Roberts Gorden UHD-XSR125, UHD-XSR75 User Manual

Page 1
®
Combat
UHD-Series
Tubular Duct Furnace
(Low Profile Range)
Installation, Operation
& Service Manual
Models UHD[X][S][R]
75, 100, 125
Quality in Any Language™
© 2008 Roberts-Gordon LLC
Roberts-Gordon LLC
1250 William Street P. O . B o x 44 Buffalo, New York 14240-0044 Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
www.rg-inc.com
P/N 113000NA 11/08 Orig.
Page 2
Page 3
© 2008
Roberts-Gordon LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon LLC.
TABLE OF CONTENTS
SECTION 1: Heater Safety...................................................... 1
1.1 Manpower Requirements .............................................1
SECTION 2: Installer Responsibility ..................................... 2
2.1 Wall Tag .......................................................................2
2.2 Corrosive Chemicals.................................................... 2
2.3 National Standards and Applicable Codes ..................2
SECTION 3: Critical Considerations ..................................... 3
3.1 Basic Information .........................................................3
3.2 Manufactured Units......................................................3
3.3 Location and Suspension ............................................3
3.4 Minimum Required Installation Clearances .................3
3.5 Clearances to Combustibles ........................................ 3
3.6 Ventilation ....................................................................4
3.7 Gas Supply.................................................................. 4
3.8 Electrical Supply.......................................................... 4
3.9 Vent..............................................................................4
SECTION 4: National Standards and Applicable Codes .....5
4.1 Gas Codes...................................................................5
4.2 Aircraft Hangars........................................................... 5
4.3 Parking Structures and Repair Garages ......................5
4.4 Electrical ...................................................................... 5
4.5 Venting.........................................................................5
4.6 High Altitude ................................................................6
SECTION 5: Duct Heater Installation.....................................7
5.1 General........................................................................ 7
5.2 Shelf Mounting and Suspension..................................8
5.3 Wall Mounting ..............................................................8
SECTION 6: Venting.............................................................. 10
6.1 Changing Vent and Air Intake Orientation.................. 10
6.2 Venting....................................................................... 10
6.3 Vent Installation ......................................................... 10
6.4 Unvented Operation................................................... 11
6.5 Horizontal Venting...................................................... 11
6.6 Vertical Venting.......................................................... 11
6.7 Length Requirements ................................................ 11
6.8 Vent Material.............................................................. 12
6.9 Replacing an Existing Heater in a Venting System.... 12
SECTION 7: Air Supply......................................................... 17
7.1 Separated Combustion Installation............................. 17
7.2 Unvented Installation.................................................. 17
7.3 Building Ventilation..................................................... 17
7.4 Outside Combustion Air Supply.................................. 17
SECTION 8: Gas Piping........................................................18
8.1 Connections............................................................... 18
SECTION 9: Wiring................................................................ 19
9.1 Positioning Thermostats ............................................ 19
9.2 Low Voltage Thermostat with One Heater ................. 19
9.3 Internal Wiring Diagram .............................................20
9.4 Ladder Wiring Diagram.............................................. 21
9.5 Electrical Connection to the Heater ........................... 22
SECTION 10: Operation and Maintenance..........................23
10.1 Pre-Start-Up Checks ................................................23
10.2 Begin Start-Up .........................................................23
10.3 Complete Start-Up ...................................................25
SECTION 11: User Instructions............................................26
11.1 User Instructions.......................................................26
11.2 Heater Operation ......................................................26
11.3 Common User Controls.............................................26
11.4 Lighting Instructions..................................................26
11.5 Simple Troubleshooting.............................................27
SECTION 12: Servicing.........................................................28
12.1 Servicing Instructions...............................................28
12.2 Burner Maintenance.................................................28
12.3 Heat Exchanger Maintenance ..................................28
12.4 Gas Valve Maintenance ...........................................28
12.5 Flue Blower ..............................................................28
12.6 Venting and Air Intake Pipe......................................28
12.7 Maintenance Checklist.............................................29
SECTION 13: Troubleshooting .............................................31
13.1 General ....................................................................31
13.2 Troubleshooting For Automatic Ignition Burner
Systems ...................................................................32
13.3 Troubleshooting for Flame Supervision System .......33
13.4 Troubleshooting for Gas Valves................................34
13.5 Troubleshooting for Flue Blower...............................34
SECTION 14: Replacement Parts.........................................35
14.1 Gas Valve .................................................................35
14.2 Burner Compartment ...............................................36
14.3 Ignition Electrode and Flame Probe .........................37
14.4 Heat Exchanger .......................................................37
14.5 Flue Blower Vertical Installation ...............................38
14.6 Pressure Switch........................................................39
14.7 Ignition Control .........................................................39
14.8 Limit Switches ..........................................................39
SECTION 15: Specifications.................................................40
15.1 Dimension Data........................................................40
15.2 General Technical Data Table ..................................41
15.3 Technical Data Table ................................................41
SECTION 16: ROBERTS GORDON
Warranty..........................................................43
®
COMBAT® UHD-Series
Printed in U.S.A.
Page 4
Page 5
TABLE OF FIGURES
Figure 1: Clearances to Combustibles ...................................... 3
Figure 2: Air Flow Direction....................................................... 7
Figure 3: Suspension Methods ................................................. 8
Figure 4: Shelf-Mounting Methods............................................9
Figure 5: Wall Shelf Mounting and Suspension ........................9
Figure 6: Vent and Roof Detail ................................................ 13
Figure 7: Standard Vented Heater - Vertical and Horizontal
Vent Termination...................................................... 13
Figure 8: Standard Vented Heater - Common Vertical Vent
Termination .............................................................. 14
Figure 9: Separated Combustion Heater - Vertical and
Horizontal Vent Termination..................................... 15
Figure 10: Concentric Vent Box...............................................15
Figure 11: Concentric Vertical and Horizontal Vent Termination -
Separated Combustion Heater...............................16
Figure 12: Gas Connection ..................................................... 18
Figure 13: Automatic Burner Control Sequence...................... 24
Figure 14: Gas Valve .............................................................. 24
Figure 15: Manual Reset Limit Switch.....................................26
Figure 16: LED Diagnostic Codes ...........................................27
Page 6
Page 7
SECTION 1: HEATER SAFETY
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
Installation, service and quarterly inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, operation or service of this equipment. Heaters are not approved for residential installations. These instructions, the layout drawing, local codes and ordinances and applicable standards that apply to gas piping, electrical wiring, venting, etc. must be thoroughly understood before proceeding with the installation. Protective gear is to be worn during installation, operation and service. Thin sheet metal parts, including the various venting components, have sharp edges. To prevent injury, the use of work gloves is recommended.
SECTION 1: HEATER SAFETY
Before installation, check that the local distribution conditions, nature of gas and pressure and adjustment of the appliance are compatible.
1.1 Manpower Requirements
To prevent personal injury and damage to the heater, two persons will be required for installation.
1
Page 8
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To install the heater, as well as the gas and
electrical supplies, in accordance with applicable specifications and codes. Roberts-Gordon recommends the installer contact a Local
2.2 Corrosive Chemicals Caution: Do not use heater in an area containing
corrosive chemicals. Avoid the use of corrosive chemicals to ensure a longer life of the burner, heat exchanger and other parts.
Building Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing
and in the manual together with the cited codes and regulations to perform the installation.
• To install the heater in accordance with the
clearances to combustibles.
• To furnish all needed materials not furnished as
standard equipment.
Roberts-Gordon cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility of the installer. It is essential that the contractor, the sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
• To plan location of supports, vents and air
intakes.
• To provide access for servicing.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as support for a ladder or
other access equipment and never hang or suspend anything from heater.
• To ensure there is adequate air circulation
around the heater and to supply air for combustion, ventilation and distribution in accordance with local codes.
• To provide a method that ensures that the air flow
through the heat exchanger is within the acceptable range indicated on the rating plate prior to energizing the heater, and that such air flow continues at least 90 seconds after the heater is de-energized.
2.1 Wall Tag
A laminated wall tag is included with the heater as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Affix the tag by peeling off the backing of the adhesive strips on the rear surface and position the tag on a wall near the heater.
A copy of the wall tag (P/N 91039831) is illustrated on the back cover.
Know your model number. Model number is found on the heater and throughout the Installation, Operation and Service Manual.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen ele­ments (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the life span of the heater components will be greatly reduced. An out­side air supply must be provided to the burners whenever the presence of these compounds is suspected. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with the latest revision of the applicable standards and national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in public garages, aircraft hangars, etc. may be applicable.
2
Page 9
SECTION 3: CRITICAL CONSIDERATIONS
Clearance to Vent: 2" (5 cm)
*18" (46 cm) minimum is necessary for servicing.
3.1 Basic Information
UHD[X][S][R] heaters have automatic ignition burners for ON/OFF operation only.
