Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or
property damage. Read the Installation, Operation
and Service Manual thoroughly before installing or
servicing this equipment.
WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas
supplier after leaving the building.
Follow the gas supplier’s
instructions.
8. If you cannot reach your gas
supplier, call the Fire Department.
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to combustibles away from
heater.
Some objects will catch fire or explode
when placed close to heater.
Failure to follow these instructions can
result in death, injury or property
damage.
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Roberts-Gordon LLC.
Yo ur Safety is Important to Us!
This symbol is used throughout
the manual to notify you of possible fire, electrical or burn hazards.
Please pay special attention when
reading and following the
warnings in these sections.
Installation, service and annual inspection of heater
must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
Read this manual carefully before installation, operation or service of this equipment.
This heater is designed for heating nonresidential
indoor spaces. Do not install in residential spaces.
This heater is not certified to meet the requirements
of NFPA30A-2012 Section 7.6.6. (maximum tube
temperature of 750 °F (399 °C)). Do not install this
heater in facilities where compressed natural gas
(CNG) or liquid natural gas (LNG) are present. These
instructions, the layout drawing, local codes and
ordinances, and applicable standards that apply to
gas piping, electrical wiring, venting, etc. must be
thoroughly understood before proceeding with the
installation.
Protective gear is to be worn d
uring installation,
operation and service in accordance to the
Occupational Safety and Hazard Administration
(OSHA). Gear must be in accordance to NFPA 70E,
latest revision when working with electrical
components. Thin sheet metal parts have sharp
edges. To prevent injury, the use of work gloves is
recommended. The use of gloves will also prevent
the transfer of body oils from the hands to the surface
of the reflector.
Before installation, check that the local distribution
conditions, nature of gas and pressure, and adjust-
ment of the appliance are compatible.
This heater must be applied and operated under the
general concepts of reasonable use and installed
using best building practices.
This appliance is not intended for use by persons
(including children) with reduced physical, sensory or
mental capabilities, or lack of experience and
knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a
person responsible for their safety. Children shou
ld
be supervised to ensure that they do no play with the
appliance.
For additional copies of the Installation, Operation
and Service Manual, please contact Roberts-Gordon
LLC.
1.1 Manpower Requirements
To p r event personal injury and damage to the heater,
two persons will be required for installation.
1.2 Safety Labels and Their Placement
Product safety signs or labels should be replaced by
the product user when they are no longer legible.
Please contact Roberts-Gordon or your ROBERTS
®
GORDON
independent distributor to obtain
replacement signs or labels. See Page 2, Figure 1 through Page 3, Figure 2.
1.3 California Proposition 65
In accordance with California Proposition 65 require-
ments, a warning label must be placed in a highly
visible location on the outside of the equipment (i.e.,
near equipment’s serial plate). See label placement
drawing on Page 2, Figure 1 for label location. Avoid
placing label on areas with extreme heat, cold, corrosive chemicals or other elements. To order additional
labels, please contact Roberts-Gordon LLC or your
ROBERTS GORDON
®
independent distributor.
1
Page 8
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Logo Label
Rating Plate Label
Bottom
Panel
Top Panel
Gas Connection Label
Proposition 65 Label
DescriptionPart Number
Logo Label91013221
Rating Plate Label91010401
Gas Connection Label91018122
Proposition 65 Label91070016
Burner Status Label91033301
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To install the heater, as well as the gas and electrical supplies, in accordance with applicable specifications and codes. Roberts-Gordon recommends
the installer contact a local Building Inspector or
Fire Marshal for guidance.
• To use the information given in a layout drawing
and in the manual together with the cited codes
and regulations to perform the installation.
• To install the heater in accordance with the
clearances to combustibles.
• To furnish all needed materials not furnished as
standard equipment.
• To plan location of supports.
• To provide access to burners for servicing on all
sides for burner removal.
• To provide the owner with a copy of this installation, operation and service manual.
• To never use heater as support for a ladder or
other access equipment and never hang or sus-
pend anything from heater.
•To ensure there is adequate air circulation around
the heater and to supply air for combu
stion, ventilation and distribution in accordance with local
codes.
• To safely and adequately install heater using
materials with a minimal working load of 75 lbs
(33 kg).
• To ensure the heater is placed in a approved
application.
2.1 Wall Tag
A laminated wall tag is available for the heater as a
permanent reminder of the safety instructions and
the importance of the required clearances to combustibles. Please contact Roberts-Gordon or your
ROBERTS GORDON
®
independent distributor to
obtain the wall tag. Affix the tag by peeling off the
backing of the adhesive strips on the rear surface
and position the tag on a wall near the heater (e.g.
thermostat or ROBERTS GORDON
®
Controller).
A copy of the wall tag (P/N 91037912) is illustrated on
the back cover. For an immediate solution, you may
affix this copy on the wall near the heater.
Know your model number and installed configuration.
Model number and installed configuration are found
on the burner and in the Installation, Operation and
Service Manual. See Page 5, Figure 3 through Page 8, Figure 12. Write the proper clearance dimensions
in permanent ink according to your model number
and configuration in the open spaces on the tag.
2.2 Corrosive Chemicals
CAUTION
Product Damage Hazard
Do not use heater in area containing
corrosive chemicals.
Refer to appropriate Material Safety Data
Sheets (MSDS).
Failure to follow these instructions can result
in product damage.
Roberts-Gordon cannot be responsible for ensuring
that all appropriate safety measures are undertaken
prior to installation; this is entirely the responsibility of
the installer. It is essential that the contractor, the
sub-contractor, or the owner identifies the presence
of combustible materials, corrosive chemicals or
halogenated hydrocarbons* anywhere in the
premises.
* Halogenated Hydrocarbons are a family of chemical
compounds characterized by the presence of halogen
elements (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning
agents, solvents, etc. If these compounds enter the air
supply of the burner, the life span of the heater components will be greatly reduced. An outside air supply must
be provided to the burners whenever the presence of
these compounds is suspected. Warranty will be invalid if
the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installations in Public Garages, Aircraft Hangars,
etc. may be applicable.
4
Page 11
SECTION 3: CLEARANCES TO COMBUSTIBLES
WARNING
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to
combustibles away from heater.
