for other thermostat wiring configurations.
Heater(s) modulates based on heater and thermostat cycle timing, history and desired setpoint by using a pre-programmed algorithm. When using thermostat control, heater modulation response to rapid air temperature change is not immediate. Thermostat control is not recommended for use in areas with frequent or high air changes.
It is important to note that during normal operation, heater cycle continues beyond meeting thermostat setpoint.
44 of 71
Page 51
SECTION 10: WIRING
10.4.3 Analog Signal Modulating Thermostat (P/N
90425105)
A programmable, 7-day programming, modulating thermostat can be installed to supply an analog (4­20mA) or (2-10Vdc with 500 Ohm resistor) control signal to dictate the heater(s) firing rate. The thermostat shall energize the T24 and T25 (R and W) terminals. For thermostat wiring, See Page 49, Figure 29 and Page 50, Figure 30. Optional room sensors (P/N 10081520) and outdoor air sensors (P/N 10081521) are available.
Room temperature averaging networks can be created with up to nine room sensors (P/N
10081520). Refer to thermostat installation instructions for wiring.
10.4.4 Analog Signal Modulating Thermostat with
®
LonWorks
If LonWorks
Communication (P/N 90425104)
®
communication is required, a modulating thermostat can be installed to supply an analog (4-20mA or 2-10Vdc) signal to control the heater(s) firing rate. For thermostat wiring, See Page 49, Figure 29 and Page 50, Figure 30. Optional room sensors (P/N 10081520) and outdoor air sensors (P/N 10081521) are available for this thermostat, as well.
The modulating thermostat with LonWorks networking capability in a LonWorks
®
®
system.
provides
Communications port running at 78 kilobits per second (kbs), this thermostat can be configured to perform a variety of activities in which data is sent or
®
received on the LonWorks
. Information that can be
shared, viewed and modified with network includes:
• Current year, month, day, hour, minute, second.
• System Mode.
• Space Temperature
• Outdoor air temperature
• Current setpoint
• Occupied/Unoccupied schedule commands.
• Space Temperature
®
allow integral peer to peer BACnet
MS/TP LAN network communications with configurable baud rates and can easily integrate with a building automation system.
MS/TP Wiring
Connect the -A terminal in parallel with all other -A terminals on the network and the +B terminal in parallel with other +B terminals.
10.4.6 Sequence of Operation for Modulating Thermostats
The thermostat will control the heater(s) firing rate based on the demand signal communicated from thermostat program taking into account space temperature. The thermostat will energize T25 (W) terminal. At high heat, a demand signal will turn the heater(s) on at maximum heater(s) firing rate. Once the room temperature gets close to the thermostat set point, then the thermostat program will slow the heater(s) firing rate down until the room temperature reaches the thermostat set point.
10.4.5 Analog signal Modulating with BACnet Programmable Thermostat (P/N 90425109).
®
If BACnet
communication is required, a BACnet® enabled modulating thermostat can be installed to supply an analog output (0-10VDC) signal control to dictate the heater(s) firing rate. For thermostat wiring, See Page 51, Figure 31.
This thermostat is a flexible wall-mounted stand- alone control with combined controller/sensor. Temperature sensing is standard with optional humidity and motion sensing. BACnet
®
connections
®
45 of 71
Page 52
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
10.4.7 Cable Termination
Tab le li s t s wiring types, sizes and distances for modulating thermostat with LonWorks
®
communication (P/N 90425104), modulating thermostat without communication (P/N 90425105)
®
and BACnet
programmable thermostat
(P/N 90425109)
Table 4:
Digital Outputs 18 AWG (0.75 sq mm) Standard thermostat wire 1000 ft (304 m) Modulating Outputs 18 AWG (0.75 sq mm) 1 pair 500 ft (152 m) Outdoor Air Temperature Sensor 18 AWG (0.75 sq mm) 1 pair 500 ft (152 m) Remote Sensor 18 to 22 AWG
Power Wiring 18 to 14 AWG
LonWorks
MS/TP (P/N 90425109) 18 AWG (0.75 sq mm) Shield Belden cable #82760 or equivalent Refer to Thermostat Installation Guide
Cable Requirements
Wire Function Recommended Wire Size
(Minimum)
(0.75 to 0.34 sq mm)
®
(P/N 90424104 only)
( 0.75to 2.0 sq mm) 18 AWG
(0.75 sq mm) nonshielded
Specification or
Distance (Maximum)
Requirement
Twisted pair wire 1000 ft (304 m)
NEC Class II 140ºF (60°C ) Limited by line-loss effects on power
consumption.