3.2 Manufactured Units
Gas-fired, power-vented duct furnace with tubular heat exchanger. Units shall have a minimum of 82% thermal efficiency. The standard unit shall consist of a non-separated combustion design with an aluminized heat exchanger. Design and heat exchanger alternatives shall be offered as follows:
• Separated Combustion: A separated combustion unit shall feature an enclosed, sealed burner box. A piece of flexible air duct connects this burner box to a flange on the cabinet. Combustion air should be ducted from outside the heated space, with the ductwork connecting to the unit with the use of the flange.
• Stainless Steel Heat Exchanger: A stainless steel heat exchanger unit shall consist of heat exchanger tubes, heat exchanger tube supports, heat exchanger tube plates and vent box produced of 409 stainless steel.
SECTION 3: CRITICAL CONSIDERATIONS
3.5 Clearances to Combustibles
WARNING
Fire Hazard
Some objects can catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
Clearances must be as indicated on Page 3, Figure
1. If clearances to combustibles are not indicated,
then installation clearances apply.
Figure 1: Clearances to Combustibles
3.3 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed on the positive pressure side of the air circulation blower.
• Must be installed in a level position with horizontal discharge.
• May be mounted on a shelf of non-combustible material using shelf mounting brackets.(See Page 9, Figure 4 and Page 9, Figure 5 for details.)
• May be suspended from above (See Page 8, Figure 3) or from wall brackets of sufficient strength to support the heater as listed in the Dimension Data Table on Page 40, Section 15.1.
• Must be installed in a manner which allows access to all serviceable components. See Page 3, Figure 1 for details.
3.4 Minimum Required Installation Clearances
Clearances around the heater and vent must be as indicated on Page 3, Figure 1 and Page 13, Figure 6 through Page 16, Figure 11 to ensure access for servicing, and correct operation.
3
Page 10
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Electrical Shock Hazard
Disconnect electrical and gas supply before servicing.
This appliance must be connected to a properly grounded electrical source.
Failure to follow these instructions can result in death or electrical shock.
3.6 Ventilation
WARNING
Carbon Monoxide Hazard
Heaters may be installed vented or unvented.
Vented heaters must be vented outdoors.
Unvented heaters must be installed in buildings with ventilation rates as per section 6.4.
Failure to follow these instructions can result in death or injury.
It is important to ensure that there is adequate air space around the heater to supply air for combustion, ventilation and distribution in accordance with local and national codes. See Page 10, Section 6.
3.8 Electrical Supply
A permanent 120 V /1 Ø/60 Hz electrical supply is required for the main electrical power. The heater also requires suitable controls in accordance with Page 19, Section 9.
3.7 Gas Supply
WARNING
Fire Hazard
Connect gas supply according to Figure 12.
Do not use gas supply pipe and electrical connections to support heater’s weight.
Gas can leak if not installed properly.
Failure to follow these instructions can result in death, injury or property damage.
It is important that the gas supply pipe is sized correctly to provide the inlet pressure as stated on the heater data plate. The gas supply pipe and electrical connections must not support any of the heater's weight. See Page 18, Section 8.
3.9 Vent
Choose heater orientation to allow for proper location of the vent. Each heater must be fitted with a correctly sized sealed vent system.
If vented horizontally, no other appliance may be connected to the vent. See Page 10, Section 6.
4
Page 11
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the name plate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company.
United States: Refer to NFPA 54/ ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in accordance with the following codes:
United States: Refer to Standard for Aircraft Hangars, NFPA 409 - latest revision.
Canada: Refer to Standard CSA B149.1 Natural Gas and Propane Installation Code.
• In aircraft storage and servicing areas, heaters shall be installed at least 10' (3 m) above the upper surface of wings or of engine enclosures of the highest aircraft which may be housed in the hangar. The measurement shall be made from the wing or engine enclosure (whichever is higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft hangars communicating with aircraft storage or servicing areas, heaters shall be installed not less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so located in all spaces of aircraft hangars that they shall not be subject to injury by aircraft, cranes, movable scaffolding or other objects. Provisions shall be made to assure accessibility to suspended heaters for recurrent maintenance purposes.
4.3 Parking Structures and Repair Garages
Installation in garages must be in accordance with the following codes:
United States: Standard for Parking Structures NFPA 88A - latest revision or the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision. Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
• In accordance with the Standard for Parking Structures NFPA 88A, heaters must be located a minimum of 18" (50 cm) below the floor-ceiling assembly or 18" (50 cm) above the floor.
• In accordance with the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision, heaters must not be installed less than 8' (2.4 m) above the floor.
4.4 Electrical
The heater must be electrically grounded in accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance with the requirements within this manual and the following codes:
United States: Refer to NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.
5
Page 12
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
4.6 High Altitude
These heaters are CSA-approved (without modifications) for installations up to 2000' (610 m) in US and Canada. CSA approved heaters installed above 2000' (610 m) must be de-rated. For installations above 2000' (610 m) in US, consult factory for information on burner de­rating. For installations from 2000' (610 m) to 4500' (1370m) in Canada, high altitude conversion kits are available. Heaters installed over 4500' (1370 m) in Canada are not CSA­approved and must be approved by the local or provincial authority.
6
Page 13
SECTION 5: DUCT HEATER INSTALLATION
SECTION 5: DUCT HEATER INSTALLATION
5.1 General
To connect the inlet and outlet ducts to the heater, Duct-Mate or similar flanges may be slid over the duct connector flanges supplied on the unit and secured with screws. The connection to the duct then can be made using the Duct-Mate clips. The ducts must have removable access panels upstream and downstream of the heater. These panels must be of appropriate size and placement so that smoke or reflected light could be observed to indicate the presence of leaks in the heat exchanger. Covers for these openings should be sealed to prevent leakage.
Any transition into the inlet of the heater should be smooth, with a taper of no more than 15 degrees. If elbows are required, they should be of either broad radius or fitted with properly designed air turns. Consult a professional to ensure air turns are properly designed.
The heater must be installed on the positive pressure side of the circulating air blower. Air flow through the heater must be as shown on Page 7, Figure 2 and may not be reversed. The air flow must be adjusted such that it is within the acceptable
range shown on Page 7, Section 5.1.3. The minimum inlet duct lengths shown on Page 7, Section 5.1.1 should be observed. Pressure drop through the heat exchanger at various air flows is given on Page 7, Section 5.1.2.
Figure 2: Air Flow Direction
OUTLET DUCT
AIR FLOW
INLET DUCT
5.1.1 Minimum Inlet Duct Length
Model Duct Length Duct Size (W X H)
UHD[X][S][R] 75 32" (81 cm) 16 1/8" x 15 7/8" (41 cm x 40 cm) UHD[X][S][R] 100 &125 37" (94 cm) 21 3/4" x 15 7/8" (55 cm x 40 cm)
5.1.2 Temperature Rise and Pressure Drop Ranges
UHD[X][S][R] 75 UHD[X][S][R] 100 UHD[X][S][R] 125
Airflow
(CFM)
850 68.0 0.06 950 78 0.05 1,020 92 0.06 1,200 48.3 0.10 1,500 50 0.18 1,650 57 0.14 1,625 36.4 0.16 2,500 31 0.28 2,340 41 0.27 1,965 30.3 0.22 3,000 26 0.39 3,480 28 0.56 2,450 24.4 0.31 3,300 24 0.46 4,240 23 0.80 2,650 22.0 0.36 3,660 22 0.55 4,750 20 0.98
Temperature
Rise (°F)
Pressure Drop
(in wc)
Airflow
(CFM)
Temperature
Rise (°F)
Pressure Drop
(in wc)
Airflow
(CFM)
Temperature
Rise (°F)
Pressure Drop
(in wc)
5.1.3 Air Flow and Temperature Rise Ranges
Model Rate Air Flow Temperature Rise
UHD[X][S][R] 75 75,000 850 2,650 22 68 UHD[X][S][R] 100 100,000 950 3,660 22 78 UHD[X][S][R] 125 125,000 1,020 4,750 20 92
(Btu/h) Minimum (CFM) Maximum (CFM) Minimum (°F) Maximum (°F)
7
Page 14
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Crush Hazard
Use 3/8" threaded rod minimum.
Failure to follow these instructions can result in death, injury or property damage.
NOTE: Duct supports
not shown. Duct supports and duct are not provided by manufacturer.
Support Points
Ensure all suspension hardware is torqued to a minimum of 20 ft lbs.
Washer
3/8"
Threaded
Rod
Nut
Unistrut
Channel
Nut
Cone Point
Set Pin
Window
Clamp
Unistrut
3/8"
Threaded
Rod
Nut
Washer
Riv Nut
5.2 Shelf Mounting and Suspension
Four suspension points (3/8" nuts) are located on the top of the heater. Drop rods must be 3/8" diameter mild steel.