Some objects will catch fire or explode when
placed close to heater.
Failure to follow these instructions can result
in death, injury or property damage.
3.1 Required Clearances to Combustibles
Clearances are the required distances that combusti-
ble objects must be away from the heater to prevent
serious fire hazards. Combustibles are materials that
may catch on fire and include common items such as
wood, paper, rubber, fabric, etc. Maintain clear-
ances to combustibles at all times for safety.
Clearances for all heater models are located on the
burner of the heater and on Page 5, Figure 3 through Page 8, Figure 12 in this manual. Check the clear-
ances on each burner for the model heater being
installed to make sure the product is suitable for your
application and the clearances are maintained. Read
and follow the safety guidelines below:
• Keep gasoline or other combustible materials
including flammable objects, liquids, dust or
vapors away from this heater or any other appli-
ance.
• The stated clearances to combustibles represents
a surface temperature of 90° F (32°C) above room
temperature. Building materials with a low heat tol-
erance (such as plastics, vinyl siding, canvas, triply, etc) may be subject to degradation at lower
temperatures. It is the installer’s responsibility to
assure that adjacent materials are protected from
degradation.
• Maintain clearances from heat sensitive
equipment and workstations.
• Maintain clearances from vehicles parked below
the heater.
• Maintain clearances from swinging and overhead
doors, overhead cranes, vehicle lifts, partitions,
storage racks, hoists, building construction, etc.
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
SECTION 3: CLEARANCESTO COMBUSTIBLES
• In locations used for the storage of combustible
materials, signs must be posted to specify the
maximum permissible stacking height to maintain
required clearances from the heater to the combustibles. Signs must be posted adjacent to the
heater thermostat. In the absence of a thermostat,
signs must be posted in a conspicuous
location.
• Consult local Fire Marshal, Fire Insurance Carrier
or other authorities for approval of proposed installation when there is a possibility of exposure to
combustible airborne materials or vapors.
• Hang heater in accordance to the minimum sus-
pension requirements
• If the radiant tubes must pass through the building
structure, be sure that adequate sleeving and fire
stop is installed to prevent scorching and/or fire
hazard.
on Page 16, Figure 15
.
FIGURE 3: LEVEL REFLECTOR
Model ABCDABCD
CTH2V-406275327166913569
CTH2V-60 6 356335168916189
CTH2V-806386638169716897
CTH2V-100640714016102181102
CTH2V-125646774616117196117
CTH2V-150650805016127204127
CTH2V-175852825221133209133
(inches)(centimeters)
5
Page 12
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
A
C
D
B
A
C
D
B
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
FIGURE 4: LEVEL SIDE REFLECTOR
Model ABCDABCD
CTH2V-406953441623135112
CTH2V-606963471623161120
CTH2V-806970541623178138
CTH2V-1006977591623196150
CTH2V-1256983651623211166
CTH2V-1506986691623219176
CTH2V-1758988732123224186
FIGURE 5: TWO SIDE REFLECTORS
Model ABCDABCD
CTH2V-406155315163913539
CTH2V-606236623165916859
CTH2V-806257225166418364
CTH2V-1006277827166919969
CTH2V-1256328432168221482
CTH2V-1506358835168922489
CTH2V-175840914021102232102
(inches)(centimeters)
(inches)(centimeters)
FIGURE 6: 45° TILT REFLECTOR
(inches)(centimeters)
Model ABCDABCD
CTH2V-408851462121130117
CTH2V-608860542121153138
CTH2V-808866602121168153
CTH2V-10010874642621188163
CTH2V-12510878692621199176
CTH2V-15012884743121214188
CTH2V-17512885793121216201
6
Page 13
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
A
C
D
B
B
C
D
A
A
C
D
B
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
FIGURE 7: U-TUBE, LEVEL REFLECTOR
Model ABCDABCD
CTH2V-40
CTH2V-606356330168916177
CTH2V-806386937169717694
CTH2V-100640763916102194100
CTH2V-125646794316117201110
CTH2V-150650844716127214120
CTH2V-175854875121138221130
FIGURE 8: U-TUBE, 45°
Model ABCDABCD
SECTION 3: CLEARANCESTO COMBUSTIBLES
(inches)(centimeters)
- UNAPPROVED -
- UNAPPROVED -
(inches)(centimeters)
CTH2V-40
- UNAPPROVED -- UNAPPROVED -
CTH2V-608860422121153107
CTH2V-808866462121168117
CTH2V-1008874522121188133
CTH2V-1258878612121199155
CTH2V-1508884662121214168
CTH2V-1758885702121216178
FIGURE 9: U-TUBE, OPPOSITE 45° REFLECTOR
(inches)(centimeters)
Model ABCDABCD
CTH2V-40
CTH2V-6085460222113815356
CTH2V-8086066222115316856
CTH2V-100106474222616318856
CTH2V-125107078222617819956
CTH2V-150127484223118821456
CTH2V-175127685223119421656
- UNAPPROVED -- UNAPPROVED -
7
Page 14
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
A
C
D
B
A
C
D
B
Radiant Tubes
Vent
Pipes
Unvented
Vented
A
E
F
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
FIGURE 10: 2-FOOT DECO GRILLE AND PROTECTIVE GRILLE
(inches)(centimeters)
Model ABCDABCD
CTH2V-406275327166913569
CTH2V-606356335168916189
CTH2V-806386638169716897
CTH2V-100640714016102181102
CTH2V-125646774616117196117
CTH2V-150650805016127204127
CTH2V-175852825221133209133
FIGURE 11: LOWER CLEARANCE SHIELD*
(inches)(centimeters)
Model ABCDABCD
CTH2V-40634273416876987
CTH2V-6063933391610084100
CTH2V-8064038401610297102
CTH2V-100650445016127112127
CTH2V-125654485416138122138
CTH2V-150655505516140127140
*When installed in the first 10' (3 m).