1 pair Refer to E-bus Wiring Guide 74-2865
for maximum length and generic cable specifications.
Power Requirements
Modulating thermostats require 24 volts, AC power.
10.4.8 Remote Analog Signal
Remote Analog Signal 0-10 Vdc or 4-20mA output from external controller or Building Management System (BMS) directly dictates heater(s) firing rate. An algorithm must be programmed into the BMS or external controller to receive zone air temperature signals from its own temperature sensors and then deliver an output signal to the heater(s) for the desired firing rate.
For 0-10Vdc control of the heater(s) firing rate, the following control conditions apply:
ON/OFF relay at the external controller or BMS must be wired to R and W terminals on the heater control board to turn the heater ON and OFF.
Minimum rated input at 1% of signal (0-1Vdc). Full rated input at 90% of signal (9Vdc). Input varies linearly between 1Vdc and 9Vdc.
46 of 71
Page 53
SECTION 10: WIRING
*OPTIONAL
SWITCH
SATELLITE HEATER CONTROL
FOR SATELITTE CONTROLLERS, J9 JUMPER CAN BE LEFT IN ORIGINAL POSITION REGARDLESS OF CONTROL METHOD.
J10 JUMPER POSITION SHOWS "SATELLITE" DESIGNATION.
MODULATION CONTROL WIRING TO ADDITIONAL SATELLITE HEATER CONTROL TERMINALS T28 and T29.
ON/OFF SWITCH REQUIRED
MODULATION CONTROL WIRING TO SATELLITE HEATERS
CENTRAL HEATER CONTROL
REMOTE ANALOG CONTROL SIGNAL FROM SEPARATE CONTROLLER 0-10Vdc OR 4-20mA
ANALOG INPUT CONTROL IS USED TO SELECT ANALOG SIGNAL TYPE 0-10Vdc OR 4-20mA (4-20mA POSITION SHOWN).
J10 JUMPER POSITION SHOWS "CENTRAL" DESIGNATION AND "ANALOG" CONTROL METHOD.
J10
J9
W
R
-+
-
+
-+
OUT
RATE
FIRING
IN
RATE
FIRING
EXT. POT
GND
WIPER
HIGH
GND
BAR
SLIDE
GND
THERMISTOR
INPUT
ANALOG
THERMOSTAT
T31
T29
T19
T18
T16
T14
T27
T25
T30
T28
T17
T15
T13
T26
T24
-
+
J10
J9
W
R
-+
-
+
-+
OUT
RATE
FIRING
IN
RATE
FIRING
EXT. POT
GND
WIPER
HIGH
GND
BAR
SLIDE
GND
THERMISTOR
INPUT
ANALOG
THERMOSTAT
T31
T29
T19
T18
T16
T14
T27
T25
T30
T28
T17
T15
T13
T26
T24
A B
A B
* Separate on/off switch is optional for "satellite" heaters (install at user level). On/Off switch is used to disable heater operation or reset a heater that is in "lockout" mode. If on/off switch is not desired, leave jumper wire between R and W terminals in place.
For 4-20mA control of the heater(s) firing rate, the following control conditions apply:
ON/OFF relay at the external controller or BMS must be wired to R and W terminals on the heater control board to turn the heater ON and OFF. (Open Circuit = OFF, Closed Circuit = ON). Minimum rated input at 1% of signal (0-4 mA). Full rated input at 90% of signal (18 mA). Input varies linearly between 4 mA and 18 mA.
BMS controllers often offer PID loop control that can optimize output signal and rate of change of the output signal. Common analog application is defined as follows:
1. BMS sensors that monitor zone air temperatures are located in the heating space.
FIGURE 27: Analog Control Signal Wiring Diagram
2. Based on sensed temperatures, the BMS will output an analog signal for the desired heater(s) firing rate.
3. As heater(s) receive the analog signal from the BMS, the heater(s) modulate to the correspond­ing firing rate.
4. As sensed air temperature rises closer to the desired temperature setpoint, the BMS will reduce the output signal, in turn reducing heater firing rate.