When handling or supporting the heater from below, ensure that the weight is taken at the support points. For typical suspension, See Page 8, Figure 3. For typical shelf mounting on existing shelf, See Page 9, Figure 4.
The gas or electrical supply lines must not be used to support the heater.
Do not locate the gas or electrical supply lines directly over the path of the flue products from the heater.
The heater must be installed in a location that is readily accessible for servicing.
The heater must be installed in accordance with clearances to combustibles as indicated on the wall tag and in this manual.
5.3 Wall Mounting
For typical suspension, See Page 9, Figure 5. Wall mounted heaters blowing parallel to the wall can only be installed with the service door away from the wall.
The wall mounting brackets must be attached to a suitable wall using all mounting holes. Screw sizes less than 3/8" may not be used. In order for the wall mounting brackets to adequately carry the weight of the heater, it must be installed according to best building practices.
Figure 3: Suspension Methods
8
Page 15
Figure 4: Shelf-Mounting Methods
Shelf Mounting
Brackets
Description Part Number Qty. Shelf Mounting Bracket Kit 12011000K
Shelf Mounting Bracket 11111510 2 Screw #10 x 1/2" Type AB Phil HWH Z
94311008 2
Existing cabinet screws must be re-used.
Shelf Mounting Brackets (Fasten to Wall Mounting Bracket)
5/16" x 3 1/2" Bolt 5/16" Flat Washer 5/16" Locknut with Nylon Insert Tor que to 40 in lb (4.5 Nm).
Wall Shelf Mounting
Wall Mounting
Bracket Arm (Right & Left)
Wall Suspension Mounting
Wall Mounting Bracket Vertical
Wall Mounting
Bracket Diagonal
3/8" Fasteners
Description Part Number Qty. Wall Shelf Mounting Bracket Kit 12011002K
Wall Suspension Mounting Bracket Kit 12011001K 1 Shelf Mounting Bracket Kit 12011000K 1
Description Part Number Qty. Wall Suspension Mounting Bracket Kit 12011001K
Wall Mounting Bracket Arm Left 111WALL1 1 Wall Mounting Bracket Arm Right 111WALL1 1 Wall Mounting Bracket Vertical 111WALL2 2 Wall Mounting Bracket Diagonal 111WALL3 2 5/16" x 3 1/2" Bolt 97213925 6 5/16" Lock Nut with Nylon Insert 92114000 6 5/16" Flat Washer 95211600 6 5/16" Lockwasher 96411600 6
Hardware provided to construct mounting bracket assembly only.
Figure 5: Wall Shelf Mounting and Suspension
SECTION 5: DUCT HEATER INSTALLATION
9
Page 16
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Carbon Monoxide Hazard
Heaters may be installed vented or unvented.
Vented heaters must be vented outdoors.
Unvented heaters must be installed in buildings with ventilation rates as per section 6.4.
Failure to follow these instructions can result in death or injury.
SECTION 6: VENTING
6.1 Changing Vent and Air Intake Orientation
The heater is sold with rear horizontal vent and air intake connections as standard. (Only separated combustion models have air intake connection). If vertical vent and air intake connections are required, follow the instructions on Page 38, Section 14.5.
sheet metal screws. For single wall venting, pressure sensitive aluminum
tape or silicone sealant must be used to seal all joints.
Aluminum tape shall have a minimum temperature rating of 400° F (204° C) and meet SMACNA AFTS­100-73 standards. High temperature silicone sealant must have a minimum temperature rating of 480° F (250° C).
6.2.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below, 4' (1.2 m) horizontally from, or 1' (.3 m) above any door, operable window, or gravity air inlet into any building.
NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code specifies a 4' (1.2 m) horizontal vent terminal clearance from gas and electric meters, regulators and relief equipment.
6.2 Venting
This heater must be vented in accordance with the rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply: United States: Refer to NFPA54/ANSI Z223.1 - latest revision, National Fuel Gas Code; Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code. Any portion of vent pipe passing through a combustible wall must have a listed thimble to conform with the above codes.
The heater may be installed unvented in certain circumstances according to building ventilation codes. Refer to the above codes and Page 11, Section 6.4 for further information. Unvented operation also requires compliance with the clearances to combustibles given on Page 3, Figure 1.
The bottom of the vent or air intake terminal shall not be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m) above grade where located adjacent to public walkways.
Vent terminal must be installed at a height sufficient to prevent blockage by snow and building materials protected from degradation by flue gasses.
Vent terminal must be beyond any combustible overhang.
Secure all joints with corrosion resistant #8 x 3/8"
10
6.2.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a mechanical air supply inlet to any building.
The vent shall not terminate within 3' (.9 m) of a window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.
6.3 Vent Installation
Maintain clearances to combustibles at all times for safety. Clearances are the required distances that combustible objects must be away from the heater to prevent serious fire hazard. See Page 3, Figure
3.5. For vented units, the vent must terminate outside of the building. Vents must be fully sealed and correctly sized for the model. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.
For separated combustion models, vents and air intakes must be a fully sealed system and correctly sized for the model. Vent should be assembled as detailed on Page 13, Figure 6 through Page 16, Figure 11. The joints between the vent terminal and the roof or wall must be properly sealed. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.
Page 17
SECTION 6: VENTING
Vents and air intakes must be adequately supported so that the heater does not bear the weight of the pipes.
For vent termination See Page 13, Figure 6 through Page 16, Figure 11.
6.3.1 Standard Vented Heaters (Models UHD[X][R] 75 - 125)
The vent must be fitted with a low resistance terminal. See Page 13, Figure 6 through Page 13, Figure 7. Standard vented heaters do not allow outdoor air intake for combustion air.
6.3.2 Separated Combustion Heaters (Models UHD[X]S[R] 75 - 125)
The heaters are designed to be installed as separated combustion heaters. The vent and air intake are run as separate pipes to the wall or roof terminals. See Page 15, Figure 9. As an option, the vent and air intake are run as separate pipes to a concentric vent box and a concentric vent/air intake pipe penetrates the wall or roof. See Page 15, Figure 10 and See Page 16, Figure 11.
For separated combustion installation, the vent and air intake must be fitted with an individual and correctly sized sealed system and the vent and air intake must terminate at approved wall and roof terminals.
Separated combustion units may not be common vented. See Page 10, Section 6.
6.4 Unvented Operation
WARNING
Carbon Monoxide Hazard
Heaters may be installed vented or unvented.
Vented heaters must be vented outdoors.
Unvented heaters must be installed in buildings with ventilation rates as per section 6.4.
Failure to follow these instructions can result in death or injury.
This heater is not approved to be installed in residential buildings.
For unvented operation in commercial installations, sufficient building ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United
States); 3 cfm per 1000 Btu/h firing rate (Canada).
WARNING: Combustion by-products contain a chemical known to the State of California to cause cancer and birth defects or other reproductive harm.
6.5 Horizontal Venting
Horizontally vented heaters must be individually vented.
Vent pipe must be sloped ¼" (.6 cm) downward for every 1' (.3 m). For vent lengths greater than 5' (1.5 m), condensation will form. Insulation is recommended and condensation drains may be desired.
In noncombustible walls only, vent terminal (P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or noncombustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal. Follow the manufacturer's instructions for proper installation.
Instead of an insulated vent terminal, a listed thimble (with 2" (5 cm) air gap) may be used with a 4" (10 cm) vent cap (P/N 90502102).
6.6 Vertical Venting
Vertically-vented standard-vented heaters can be common vented (up to four heaters). For vent lengths greater than 5' (1.5 m), condensation will form. Insulation is recommended and condensation drains may be desired. Venting through the top of the heater cabinet is not recommended if vent lengths are longer than 10' (3 m). In this case, vent from the rear of the heater cabinet then run the vent vertically and use a condensate drain at the bottom of the vertical vent. Vent pipe must be sloped 1/4'' (.6 cm) for every 1' (.3 m).
For 4'' (10 cm), an approved vent cap (P/N 90502102) must be used.
For 6'' (15 cm) common vent, an approved vent cap (P/N 90502103) must be used.
For common vertical venting of more than two heaters, See Page 14, Figure 8.
A vent shall not extend less than 2' (.6m) above the highest point where it passes through a flat roof of a building.
6.7 Length Requirements
If using vent lengths greater than 5' (1.5 m), condensation will form in the vent pipe. Insulation
11
Page 18
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
and additional sealing measures (high temperature silicone at all seams) are required. The entire vent should be insulated with foil faced fiberglass insulation (1/2" thick, 1-1/2# density minimum).
