Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or
property damage. Read the Installation, Operation
and Service Manual thoroughly before installing or
servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas
supplier after leaving the building.
Follow the gas supplier’s
instructions.
8. If you cannot reach your gas
supplier, call the Fire Department.
®
Combat
UHD-Series
Tubular Duct Furnace
(Low Profile Range)
WARNING
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to combustibles away from
heater.
Some objects will catch fire or explode
when placed close to heater.
Failure to follow these instructions can
result in death, injury or property
damage.
1250 William Street
P.O. Box 44
Buffalo, New York 14240-0044
Telephone: +1.716.852.4400
Fax: +1.716.852.0854
Toll Free: 800.828.7450
www.robertsgordon.com
www.rg-inc.com
P/N 113000NA 09/12 Rev B
Page 2
Page 3
POUR VOTRE SECURITE
Si vous sentez une odeur de gaz:
1. Ouvrez les fenêtres.
2. N’essayez PAS d’allumer un appareil.
3. N’utilisez PAS d’interrupteurs
électriques.
4. N’utilisez PAS de téléphone dans votre
bâtiment.
5. Eteignez toute flamme nue.
6. Quittez le bâtiment.
7. Après avoir quitté le bâtiment, appelez
immédiatement votre fournisseur local
de gaz.
Suivez les instructions du fournisseur
de gaz.
8. Si vous ne pouvez pas joindre votre
fournisseur de gaz, appelez le service
d’incendie.
®
Combat
UHD-Series
Appareil de chauffage conduit à
échangeur tubulaire
AVERTISSEMENT
Risque d’incendie
Garder tous les objets, liquides ou vapeurs
inflammables à la distance minimale de
l’unité de chauffage requise avec les
matériaux combustibles.
Certains objets prendront feu ou exploseront
s’ils sont placés à proximité de l’unité de
chauffage.
Le non respect de ces instructions peut
entraîner la mort, des blessures corporelles
ou des dommages matériels.
(Gamme compacte)
Manuel d’installation,
d’operation, et de service
Modèles UHD[X][S]
75, 100, 125
AVERTISSEMENT
L’installation, le réglage, la modification, la réparation ou
la maintenance inadapté peut entraîner la mort, des
blessures ou des dommages matériels. Lire attentivement
le manuel d'installation, d'utilisation et d'entretien avant
d’installer ou de réparer cet équipement.
L’installation doit être effectuée par un entrepreneur
qualifié dans l'installation et l'entretien d'appareils de
chauffage au gaz ou par votre fournisseur de gaz.
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Roberts-Gordon LLC.
Figure 18: LED Diagnostic Codes...........................................29
Page 8
Page 9
SECTION 1: HEATER SAFETY
Yo ur Safety is Important to Us!
This symbol is used throughout
the manual to notify you of
possible fire, electrical or burn
hazards. Please pay special
attention when reading and
following the warnings in these
sections.
Installation, service and, at a
minimum, annual inspection of heater must be done
by a contractor qualified in the installation and
service of gas-fired heating equipment.
Read this manual carefully before installation,
operation or service of this equipment.
Heaters are not approved for residential
installations. These instructions, the layout drawing,
local codes and ordinances and applicable
standards that apply to gas piping, electrical wiring,
venting, etc. must be thoroughly understood before
proceeding with the installation.
Protective gear is to be worn during installation,
operation and service. Thin sheet metal parts,
including the various venting components, have
sharp edges. To prevent injury, the use of work
gloves is recommended.
SECTION 1: HEATER SAFETY
1.2 Safety Labels and Their Placement
Product safety signs or labels should be replaced by
the product user when they are no longer legible.
Please contact Roberts-Gordon LLC or your
®
ROBERTS GORDON
independent distributor to
obtain replacement signs or labels. See Page 2, Figure 1through Page 3, Figure 2.
1.3 California Proposition 65
In accordance with California Proposition 65
requirements, a warning label must be placed in a
highly visible location on the outside of the
equipment (i.e. near equipment's serial plate). See
label placement drawing on Page 2, Figure 1 through Page 3, Figure 2 for label location. Avoid
placing label on areas with extreme heat, cold,
corrosive chemicals or other elements. To order
additional labels, please contact Roberts-Gordon
LLC or your ROBERTS GORDON
®
independent
distributor.
Before installation, check that the local distribution
conditions, nature of gas and pressure and
adjustment of the appliance are compatible.
This heater must be applied and operated under the
general concepts of reasonable use and installed
using the best building practices.
This appliance is not intended for use by persons
(including children) with reduced physical, sensory
or mental capabilities, or lack of experience and
knowledge, unless they have been given
supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they
do not play with the appliance.
For additional copies of the Installation, Operation
and Service Manual, please contact RobertsGordon LLC.
1.1 M anp o wer Re q uirements
To prevent personal injury and damage to the
heater, two persons will be required for installation.
1 of 47
Page 10
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
Fire Hazard
Some objects can catch fire or explode when placed close
to heater.
Keep all flammable objects, liquids and vapors the
required clearances to combustibles away from heater.
Refer to installation manual for clearances and proper
installation.
ATTENTION
Electrical Shock Hazard
Disconnect electrical power before servicing.
This appliance must be grounded.
Explosion Hazard
Connect fuel supply according to installation manual.
Improper installation can cause fuel leak.
Failure to follow these instructions can result in death, injury or property damage.
Le non-respect de ces instructions peut entraÎner de la mort,
des blessures ou des dégâts matériels.
Risque d'Incendie
Certains objets peuvent s'enflammer ou s'exploser quand
ils se trouvent près de l'appareil de chauffage.
Eloigner tout objet, liquide, ou vapeur inflammable de
l'appareil de chauffage. Les distances minimales de
dégagement par rapport aux matériaux combustibles
doivent être impérativement respectées.
Reférer au manuel d'installation pour les distances de
dégagement et les instructions pour un installation
correct.
Risque de Choc Electrique
Débrancher le courant électrique avant toute
intervention.
Cet appareil doit être mis à la terre.
Risque d'Explosion
Le service de gaz doit être connecté selon le manuel
d'installation.
Un installation incorrect peut causer une fuite de gaz.
Lighting and Operation Instructions located on the other side of this panel.
Les instructions d'allumage et d'operation sont situées à l'autre côté de
ce panneau.
This heater must be installed in accordance with the manufacturer's
instructions and local codes. In the absence of local codes, follow
the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 or the CAN/CSAB149 installation code.