5. Upon satisfying temperature setpoint, the BMS will either:
a. Tu
rn off the heater.
b. Reduce the signal so that the minimum
heater firing rate is maintained until the sensed temperature rises above the setpoint to a cut-off limit temperature when the BMS turns off the heater.
47 of 71
Page 54
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
*OPTIONAL
SWITCH
SATELLITE HEATER CONTROL
J10 JUMPER POSITION SHOWS "SATELLITE" DESIGNAT ION.
MODULATION CONTROL WIRING
TO ADDITIONAL SATELLITE HEATER CONTROL TERMINALS T28 AND T29.
MODULATION CONTROL WIRING TO SATELLITE HEAT ERS
CENTRAL HEATER CONTROL
J10
W
R
-+
-
+
-+
OUT
RATE
FIRING
IN
RATE
FIRING
EXT. POT
GND
WIPER
HIGH
GND
BAR
SLIDE
GND
THERMISTOR
INPUT
ANALOG
THERMOSTAT
T31
T29
T19
T18
T16
T14
T27
T25
T30
T28
T17
T15
T13
T26
T24
J10
W
R
-+
-
+
-+
OUT
RATE
FIRING
IN
RATE
FIRING
EXT. POT
GND
WIPER
HIGH
GND
BAR
SLIDE
GND
THERMISTOR
INPUT
ANALOG
THERMOSTAT
T31
T29
T19
T18
T16
T14
T27
T25
T30
T28
T17
T15
T13
T26
T24
ON/OFF SWITCH or THERMOSTAT
A B
A B
J10 JUMPER POSITION SHOWS "CENTRAL"
DESIGNATION AND "POTENTIOMETER" CONTROL METHOD.
POTENTIOMETER
(10K Ohm)
* Separate on/off switch is optional for "satellite" heaters (install at user level). On/Off switch is used to disable heater operation or reset a heater that is in "lockout" mode. If on/off switch is not desired, leave jumper wire between R and W terminals in place.
10.4.9 Potentiometer Control Device
Potentiometer (10K Ohm"Linear Taper") device offers manual control over heater(s) firing rate. This type of potentiometer can be found at Radio Shack
®
. Potentiometer dial position directly dictates heater(s) firing rate. Dial positions range between "Min" and "Max". Minimum and maximum heater firing rates (inputs) are marked on the heater's rating plate. ON/ OFF switch or thermostat is used to disable heater operation or reset heater from lockout.
FIGURE 28: Potentiometer Control Wiring Diagram
48 of 71
Page 55
SECTION 10: WIRING
Description Part Number
Thermostat, modulating 90425105 Thermostat, modulating LonWorks
®
90425104
* Separate on/off switch is optional for "satellite" heaters (install at user level). On/Off switch is used to disable heater operation or reset a heater that is in "lockout" mode. If on/off switch is not desired, leave jumper wire between R and W terminals in place.
NOTE: 1. For non-communicating thermostats without LonWorks
®
bus, thermostat terminals marked "EB"
will be marked "_____" and no LonWorks
®
bus communication wires are used.
FIGURE 29: Modulating Thermostat Wiring Diagram (LonWorks
®
[4-20 mA] optional)
49 of 71
Page 56
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
* Separate on/off switch is optional for "satellite" heaters (install at user level). On/Off switch is used to disable heater operation or reset a heater that is in "lockout" mode. If on/off switch is not desired, leave jumper wire between R and W terminals in place.
NOTE: 1. For non-communicating thermostats without LonWorks
®
bus, thermostat terminals marked "EB"
will be marked "_____" and no LonWorks
®
bus communication wires are used.