FIGURE 12: VENTING
8
CTH2V-175
- UNAPPROVED -- UNAPPROVED -
(inches)(centimeters)
ModelAEFAEF
CTH2V-40141818364646
CTH2V-60141818364646
CTH2V-80202418516146
CTH2V-100202418516146
CTH2V-125202418516146
CTH2V-150203018517746
CTH2V-175203018517746
Page 15
SECTION 4: NATIONAL STANDARDS AND
APPLICABLE CODES
SECTION 4: NATIONAL STANDARDSAND APPLICABLE C ODES
4.1 Gas Codes
The type of gas appearing on the nameplate
must be the type of gas used. Installation must
comply with national and local codes and
requirements of the local gas company.
United States: Refer to National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code CSA B149.1 - latest revision.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in
accordance with the following codes:
United States: Refer to Standard for Aircraft
Hangars, NFPA 409 - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code CSA B149.1 - latest revision.
In aircraft storage and servicing areas, heaters
shall be installed at least 10' (3 m) above the
upper surface of wings or of engine enclosures
of the highest aircraft which may be housed in
the hangar. The measurement shall be made
from the wing or engine enclosure (whichever is
higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft
hangars communicating with aircraft storage or
servicing areas, heaters shall be installed not
less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so
located in all spaces of aircraft hangars that they
shall not be subject to injury by aircraft, cranes,
movable scaffolding or other objects. Provisions
shall be made to assure accessibility to
suspended heaters for recurrent maintenance
purposes.
4.3 Public Garages
Installation in garages must be in accordance
with the following codes:
United States: Refer to Standard for Parking
Structures NFPA 88A - latest revision or the
Code for Motor Fuel Dispensing Facilities and
Repair Garages, NFPA 30A - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code CSA B149.1 - latest revision.
• Heaters must not be installed less than 8'
(2.4 m) above the floor. Minimum clearances to
combustibles must be maintained from vehicles
parked below the heater.
• When installed over hoists, minimum
clearances to combustibles must be maintained
from the upper most point of objects on the hoist.
4.4 Electrical
The heater must be electrically grounded in
accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code,
CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance with
the requirements within this manual and the
following codes:
United States: Refer to National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code CSA B149.1 - latest revision.
4.6 High Altitude
These heaters are approved for installations up
to 2000' (610 m)(US), 4500' (1370 m)(Canada)
without modification. Consult factory if US
installation is above 2000' (610 m) or Canadian
installation is above 4500' (1370 m).
9
Page 16
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Burner with Tube
Gasket
Must be installed
with the flame
observation window
facing down.
Standard
Reflector
(Aluminum or
Stainless
Steel)
Alternate overlap as
shown on overview and on Page 18, Figure 17. Minimum
overlap is 6" (16 cm).
Tube and Reflector Hanger
with Clamp Package
Position this hanger no more
than 4" (10 cm) away from the
burner.
Coupling Assembly
with Lock
Reflector End Cap
Punch out center
section to
accommodate tube.
Tube and Reflector Hanger
Suspend system from these
hangers.
Flex Gas Line with
Shut Off Cock
Tube
Hot rolled or heat
treated aluminized tube
supplied in 10' (3 m) lengths.
Reflector Support Strap &
Wire Form
Turbulator
Install turbulator
as specified in the
"Turbulator Installation" chart. See Page 22, Step 6.4.
Turbulator is not required on the
CTH2V-125/150/175.
Vent Adapter
Burner Tube
Supplied in 10' (3 m) lengths.
Burner tube is always the first
tube after the burner.
SECTION 5: MAJOR COMPONENTS
FIGURE 13: Major Component Descriptions - Standard Reflector
10
Page 17
FIGURE 14: Major Component Descriptions - High Efficiency Reflector
Burner with Tube
Gasket
Must be installed with
the flame observation window facing down.
High Efficiency Reflector
(Aluminum)
Alternate
overlap as
shown on
overview
and
on Page 18, Figure 17.
Minimum overlap is 6" (16 cm).
Tube and Reflector Hanger
with Clamp Package-EF
Position this hanger no more
than 4" (10 cm) away from
the burner.
Coupling Assembly
with Lock
Reflector End Cap-EF
Punch out center
section to
accommodate tube.
Tube and Reflector Hanger-EF
Suspend system from these
hangers.
Flex Gas Line with
Shut Off Cock
Tube
Hot rolled or heat
treated aluminized tube
supplied in 10' (3 m) lengths.
Reflector Support Strap &
Wire Form
Turbulator
Install turbulator
as specified in the
"Turbulator Installation" chart. See Page 22, Step 6.4.
Turbulator is not required on the
CTH2V-125/150/175.
Vent Adapter
Burner Tube
Supplied in 10' (3 m) lengths.
Burner tube is always the first
tube after the burner.
SECTION 5: MAJOR COMPONENTS
11
Page 18
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
5.1 Standard Parts List
Table 1: Contents of the Burner Carton
Part No.DescriptionCTH2V-40 CTH2V-60CTH2V-80CTH2V-
100
031XXXXX Burner Assembly (Rate and Fuel Varies)1111111
02568200 Gasket (Burner to Burner Tube)1111111
131200NA Installation, Operation and Service Manual1111111
Although not recommended, additional tube lengths may be added to the heater. Tubing must be hot-rolled
steel, aluminized (heat-treated) or porcelain coated. Additional tube lengths beyond the specified minimum
tubing length are considered vent pipe for length determination. Maximum vent length allowed is 45' (13.7 m)
total.
14
Page 21
SECTION 6: HEATER I NSTALLATION
WARNING
Severe Injury Hazard
Secure burner to burner tube with nuts and
lockwashers.
Hang heater with materials with a minimum
working load of 75 lbs (33 kg).
Failure to follow these instructions can result
in death, injury or property damage.
WARNING
Cut/Pinch Hazard
Wear protective gear during installation,
operation and service.
Edges are sharp.
Failure to follow these instructions can result
in injury.
SECTION 6: HEATER INSTALLATION
Typical installation configurations are shown in
Figure 15.
Expansion and contraction of the tube dictates that
the minimum suspension lengths in the table on Page 16, Figure 15 be maintained.
To ensure your safety, and comply with the terms of
the warranty, all units must be installed in accordance with these instructions.
The gas or the electrical supply lines must not be
used to support the heater.
Do not locate the gas or electric supply lines directly
over the path of the flue products from the heater.