Cet aérotherme doit être installé en accord avec les instructions du
fabricant et les régulations locaux. S'il n'y a pas des régulations locaux,
l'installation doit être en accord avec le Code National de Gaz de Carburant,
ANSI Z223.1 / NFPA 54 ou le Code d'Installation, CAN/CSA-B149.
Improper installation, adjustment, alteration, service or maintenance
can result in death, injury or property damage. Read the Installation,
Operation and Service Manual thoroughly before installing or
servicing this equipment.
Installation, modification, réglage ou maintenance incorrectes
peuvent provoquer de la mort, des blessures ou des dégâts
matériels. Liser attentivement le manuel d'installation, d'operations
et d'entretien avant l'installation ou l'entretien de cet équipment.
A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplie
r from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repai
r may result in a
fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to
inspect the appliance and to replace any part of the control system and any gas control which
has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device. Do not try to light the burner by hand.
5. Remove control access panel.
6. Push in gas control knob slightly and turn clockwise to "OFF".
NOTE: Knob cannot be turned to "OFF" unless it is pushed in slightly.
Do not force.
7. Wait five (5) minutes to clear out any gas. Then smell for gas i
ncluding near
the floor. if you smell gas, STOP! Follow "B" in the safety information above
on this label. If you don't smell gas, go to the next step.
8. Turn gas control knob counterclockwise to "ON".
9. Replace control access panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions "To Turn Off Gas
to Appliance" below on this label and call your service techn
ician or
gas supplier.
TO TURN OFF GAS APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove control access panel.
4. Push in gas control knob slightly and turn clockwise to "OFF".
Do not force.
5. Replace control access panel.
½PSI IN
OFF
ON
A. Cet appareil ne comporte pas de veilleuse. Il est muni d'un dispositif d'allumage qui allume automatiquement
le brûleur. Ne tentez pas d'allumer le brûler manuellement.
B. AVANT DE FAIRE FONCTIONNER, reniflez tout autour de l'appareil pour déceler une odeur de gaz.
Reniflez près du plancher, car certains gaz sont plus lourds que l'air et peuvent s'accumuler
auniveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâitment.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions de fournisseur.
• Si vous ne pouvez pas rejoindre le fournisseur, appelez le ser
vice des incendies.
C. Poussez ou tournez la manette d'admission du gaz qu'à la main; ne jamais utiliser d'outil. Si la manette reste
coincée, ne pas tenter de la réparer; appelez un technicien qualifié. Le fait de forcer la manette ou de la réparer peut
déclencher une explosion ou un incendie.
D. N'utilisez pas cet appareil s'il a été plongé dans l'ea
u, même partiellement. Faites inspecter l'appareil parun
technicien qualifié et remplacez toute commande qui ont été plongés dans l'eau.
INSTRUCTIONS DE MISE EN MARCHE
1. ARRÊTEZ! Lisez les instructions de sécurité sur la portion supérieure de cette étiquette.
2. Appareil pourvu d'un thermostat réglable ou destiné à être utilisé avec un tel dispositif:
Réglez le thermostat à la température la plus basse.
3. Appareil à alimentation électrique externe: Coupez l'alimentation électrique de l'appareil.
4. Fournir des instructions qui indiquent de ne pas te
nter d'allumer la veilleuse de façon manuelle.
5. Si des panneaux ou des pièces de l'appareil doivent être retirés pour atteindre la commande d'admission du gaz, des instructions
doivent indiquer la marche à suivre.
6. Des instructions, et une illustration, doivent être fournies pour la fermeture complète (position OFF) du robinet de l'admissio
n du
gaz. Lorsqu'une rotation est requise, les mots et symboles suivants doivent être utilisés pour indiquer le sens de la rotation.
sens horaire sens antihoraire
7. Attendre cinq (5) minutes pour laisser échapper tout le gaz. Reniflez tout autour de l'appareil, y compris près du plancher, pour déceler
une ode
ur de gaz. Si vous sentez une odeur de gaz, ARRÊTEZ! Passez à l'étape B des
instructions de sécurité sur la portion supérieure de cette étiquette. S'il n'y a pas d'odeur de gaz,
passez à l'étape suivante.
8. Fournir des instructions pour l'ouverture (position ON) du robinet manuel de l'admission de gaz.
9. Le cas échéant, fournir des instructions sur la réinstallation des panneau
x ou pièces d'accès à la
commande d'admission de gaz.
10. Le cas échéant: Mettez l'appareil sous tension.
11. Le cas échéant: Réglez le thermostat à la température désirée.
12. Fournir des instructions donnant les mesures à prendre si l'appareil ne fonctionne pas même si
les instructions ci-dessus ont été respectées ainsi que l'énoncé suivant: Si l'appareil ne se met
pas en marche, suivez les inst
ructions intitulées "Comment couper l'admission de gaz de
l'appareil" et appelez un technicien qualifié ou le fournisseur de gaz. Le fabricant peut spécifier un intervalle plus long.
COMMENT COUPER L'ADMISSION DE GAZ DE L'APPAREIL
1. Le cas échéant: Réglez le thermostat à la température la plus basse.
2. Le cas échéant: Coupez l'alimentation électrique de l'appareil s'il faut procéder à l'entretien.
3. Le cas échéant, fournir des instructions sur la méthode à suivre pour atteindre la commande
d'admission du gaz.
4. Fournir des instructions pour la fermeture complète (position OFF) du robinet manuel de
l'admission du
gaz.
5. Le cas échéant, fournir des instructions sur la réinstallation des panneaux d'accès à la
commande d'admission de gaz.
For Models 30/45 / Pour Modèles 30/45
For Models 60 - 400 / Pour Modèles 60 - 400
ON
OFF
Gas valve shown in
"OFF" position.
Le robinet de
l'admission du gaz
est en la position
OFF.
WARNING
Explosion Hazard
Read instructions completely before operating heater.
Failure to follow these instructions can result in death,
fire, explosion, injury or property damage.
Printed in the U.S.A/Imprimé aux Etats-Unis. P/N 91010425
Some objects can catch fire or explode when placed close
to heater.
Keep all flammable objects, liquids and vapors the
required clearances to combustibles away from heater.
Refer to installation manual for clearances and proper
installation.
ATTENTION
Electrical Shock Hazard
Disconnect electrical power before servicing.