Description Part Number
Thermostat, modulating 90425105 Thermostat, modulating LonWorks
®
90425104
FIGURE 30: Modulating Thermostat Wiring Diagram (LonWorks optional)
®
[2-10Vdc with 500 Ohm resistor]
50 of 71
Page 57
SECTION 10: WIRING
Description Part Number
Thermostat, modulating BACnet
®
90425109
NOTES:
1. A j umper is pre-installed between phase R(24VAC) and SC1-3 (24VAC Relay).
2. Ground ONLY ONE END of the shielded cable.
* Separate on/off switch is optional for "satellite" heaters (install at user level). On/Off switch is used to disable heater operation or reset a heater that is in "lockout" mode. If on/off switch is not desired, leave jumper wire between R and W terminals in place.
FIGURE 31: Modulating Thermostat Wiring Diagram with BACnet
®
(optional)
51 of 71
Page 58
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
10.5 Internal Wiring
See Page 39, Section 10.1 through Page 48, Section
10.4.9 for temperature control device options and
wiring schematic.
52 of 71
Page 59
10.6 Ladder Diagram
L1
L2
24V
120V
CONTROL
GAS VALVE
SURFACE
IGNITER
HOT
MOTOR
FLAME SENSOR
SWITCH
DOOR
AIR SWITCH
BLK
WHT
WHT
BLK
BLK
BLK
BLK
WHT
WHT
BLU
YEL
ORG
BLU
BLU
BLU
PRP
BRN
BRN
BRN
BLU
BLK
GRN
BLU
BLU
GRN
SECTION 10: WIRING
See Page 39, Section 10.1 through Page 48, Section 10.4.9 for temperature control device options and wiring schematic.
53 of 71
Page 60
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Gnd.
120 V-60 Hz
Supply Circuit
H
N
H
N
L1 L2
Gnd.
Gnd.
Burner 2
Burner 3
Gnd.
Burner 1
H
N
NOTE: The burners must have an uninterrupted 120 V, 60 Hz, 1 Ø power supply.
BX or Romex Connector
Junction Box
Electrical Cord or
Flexible Conduit
Burner
Connect wires together
with suitable approved
wire connectors.
Green to Ground
White to L2
Black to L1
L1 L2
Ground
Black
White
Green
10.7 Line Voltage Power Wiring
10.8 Electrical Connection to the Burner
54 of 71
Page 61
10.9 Low Voltage Control Wiring Installation
Description Part Number
Cable Grommet with Tie 91309605
SECTION 10: WIRING
55 of 71
Page 62
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 11: OPERATION AND MAINTENANCE
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be connected to a properly grounded electrical source.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
11.1 Sequence of Operation
The control inside the heater's control compartment is equipped with a tri-color LED. The LED offers comprehensive diagnostic capability. The LED status will be referenced throughout this section.
1. When the control is powered and there is no call for heat from external heat demand device, the LED on the control flashes slow green; LED is ON for the same period it is OFF.
2. On a call for heat from the heat demand device, the heater will go to PRE-PURGE. The LED indicates one green flash. The blower speed will
vary as the pressure switch setpoints are verified. When the PRE-PURGE is successfully
completed, the heater will go into the PRE-IGNITION state and power the hot surface igniter (H.S.I.).
3. After the igniter warms up, the heater will go to the IGNITION state. Power is supplied to the gas valve operator, gas flows, ignites and the flame is proven. The LED shows two green flashes on the LED. If a flame is not sensed, the heater will RETRY, See Item 6 below for further details.
4. When the IGNITION state is completed, the heater will go to WARM UP state. The unit will fire at maximum input for 15 seconds. When the WARM UP state is completed the device will go into RUN state. The control board will monitor the heat demand device and modulate the heater input to meet the demand. The LED still shows two green flashes.
5. When the call for heat has been satisfied, the heater closes the gas valve. The blower
Explosion Hazard
Turn off gas supply to heater before service.
WARNING
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
continues to run for a 45 second post-purge period. After the post-purge, the heater turns OFF and the LED on the control board flashes slow green.
6. If flame is lost at any time during heater operation, the heater will RETRY for ignition. Upon RETRY the LED shows a fast yellow flash (LED rapidly flashes). The heater will RETRY for ignition three times. After four ignition attempts, the heater will lockout for one hour or until reset. To reset the heater, remove power for 10 seconds, then re-apply power. Turn heater ON with call for heat from the heat demand device.