6.7.1 Maximum Vent Lengths
Model UHD[X][S][R] 75, 100, 125 Number of Elbows
40 ft (12.2 m) 1 35 ft (10.7 m) 2
30 ft (9.1 m) 3
25 ft (7.6 m) 4
20 ft (6.1 m) 5
6.8 Vent Material
Vent material may be single wall 26 ga. (minimum) galvanized steel or equal thickness stainless steel. Completely seal all joints, refer to Page 10, Section
6.3. If penetrating a combustible wall or roof, a listed thimble with 2" (5 cm) clearance must be used. Where local codes permit, a single section of type B-1 vent material may be used at the roof or wall penetration instead of a thimble. Ensure vent manufacturer's clearance from vent material is maintained. Seal annular space of the type B-1 vent as well as all joints in the remaining vent.
6.9 Replacing an Existing Heater in a Venting System
When replacing an existing heater in a venting system, the venting system may not be properly sized to vent the new heater. The following steps must be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required by the NFPA 54/ ANSI Z223.1 - latest revision, National Fuel Gas Code (US) or Standard CSA B149.1 Natural Gas and Propane Installation Code (Canada) and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. Close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any exhaust fans, such as range hoods and bathroom exhausts so that they shall operate at maximum speed.
Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so that the appliance will operate continuously.
5. For any appliance having a draft hood, test for draft hood appliance spillage at the draft hood relief opening after five minutes of main burner operation. Use the flame of a match or candle.
6. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliances to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the venting system must be corrected by a contractor qualified in the installation and service of gas-fired equipment or your local gas supplier. If the venting must be resized, use appropriate tables in (US) Appendix G of NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code (US) or Standard CSA B149.1 Natural Gas and Propane Installation Code (Canada) to determine minimum size. All vent corrections must be in accordance with the appropriate local codes and the NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code (US) or Standard CSA B149.1 Natural Gas and Propane Installation Code (Canada).
12
Page 19
Figure 6: Vent and Roof Detail
Model Vent Diameter Part Number
UHD[X][R] 75 - 125 4" (10 cm) 90502102
SECTION 6: VENTING
Figure 7: Standard Vented Heater - Vertical and Horizontal Vent Termination
13
Page 20
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Figure 8: Standard Vented Heater - Common Vertical Vent Termination
14
Page 21
Figure 9: Separated Combustion Heater - Vertical and Horizontal Vent Termination
Model
Air Intake &
Vent Diameter
Part Number
UHD[X]S[R] 75 - 125 4" (10 cm) 90502102
4" (10 cm) Single Wall Vent Pipe (By Others)
Seal joint between single wall and Type B vent with silicone sealant.
Use 3 sheetmetal screws equally spaced around joint.
Use 3 sheetmetal screws equally spaced around collar.
Concentric Vent Box
6" (15 cm) Single Wall Inlet Air Pipe (By Others)
One piece of 4" (10 cm) diameter, 1/4" (6 cm) airspace type
“B” vent. Selkirk Model RV or equivalent. (By others)
Combustion Air to Heater
To ward Outside
Exhaust from Heater
SECTION 6: VENTING
Figure 10: Concentric Vent Box
15
Page 22
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Description Part Number Qty. Concentric Vent Kit UHVK1
Concentric Vent Box Top & Side Assembly 90504113 1 Concentric Vent Box Bottom Assembly 90504112 1 Screw #6 x 3/8 Self Drilling 91119100 14 4" (10 cm) Vent Terminal with Baffle Plate 90502102R 1 6" (15 cm) Combustion Air Terminal 90502103 1
Figure 11: Concentric Vertical and Horizontal Vent Termination - Separated Combustion Heater
16
Page 23
SECTION 7: AIR SUPPLY
7.1 Separated Combustion Installation
When installed as a separated combustion heater (UHD[X]S[R]), the air for combustion is drawn in from outside the building.
7.2 Unvented Installation
It is important to ensure that there is adequate fresh air supply at all times for both combustion and heating requirements in accordance with local and national codes.
WARNING: Combustion by-products contain a chemical known to the State of California to cause cancer and birth defects or other reproductive harm.
7.3 Building Ventilation
Where ventilation is required, air must be taken from an outside point where it is not likely to be contaminated or obstructed.
SECTION 7: AIR SUPPLY
7.4 Outside Combustion Air Supply
If outside combustion air supply is required, separated combustion model (UHD[X]S[R]) heaters must be used.
Caution: If the building has a slight negative pressure or corrosive contaminants such as halogenated hydrocarbons are present in the air, an outside combustion air supply to the heater is required. Seal all combustion air pipe joints. The flexible air supply duct may have to be insulated to prevent condensation on the outer surface. The outside air terminal must not be more than 1' (31 cm) above the vent terminal.
7.4.1 Length Requirements
Follow the constraints listed on Page 11, Section
6.7.
17
Page 24
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Fire Hazard
Connect gas supply according to Figure 12.
Do not use gas supply pipe and electrical connections to support the heater’s weight.
Gas can leak if not installed properly.
Failure to follow these instructions can result in death, injury or property damage.
Do not bend flexible
gas connector
sharply.
• Hold gas nipple securely with pipe wrench when attaching the flexible gas connector.
• Do not twist flexible gas connector.
• Ensure all joints are gas tight.
SECTION 8: GAS PIPING
A gas meter is connected to the service pipe by the gas supply company. An existing meter should be checked, preferably by the company, to ensure that the meter is adequate for the rate of gas supply required.
Installation pipes must be fitted in accordance with local and national codes. Pipes of smaller size than the heater inlet gas connection should not be used.
8.1 Connections
Connect the heater to the gas supply ensuring that the final connections are as follows:
Figure 12: Gas Connection
• Gas supply pipe work is run in medium or heavy gauge tubing in compliance with local and national codes.
• Meter and service must be large enough to handle all the burners being installed plus any other connected load. The gas pipe which feeds the system must be large enough to supply the required gas with a maximum pressure drop of 1/2" wc. When gas piping is not included in the layout drawing, contact the local gas supplier.
• An isolating valve and union connection should be used and fitted into the supply adjacent to the heater.
• A minimum 1/8" NPT plugged tapping accessible for test connection must be installed immediately upstream of the gas supply connection to the heater.
• For suspended heaters, an approved metal flexible connection between the isolating valve and the heater may be used. To reduce
pressure loss, use one pipe size larger than the heater gas connection.
IMPORTANT - The complete installation must be
purged and tested for gas soundness in accordance with local and national codes.
Caution: Do not high pressure (in excess of 1/2 psi [14" wc]) test the gas piping with the burner connected. Close manual shut-off valve during any pressure testing equal to or less than 1/2 psi (14" wc).
Check the pipe and tubing ends for leaks before placing heating equipment into service. When checking for gas leaks, use a soap and water solution; never use an open flame.
18
Page 25
SECTION 9: WIRING
WARNING
Electrical Shock Hazard
Disconnect electrical and gas supply before servicing.
This appliance must be connected to a properly grounded electrical source.
Failure to follow these instructions can result in death or electrical shock.
Electrical
Supply
Terminal
Strip
R G W C
R
W
24 Volt Thermostat
Gas
Supply
All heater models require constant 120 V/1Ø/ 60 Hz power supply. Check heater rating plate for electrical rating for proper circuit sizing. For servicing, a disconnect switch of proper electrical rating should be installed in the vicinity of the heater.
SECTION 9: WIRING
All heaters are equipped with thermostat connections suitable to power a 24 V thermostat.
Heater must be wired and electrically grounded in accordance with local codes. In the absence of local
codes in accordance with: United States: refer to National Electrical Code
®
NFPA 70 - latest revision; Canada: refer to Canadian Electrical Code CSA C22.1 Part I - latest revision.
9.1 Positioning Thermostats
A room thermostat should be mounted on a vibration-free wall or column at a height of approximately 5' (1.5 m) from the floor to measure the ambient temperature. It should be clear of both cold drafts and the direct path of warm air from the heater. Avoid mounting thermostat on outside walls or in areas directly exposed to radiant heat or sunlight. Install wall tag in a visible location near thermostat. See Page 2, Section 2.1 for wall tag details.
9.2 Low Voltage Thermostat with One Heater
19
Page 26
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105 °C (221 °F) and 600 V. For supply connections, use No. 14 AWG or larger wires.