This appliance must be grounded.
Explosion Hazard
Connect fuel supply according to installation manual.
Improper installation can cause fuel leak.
Failure to follow these instructions can result in death, injury or property damage.
Le non-respect de ces instructions peut entraÎner de la mort,
des blessures ou des dégâts matériels.
Risque d'Incendie
Certains objets peuvent s'enflammer ou s'exploser quand
ils se trouvent près de l'appareil de chauffage.
Eloigner tout objet, liquide, ou vapeur inflammable de
l'appareil de chauffage. Les distances minimales de
dégagement par rapport aux matériaux combustibles
doivent être impérativement respectées.
Reférer au manuel d'installation pour les distances de
dégagement et les instructions pour un installation
correct.
Risque de Choc Electrique
Débrancher le courant électrique avant toute
intervention.
Cet appareil doit être mis à la terre.
Risque d'Explosion
Le service de gaz doit être connecté selon le manuel
d'installation.
Un installation incorrect peut causer une fuite de gaz.
Warning Label
Lighting Instructions
Label
Lighting and Operation Instructions located on the other side of this panel.
Les instructions d'allumage et d'operation sont situées à l'autre côté de
ce panneau.
Cut Hazard
Turn off electrical supply before
maintenance.
Fan can start automatically.
Failure to follow these
instructions can result in serious
injury or property damage.
ATTENTION
Risque de Coupure
Couper l'alimentation
électrique
avant l'entretien.
Le ventilateur peut démarrer
automatiquement à tout
moment.
Le non-respect de ces
instructions peut entraîner
desblessures graves ou des
dommages.
WARM AIR MODELS / Chauffages à l'air chaud Maximum Minimum
Models 30-75 Vent Combustion / Air Duct Length 25' (7.6 m) 3' (1 m)
Longeur totale de l'évacuation de gaz ou l'alimentation en air pour les modèles 30 - 75
Models 100-400 Vent Combustion / Air Duct Length 40' (12.2 m) 3' (1 m)
Longeur totale de l'évacuation de gaz ou l'alimentation en air pour les modèles 100 - 400
If using vent lengths greater than 5' (1.5 m), condensation will form in the vent pipe. Insulate the pipe to reduce
formation of condensate. For Category IV appliances, condensate tee and drain must be used. L’emploi d’une
évacuation de gaz de plus de 5' (1.5 m) provoquera la formation de condensation dans le tuyau d’évacuation
de gaz. Isolez le tuyau pour réduire la formation de condensation. Pour les appareils en catégorie IV, un pièce
en T pour la condensation et un tuyau d'écoulement doivent être utilisés
SEE INSTALLATION MANUAL FOR PARTS LIST, METHOD OF INSTALLATION AND FURTHER VENTING DETAILS.
VOIR LE MANUEL D’INSTALLATION POUR PLUS DE RENSEIGNEMENTS.
WARNINGATTENTION
VENT HEATER TO OUTDOORS / ECHAPPEMENT DU BRULEUR A L'EXTERIEUR
VENT LENGTH RE QUIR EME NT / Exigence du Longeur de l'évacuation de Gaz
Heaters must be installed
according to the installation
manual.
Failure to follow these
instructions can result in
death or injury.
Risque d'Oxyde de Carbone
Cet appareil doit avoir un
échappement spécial.
Les aérothermes doivent être
installés selon le manuel
d'installation.
Le non-respect de ces
consignes peut entraîner de la
mort ou des blessures.
Vent to
Outdoors
Label
WARM AIR MODELS / Chauffages à l'air chaud Maximum Minimum
Models 30-75 Vent Combustion / Air Duct Length 25' (7.6 m) 3' (1 m)
Longeur totale de l'évacuation de gaz ou l'alimentation en air pour les modèles 30 - 75
Models 100-400 Vent Combustion / Air Duct Length 40' (12.2 m) 3' (1 m)
Longeur totale de l'évacuation de gaz ou l'alimentation en air pour les modèles 100 - 400
If using vent lengths greater than 5' (1.5 m), condensation will form in the vent pipe. Insulate the pipe to reduce
formation of condensate. For Category IV appliances, condensate tee and drain must be used. L’emploi d’une
évacuation de gaz de plus de 5' (1.5 m) provoquera la formation de condensation dans le tuyau d’évacuation
de gaz. Isolez le tuyau pour réduire la formation de condensation. Pour les appareils en catégorie IV, un pièce
en T pour la condensation et un tuyau d'écoulement doivent être utilisés
SEE INSTALLATION MANUAL FOR PARTS LIST, METHOD OF INSTALLATION AND FURTHER VENTING DETAILS.
VOIR LE MANUEL D’INSTALLATION POUR PLUS DE RENSEIGNEMENTS.
WARNINGATTENTION
VENT HEATER TO OUTDOORS / ECHAPPEMENT DU BRULEUR A L'EXTERIEUR
VENT LE NGT H RE QUIR EMEN T / Exigence du Longeur de l'évacuation de Gaz
A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplie
r from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Neveruse tools. If the knob will not push in or
turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repai
r may result in a
fire or explosion.
D. Do not use this appliance if any part has beenunder water. Immediately call a qualified service technician to
inspect the appliance and to replace any part of the control system and any gas control which
has beenunder water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device. Do not try to light the burner by hand.
5. Remove control access panel.
6. Push in gas control knob slightly and turn clockwise to "OFF".
NOTE: Knob cannot be turned to "OFF" unless it is pushed in slightly.
Do not force.
7. Wait five (5) minutes to clear out any gas. Then smell for gas i
ncluding near
the floor. if you smell gas, STOP! Follow "B" in the safety information above
on this label. If you don't smell gas, go to the next step.
8. Turn gas control knob counterclockwise to "ON".
9. Replace control access panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions "To Turn Off Gas
to Appliance" below on this label and call your service techn
ician or
gas supplier.
TO TURN OFF GAS APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove control access panel.
4. Push in gas control knob slightly and turn clockwise to "OFF".
Do not force.
5. Replace control access panel.
½PSI IN
OFF
ON
A. Cet appareil ne comporte pas de veilleuse. Il est muni d'un dispositif d'allumage qui allume automatiquement
le brûleur. Ne tentez pas d'allumer le brûler manuellement.