11.2 To Shut Off Heater
Set external heat demand dev Turn OFF electric power to heater. Turn OFF manual gas valve in the heater supply line.
11.3 To Start Heater
Turn gas valve and electric power OFF and wait five minutes for unburned gases to vent from heater.
Turn ON main gas valve. Turn ON electric power. Set heat demand device to desired temperature.
Burner should light automatically.
11.4 Pre-Season Maintenance and Annual Inspection
To e n s ure your safety and years of trouble-free operation of the heating system, service and annual inspections must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
Turn off gas and electric supplies before performing
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
ice to lowest setting.
56 of 71
Page 63
SECTION 11: OPERATION AND MAINTENANCE
service or maintenance. Allow heater to cool before servicing.
Before every heating season, a contractor qualified in the installation and service of gas-fired heating equipment must perform a thorough safety inspection of the heater.
For best performance, the gas, electrical, thermostat connections, tubing, venting, suspensions and overall heater condition should be thoroughly inspected.
NOTE: Gas flow and burner ignition are among the first things that should be inspected.
Please See Page 57 for suggested items to inspect.
Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon LLC and conform to all requirements set forth in the ROBERTS GORDON
®
manuals and all applicable governmental authorities pertaining to the installation, service, operation and labeling of the equipment.
To help facilitate optimum performance and safety, Roberts-Gordon LLC recommends that a qualified contractor conduct, at a minimum, annual inspections of your ROBERTS GORDON
®
equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts­Gordon LLC.
The Vicinity of the Heater Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 5, Section 3.
Vehicles and Other Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
®
Make sure nothing is lodged underneath the reflector, in between the tubes or in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 5, Section 3.
Reflector Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. See Page 20, Section 6.5.1.
Clean outside surface with a damp cloth.
Vent Pipe Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and d
ust. Clean as required.
Remove any carbon deposits or scale using a wire brush.
See Page 31, Section 8.
Outside Air Inlet Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
Tubes Make sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 12, Section 6.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
57 of 71
Page 64
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Gas Line Check for gas leaks. See Page 37, Section 9. Burner Observation
Window
Blower Scroll, Wheel and Motor
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
Burner Cup and Orifice Clear of obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Hot-Surface Igniter Replace if cracked or broken. Heat Demand Device:
Thermostat, Zone Sensor, External Pot or 0-10 Vdc or
There should be no exposed wire or damage to the device or wiring.
See Page 39, Section 10.
4 - 20 mA wiring Suspension Points Make sure the heater is hanging securely.
Look for signs of wear on the chain or ceiling.
See Page 13, Figure 14.
Decorative and Protective Grille (optional)
The grille must be securely attached.
Check that the side reflector extensions are installed correctly and secured in place if necessary. (Decorative grille only.)
See Page 28, Section 7.5 and Page 30, Section 7.6
Make sure shield is installed correctly and secured in place if necessary.
Lower Clearance Shield (optional)
(Decorati The lower shield must be securely attached.
Inspect shield support straps and lower clearance shield anchor points.
ve grille only.) See Page 29, Section 7.5.2.
See Page 28, Section 7.4.
Make sure shield is installed correctly and secured in place if necessary.
See Page 28, Section 7.4.
Silicone Tubing Ensure tight, secure fit on all pressure fittings at gas valve, pressure switch,
pressure sensor, burner partition, and blower outlet.
Gas Valve Verify silicone tubing has a tight secure fit on "vent" fitting.
Verify that plastic cap on covering pressure regulator adjustment screw is secure and has not been tampered with.
Do not remove plastic regulator cap or attempt to adjust valve pressure regulator.
Verify all wiring connections.
Wall Tag
If wall tag is present, make sure it is legible and accurate. Please contact Roberts-Gordon LLC or your ROBERTS GORDON
®
independent distributor, if
you need a wall tag. See Page 4, Section 2.1.
Safety Labels Product safety signs or labels should be replaced by the product user when
they are no longer legible. Please contact Roberts-Gordon LLC or your ROB-
®
ERTS GORDON
independent distributor to obtain replacement signs or
labels. See Page 2, Figure 1 through Page 3, Figure 2.