BLUE
BLACK
ORANGE
ORANGE
YELLOW
BROWN
WHITE
WHITE
L2
L1
ORANGE
ORANGE
BLACK
BLACK
GREEN
WHITE
BLUE
BLACK
GREEN
BLUE
GREEN
YELLOW
24 VAC
HOT
GROUND
FLAME
BLACK
BLACK
6
3
4
2
1
45
31
SENSE
ELECTRODE
LIMIT SWITCH
PRESSURE SWITCH
GAS VALVE
IGNITION MODULE
TRANSFORMER
LIMIT SWITCH (UHD 300, 350, 400 ONLY)
MANUAL RESET LIMIT SWITCH (RESIDENTAL UNITS ONLY)
THERMOSTAT INPUT: FIELD SUPPLIED
R = 24 VAC TO THERMOSTAT (RED)
G = MANUAL FAN INPUT FROM THERMOSTAT (GREEN)
W = HEAT DEMAND INPUT FROM THERMOSTAT (WHITE)
C = COMMON GROUND TO THERMOSTAT
FLUE
BLOWER
R
G
W
C
ACC
L1
CMB BLOWER
5
9.3 Internal Wiring Diagram
20
Page 27
9.4 Ladder Wiring Diagram
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105 °C (221 °F) and 600 V. For supply connections, use No. 14 AWG or larger wires.
FLAME
SENSOR
PRESSURE SWITCH
THERMOSTAT CONNECTION
6
3
4
5
2
1
120 VAC
TRANSFORMER
FLUE BLOWER
GAS
VALVE
ELECTRODE
IGNITION MODULE
FLAME
SPARK
LIMIT SWITCH
LIMIT SWITCH (UHD 300, 350, 400 ONLY)
MANUAL RESET LIMIT SWITCH (UHD 75 - 125 ONLY)
FLUE BLOWER
SECTION 9: WIRING
21
Page 28
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
BX Connector
Junction Box
Flexible Conduit
Burner
Connect wires together
with suitable approved
wire connectors.
Green to Ground
White to L2
Black to L1
L1 L2
Ground
Black
White
Green
9.5 Electrical Connection to the Heater
IMPORTANT: Junction box is not provided with heater.
Conduit can also be attached directly to heater with wire junction made within the heater cabinet.
22
Page 29
SECTION 10: OPERATION AND MAINTENANCE
WARNING
Explosion Hazard
Installation, service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
SECTION 10: OPERATION AND MAINTENANCE
Read this manual carefully before installation, operation, or service of this equipment. All components are accessed via the door secured by four sheet metal screws. Opening the door exposes live electrical connections and hot components.
10.2 Begin Start-Up
10.2.1 Before Operating the Heater
To ensure that all the controls are in safe working order, operate the heater for the first time with the isolating gas valve turned off and power supply turned on.
1. Turn off the isolating gas valve.
2. Turn up the thermostat above room temperature. The automatic ignition sequence will now begin as described on Page 24, Figure 13.
There will be no ignition of the burner and lockout will occur, which proves the controls are operating correctly.
10.1 Pre-Start-Up Checks
All pre-start-up checks must be carried out before lighting the heater.
Ensure that the heater and all controls are suitable for the gas, pressure and electrical supply to which they are to be connected.
10.1.1 Electrical Checks
1. Check that all site wiring is connected in accordance with the appropriate wiring diagram on Page 20, Section 9.3.
10.1.2 Gas Supply
All aspects of the gas installation including the gas meter must be inspected, tested for gas tightness and purged in accordance with local and national codes.
Ensure that the air is fully purged from the heater inlet pipe up to the main gas valve inlet test nipple.
10.1.3 Mechanical Checks
1. Check that the flue (and air intake for separated combustion units) is installed in accordance with these instructions and local regulations.
23
Page 30
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Burner Sequence for Ignition Control
Flame Signal
Start Gas Valve
Ignition Spark
Thermostat 24 V
SHUT DOWN
RUNSTART
ts = 10 Seconds
Signals Output By Control
Required Incoming Signals
Flue Blower
Pressure
Switch
P
C
NO
NC
30 Seconds Purge*
*Purge time begins at pressure switch change over.
30 Seconds Post
If at any stage the flame fails, the control will retry for ignition. The control has four trials for ignition before a one hour lockout.
Description Part Number
Gas Valve NG 90032505 Gas Valve LP 90032506
Figure 13: Automatic Burner Control Sequence
Figure 14: Gas Valve
Gas Inlet
END VIEW
Regulator
TOP VIEW
½PSI IN
C
ON
OFF
Outlet Pressure
24
Inlet Pressure
Page 31
10.2.2 Start-Up the Gas Valve (All Gases)
10.2.2.1 Check Burner Gas Pressure
1. Remove the plug in the outlet (burner) pressure test point and connect a pressure tap and a manometer.
2. With the burner firing, measure the pressure on the manometer. To adjust the burner pressure, remove the regulator cover from the valve and turn the regulator adjustment screw to set the required burner pressure as stated in the Technical Data Tables for the correct gas and model on Page 41, Section 15.3.
IMPORTANT: If the correct burner pressure cannot be reached, then check the inlet pressure to the valve with the burner firing. See Technical Data Ta bl e s on Page 41, Section 15.3 for inlet pressure requirement.
SECTION 10: OPERATION AND MAINTENANCE
10.3 Complete Start-Up
Ensure that all covers are fitted correctly and all test points are properly sealed.
10.3.1 Instruction to the User
Explain the controls of the heater to the user including how to turn it on and off, using the controls fitted on site.
Give this manual to the user. Ensure that the user is shown and understands the
importance of maintaining clearances to combustibles on Page 3, Figure 1 and the user instructions on Page 26, Section 11 through Page 27, Section 11.5 and all warnings defined in this manual.
Do not continue to adjust the regulator if the pressure is not changing.
If the inlet pressure is too low to allow correct burner pressure setting, then the gas inlet pressure must be corrected before completing the start-up.
Check Gas Rate
1. After burner pressure adjustment, allow the heater to operate for at least 15 minutes and then re-check settings. Adjust pressure setting if necessary.
2. Check gas flow rate at gas meter.
3. Turn off heater and electrical supply.
4. Remove the manometer and refit all covers to the valve and tighten the screw of the outlet pressure tap.
10.2.3 Pressure Switch
The pressure switch is factory pre-set for each model and is not adjustable.
10.2.4 Turning Off the Heater
Set the thermostat to the "OFF" position or lowest setting and the main burner will stop.
10.2.5 External Controls
External controls may include time switch, interlock switch, room thermostat and frost thermostat. Operate each control to ensure that they function correctly. Set the switches (if fitted) and thermostat(s) to the users’ requirements.
25
Page 32
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Explosion Hazard
Do not make more than one attempt to restart the heater if manual reset limit switch locks out.
The vent or heat exchanger may be blocked.
The fault must be traced and repaired.
Failure to follow these instructions can result in death, injury or property damage.
Reset Button
To reset manual reset limit switch, press reset button. NOTE: To reset, the switch must be cool.
Description Part Number
Manual Reset Limit Switch 90412106
SECTION 11: USER INSTRUCTIONS
WARNING
Explosion Hazard
Installation, service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
11.1 User Instructions
The UHD[X][S][R] Series heaters are fully automatic and operate from the external controls fitted on site.
The only user control at the heater is the Manual Reset Limit Switch - See Page 26, Section 11.3.1
11.3 Common User Controls
11.3.1 Manual Reset Limit Switch
The limit thermostat is located inside the access door of the heater. See Page 37, Section 14.3. This control protects against excessive heat build-up inside the burner compartment.
11.2 Heater Operation
When the heater has been switched on by the thermostat installed on site, the main burner will automatically turn on.
The burner control box will control the safe ignition of the flame.
All heaters require a constant gas and electricity supply which must not be interrupted during the normal operation of this heater.
26
Figure 15: Manual Reset Limit Switch
11.4 Lighting Instructions
11.4.1 To Turn On Heater
1. Ensure that the electrical and gas supplies to the heater are on. Check that the on site controls are "ON".
IMPORTANT: The thermostat setting must be above the ambient temperature for the heater to operate.
2. The automatic firing sequence will begin as described on Page 24, Figure 13. The heater will now operate automatically under the control of the on site controls.
Page 33
11.4.2 To Turn Heater Off
Set the thermostat to the "OFF" position. The burner will turn off immediately. To restart, turn the thermostat above room temperature.
11.5 Simple Troubleshooting
Some possible reasons for the heater not operating are:
1. Gas supply not "ON".
2. Electricity supply not "ON".
3. The time and/or temperature controls are not "ON".
4. A limit switch may have operated. This may be caused by an interruption of the electrical supply, failure of the distribution fan or vent or heat exchanger blockage.
If a temperature limit switch persistently trips, there is a fault which must be investigated by a contractor qualified in the installation and service of gas-fired heating equipment.
SECTION 11: USER INSTRUCTIONS
11.5.1 Simple Troubleshooting (Burner Faults)
If the burner fails to ignite for any reason, it will retry for ignition (four trials total). After four unsuccessful ignition trials, the control will put the heater into lockout for one hour.
Lockout should not occur during normal operation of the heater and indicates there is a fault condition which must be corrected. There is an LED light on the ignition control that flashes codes to assist in fault correction. See Page 27, Figure 16 for LED indication codes.