The heater must be installed in a location that is
readily accessible for servicing.
The heaters must be installed in accordance with
clearances to combustibles as indicated on the rating
plate and in this instruction manual.
The minimum and maximum gas inlet pressures
must be maintained as indicated on the rating plate.
15
Page 22
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Close coupling and slide
opposite end into tab.
Position tab underneath
guide rail.
B
Insert wide end of slide bar/coupling lock into
guide rail on opposite end of tabs. Slide the slide
bar/coupling lock up the guide rail until snug
(approximately 3" (8 cm) to 4" (10 cm)).
C
Insert tubes into coupling
until end of each tube rests
against internal pins.
D
Strike slide bar/coupling lock with mallet or hammer
until tight.
Support reflector with reflector hanger
and support strap.
Reflector must not touch tube.
Failure to follow these instructions can result
in death, injury or property damage.
SECTION 6: HEATER I NSTALLATION
23
Page 30
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
1. Slide first reflector after burner a minimum 2” (4 cm) through first hanger and
ensure reflector end cap is securely fastened via U-clips, pop rivets, or sheet
metal screws. Position reflector support with tight screws in middle of first
reflector.
NOTE: High efficiency
reflectors should NOT
be used in applications
exposed to wind.
DescriptionPart Number
Reflector Support Package030500XX
Wire Form91908004
Reflector Support Strap0305000X
Screw #8 x 3/494320812
U-Clip Package91107720
Reflector End Cap027508XX
Step 6.5.1 Reflector, U-Clip and Reflector Support Installation
The pictorial drawings of the heater construction in Section 6 are schematic only and provide a general
guideline of where hangers, reflector supports and
U-clips are to be installed.
To ensure proper expansion and contraction move-
ment of the reflectors, a combination of U-clips and
tor supports and U-clips depends on the individual
installation. Use either pop rivets or sheet metal
screws instead of u-clips when installing end caps
and joint pieces in areas where impact and high wind
may be a factor. The following rules must be
observed.
reflector supports are used. The positioning of reflec-
24
Page 31
Step 6.6 Burner Installation
NOTE: To ensure proper orientation,
attached burner tube with tube weld
facing downward
DescriptionPart Number
Burner031XXXXX
Lock Washer96411600
Gasket02568200
SECTION 6: HEATER I NSTALLATION
25
Page 32
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
WARNING
Cut/Pinch Hazard
Wear protective gear during installation,
operation and service.
Edges are sharp.
Failure to follow these instructions can result
in injury.
SECTION 7: OPTIONAL HEATER ACCESSORIES
7.1 U-Tube Configuration
Heaters (except CTH2V-40) are approved for optional
U-Tube configurations.
The U-Tube may be installed in either a standard hor-
izontal position, a 45° position or in an opposite 45°
position as shown on Page 7, Figure 7 through Figure
9. When using a U-Tube configuration, the following
additional rules must be adhered to:
• A minimum of 10' (3 m) on CTH2V-60/80 and a
minimum of 15' (4.5 m) on CTH2V-100/125/150/
175 is required between the burner and the UTube.
• The correct turbulator (
must be installed in the last standard section of
tube.
• The burner must never be operated in a tilted position.
• The heater must be properly supported at all locations.
See Page 28, Figure 20
See Page 22, Figure 6.4
.
)
26
Page 33
FIGURE 19: U-Tube Heater Assembly Overview
DescriptionPart Number
U-Tube Package03011XXX
180° U-Tube013359XX
Tube and Reflector Hanger030901XX
Coupling01312700
Reflector End Cap027508XX
U-Tube Support Bracket030205XX
4" (10 cm) U-Bolts91912500
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
DescriptionPart Number
Deco Grille Shield - 24" (61cm)01365900
Distance "A"Extension
MinimumMaximumPart No.Width
2" (4 cm)6" (15 cm)013704XX8" (20 cm)
6" (15 cm)10" (26 cm)013704XX12" (30 cm)
10" (26 cm)14" (37 cm)013704XX16" (40 cm)
DescriptionPart Number
Reflector Side Extension013704XX
Step 7.5.2 Frame Shield Installation
Step 7.5.3 Reflector Side Extension Installation for Decorative Grilles
34
Page 41
7.6 Protective Grille Installation
Silicone Cap
Grille
Finger
DescriptionPart Number
Grille Section08050001
Grille End Cap08050002
Silicone Cap91915951-6P
NOTE: Protective grille available for use with
standard reflector ONLY.
Bend up 90°.
Pull outward.
Grille
GrilleEndCap
A
B
C
D
Grille
Grille
End Cap
Reflector
FinalGrille
Section
40"
(101 cm)
Step 7.6.1 Silicone Cap Installation
SECTION 7: OPTIONAL H EATER ACCES SORIES
Step 7.6.2 Grille End Cap Installation
Step 7.6.3 Grille Installation
35
Page 42
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
WARNING
Carbon Monoxide Hazard
Heaters installed unvented must be interlocked
with sufficient building exhaust.
Heaters must be installed according to the
installation manual.
Failure to follow these instructions can result
in death or injury.
WARNING
Cut/Pinch Hazard
Wear protective gear during installation,
operation and service.
Edges are sharp.
Failure to follow these instructions can result
in injury.
SECTION 8: VENTING
Vent pipe must be sloped downward away from the
burner 1/2'' (1 cm) for every 20' (6 m).
The heater may be individually vented or common vented. When venting horizontally, a maximum of two
heaters can be commonly vented. See Page 38, Section 8.9. When venting vertically, a maximum of
four heaters can be commonly vented. See Page 39, Section 8.10.
The heater may also be installed unvented in certain
circumstances according to building
codes. Refer to the above codes and Page 36, Section 8.2 for further information. Unvented
operation also requires compliance with the
clearances to combustibles given on Page 8, Figure
12.
The bottom of the vent or air intake terminal shall not
be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m)
above grade where located adjacent to public walkways.
Vent terminal must be installed at a height sufficient
to prevent blockage by snow and building materials
protected from degradation by flue gasses.
ventilation
8.1 General Venting Requirements
This heater must be vented in accordance with the
rules contained in this manual and with the following
national codes and any state, provincial or local
codes which may apply:
United States: Refer to National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code CSA B149.1 - latest revision.