B. AVANT DE FAIRE FONCTIONNER, reniflez tout autour de l'appareil pour déceler une odeur de gaz.
Reniflez près du plancher, car certains gaz sont plus lourds que l'air et peuvent s'accumuler
au niveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâitment.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions de fournisseur.
• Si vous ne pouvez pas rejoindre le fournisseur, appelez le ser
vice des incendies.
C. Poussez ou tournez la manette d'admission du gaz qu'à la main; ne jamais utiliser d'outil. Si la manette reste
coincée, ne pas tenter de la réparer; appelez un technicien qualifié. Le fait de forcer la manette ou de la réparer peut
déclencher une explosion ou un incendie.
D. N'utilisez pas cet appareil s'il a été plongé dans l'ea
u, même partiellement. Faites inspecter l'appareil parun
technicien qualifié et remplacez toute commande qui ont été plongés dans l'eau.
INSTRUCTIONS DE MISE EN MARCHE
1. ARRÊTEZ! Lisez les instructions de sécurité sur la portion supérieure de cette étiquette.
2. Appareil pourvu d'un thermostat réglable ou destiné à être utilisé avec un tel dispositif:
Réglez le thermostat à la température la plus basse.
3. Appareil à alimentation électrique externe: Coupez l'alimentation électrique de l'appareil.
4. Fournir des instructions qui indiquent de ne pas te
nter d'allumer la veilleuse de façon manuelle.
5. Si des panneaux ou des pièces de l'appareil doivent être retirés pour atteindre la commande d'admission du gaz, des instructions
doivent indiquer la marche à suivre.
6. Des instructions, et une illustration, doivent être fournies pour la fermeture complète (position OFF) du robinet de l'admissio
n du
gaz. Lorsqu'une rotation est requise, les mots et symboles suivants doivent être utilisés pour indiquer le sens de la rotation.
sens horaire sens antihoraire
7. Attendre cinq (5) minutes pour laisser échapper tout le gaz. Reniflez tout autour de l'appareil, y compris près du plancher, pour déceler
une ode
ur de gaz. Si vous sentez une odeur de gaz, ARRÊTEZ! Passez à l'étape B des
instructions de sécurité sur la portion supérieure de cette étiquette. S'il n'y a pas d'odeur de gaz,
passez à l'étape suivante.
8. Fournir des instructions pour l'ouverture (position ON) du robinet manuel de l'admission de gaz.
9. Le cas échéant, fournir des instructions sur la réinstallation des panneau
x ou pièces d'accès à la
commande d'admission de gaz.
10. Le cas échéant: Mettez l'appareil sous tension.
11. Le cas échéant: Réglez le thermostat à la température désirée.
12. Fournir des instructions donnant les mesures à prendre si l'appareil ne fonctionne pas même si
les instructions ci-dessus ont été respectées ainsi que l'énoncé suivant: Si l'appareil ne se met
pas en marche, suivez les inst
ructions intitulées "Comment couper l'admission de gaz de
l'appareil" et appelez un technicien qualifié ou le fournisseur de gaz. Le fabricant peut spécifier un intervalle plus long.
COMMENT COUPER L'ADMISSION DE GAZ DE L'APPAREIL
1. Le cas échéant: Réglez le thermostat à la température la plus basse.
2. Le cas échéant: Coupez l'alimentation électrique de l'appareil s'il faut procéder à l'entretien.
3. Le cas échéant, fournir des instructions sur la méthode à suivre pour atteindre la commande
d'admission du gaz.
4. Fournir des instructions pour la fermeture complète (position OFF) du robinet manuel de
l'admission du
gaz.
5. Le cas échéant, fournir des instructions sur la réinstallation des panneaux d'accès à la
commande d'admission de gaz.
For Models 30/45 / Pour Modèles 30/45
For Models 60 - 400 / Pour Modèles 60 - 400
ON
OFF
Gas valve shown in
"OFF" position.
Le robinet de
l'admission du gaz
est en la position
OFF.
WARNING
Explosion Hazard
Read instructions completely before operating heater.
Failure to follow these instructions can result in death,
fire, explosion, injury or property damage.
Printed in the U.S.A/Imprimé aux Etats-Unis. P/N 91010425
Risque d'Explosion
Liser ces instructions complètement avant l'opération
de l'aerotherme.
Le non-respect de ces instructions peut entraîner du feu,
de l'explosion, du mort, des blessures ou des dommages.
Pour votre sécurité, liser ces instructions avant l'opération de cet appareil.
Venting Arrangement: For separated combustion units, vent terminal and outside air intake must
be located in the same pressure zone. Optional concentric vent kits may be used. See Installation,
Operation and Service Manual for details and part numbers. Vent heater through wall/roof of
minimum thickness 0", maximum thickness 18".
Arrangement pour Ventilation: Pour les aérothermes à combustion séparée, la conduite de
fumée et la prise d'air doivent être situées dans la même zone de pression. On peut utiliser le
système, concentrique optionel. Voir le manuel d'installation, de fonctionnement et d'entretien
pour les détails et les références de pièce. Ventiler l'aérotherme au t
ravers d'un mur ou d'un toit
avec une épaisseur minimum de 0" et une épaisseur maximum de 18".
*Venting Arrangement
Label
Venting Arrangement: For separated combustion units, vent terminal and outside air intake must
be located in the same pressure zone. Optional concentric vent kits may be used. See Installation,
Operation and Service Manual for details and part numbers. Vent heater through wall/roof of
minimum thickness 0", maximum thickness 18".
Arrangement pour Ventilation: Pour les aérothermes à combustion séparée, la conduite de
fumée et la prise d'air doivent être situées dans la même zone de pression. On peut utiliser le
système, concentrique optionel. Voir le manuel d'installation, de fonctionnement et d'entretien
pour les détails et les références de pièce. Ventiler l'aérotherme au t
ravers d'un mur ou d'un toit
avec une épaisseur minimum de 0" et une épaisseur maximum de 18".
Rating Plate Label
WARNING
This heater must be installed in accordance with the manufacturer's
instructions and local codes. In the absence of local codes, follow
the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 or the CAN/CSAB149 installation code.
Cet aérotherme doit être installé en accord avec les instructions du
fabricant et les régulations locaux. S'il n'y a pas des régulations locaux,
l'installation doit être en accord avec le Code National de Gaz de Carburant,
ANSI Z223.1 / NFPA 54 ou le Code d'Installation, CAN/CSA-B149.