Figure 16: LED Diagnostic Codes
LED INDICATION FAULT MODE
Slow Flash Normal Operation - No call for heat.
Fast Flash Normal Operation - Call for heat.
2 Flashes Ignition Lockout - No flame detected.
3 Flashes Airflow Fault - Pressure switch open or closed.
4 Flashes Temperature Limit or
Manual Reset Limit Switch Open
5 Flashes Flame Sense Error - Gas valve not energized.
Steady On Internal Control Failure
27
Page 34
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 12: SERVICING
WARNING
Explosion Hazard
Installation, service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
12.1 Servicing Instructions
After start-up, the heater will require maintenance to be carried out annually. If the heater is used in a dirty or dusty area, more frequent maintenance may be required.
IMPORTANT: After any maintenance or repair work, always test fire the heater in accordance with the start-up instructions on Page 23, Section 10 through Page 25, Section 10.3.1 to ensure all safety systems are in working order before leaving the heater to operate. Minor faults may be traced by using the troubleshooting charts on Page 31, Section 13 through Page 34, Section 13.5.
IMPORTANT: Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks. Any cracks in the pipes or pipe joints must be repaired.
IMPORTANT: Inspect all suspended components and hardware. Ensure that they are in good condition, properly tightened, and corrosion free.
3. Remove the ignition electrode and flame probe. Check condition of ignition electrode and flame probe. Clean off any deposits which may have been formed, check condition of ceramic insulators. Replace as required.
12.3 Heat Exchanger Maintenance
The heat exchanger will remain clean unless a problem has developed with combustion. Inspect the heat exchanger. Look for signs of overheating at the front tubes which may indicate burner over firing or persistently low air flows.
12.4 Gas Valve Maintenance
No regular maintenance is required on this device. To change gas control valves, See Page 35, Section
14.1.
Do not repair or disassemble gas valve.
Replace faulty gas valves with replacement parts sold and supplied by Roberts-Gordon.
12.5 Flue Blower
The flue blower should not require maintenance. However, if the air pressure switch is causing burner lockout, then remove the flue blower from the vent box by unscrewing the three screws at the mounting plate. Remove the four screws attaching the mounting plate to the fan inlet (See Page 38, Section 14.5). Ensure that the fan is free to run and that the fan wheel is clean.
12.6 Venting and Air Intake Pipe
Inspect all venting and air intake pipe. Ensure that all seams are sealed and suspension points secure. Repair suspension points if any part of the venting or combustion air pipe is sagging. Check to make sure any insulation is not missing or in poor condition. Replace as required. Check all venting and air intake components to ensure they are in good condition, gas tight and corrosion-free.
12.2 Burner Maintenance
1. Open the door and remove the burner compartment cover. See Page 36, Section
14.2.
2. Clean any deposits from the main burner which may have formed in the injectors or venturi of the burner. See Page 36, Section 14.2.
28
Page 35
12.7 Maintenance Checklist
WARNING
Explosion Hazard
Installation, service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
SECTION 12: SERVICING
Installation Code and Annual Inspections: All
installations and service of ROBERTS GORDON
®
equipment must be performed by a contractor qualified in the installation and service equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS
GORDON
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment.
To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS
GORDON
®
equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.
The Vicinity of the Heater Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 3, Section 3.
Vehicles and Other Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged in between the heat exchanger tubes.
Immediately remove objects in violation of the clearances to combustibles.
See Page 3, Section 3.
Vent Pipe/Terminals Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
If the vent terminal has a screen built in, remove any dirt, dust or deposits from the screen.
See Page 17, Section 7.
Combustion Air Intake Pipe
Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Heat Exchanger Make sure there are no cracks.
Clean and reinstall as required.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
See Page 18, Section 8.
29
Page 36
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Gas Line and Shut-off Valves
Burner Observation Window
Flue Blower Scroll, Wheel
Check for gas leaks.
See Page 18, Section 8.
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
and Motor Inshot Burners and
Orifices
Clear obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Direct-Spark Igniter Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8" (3.2 mm).
Thermostat There should be no exposed wire or damage to the device or wiring.
See Page 19, Section 9.1.
Suspension Points Make sure the heater is hanging securely.
Look for signs of wear on the suspension materials or ceiling.
See Page 8, Figure 3.
Silicone Tubing Ensure tight, secure fit on all pressure fittings at pressure switch,
burner partition, and blower outlet.
Gas Valve Verify that cap covering pressure regulator adjustment screw is secure and
has not been tampered with.
Verify all wiring connections.
Condensate Drain
Flush drain and clear any obstructions.
(when installed) Ductwork Consult an indoor air quality professional for proper cleaning procedures. Air Circulation Blower For a complete inspection, refer to the manufacturers installation, operation
and service manual.
Wall Tag If wall tag is present, make sure it is legible and accurate. Please contact
Roberts-Gordon LLC or your ROBERTS GORDON
®
independent distributor if
you need a wall tag. See Page 2, Section 2.1.
30
Page 37
SECTION 13: TROUBLESHOOTING
WARNING
Explosion Hazard
Installation, service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
13.1 General
START
SECTION 13: TROUBLESHOOTING
Are gas & electrical
supplies on?
Ye s
Is ignition control showing a
"4 flashes" LED code?
No
Is ignition control showing a
"2 flashes" LED code?
No
Does the flue blower run?
No
Ye s
Ye s
No
Turn on supplies.
UHD 75: Press in reset button on manual reset limit switch. UHD 100 - 125: Wait
10 - 15 minutes for limit
switch to cool. Does fan
stop running?
No
Replace temperature limit
switch.
Burner has locked out due
to ignition failure. Use
Tro ubleshooting for Automatic
Ignition Burner Systems
section to test burner.
Use Troubleshooting for
Flue Blower section to test
fan.
Ye s
Fan and limit switch are
operating normally.
Ye s
Ye s
With external controls (i.e.
thermostat) on, does the
burner continue through the
heating cycle?
Ye s
Heater Operating
TROUBLESHOOT ENDS.
Has burner “Locked Out”?
No
Use Troubleshooting for
Automatic Ignition Burner
Systems section to test burner.
If problems persist, contact
No
Roberts-Gordon, LLC at
Ye s
www.rg-inc.com
No
The limit switch has
tripped. See Manual Reset
Limit Switch Figure.
Ensure air flow through the
heat exchanger is
appropriate per the rating
Ye s
plate.
No
Replace limit switch.
31
Page 38
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
For optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon.
Conduct start-up procedure as shown on Page 23, Section 10.
13.2 Troubleshooting For Automatic Ignition Burner Systems
START
Are gas & electrical
supplies on?
Ye s
Are external controls (i.e. Thermostat) on?
Ye s
Is ignition control showing a
"4 flashes" LED code?
No
Does flue blower run?
No
Turn on supplies.
No
Ye s
No
Turn on controls.
UHD 75: Press in reset button on manual reset limit switch. UHD 100 - 125: Wait
10 - 15 minutes for limit switch to cool. Does fan
stop running?
Replace temperature limit
Is 120 V supply at fan
connections?
No
switch.
No
Ye s
Fan and limit switch are
Ye s
operating normally.
Flue blower faulty;
replace
Ye s
Does air pressure switch
change over?
Ye s
Wait 30 - 40 seconds.
Does ignition spark
operate?
Ye s
Does the flame light?
Ye s
Is ignition control showing
a "2 flashes" LED code?
No
Heater Operating
TROUBLESHOOT ENDS.
Burner control faulty or wiring
connections faulty. Repair
or replace as required
Check for too much vent/air inlet duct. Check for blockage in
vent and combustion air circuit. Check for faulty air pressure
No
switch. Check pressure switch hoses for leaks or cracks. Do not attempt to circumvent pressure switch circuit to place unit in operation.See Pressure Switch section for details.
No
No
Ye s
No
Is ignition lead okay and
connected?
Is spark electrode okay?
Is the gas valve operating?
To test valve, See
Tro ubleshooting for Gas
Valves section.
Is the flame current at
least 1 μAmp DC when
the flame ignites?
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Ye s
No
Ye s
Ignition control faulty;
See Ignition Control section.
Replace valve.
Trace fault in supervision
system. See
Tro ubleshooting
for Flame Supervision
System section.
replace.
32
Page 39
13.3 Troubleshooting for Flame Supervision System
NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.
To measure flame current, connect a 0 - 50 μA DC meter in series with the flame probe. If the meter reads negative values, then reverse the test leads.
START
Connect a DC ammeter in
series with the flame probe.
SECTION 13: TROUBLESHOOTING
Is the flame present and
at least 1 μA DC flame
current?
Ye s
Is there a current flowing in the flame probe circuit with
no flame present?
No
No
Ye s
Does “lockout” occur when
there is a flame present?
No
Heater Operating
TROUBLESHOOT ENDS.
Ye s
No
Use General
Tro ubleshooting section to
trace the fault.