Exhaust end of heater will accept a 4
pipe using the vent adapter (P/N 90502700). To
prevent leakage of condensation, install the vent
adapter with the seam on top and seal the joint using
a high temperature silicone sealant.
Any portion of vent pipe passing through a
combustible wall must have an approved thimble
to conform with the above listed codes.
' (10 cm) vent
Secure all joints with #8 x 3/8 sheet metal screws.
Seal all joints with high temperature silicone sealant.
Vent terminal must be beyond any combustible
overhang.
8.1.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any
forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below, 4'
(1.2 m) horizontally from, or 1' (.3 m) abov
operable window, or gravity air inlet into any building.
8.1.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a
mechanical air supply inlet to any building.
The vent shall not terminate within 3' (.9 m) of a window or door that can be opened in any building,
any non-mechanical air supply inlet to any building,
or of the combustion air inlet of any other appliance.
8.2 Unvented Operation
Sufficient ventilation must be provided in the amount
of 4 cfm per 1000 Btu/h firing rate (United States); 3
cfm per 1000 Btu/h firing rate (Canada).
Use of optional outside combustion air is not
recommended with unvented heaters.
If exhaust fans are used to supply ventilation air, an
interlock switch must be used to prevent the heater
from coming on when the fans are off. This may be
done using a pressure sw
In noncombustible walls only, vent terminal
(P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or
noncombustible walls, use Tjernlund VH1-4 (P/N
90502100) or equivalent insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
For 6'' (15 cm) common vents in either combustible
or noncombustible walls, use Tjernlund VH1-6 (P/N
90502101) or equivalent insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
8.4 Vertical Venting
For 4'' (10 cm), an approved vent cap
(P/N 90502300) must be used.
For 6'' (15 cm) common vent, an approved vent cap
(P/N 90502302) m
ust be used.
For common vertical venting of more than two
heaters, See Page 39, Section 8.10.
A vent shall not extend less than 2' (.6m) above the
highest point where it passes through a flat roof of a
building.
8.5 Unvented Operation Tube Termination
Turndown type vent terminal with a screen must be
installed at the exhaust end of the tube. Vent terminal
design shall not incorporate backdraft flap.
FIGURE 23: Tube Termination
8.6 Length Requirements
The maximum vent length allowed is 45' (13.7 m).
The maximum outside air supply duct length allowed
is 45' (13.7 m).
The total vent length, plus outside air duct length,
plus any extensions to minimum heat exchanger
lengths, cannot exceed 65' (19.8 m).
Vent length should be limited to less than 20' (6 m). If
using vent lengths greater than 20' (6 m),
condensation will form in the vent pipe. Insulation
and additional sealing measures (high temperature
silicone at all seams) are required. Optional heat
exchanger beyond minimum lengths is considered as
vent length for length determination.
Subtract 15' (4.6 m) of maximum allowed vent or duct
length per vent elbow if more than two are used.
3. Single wall flue pipe - minimum 26 ga.
(Supplied by others)
NOTE: 4" (10 cm) O.D. Porcelain coated tubing (P/N
9141030D), 4" (10 cm) O.D. Heat treated aluminized
tubing (P/N 91409408), and 6" (15 cm) O.D. Heat
treated aluminized tubing (P/N E0009105) are equiv-
alent to single wall flue pipe.
8.7 Horizontal Ventilation 4" (10 cm) Pipe
37
Page 44
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
DescriptionPart Number
Vent Cap 4" (10 cm)90502300
DescriptionPart Number
Vent Terminal 6" (15 cm)90502101
8.8 Vertical Ventilation 4" (10 cm) Pipe
Step 8.9 Common Sidewall Venting
Requirements:
• Maximum of two heaters can be commonly
vented through a side wall.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common
thermostat.
38
Page 45
8.10 Common Vertical Venting
SECTION 8: VENTING
Requirements:
• Maximum of four heaters can be commonly vented
through the roof.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common
thermostat.
• Connections to a common stack must be positioned to avoid direct opposition between streams
of combustion gases.
39
Page 46
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
DescriptionPart Number
Vent Cap 4" (10 cm)90502300
DescriptionPart Number
Vent Cap 4" (10 cm)90502300
Band Clamp
(Recommended)
Flex Hose
(Recommended)
Vent Cap
Wall
4" (10 cm)
Single Wall Pipe
Burner
8.11 Outside Combustion Air Supply
IMPORTANT: If the building has a slight negative
pressure or corrosive contaminants, such as halogenated hydrocarbons, are present in the air, an outside
combustion air supply to the heater is required. Seal
all combustion air pipe joints.
Use of optional outside combustion air is not recommended with unvented heaters.
The air supply duct may have to be insulated to pre-vent condensation on the outer surface. The outside
air terminal must not be more than 1' (31 cm) above
the vent termination while maintaining a minimum
distance of 3' (93 cm) for both vertical and horizontal venting.
8.11.1 Length Requirements
Follow the constraints listed on Page 37, Section 8.6.
8.11.2 Vertical Outside Air Supply for Single Heater Installation
8.11.3 Horizontal Outside Air Supply for Single Heater Installation
40
Page 47
8.11.4 Vertical Outside Air Supply for Double Heater Installation
DescriptionPart Number
Vent Cap 6" (15 cm)90502302
DescriptionPart Number
Vent Cap 6" (15 cm)90502302
SECTION 8: VENTING
Requirements:
• Heaters must be controlled by a common thermostat.
8.11.5 Horizontal Outside Air Supply for Double Heater Installation
Requirements:
• Heaters must be controlled by a common thermostat.
41
Page 48
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
WARNING
Explosion Hazard
Leak test all components of gas piping
before operation.
Gas can leak if piping is not installed
properly.
Do not high pressure test gas piping with
heater connected.
Failure to follow these instructions can result
in death, injury or property damage.
SECTION 9: GAS PIPING
WARNING
Fire Hazard
Tighten gas hose fittings to connect gas
supply according to Figure 23.
Gas hose can crack when twisted.
Gas hose moves during normal operation.