58 of 71
Page 65
SECTION 12: TROUBLESHOOTING
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
Explosion Hazard
Turn off gas supply to heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be required to disconnect electric from heater.
Heater must be properly grounded to an electrical source.
Failure to follow these instructions can result in death or electrical shock.
SECTION 12: TROUBLESHOOTING
59 of 71
Page 66
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
12.1 Control LED
The control inside the heater's control compartment is equipped with a tri-color LED. The LED offers comprehensive diagnostic capability. The LED is showing some form of status signal at all times when the control is powered. The color of the LED differentiates normal from error conditions as follows:
GREEN indicates normal operation. RED indicates an error condition. YELLOW (fast flashing) indicates a RETRY attempt. LED NOT LIT indicates no power to control.
12.2 General LED Codes
No LED: No Power to control.
Slow Green: LED slowly flashes on and off,
indicates power to the control board but no call for heat.
GREEN, 1 flash: Call for heat indicates the
heater is performing the safe start pre-purge function or H.S.I. warm-up.
GREEN, 2 flashes: Call for heat indicates the
heater is performing light off, heater warm-up, or heater run.
GREEN, 3 flashes: *Only applicable for
thermostat control* Gas ON - No call for heat, unit
modulating from single stage thermostat.
AMBER, 1 flash: Call for heat when flame signal
is below 1µA
AMBER, Fast Flashing: Heater is in RETRY mode.
RED Steady LED: Control FAILURE,
No 24 V power supply.
RED, 1 flash: Lockout- Insufficient sensed
air pressure when blower is on. Condition could be caused by:
• Air Side Door
• Blower
• Obstruction in inlet or outlet
• Pressure hose fittings
• Pressure Switch
RED, 2 flashes: Lockout- Blower air pressure
reads above zero level when blower is off. Condition is caused by a pressure sensor failure or complete blockage of air intake or exhaust vent.
RED, 3 flashes: Lockout- Flame is sensed on
when it should be off or off when it should be on.
Could be caused by:
• Flame Rod
• H.S.I.
• Gas Supply
• 120 V Supply Polarity
• Board Fault
RED, 4 flashes: Locko
ut- Gas Valve. Condition caused by main valve on gas valve. Check gas valve wiring.
AMBER, 2 flashes: Gas ON - Call for heat when
flame signal is below 1µA
AMBER, 3 flashes: *Only applicable for
thermostat control* Gas ON - No call for heat, unit
modulating from single stage thermostat when flame signal is below 1µA.
60 of 71
RED, 5 flashes: Lockout- Board Failure.
Board must be replaced.
RED, 6 flashes: Not used.
RED, 7 flashes: Lockout- Fuse Open.
Condition could be caused by:
• Fuse blown
• High Limit Switch open a
board location J3
Page 67
RED, 8 flashes: Lockout- Pressure switch
failed to operate or modulation current was incorrect. Condition could be caused by:
• Pressure Sensor
• Pressure Switch
(faulty or hoses reversed)
• Gas Valve Modulation Coil
• Wire Harness (6 wire)
RED, 9 flashes: Lockout- Air Supply.
Condition could be caused by:
• Blower
• Pneumatic Conections to Pressure Sensor
• Blockage in flue or inlet
SECTION 12: TROUBLESHOOTING
61 of 71
Page 68
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
12.3 Troubleshooting Flow Chart
62 of 71
Page 69
SECTION 12: TROUBLESHOOTING
63 of 71
Page 70
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
WARNING
Carbon Monoxide Hazard
Do not adjust gas valve pressure regulator.
Do not tamper with sealed parts.
Pressure regulator is factory calibrated for safe operation.
Failure to follow these instructions can result in death or injury.