Improper installation, adjustment, alteration, service or maintenance
can result in death, injury or property damage. Read the Installation,
Operation and Service Manual thoroughly before installing or
servicing this equipment.
Installation, modification, réglage ou maintenance incorrectes
peuvent provoquer de la mort, des blessures ou des dégâts
matériels. Liser attentivement le manuel d'installation, d'operations
et d'entretien avant l'installation ou l'entretien de cet équipment.
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
2.2 Corrosive Chemicals
• To install the heater, as well as the gas and
electrical supplies, in accordance with applicable
specifications and codes. Roberts-Gordon LLC
recommends the installer contact a Local
Building Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing
and in the manual together with the cited codes
and regulations to perform the installation.
• To install the heater in accordance with the
clearances to combustibles.
• To furnish all needed materials not furnished as
standard equipment.
Do not use heater in area containing
corrosive chemicals.
Refer to appropriate Material Safety Data
Sheets (MSDS).
CAUTION
Product Damage Hazard
• To plan location of supports, vents and air
intakes.
• To provide access for servicing.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as support for a ladder or
other access equipment and never hang or
suspend anything from heater.
• To ensure there is adequate air circulation
around the heater and to supply air for
combustion, ventilation and distribution in
accordance with local codes.
• To provide a method that ensures that the air flow
through the heat exchanger is
within the
acceptable range indicated on the rating plate
prior to energizing the heater, and that such air
flow continues at least 90 seconds after the
heater is de-energized.
• To ensure the heater is placed in an approved
application.
2.1 Wall Tag
A laminated wall tag is included with the heater as a
permanent reminder of the safety instructions and
the importance of the required clearances to
combustibles. Affix the tag by peeling off the backing
of the adhesive strips on the rear surface and
position the tag on a wall near the heater.
A copy of the wall tag (P/N 91039831) is illustrated
on the back cover.
Know your model number. Model number is found
on the heater and throughout the Installation,
Operation and Service Manual.
Failure to follow these instructions can result
in product damage.
Roberts-Gordon LLC cannot be responsible for
ensuring that all appropriate safety measures are
undertaken prior to installation; this is entirely the
responsibility of the installer. It is essential that the
contractor, the sub-contractor, or the owner
identifies the presence of combustible materials,
corrosive chemicals or halogenated hydrocarbons*
anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical
compounds characterized by the presence of halogen
elements (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning
agents, solvents, etc. If these compounds enter the air
supply of the burner, the life span of the heater compo-
nents will be greatly reduced. An outside air supply must
be provided to the burners whenever the presence of
these compounds is suspected. Warranty will be invalid
if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installations in public garages, aircraft hangars,
etc. may be applicable.
4 of 47
Page 13
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
UHD[X][S] heaters have automatic ignition burners
for ON/OFF operation only.
SECTION 3: CRITICAL CONSIDERATIONS
•Must be installed in a manner which allows
access to all serviceable components. See Page 6, Figure 3 for details.
3.2 Manufactured Units
Gas-fired, power-vented duct furnace with tubular
heat exchanger. Units shall have a minimum of 82%
thermal efficiency. The standard unit shall consist of
a non-separated combustion design with an
aluminized heat exchanger. Design and heat
exchanger alternatives shall be offered as follows:
• Separated Combustion: A separated
combustion unit shall feature an enclosed,
sealed burner box. A piece of flexible air duct
connects this burner box to a flange on the
cabinet. Combustion air should be ducted from
outside the heated space, with the ductwork
connecting to the unit with the use of the flange.
• Stainless Steel Heat Exchanger: A stainless
steel heat exchanger unit shall consist of heat
exchanger tubes, heat exchanger tube supports,
heat exchanger tube plates and vent box
produced of 409 stainless steel.
The use of stainless steel heat exchanger is
recommended when air inlet temperatures are
below 40° F (4.4° C) or temperature rise is less
than 40° F (22.2° C) as condensation may form
on the heat exchanger resulting in corrosion that
may shorten its life.
3.4 Minimum Required Installation Clearances
Clearances around the heater and vent must be as
indicated on Page 6, Figure 3
and Page 14, Figure 8
to ensure access for servicing, and correct
operation.
3.5 Ventilation
It is important to ensure that there is adequate air
space around the heater to supply air for
combustion, ventilation and distribution in
accordance with local and national codes. See Page 12, Section 7.
3.6 Gas Supply
It is important that the gas supply pipe is sized
correctly to provide the inlet pressure as stated on
the heater data plate. The gas supply pipe and
electrical connections must not support any of the
heater's weight. See Page 20, Section 9.
3.7 Electrical Supply
A permanent 120 V /1 Ø/60 Hz electrical supply is
required for the main electrical power. The heater
also requires suitable controls in accordance with Page 22, Section 10.
3.3 Location and Suspension
All models:
•Must be installed indoors.
•Must be installed on the positive pressure side of
the air circulation blower.
•Must be installed in a level position with
horizontal discharge.
• May be mounted on a shelf of non-combustible
material using shelf mounting brackets.(See Page 11, Figure 6and Page 11, Figure 7 for
details.)
• Drop rods must be a minimum of 3/8" diameter
mild steel. Four suspension points (3/8" nuts)
are located on top of the heater.
• May be suspended from above (See Page 10, Figure 5) or from wall brackets of sufficient
strength to support the heater as listed in the
Technical Data Table on Page 45, Section 16.2.
3.8 Vent
Choose heater orientation to allow for proper
location of the vent. Each heater must be fitted with
a correctly sized sealed vent system.
If vented horizontally, no other appliance may be
connected to the vent. See Page 12, Section 7.
5 of 47
Page 14
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
WARNING
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to
combustibles away from heater.
Some objects will catch fire or explode when
placed close to heater.
Failure to follow these instructions can result
in death, injury or property damage.
Clearance to Vent: 2" (5 cm)
*18" (46 cm) minimum is necessary for
servicing.
SECTION 4: CLEARANCES TO COMBUSTIBLES
4.1 Required Clearances to Combustibles
Clearances are the required distances that
combustible objects must be away from the heater
to prevent fire hazard. Combustible material that
may catch fire include common items such as wood,
paper, rubber, fabric, etc. Maintain clearances to
combustibles at all times for safety.
Clearances for all heater models are located on the
serial plate of the heater and throughout the manual.