Use only 36" (91 cm) long connector of 1/2" or
3/4" nominal ID.
Connector supplied with heater for U.S.
models (not with Canadian models).
Failure to follow these instructions can result
in death, injury or property damage.
There is an expansion of the tube with each firing
cycle. This will cause the burner to move with respect
to the gas line. This can cause a gas leak resulting in
an unsafe condition if the gas connection is not made
in strict accordance with Figure 24.
Meter and service must be large enough to handle all
the burners being installed plus any other connected
load. The gas line which feeds the system must be
large enough to supply the required gas with a maximum pressure drop of 1/2" wc When gas piping is not
included in the layout drawing, the local gas supplier
will us
ually help in planning the gas piping.
Gas lines must meet applicable codes:
United States: The Flexible Stainless Steel Gas
Hose (US models) supplied with the heater is certified per the Standard for Connectors for Gas Appliances, ANSI Z21.24/CSA 6.10 - latest revision.
Canada: The Rubber Type 1 Gas Hose (Canadian
models) optional with the heater is certified as being
in compliance with the Standard for Elastomeric
Composite Hose and Hose Couplings for Conducting
Propane and Natural Gas, CAN/CGA 8.1 - Latest
revision.
• Check the pipe and tubing ends for leaks
before placing heating equipment into service. When checking for gas leaks, use a soap
and water solution; never use an open flame.
Install the gas hose as shown in Figure 24. The gas
hose accommodates expansion of the heating
system and allows for easy installation and service of
the burner. Before connecting the burners to the
supply system, verify that all high pressure testing of
the gas piping has been completed.
42
Page 49
FIGURE 24: Gas Connection with Flexible Gas Hose
DescriptionPart Number
1/2" Flexible Stainless Steel Gas Hose (US Models)91412200
3/4" Flexible Stainless Steel Gas Hose (US Models)91412203
1/2" Rubber Type 1 Gas Hose (Canadian Models)91412206
3/4" Rubber Type 1 Gas Hose (Canadian Models)91412207
DescriptionPart Number
High Pressure Regulator - 2 psi90207600
High Pressure Regulator - 5 psi90207601
CORRECT POSITIONS
Shut-Off Valve (included
with gas hose) must be
parallel to burner gas
inlet. The 3" (8 cm)
displacement shown is
for the cold condition.
This displacement may
reduce when the
system is fired.
3" (8 cm)
12"
(30 cm)
max. displacement
Side View
SECTION 9: GAS P IPING
CAUTION
Product Damage Hazard
Hold gas nipple securely with pipe wrench
when attaching gas hose.
Failure to follow these instructions can result
in product damage.
Vertical
(as shown left)
45°
Alternate
positions
okay
Flexible Gas Hose
36" (91 cm) length
Heater Movement
Horizontal
End View
43
Page 50
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Line Voltage
Thermostat
Gnd.Gnd.
120 V-60 Hz
Supply Circuit
HNHN
Gnd.
L1
L2
T
Jumper Between R
and W
C
R
W
Gnd.
120 V-60 Hz
Supply Circuit
HN
Gnd.
L1
L2
Low Voltage
Thermostat
T
C
R
W
Low Voltage Thermostat
with Ground
NOTE: Terminals “C” and “R” provide 24 VAC to power thermostat
SECTION 10: WIRING
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.
Failure to follow these instructions can result
in death or electrical shock.
Heaters can be controlled using several methods.
Normally thermostats are used to control the heaters
but they can also be controlled by an Energy
10.1 Line Voltage Thermostat Wiring
Management System. Section 10.1 below illustrates
the connection for heaters controlled by a line voltage
thermostat. NOTE: In order to use line voltage thermostats, the low voltage terminal located at the back
of each burner must be connected as shown in the
detail. For a single heater on a low voltage thermostat, See Section 10.2 below. To control multiple
heaters on one low voltage thermostat, See Page 45, Section 10.3. NOTE: In order to control multiple heat-
ers on one low voltage thermostat, the low voltage
terminals on each heater must be connected as
shown in detail. Heater must be grounded in accor-
dance with applicable codes: United States: refer to
National Electrical Code
®
NFPA 70 - latest revision Canada: refer to Canadian Electrical Code, CSA
C22.1 Part I - latest revision.If any of the original
internal wiring must be replaced, it must be replaced
with wiring materials having a temperature rating of at
least 105° C and 600 V.
10.2 Low Voltage Thermostat with One Burner
.
44
Page 51
10.3 Low Voltage Thermostat Wiring with Multiple Burners
NH
Gnd.
NH
Gnd.
L1
L2
Gnd.
120V-60 Hz
supply circuit
Low Voltage Thermostat
RC
W
G
Y
1
2
3
456
COILCOIL
Black
Black
WhiteRed
Transformer Relay
FRONT VIEWBACK VIEW
Burner 1Burner 2
NH
Gnd.
Burner 3
NH
Gnd.
Burner 4
Purple
Red/Yellow
When using 1-2 burners, use SPST
Transformer Relay.
When using 3-4 burners, use SPDT
Transformer Relay.
2
Jumper Between
R and W
C
R
W
NOTE:
24VAC thermostat
powered by others
when controlling
multiple burners
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
120VAC
R1
120VAC
24VAC
RELAY
24V
PRESSURE
THV2
S1
SPARK
C2
TRANSFORMER
(L1)
GND
(L2)
SWITCH
THERMOSTAT
BLOWER
LINE
NUETRAL
R1
ELECTRODE
GAP
V
BURNER ON
GAS VALVE
DOOR
SWITCH
10.5 Ladder Diagram
10.6 Electrical Connection to the Burner
46
Page 53
SECTION 11: OPERATION AND MAINTENANCE
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
Explosion Hazard
Turn off gas supply to
heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric
before service.
Heater must be
connected to a properly
grounded electrical
source.
SECTION 11: OPERATIONAND MAINTENANCE
This heater is equipped with a direct spark ignition
system.
11.1 Sequence of Operation
4. Turn the thermostat up. When the thermostat
calls for heat, the blower motor will energize.
5. When the motor approaches nominal running
RPM, the pressure switch closes and activates
the ignition module.