12.4 Manifold Gas Pressure Measurement
64 of 71
Page 71
12.5 Pneumatic Connections
SECTION 12: TROUBLESHOOTING
65 of 71
Page 72
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Carbon Monoxide Hazard
WARNING
Use only genuine ROBERTS GORDON® replacement parts per this installation, operation and service manual.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Explosion Hazard
DANGER
Electrical Shock Hazard
Fire Hazard
SECTION 13: REPLACEMENT PARTS
66 of 71
Page 73
SECTION 13: REPLACEMENT PARTS
67 of 71
Page 74
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Description Part Number
Gas Valve (Natural) 90033105K Gas Valve (LP) 90033104K Tube Gasket 02568200 Blower Inlet Gasket (80, 115 models) 03050900 Blower Inlet Gasket (150, 200 models) 90709910 Blower Assembly (80, 115) 90708602-P Blower Assembly (150, 200) 90709900-P Air Collar (80, 115 models) 91911700 Air Collar (150, 200 models) 91911701 Inlet Screen (80, 115) 03050800 Inlet Screen (150, 200) 09050001 Door Switch 90436800 Burner Cup Assembly 03020100 Hot Surface Igniter 90436600K Mica Window Assembly 02553203 Flame Sensor 90439300 Transformer 90436900K Fuse (Control) 3 A 91321403 Pressure Switch (80 NG, 80 LP, 115 NG, 115 LP) 90439812K (150 NG, 150 LP, 200 NG, 200 LP) 90439803K Control 80NG 90320109K 80LP 90320110K 115NG 90320111K 115LP 90320112K 150NG 90320113K 150LP 90320114K 200NG 90320115K 200LP 90320116K
68 of 71
Page 75
SECTION 14: GENERAL SPECIFICATIONS
Turbulator
(Select Models)
Side View
Reflector
17.5"
(44 cm)
Minimum Length "A"
End View
13.5"
(34 cm)
9.5"
(24 cm)
Burner Tube
Heat Input Rate
(NG)
Heat Input
Rate
(LP)
Length “A”
Recommended
Minimum Mounting Height*
Model
(Btu/h) X (1000)
Min. to Max.
(Btu/h) X
(1000)
Min. to Max.
Minimum Space Spot
CTH3-80 52 to 80 55 to 80 20' (6m) 12'-15' (3.6 - 4.5 m) 11' (3.3 m)
CTH3-115 75 to 115 78 to 115 30' (9m) 15'-20' (4.5 - 6 m) 15' (4.6 m)
CTH3-150 100 to 150 105 to 150 40' (12m) 20'-25' (6 - 7.6 m) 20’ (6.1 m)
CTH3-200 130 to 200 135 to 190 50' (15m) 25' (7.6 m) 23' (7 m)
14.1 Material Specifications
14.1.1 Reflectors
.024 Aluminum (Optional .024 Stainless Steel Type 304)
14.2 Heater Specifications
14.2.1 Control System
Modulating Gas Valve and Hot Surface Electronic Ignition Control with Four-try, 100% shut-off, Prepurge, Post-Purge, Auto Reset, Tri-color LED Status/Fault Indicator.
General Specifications for the heaters are as follows:
SECTION 14: GENERAL SPECIFICATIONS
14.3 Suspension Specifications
Hang heater with materials with a minimum working load of 75 lbs (33 kg). See Page 13, Figure 14.
14.4 Controls Specifications
Time switches, sensors, etc. can be wired into the electrical supply. External controls supplied as an optional extra.
*See Page 5, Section 3 for clearances to combustibles.
GAS PRESSURE AT MANIFOLD:
Natural Gas: 4.5" wc LP Gas: 11.0" wc
GAS INLET PRESSURE: Natural Gas:
for 80, 115 & 150 models 5.5" wc Minimum
PIPE CONNECTION:
1/2" NPT (for 80 & 115 models) 3/4" NPT (for 150 & 200 models)
DIMENSIONS:
Vent Connection Size: 4" (10 cm) Outside Air Connection Size: 5" (13 cm) for 150 & 200 models 4" (10 cm) for 80 & 115 models
for 200 6.0" wc Minimum
LP Gas: 12.0" wc Minimum
ELECTRICAL RATING (ALL MODELS):
120V - 60 Hz., 4.8 A (start), 1.3 A (run)
Refer to figure above for dimensional information.
14.0" wcMaximum
14.0" wcMaximum
14.0" wcMaximum
69 of 71
Page 76
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
70 of 71
Page 77
SECTION 15: THE ROBERTS GORDON® VANTAGE® MODULATING WARRANT Y
SECTION 15: THE ROBERTS GORDON VANTAG E
®
MODULATING WARRANTY
®
ROBERTS-GORDON WILL PAY FOR:
Within 36 months from date of purchase by buyer or 42 months from date of shipment by Roberts-Gordon LLC (whichever occurs first), replacement parts will be provided free of charge for any part of the product which fails due to a manufacturing or material defect.