Check the clearances on the serial plate to make
sure the product is suitable for your application and
the clearances are maintained. Read and follow the
safety guidelines below:
• Keep gasoline or other combustible material
including flammable objects, liquids, dust or
vapors away from this heater or any other
appliance.
• The stated clearances to combustibles
represents a surface temperature of 90° F
(50° C) above room temperature. Building
materials with a low heat tolerance (such as
plastics, vinyl siding, canvas, tri-ply, etc.) may be
subject to degradation at lower temperatures. It
is the installer's and owner's responsibility to
assure that adjacent materials are protected
from degradation.
•Consult local Fire Marshall, Fire Insurance
Carrier or other authorities for approval of
proposed installation when there is a possibility
of exposure to combustible airborne materials or
vapors.
4.2 Clearances to Combustibles
Clearances must be as indicated on Page 6, Figure
3. If clearances to combustibles are not indicated,
then installation clearances apply.
Figure 3: Clearances to Combustibles
6 of 47
Page 15
SECTION 5: NATIONAL STANDARDSAND APPLICABLE CODES
SECTION 5: NATIONAL STANDARDS AND APPLICABLE CODES
5.1 Gas Codes
The type of gas appearing on the name plate
must be the type of gas used. Installation must
comply with national and local codes and
requirements of the local gas company.
United States: Refer to NFPA 54/ ANSI Z223.1 latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and
Propane Installation Code.
5.2 Aircraft Hangars
Installation in aircraft hangars must be in
accordance with the following codes:
United States: Refer to Standard for Aircraft
Hangars, NFPA 409 - latest revision.
Canada: Refer to Standard CSA B149.1 Natural
Gas and Propane Installation Code.
• In aircraft storage and servicing areas, heaters
shall be installed at least 10' (3 m) above the
upper surface of wings or of engine enclosures
of the highest aircraft which may be housed in
the hangar. The measurement shall be made
from the wing or engine enclosure (whichever is
higher from the floor) to the bottom of the
heater.
• In shops, offices and other sections of aircraft
hangars communicating with aircraft storage or
servicing areas, heaters shall be installed not
less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so
located in all spaces of aircraft hangars that
they shall not be subject to injury by aircraft,
cranes, movable scaffolding or other objects.
Provisions shall be made to assure accessibility
to suspended heaters for recurrent
maintenance purposes.
5.3 Parking Structures and Repair Garages
Installation in garages must be in accordance
with the following codes:
United States: Standard for Parking Structures
NFPA 88A - latest revision or the Code for Motor
Fuel Dispensing Facilities and Repair Garages,
NFPA 30A - latest revision. Canada: Refer to
CSA B149.1 Natural Gas and Propane
Installation Code.
• In accordance with the Standard for Parking
Structures NFPA 88A, heaters must be located
a minimum of 18" (50 cm) below the floor-ceiling
assembly or 18" (50 cm) above the floor.
• In accordance with the Code for Motor Fuel
Dispensing Facilities and Repair Garages,
NFPA 30A - latest revision, heaters must not be
installed less than 8' (2.4 m) above the floor.
5.4 Electrical
The heater must be electrically grounded in
accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
, local ordinances and any special
Code
diagrams furnished.
Canada: Refer to Canadian Electrical Code,
CSA C22.1 Part 1 - latest revision.
5.5 Venting
The venting must be installed in accordance
with the requirements within this manual and
the following codes:
United States: Refer to NFPA 54/ANSI Z223.1 latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natural Gas and
Propane Installation Code.
7 of 47
Page 16
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
5.6 High Altitude
These heaters are approved (without
modifications) for installations up to 2000' (610
m) in US and Canada. Heaters installed above
2000' (610 m) must be de-rated. For
installations above 2000' (610 m) in US, consult
factory for information on burner de-rating. For
installations from 2000' (610 m) to 4500'
(1370m) in Canada, high altitude conversion
kits are available. Heaters installed over 4500'
(1370 m) in Canada are not approved and must
be approved by the local or provincial authority.
8 of 47
Page 17
SECTION 6: DUCT HEATER INSTALLATION
SECTION 6: DUCT HEATER INSTALLATION
6.1 General
To connect the inlet and outlet ducts to the heater,
Duct-Mate or similar flanges may be slid over the
duct connector flanges supplied on the unit and
secured with screws. The connection to the duct
then can be made using the Duct-Mate clips. The
ducts must have removable access panels
upstream and downstream of the heater. These
panels must be of appropriate size and placement
so that smoke or reflected light could be observed to
indicate the presence of leaks in the heat
exchanger. Covers for these openings should be
sealed to prevent leakage.
Any transition into the inlet of the heater should be
smooth, with a taper of no more than 15 degrees. If
elbows are required, they should be of either broad
radius or fitted with properly designed air turns.
Consult a professional to ensure air turns are
properly designed.
The heater must be installed on the positive
pressure side of the circulating air blower. Air flow
through the heater must be as shown on Page 9, Figure 4 and may not be reversed. The air flo
w must
be adjusted such that it is within the acceptable
range shown on Page 9, Section 6.1.3. The
minimum inlet duct lengths shown on Page 9, Section 6.1.1 should be observed. Pressure drop
through the heat exchanger at various air flows is
given on Page 9, Section 6.1.2.
Figure 4: Air Flow Direction
OUTLET DUCT
AIR FLOW
INLET DUCT
6.1.1 Minimum Inlet Duct Length
ModelDuct LengthDuct Size (W X H)
UHD[X][S] 75 32" (81 cm)16 3/4" x 15 7/8" (43 cm x 40 cm)
UHD[X][S] 100 &12537" (94 cm)21 3/4" x 15 7/8" (55 cm x 40 cm)
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
WARNING
Crush Hazard
Use 3/8" threaded rod
minimum.
Failure to follow these
instructions can result in
death, injury or property
damage.
6.2 Shelf Mounting and Suspension
Four suspension points (3/8" nuts) are located on
the top of the heater. Drop rods must be 3/8"
diameter mild steel minimum.
When handling or supporting the heater from below,
ensure that the weight is taken at the support points.
For typical suspension, See Page 10, Figure 5.
For typical shelf mounting on existing shelf, See Page 11, Figure 6.
The gas or electrical supply lines must not be used
to support the heater.
Do not locate the gas or electrical supply lines
directly over the path of the flue products from the
heater.
The heater must be installed in a location that is
readily accessible for servicing.
The heater must be installed in accordance with
clearances to combustibles as indicated on the wall
tag and in this manual.