6. After a 45 second prepurge, the ignition module
then opens the gas valve and energizes the
spark igniter.
7. When the flame is established, the sparking
sequence ceases.
8. If the flame is not established during the ignition
sequence, the ignition module closes the gas
valve and purge begins. Module will try 2
additional times for ignition (with purges in
between trials). If ignition is not established, the
module will lockout.
9. If the flame extinguishes during operation, the
ignition module will attempt the multiple trial
sequence described in step 5. If ignition is not
re-established, the module w
hour or until reset.
10.After lockout, the control can be reset by turning
down thermostat for five seconds, and then
raising it again to desired temperature, or by
disconnecting power and then reconnecting.
ill lockout for one
11. When thermostat is satisfied, all power to the
unit is shut off.
11.2 To Shut Off Heater
Set thermostat to lowest setting.
Turn OFF electric power to heater.
Turn OFF manual gas valve in the heater supply line.
11.3 To Start Heater
Turn gas valve and electric power OFF and wait five
minutes for unburned gases to vent from heater.
Turn ON main gas valve.
Turn ON electric power.
Set thermostat to desired temperature. Burner
should light automatically.
11.4 Pre-Season Maintenance and Annual
Inspection
To e n s ure you
ation of the heating system, service and annual
inspections must be done by a contractor qualified in
the installation and service of gas-fired heating
equipment.
Turn off gas and electric supplies before performing
service or maintenance. Allow heater to cool before
servicing.
Before every heating season, a contractor qualified in
the installation and service of gas-fired heating
equipment must perform a thorough safety inspection of the heater.
For best performance, the gas, electrical, thermostat
connections, tubing, venting, suspensions and over-
r safety and years of trouble-free oper-
47
Page 54
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
all heater condition should be thoroughly inspected.
NOTE: Gas flow and burner ignition are among the
first things that should be inspected.
Please see Page 48, Section 11.5 for suggested
items to inspect.
conform to all requirements set forth in the
®
ROBERTS GORDON
manuals and all applicable
governmental authorities pertaining to the
installation, service, operation and labeling of the
equipment.
To help facilitate optimum performance and safety,
Roberts-Gordon LLC recommends that a qualified
11.5 Maintenance Checklist
Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON
equipment must be performed by a contractor
contractor conduct, at a minimum, annual
inspections of your ROBERTS GORDON
equipment and perform service where necessary,
®
using only replacement parts sold and supplied by
®
Roberts-Gordon LLC
qualified in the installation and service of equipment
sold and supplied by Roberts-Gordon LLC and
The Vicinity of the HeaterDo not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 5, Section 3.
Vehicles and Other
Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or
in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 5, Section 3.
ReflectorSupport reflector with reflector hanger and support strap.
Reflector must not touch tube.
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. See Page 24, Section 6.5.1.
Clean outside surface with a damp cloth.
Vent PipeVenting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and du
st. Clean as required.
Remove any carbon deposits or scale using a wire brush.
See Page 36, Section 8.
Outside Air InletInlet must be intact. Look for obstructions, cracks on the pipe, gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
TubesMake sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 15, Section 6.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
Gas LineCheck for gas leaks. See Page 42, Section 9.
Burner Observation
Window
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
48
Page 55
SECTION 11: OPERATIONAND MAINTENANCE
Blower Scroll, Wheel and
Motor
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
Burner Cup and OrificeClear of obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
ElectrodeReplace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8" (3.2 mm).
ThermostatThere should be no exposed wire or damage to the thermostat.
See Page 44, Section 10.
Suspension PointsMake sure the heater is hanging securely. Look for signs of wear on the chain
or ceiling. See Page 16, Figure 15.
Decorative and Protective
Grille (optional)
The grille must be securely attached.
Check that the side reflector extensions are installed correctly and secured in
place if necessary. (Decorative grille only.)
See Page 33, Section 7.5and Page 35, Section 7.6.
Make sure shield is installed correctly and secured in place if necessary.
(Decorative grille only.) See Page 34, Section 7.5.2.
Lower Clearance Shield
(optional)
The lower shield must be securely attached. Inspect shield s
upport straps
and lower clearance shield anchor points. See Page 33, Section 7.4.
Make sure shield is installed correctly and secured in place if necessary.
See Page 33, Section 7.4.
Wall TagIf wall tag is present, make sure it is legible and accurate. Please contact
Roberts-Gordon LLC or your ROBERTS GORDON
®
independent distributor,
if you need a wall tag. See Page 4, Section 2.1.
Safety LabelsProduct safety signs or labels should be replaced by the product user when
they are no longer legible. Please contact Roberts-Gordon LLC or your ROBERTS GORDON
®
independent distributor to obtain replacement signs or
labels. See Page 2, Figure 1 through Page 3, Figure 2.
49
Page 56
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Fire Hazard
Keep all flammable
objects, liquids and
vapors the minimum
required clearances to
combustibles away
from heater.
Some objects will catch
fire or explode when
placed close to heater.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
Explosion Hazard
Turn off gas supply to
heater before service.
SECTION 12: TROUBLESHOOTING
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.
Failure to follow these instructions can result
in death or electrical shock.
50
Page 57
12.1 Troubleshooting Flow Chart
Module Diagnostic Codes:
LED Problem Solution
4 second steady
flash at start of cycle Normal Wait for valve to open
Steady on Microprocessor failure Replace module
within module
Three flashes Ignition lockout Recycle unit: check for
Lockout of module spark and valve opening and
after 3 tries replace:if none, replace module
SECTION 12: TROUBLESHOOTING
51
Page 58
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
52
Page 59
12.2 Manifold Gas Pressure Setting
SECTION 12: TROUBLESHOOTING
53
Page 60
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Carbon Monoxide Hazard
WARNING
Use only genuine ROBERTS GORDON®replacement parts per this installation, operation and
service manual.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Explosion Hazard
DANGER
Electrical Shock Hazard
Fire Hazard
SECTION 13: REPLACEMENT PARTS
See warnings and important information before removing or replacing parts. After any maintenance or repair
work, always test fire the heater in accordance with the start-up instructions on Page 47, Section 11 to help
ensure all safety systems are in working order before leaving the heater to operate. Minor faults may be
traced by using the troubleshooting charts on Page 50, Section 12 through Page 53, Figure 12.2.