Roberts-Gordon LLC will require the part in question to be returned to the factory. Roberts-Gordon LLC will, at its sole discretion, repair or replace after determining the nature of the defect and disposition of part in question.
ROBERTS GORDON
®
Replacement Parts are warranted for a period of 12 months from date of shipment from Roberts-Gordon LLC or the remaining ROBERTS GORDON
®
VANTAGE® MODULATING warranty.
ROBERTS-GORDON WILL NOT PAY FOR:
Service trips, service calls and labor charges. Shipment of replacement parts. Claims where the total price of the goods have not
been paid. Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the ROBERTS GORDON
®
VANTAGE® MODULATING in
any way.
• Use of the ROBERTS GORDON
®
VANTAGE® MODU­LATING for other than its intended purpose.
• Incorrect gas or electrical supply, accident, fire, floods, acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or acces­sories not specified by Roberts-Gordon.
• Failure to install or maintain the ROBERTS GORDON VANTAGE® MODULATING as directed in the Installa­tion, Operation and Service manual.
• Relocation of the ROBERTS GORDON
®
VANTAGE®
MODULATING after initial installation
• The use of the ROBERTS GORDON
®
VANTAGE® MODULATING in a corrosive atmosphere containing contaminants.
• The use of the ROBERTS GORDON
®
VANTAGE® MODULATING in the vicinity of a combustible or explo­sive material.
• Any defect in the ROBERTS GORDON
®
VANTAGE® MODULATING arising from a drawing, design, or spec- ification supplied by or on behalf of the consumer.
• Damage incurred during shipment. Claim must be filed with carrier.
WARRANTY IS VOID IF:
The ROBERTS GORDON® VANTAGE® MODULATING is not installed by an electrician qualified in the installation and service of gas fired heating equipment.
Yo u cannot prove original purchase date and required annual maintenance history.
The data plate and/or serial number are removed, defaced, modified or altered in any way.
The ownership of the ROBERTS GORDON
®
VANTAGE® MODULATING is moved or transferred. This warranty is nontransferable.
Roberts-Gordon LLC is not permitted to inspect the damaged controller and/or component parts.
READ YOUR INSTALLATION, OPERATION AND SERVICE MANUAL
If you have questions about your controller, contact your installing professional. Should you need Replacement Parts or have additional questions, call or write:
Roberts-Gordon LLC
1250 William Street P. O . B o x 4 4 Buffalo, New York 14240-0044 Telephone: +1.716.852.4400 Fax: +1.716.852.0854 Toll Free: 800.828.7450
www.rg-inc.com www.radiantheaters.com
Roberts-Gordon LLC's liability, and your exclusive remedy, under this warranty or any implied warranty (including the implied warranties of merchantability and fitness for a particular purpose) is limited to providing replacement parts during the term of this warranty.
Some jurisdictions do not allow limitations on
how long an implied warranty lasts, so this limitation may not apply to you. There are no rights, warranties or conditions, expressed or implied, statutory or otherwise, other than those contained in this warranty.
Roberts-Gordon LLC shall in no event be responsible for incidental or consequential damages or incur
®
liability for damages in excess of the amount paid by you for the ROBERTS GORDON
®
VANTAGE® MODULATING. Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so this limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from jurisdiction to jurisdiction.
Roberts-Gordon LLC shall not be responsible for failure to perform under the terms of this warranty if caused by circumstances out of its control, including but not limited to war, fire, flood, strike, government or court orders, acts of God, terrorism, unavailability of supplies, parts or power. No person is authorized to assume for Roberts-Gordon LLC any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF REPRESENTATIVES:
No representative of Roberts-Gordon LLC, other than an Executive Officer, has authority to change or extend these provisions. Changes or extensions shall be binding only if confirmed in writing by Roberts-Gordon LLC's duly authorized Executive Officer.
71 of 71
Page 78
Page 79
Page 80
Page 81
Page 82
Loading...