Is the connecting lead damaged? Is the flame probe damaged or touching earthed
components?
Is inlet burner gas pressure
correct? Is live and neutral
polarity correct? Is
flame probe circuit correct?
No
Repair or replace as
required.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Repair or replace as
Ye s
Ye s
required.
Replace ignition control.
33
Page 40
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
For optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon.
Conduct start-up procedure as shown on Page 23, Section 10.
13.4 Troubleshooting for Gas Valves
START
Is gas pressure at inlet of the
valve correct for gas type?
Note pressure found.
Does gas pressure at outlet
of the valve rise when
valve turns on?
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
Valve Operating
TROUBLESHOOT ENDS.
13.5 Troubleshooting for Flue Blower
Ye s
Ye s
Ye s
Ye s
No
No
No
No
Fault elsewhere.
Correct pressure problem.
Valve or ignition control
faulty. Replace with one of correct type.
Valve faulty.
Replace with one of
correct type.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
START
Does flue blower run
automatically when there
is a call for heat?
Ye s
Does blower turn on and
off while burner is firing
continuously?
No
Blower Operating
TROUBLESHOOT ENDS.
Ye s
No
No
Correct power
supply problem.
Ye s
Blower motor faulty.
Replace with correct type.
Check blower motor leads
for loose connections.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
34
Page 41
SECTION 14: REPLACEMENT PARTS Burner Components
½PSI IN
C
ON
OFF
Flexible Air Duct
NOTE: Separated combustion
Description Part Number
Gas Valve, NG (Models UHD[X][S][R] 75 - 125) 90032505 Gas Valve, LP (Models UHD[X][S][R] 75 - 125) 90032506
model shown.
All serviceable burner parts are accessed by the
WARNING
door on the side of the heater. Remove the sheetmetal screws.
14.1 Gas Valve
Remove the gas supply pipe at the heater inlet.
Follow steps in Section 14.2 and Section 14.2.1 to
Explosion Hazard
Installation, service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
remove gas valve/manifold. Replace in reverse order. Verify that the gas flow
direction of the valve is correct. Use a minimum amount of gas seal on the thread joint. Check that all the joints are leak free. Reset gas valve. See Page 25, Section 10.2.2.
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
IT IS IMPORTANT THAT ONLY THE CORRECT GAS VALVE IS USED WHEN REPLACING THESE CONTROLS.
SECTION 14: REPLACEMENT PARTS
See warnings and notes on Page 28, Section 12 before removing or replacing parts.
35
Page 42
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Remove flexible air duct from spigot
Viewing port for flame probe
Flame Probe
Burner Compartment Cover
Ignition Electrode
Remove screws and pull off burner cover
NOTE: Separated combustion model shown.
The burner compartment is a sealed compartment. Following any work, re-seal the compartment with the gas pipe rubber seal fully in place and all screws fitted and tight.
Remove manifold
screws and pull
out manifold
Manifold
Inshot
Burners
Orifices
Manifold
Mounting
Bracket
Grommet
Unscrew
Orifices
Manifold
Marking
Folded
Hem
Ensure gas tight fitting of injectors.
Ensure correct alignment with burners.
Ensure all pipe joints are gas tight.
14.2 Burner Compartment
14.2.1 Burner Injectors
MODEL UHD[X][S][R] 75 UHD[X][S][R] 100 UHD[X][S][R] 125
Orifice Quantity 5 6 7
Natural Gas (G20)
Orifice Marking 49 46 46
P/N 91930049 91930046 91930046
Propane (G31)
Orifice Marking 1.15 mm 1.25 mm 1.25 mm
P/N 91930115 91930125 91930125
36
Page 43
14.3 Ignition Electrode and Flame Probe
Inshot
Burners
.120
(3 mm)
spark
gap
Ignition
Electrode
Burner Compartment
Front Views
Manual Reset
Limit Switch
(Position may vary.)
Ignition
Electrode
Flame
Probe
Limit
Switch
Flame
Probe
Inshot
Burners
Description Part Number Qty
Spark Electrode 90427411 1 Automatic Ignition Flame Probe 90439300 1 Transformer 90436900K 1 Ignition Module 90434008 1 Inshot Burners UHD[X][S][R] 75 92000002 5 Inshot Burners UHD[X][S][R] 100 92000002 6 Inshot Burners UHD[X][S][R] 125 92000002 7 Limit Switch 90412104 1 Manual Reset Limit Switch (75 only) 90412106 1
To replace the electrode or flame probe, remove the electrical lead and screw. Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the front view of the burner compartment.
SECTION 14: REPLACEMENT PARTS
14.4 Heat Exchanger
The heat exchanger consists of a six-pass design with 1.5" outer diameter [aluminized steel] [409 stainless steel] tube. The tube plates are made of [aluminized steel] [409 stainless steel]. The tube supports are made of [galvannealed steel] [409 stainless steel].
37
Page 44
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
Mounting Plate
to Vent Box
fixing screws
Flexible Air
Duct
Intake & Exhaust
Covers
Air Intake Adapter
Gasket
To remove the blower, remove screws securing the fan and mounting plate to the vent box.
To remove the blower from the mounting plate, remove screws.
Refit in reverse order.
To change the vent and air intake orientation from back to top, remove the blower and mounting plate as above.
Remove intake (if applicable) and exhaust covers from top of the heater.
Rotate the blower, mounting plate and gasket clockwise until the flue adapter lines up with the top hole. Secure screws.
If applicable, remove the flexible air duct from the air intake adapter on the back.
If applicable, remove the air intake adapter from the back of the heater and install in the appropriate hole on top. Reconnect the flexible air duct.
Install intake and exhaust covers over the back holes.
NOTE: Separated combustion model shown.
14.5 Flue Blower Vertical Installation
Intake & Exhaust Covers
Mounting Plate
to Vent Box
fixing screws
Air Intake
Adaptor
Mounting Plate
to Flue Blower
screws
Gaskets
Vent Box
MODEL UHD[X][S][R] 75 UHD[X][S][R] 100 UHD[X][S][R] 125
Flue Blower P/N 90710404 90710405 90710405
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.
Carry out a start-up after working on or changing a flue blower. See Page 26, Section 11.
38
Page 45
14.6 Pressure Switch
SECTION 14: REPLACEMENT PARTS
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are color coded for each pressure setting.
Carry out a start-up after working on or changing a pressure switch. See Page 23, Section 10.
MODEL UHD[X][S][R] 75 UHD[X][S][R] 100 UHD[X][S][R] 125
Pressure Switch Kit P/N
Color Code
Set Point in wc
Pressure Switch Snap Ring P/N
90439810 90439810 90439803
black black gray
.35 .35 .41
90439850 90439850 90439850
14.7 Ignition Control
The control mounts to the heat exchanger plate. Pull out ignition cable and wiring from board, noting their positions. Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition cable and all other wiring.
14.8 Limit Switches
14.8.1 Removal and Replacement
1. Remove the electrical connections to the switch.
2. Unscrew the two screws securing the switch.
3. Fit a new switch with two screws.
4. Reconnect the electrical connections and test operation.
39
Page 46
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 15: SPECIFICATIONS
15.1 Dimension Data
B
16.63"
(42 cm)
B
TOP VIEW
E
REAR VIEW
A
A
17.63"
(45 cm)
18.25"
(46 cm)
6"
(15 cm)
C
6"
(15 cm)
Air Intake
(UHD[X][S[]R]
only)
Flue
6"
(15 cm)
Thermostat Connection
4 x 3/8" Captive Nuts Provided
Air Intake
UHD[X][S][R]
( Optional Position)
Flue (Optional Position)
6.75"
(17 cm)
SIDE VIEW
D
6.75"
(17 cm)
only;
20.25"
( 51 cm)
B
E
Gas Supply
28.5"
(72 cm)
A
B
C
D
E
Height
Duct Connector Flange
Center of Flue [Top Option]
Center of Flue
Minimum Inlet Duct Length
Recommended Mounting Height to Heater Base
Weight lb 81 92 97
3 .3"
(8 cm
Model
(cm)
(cm)
(cm)
(cm)
(cm)
Electrical
1. 5 " (4 cm
)
in
in
in
in
in
ft
(m)
Supply
)
UHD
[X][S][R] 75
17.79
(45.09)
1. 2 5 (3)
5.2
(13.21)
2.5
(6.35)
32
(81.28)
12
(3.66)
UHD
[X][S][R] 100
23
(58.42)
1. 2 5 (3)
6.9
(17.53)
2.5
(6.35)
37
(93.98)
20
(6.10)
1. 8"
(5 cm)
UHD
[X][S][R] 125
23
(58.42)
1. 2 5 (3)
6.9
(17.53)
2.5
(6.35)
37
(93.98)
20
(6.10)
40
Page 47
15.2 General Technical Data Table
SECTION 15: SPECIFICATIONS
Model
Full Load Amps @ 115 V A 1 2 2
Minimum Air Volume CFM 850 950 1020
Temperature Rise @ Minimum Air Volume °F (
Heat Exchanger Pressure Drop @ Minimum Air Volume in wc 0.06 0.05 0.06
Maximum Air Volume CFM 2650 3660 4750
Temperature Rise @ Maximum Air Volume °F (
Heat Exchanger Pressure Drop @ Maximum Air Volume in wc 0.36 0.55 0.98
Flue Size/Air Intake** in (cm) 4 (10)-All models
°C)
°C)
UHD[X][S][R] 75UHD[X][S][R]
100
68 (20) 78 (26) 92 (33)
22 (-6) 22 (-6) 20 (-7)
UHD[X][S][R]
*Do not exceed the maximum length of flue stated or heater may not operate properly.