54
Page 61
FIGURE 25: Burner Exploded View
Description
Part Number
1Gas Valve (Natural)
90032510
1Gas Valve (LP)
90032512
Tube Gasket (Not Shown)
02568200
Blower Inlet Gasket (Not Shown)
03050900
2Motor and Blower Assembly
90708600-P
Air Adapter Collar
91911704
3Burner Cup Assembly
03020100
4Electrode Assembly
90427400
Mica Window Assembly (Not Shown)
02553203
5Transformer
90436900K
6Thermostat Connection (3 Pin)
91317904
Jumper Wire (Not Shown)
03090900
7Pressure Switch:
(175)
90439802K
(100)
90439803K
(40, 60, 125)
90439805K
(80, 150)
90439810K
824 Vac Relay
90447140
9DSI Ignition Module
90439500K
10LED Burner Status Light
91316103
SECTION 13: REPLACEMENT PARTS
55
Page 62
CTH2V-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Vent Connection Size: 4" (10 cm)
Outside Air Connection Size: 4" (10 cm)
Refer to figure above for dimensional information.
56
GAS INLET PRESSURE:
Natural Gas:
for 40,60,80,100,125,1504.6" wc Minimum
for 1755.0" wc Minimum
LP Gas:11. 0" wc Minimum
ELECTRICAL RATING (ALL MODELS):
120 V - 60 Hz., 1.0 A
14.0" wcMaximum
14.0" wcMaximum
Page 63
SECTION 15: THE ROBERTS GORDON® VANTAGE® CTH2V WARRANTY
SECTION 15: THE ROBERTS GORDON
®
VANTAGE® CTH2V WARRANTY
ROBERTS-GORDON WILL PAY FOR:
Within 36 months from date of purchase by buyer or 42
months from date of shipment by Roberts-Gordon LLC
(whichever occurs first), replacement parts will be provided
free of charge for any part of the product which fails due to
a manufacturing or material defect.
Roberts-Gordon LLC will require the part in question to be
returned to the factory. Roberts-Gordon LLC will, at its sole
discretion, repair or replace after determining the nature of
the defect and disposition of part in question.
ROBERTS GORDON
®
Replacement Parts are warranted
for a period of 12 months from date of shipment from
Roberts-Gordon LLC or the remaining ROBERTS
GORDON
®
VANTAG E® CTH2V warranty.
ROBERTS-GORDON WILL NOT PAY FOR:
Service trips, service calls and labor charges.
Shipment of replacement parts.
Claims where the total price of the goods have not
been paid.
Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the
ROBERTS GORDON
• Use of the ROBERTS GORDON
®
VANTAG E® CTH2V in any way.
®
VANTAG E® CTH2V
for other than its intended
purpose.
• Incorrect gas or electrical supply, accident, fire, floods,
acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or accessories not specified by Roberts-Gordon.
• Failure to install or maintain the ROBERTS GORDON
VANTAG E® CTH2V as directed in the Installation,
Operation and Service manual.
®
• Relocation of the ROBERTS GORDON
VANTAG E®
CTH2V after initial installation
®
• The use of the ROBERTS GORDON
VANTAG E®
CTH2V in a corrosive atmosphere containing contaminants.
®
• The use of the ROBERTS GORDON
VANTAG E®
CTH2V in the vicinity of a combustible or explosive
material.
®
• Any defect in the ROBERTS GORDON
VANTAG E®
CTH2V arising from a drawing, design, or specification
supplied by or on behalf of the consumer.
• Damage incurred during shipment. Claim must be filed
with carrier.
WARRANTY IS VOID IF:
The ROBERTS GORDON® VANTAG E® CTH2V is not
installed by a contractor qualified in the installation and
service of gas fired heating equipment.
Yo u cannot prove original purchase date and required
annual maintenance history.
The data plate and/or serial number are removed,
defaced, modified or altered in any way.
The ownership of the ROBERTS GORDON
®
VANTAG E®
CTH2V is moved or transferred. This warranty is
nontransferable.
Roberts-Gordon is not permitted to inspect the damaged
controller and/or component parts.
READ YOUR INSTALLATION, OPERATION AND
SERVICE MANUAL
If you have questions about your controller, contact your
installing professional. Should you need Replacement
Parts or have additional questions, call or write:
Roberts-Gordon LLC
1250 William Street
P. O . B o x 4 4
Buffalo, New York 14240-0044
Telephone: +1.716.852.4400
Fax: +1.716.852.0854
Toll Free: 800.828.7450
www.robertsgordon.com
Roberts-Gordon LLC's liability, and your exclusive
remedy, under this warranty or any implied warranty
(including the implied warranties of merchantability
and fitness for a particular purpose) is limited to
providing replacement parts during the term of this
warranty.
Some jurisdictions do not allow limitations on
how long an implied warranty lasts, so this limitation may
not apply to you. There are no rights, warranties or
conditions, expressed or implied, statutory or otherwise,
other than those contained in this warranty.
Roberts-Gordon LLC shall in no event be responsible
®
for incidental or consequential damages or incur
liability for damages in excess of the amount paid by
you for the ROBERTS GORDON
®
VANTAG E® CTH2V.
Some jurisdictions do not allow the exclusion or limitation
of incidental or consequential damages, so this limitation
or exclusion may not apply to you. This warranty gives you
specific legal rights, and you may also have other rights
which vary from jurisdiction to jurisdiction.
Roberts-Gordon shall not be responsible for failure to
perform under the terms of this warranty if caused by
circumstances out of its control, including but not limited to
war, fire, flood, strike, government or court orders, acts of
God, terrorism, unavailability of supplies, parts or power.
No person is authorized to assume for Roberts-Gordon
any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF
REPRESENTATIVES:
No representative of Roberts-Gordon LLC, other than an
Executive Officer, has authority to change or extend these
provisions. Changes or extensions shall be binding only if
confirmed in writing by Roberts-Gordon LLC's duly
authorized Executive Officer.
57
Page 64
Page 65
2017
Page 66
Page 67
Page 68
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.