6.3 Wall Mounting
For typical suspension, See Page 11, Figure 7. Wall
mounted heaters blowing parallel to the wall can
only be installed with the service door away from the
wall.
The wall mou
suitable wall using all mounting holes. Screw sizes
less than 3/8" may not be used. In order for the wall
mounting brackets to adequately carry the weight of
the heater, it must be installed according to best
building practices.
Wall Mou nting Bracket Arm Left111WALL1L1
Wall Mou nting Bracket Arm Right111WALL1R1
Wall Mou nting Bracket Vertical111WALL22
Wall Mou nting Bracket Diagonal111WALL32
5/16" x 3 1/2" Bolt972139256
5/16" Lock Nut with Nylon Insert921140006
5/16" Flat Washer952116006
5/16" Lockwasher964116006
Hardware provided to construct mounting bracket assembly only.
Figure 7: Wall Shelf Mounting and Suspension
SECTION 6: DUCT HEATER INSTALLATION
11 of 47
Page 20
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
WARNING
Carbon Monoxide Hazard
Heaters may be installed
vented or unvented.
Vented heaters must be
vented outdoors.
Unvented heaters must be
installed according to the
installation manual.
Failure to follow these
instructions can result in
death or injury.
SECTION 7: VENTING
7.1 Changing Vent and Air Intake Orientation
The heater is sold with rear horizontal vent and air
intake connections as standard. (Only separated
combustion models have air intake connection). If
vertical vent and air intake connections are required,
follow the instructions on Page 42, Section 15.5.
sheet metal screws.
For single wall venting, pressure sensitive aluminum
tape or silicone sealant must be used to seal all
joints.
Aluminum tape shall have a minimum temperature
rating of 400° F (204° C) and meet SMACNA AFTS100-73 standards. High temperature silicone sealant
must have a minimum temperature rating of 480° F
(250° C).
7.2.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any
forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below,
4' (1.2 m) horizontally from, or 1' (.3 m) above any
door, operable window, or gravity air inlet into any
building.
NFPA 54/ANSI Z223.1 - latest revision, National
Fuel Gas Code specifies a 4' (1.2 m) horizontal vent
terminal clearance from gas and electric meters,
regulators and relief equipment.
7. 2 V e n t in g
This heater must be vented in accordance with the
rules contained in this manual and with the following
national codes and any state, provincial or local
codes which may apply: United States: Refer to
NFPA54/ANSI Z223.1 - latest revision, National Fuel
Gas Code; Canada: Refer to CSA B149.1 Natural
Gas and Propane Installation Code.
Any portion of vent pipe passing through a
combustible wall must have a listed thimble to
conform with the above codes.
The heater may be installed unvented in
certain circumstances according to building
ventilation codes. Refer to the above codes and Page 13, Section 7.4 for further information.
Unvented operation also requires compliance with
the clearances to combustibles given on Page 6, Figure 3.
The bottom of the vent or air intake terminal shall not
be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m)
above grade where located adjacent to public
walkways.
Vent ter m inal must be installed at a height sufficient
to prevent blockage by snow and building materials
protected from degradation by flue gasses.
Vent ter m inal must be beyond any combustible
overhang.
Secure all joints with corrosion resistant #8 x 3/8"
12 of 47
7.2.2 Canadian Req
The vent shall not terminate within 6' (1.8 m) of a
mechanical air supply inlet to any building.
The vent shall not terminate within 3' (.9 m) of a window or door that can be opened in any building,
any non-mechanical air supply inlet to any building,
or of the combustion air inlet of any other appliance.
7.3 Vent Installation
Maintain clearances to combustibles at all times for
safety. Clearances are the required distances that
combustible objects must be away from the heater
to prevent serious fire hazard. See Page 6, Section
4. For vented units, the vent must terminate outside
of the building.
Vents must be fully sealed and correctly sized for
the model. If the vent passes through a wall or
ceiling of combustible material, it must be enclosed
by a listed thimble and be separated from the
thimble by at least a 2" (5 cm) air gap.
For separated combustion models, vents and air
intakes must be a fully sealed system and correctly
sized for the model. Vent should be assembled as
detailed on Page 14, Figure 8 through Page 18, Figure 13. The joints between the vent terminal and
the roof or wall must be properly sealed. If the vent
passes through a wall or ceiling of comb
material, it must be enclosed by a listed thimble and
be separated from the thimble by at least a 2" (5 cm)
air gap.
uirements
ustible
Page 21
SECTION 7: VENTING
WARNING
Carbon Monoxide Hazard
Heaters may be installed
vented or unvented.
Vented heaters must be
vented outdoors.
Unvented heaters must be
installed according to the
installation manual.
Failure to follow these
instructions can result in
death or injury.
Vents and air intakes must be adequately
supported so that the heater does not bear the
weight of the pipes.
For vent termination See Page 14, Figure 8 through
Page 18, Figure 13.
7.3.1 Standard Vented Heaters
(Models UHD[X] 75 - 125)
The vent must be fitted with a low resistance
terminal. See Page 14, Figure 8 through Page 16, Figure 10. Standard vented heaters do not allow
outdoor air intake for combustion air.
The heaters are designed to be installed as
separated combustion heaters. The vent and air
intake are run as separate pipes to the wall or roof
terminals. See Page 17, Figure 11. As an option, the
vent and air intake are run as separate pipes to a
concentric vent box and a concentric vent/air intake
pipe penetrates the wall or roof. See Page 17, Figure 12and Page 18, Figure 13.
For separated combustion installation, the vent and
air intake must be fitted with an individual and
correctly sized sealed system and the vent and air
intake must terminate at approved wall and roof
terminals.
Separated combustion units may not be common
vented. See Page 12, Section 7.
7.4 Unvented Operation
This heater is not approved to be installed in
residential buildings.
For unvented operation in commercial installations,
sufficient building ventilation must be provided in the
amount of 4 cfm per 1000 Btu/h firing rate (United
States); 3 cfm per 1000 Btu/h firing rate (Canada).
7.5 Horizontal Venting
Horizontally vented heaters must be individually
vented.
Vent pipe must be sloped ¼" (.6 cm) downward for
every 1' (.3 m). For vent lengths greater than 5' (1.5
m), condensation will form. Insulation is
recommended and condensation drains may be
desired.