15.3 Technical Data Table
Model
Total Input (Btu/h) x (1000) 75 100 125
Total Output (Btu/h) x (1000) 61.5 82 102.5
Efficiency % 82-All models
UHD[X][S][R]
75
UHD[X][S][R]
100
UHD[X][S][R] 125
125
Natural Gas (G20) Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.
Burner Pressure in. wc 3.5 2.6 3.3
LPG / Propane (G31) Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.
Burner Pressure in. wc 10.0 9.1 10.0
41
Page 48
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
42
Page 49
SECTION 16: ROBERTS GORDON® COMBAT® UHD-SERIES WARRANTY
SECTION 16: ROBERTS GORDON ROBERTS GORDON
®
WILL PAY FOR:
®
COMBAT® UHD-SERIES WARRANTY
Within 24 months from date of purchase by buyer or 27 months from the date of shipment by Roberts-Gordon (whichever comes first), replacement parts will be provided free of charge for any part of the product which fails due to a manufacturing or material defect.
Roberts-Gordon will require the part in question to be returned to the factory. Roberts-Gordon will, at its sole discretion, repair or replace after determining the nature of the defect and disposition of part in question.
ROBERTS GORDON
®
Replacement Parts are warranted for a period of 18 months from date of shipment from Roberts-Gordon or the remaining ROBERTS GORDON COMBAT® UHD-Series warranty.
ROBERTS GORDON® WILL NOT PAY FOR:
Service trips, service calls and labor charges. Shipment of replacement parts. Claims where the total price of the goods have not
been paid. Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the ROBERTS GORDON way.
• Use of the ROBERTS GORDON Series for other than its intended purpose.
• Incorrect gas or electrical supply, accident, fire, floods, acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or accessories not specified by Roberts-Gordon.
• Failure to install or maintain the ROBERTS GORDON COMBAT
®
UHD-Series as directed in the Installation,
Operation and Service manual.
• Relocation of the ROBERTS GORDON UHD-Series after initial installation
• The use of the ROBERTS GORDON UHD-Series in a corrosive atmosphere containing contaminants.
• The use of the ROBERTS GORDON UHD-Series in the vicinity of a combustible or explosive material.
• Any defect in the ROBERTS GORDON UHD-Series arising from a drawing, design, or specification supplied by or on behalf of the consumer.
• Damage incurred during shipment. Claim must be filed with carrier.
®
COMBAT® UHD-Series in any
®
COMBAT® UHD-
®
COMBAT®
®
COMBAT®
®
COMBAT®
®
COMBAT®
®
The ownership of the ROBERTS GORDON
COMBAT® UHD-Series is moved or transferred. This warranty is nontransferable.
Roberts-Gordon is not permitted to inspect the damaged controller and/or component parts.
READ YOUR INSTALLATION, OPERATION AND SERVICE MANUAL
If you have questions about your controller, contact your installing professional. Should you need Replacement Parts or have additional questions, call or write:
Roberts-Gordon
®
1250 William Street P. O . B o x 4 4 Buffalo, New York 14240-0044
716.852.4400
On the web at: www.rg-inc.com
Roberts-Gordon' liability, and your exclusive remedy, under this warranty or any implied warranty (including the implied warranties of merchantability and fitness for a particular purpose) is limited to providing replacement parts during the term of this warranty.
Some jurisdictions do not allow limitations on
how long an implied warranty lasts, so this limitation may not apply to you. There are no rights, warranties or conditions, expressed or implied, statutory or otherwise, other than those contained in this warranty.
Roberts-Gordon shall in no event be responsible for incidental or consequential damages or incur liability for damages in excess of the amount paid by you for the ROBERTS GORDON
®
COMBAT® UHD-Series.
Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so this limitation
®
or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from jurisdiction to jurisdiction.
Roberts-Gordon shall not be responsible for failure to perform under the terms of this warranty if caused by circumstances out of its control, including but not limited to war, fire, flood, strike, government or court orders, acts of God, terrorism, unavailability of supplies, parts or power. No person is authorized to assume for Roberts­Gordon any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF REPRESENTATIVES:
No representative of Roberts-Gordon, other than an Executive Officer, has authority to change or extend these provisions. Changes or extensions shall be binding only if confirmed in writing by Roberts-Gordon's duly authorized Executive Officer.
WARRANTY IS VOID IF:
The ROBERTS GORDON® COMBAT® UHD-Series is not installed by a contractor qualified in the installation and service of gas-fired heating equipment.
You cannot prove original purchase date and required annual maintenance history.
The data plate and/or serial number are removed, defaced, modified or altered in any way.
43
Page 50
Page 51
Warm Air Heating
OWNER WARRANTY REGISTRATION CARD
®
Roberts Gordon LLC • 1250 William Street, P.O. Box 44 • Buffalo, NY 14240-0044 • Phone: 716-852-4400 • Fax: 716-852-0854
About the Owner:
Name:__________________________________________________________________________________________________ Address:______________________________________City:_________________________ State:__________Zip Code:________ Phone:_________________________ Fax:_________________________ E-mail:______________________________________
About the Installer:
Name:__________________________________________________________________________________________________ Address:______________________________________City:_________________________ State:_________Zip Code:_________ Phone:__________________________Fax:_________________________ E-mail:______________________________________
Purchased From (if different than installer):
Name:__________________________________________________________________________________________________ Address:______________________________________City:_________________________ State:__________Zip Code:________ Phone:_________________________ Fax:_________________________ E-mail:______________________________________
About your Heater:
Model#:_______________________ Serial #:___________________________ Fuel:____________ Installation Date:__________
Type of Installation (check one):
o Automotive o Manufacturing o Warehouse o Recreational o Aircraft o Public Building o Office o Retail o Agricultural o Other______________
Toll Free: 800-828-7450 • www.rg-inc.com
Mail or Fax to:
Installation Code and Annual Inspections: All installations and service of ROBERTS GORDON® equipment must be performed by a
contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON
installation, service and operation of the equipment.
To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON Roberts-Gordon.
These products are not approved for residential use.
© 2008 Roberts-Gordon LLC - All rights reserved. No part of this work covered by the copyrights herein my be reproduced or copied in any form or by any means – graphic, elect recording, taping, or information storage and retrieval systems – without written permission of Roberts Gordon LLC.
®
equipment and perform service where necessary, using only replacement parts sold and supplied by
®
manuals and all applicable governmental authorities pertaining to the
ronic, or mechanical, including photcopying,
Printed in the U.S.A.
Page 52
Page 53
Page 54
WARNING
© 2008 Roberts-Gordon LLC www.rg-inc.com Printed in U.S.A. P/N 91039831
Attach this information to the wall near the ROBERTS GORDON
®
heater
Read the Installation, Operation and Service Manual thoroughly before installation, operation or service.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting (above ambient temperature). The automatic starting sequence begins.
1. Turn the thermostat/time switch to 'OFF' or lowest setting. The burner
will turn 'OFF' immediately, but fans will continue to cool heat exchanger until the fan thermostat switches off.
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your installer/contractor qualified in the installation and
service of gas-fired heating equipment.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
Fire Hazard
Some objects can catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
TO TURN OFF THE HEATER
Roberts-Gordon LLC
1250 William Street P.O. Box 44 Buffalo, NY 14240-0044 USA
®
Left Right
Bottom
Top
Clearances to Combustibles
Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help
facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor conduct annual inspections of your ROBERTS GORDON
®
equipment and perform service
where necessary, using only replacement parts sold and supplied by Roberts-Gordon.
For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.
Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please
contact us for any further information you may require, including the Installation, Operation and Service Manual.
This product is not for residential use.
Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
Top
Bottom
RightLeft
Models 75 - 125 Models 150 - 400
Models
To p Bottom Right Left Vent
75 - 125
1" 1" 1"
18"*
2"
150 - 400
6" 6"
31"*
6" 2"
* Clearance needed for servicing.
Loading...