In noncombustible walls only, vent terminal
(P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or
noncombustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
Instead of an insulated vent terminal, a listed thimble
with 2" (5 cm) air gap may be used with a 4" (10 cm)
vent cap (P/N 90502102).
7.6 Vertical Venting
Vertically-vented standard-vented heaters can be
common vented (up to four heaters).
For vent lengths greater than 5' (1.5 m),
condensation will form. Insulation is recommended
and condensation drains may be desired. Venting
through the top of the heater cabinet is not
recommended if vent lengths are longer than
10' (3 m). In this case, vent from the rear of the
heater cabinet then run the vent vertically and use a
condensate drain at the bottom of the vertical vent.
Vent pipe must be sloped 1/4'' (.6 cm) for every
1' (.3 m).
For 4'' (10 cm), an approved vent cap
(P/N 90502102) must be used.
For 6'' (15 cm) common vent, an approved vent cap
(P/N 90502103) must be used.
For common vertical venting of more than two
heaters, See Page 16, Figure 10.
A vent shall not extend less than 2' (.6 m) above the
highest point where it passes through a flat roof of a
building.
7. 7 L en gth Requirements
If using vent lengths greater than 5' (1.5 m),
condensation will form in the vent pipe. Insulation
and additional sealing measures (high temperature
silicone at all seams) are required.
The entire vent should be insulated with foil faced
fiberglass insulation (1/2" thick, 1-1/2# density
minimum).
13 of 47
Page 22
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
7.7.1 Maximum Vent Lengths
Model UHD[X][S] 75, 100, 125Number of Elbows
40 ft (12.2 m)1
35 ft (10.7 m)2
30 ft (9.1 m)3
25 ft (7.6 m)4
20 ft (6.1 m)5
7. 8 Vent Material
Vent material may be single wall 26 ga. (minimum)
galvanized steel or equal thickness stainless steel.
Completely seal all joints, refer to Page 12, Section
7.3.
If penetrating a combustible wall or roof, a listed
thimble with 2" (5 cm) clearance must be used.
Where local codes permit, a single section of type
B-1 vent material may be used at the roof or wall
penetration instead of a thimble. Ensure vent
manufacturer's clearance from vent material is
maintained. Seal annular space of the type B-1 vent
as well as all joints in the remaining vent.
7.9 Replacing an Existing Heater in a Venting
System
When replacing an existing heater in a venting
system, the venting system may not be properly
sized to vent the new heater. The following steps
must be followed with each appliance connected to
the venting system placed in operation, while any
other appliances connected to the venting system
are not in operation.
1. Seal any unused openings in the venting
system.
2. Inspect the venting system for proper size and
horizontal pitch, as required by the NFPA 54/
ANSI Z223.1 - latest revision, National Fuel
Gas Code (US) or Standard CSA B149.1
Natural Gas and Propane Installation Code
(Canada) and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which cou
ld
cause an unsafe condition.
3. Close all building doors and windows and all
doors between the space in which the
appliance(s) connected to the venting system
are located and other spaces of the building.
Tu rn on clothes dryers and any exhaust fans,
such as range hoods and bathroom exhausts
so that they shall operate at maximum speed.
Do not operate a summer exhaust fan. Close
fireplace dampers.
4. Follow the lighting instructions. Place the
appliance being inspected in operation.
Adjust thermostat so that the appliance will
operate continuously.
5. For any appliance having a draft hood, test for
draft hood appliance spillage at the draft hood
relief opening after five minutes of main burner
operation. Use the flame of a match or candle.
6. After it has been determined that each
appliance connected to the venting system
properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace
dampers and any other gas-burning appliances
to their previous conditions of use.
7. If improper venting is observed during any of
the above tests, the venting system must be
corrected by a contractor qualified in the
installation and service of gas-fired equipment
or you
r local gas supplier. If the venting must be
resized, use appropriate tables in (US)
Appendix G of NFPA 54/ANSI Z223.1 - latest
revision, National Fuel Gas Code (US) or
Standard CSA B149.1 Natural Gas and
Propane Installation Code (Canada) to
determine minimum size. All vent corrections
must be in accordance with the appropriate
local codes and the NFPA 54/ANSI Z223.1 latest revision, National Fuel Gas Code (US) or
Standard CSA B149.1 Natural Gas and
Propane Installation Code (Canada).
Figure 8: Vent and Roof Detail
14 of 47
Page 23
Figure 9: Standard Vented Heater - Vertical and Horizontal Vent Termination
ModelVent DiameterPart Number
UHD[X] 75 - 1254" (10 cm)90502102
SECTION 7: VENTING
15 of 47
Page 24
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
Figure 10: Standard Vented Heater - Common Vertical Vent Termination
Requirements:
•Maximum of four heaters can be commonly
vented through the roof.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common
thermostat.
• Connections to a common stack must be
positioned to avoid direct opposition between
streams of combustion gases.
Equipment must have access to
uncontaminated air at all times.
Failure to follow these instructions can result
in death, injury or property damage.
8.1 Separated Combustion Installation
When installed as a separated combustion heater
(UHD[X]S), the air for combustion is drawn in from
outside the building.
SECTION 8: AIR SUPPLY
8.2 Unvented Installation
It is important to ensure that there is adequate fresh
air supply at all times for both combustion and
heating requirements in accordance with local and
national codes.
8.3 Building Ventilation
Where ventilation is required, air must be taken from
an outside point where it is not likely to be
contaminated or obstructed.
8.4 Outside Combustion Air Supply
If outside combustion air supply is required,
separated combustion model (UHD[X]S) heaters
must be used.
Caution: If the building has a slight negative
pressure or corrosive contaminants such as
halogenated hydrocarbons are present in the air, an
outside combustion air supply to the heater is
required. Seal all combustion air pipe joints.
The flexible air duct may have to be insulated to
prevent condensation on the o
outside air terminal must not be more than 1' (31
cm) above the vent terminal.
uter surface. The
8.4.1 Length Requirements
Follow the constraints listed on Page 13, Section 7.7.
19 of 47
Page 28
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
Fire Hazard
Connect gas supply according to Figure 14.
Do not use gas supply pipe and electrical
connections to support the heater’s weight.
Gas can leak if not installed properly.
Failure to follow these instructions can
result in death, injury or property damage.
SECTION 9: GAS PIPING
WARNING
Explosion Hazard
Leak test all components of gas piping
before operation.
Gas can leak if piping is not installed
properly.
Do not high pressure test gas piping with
heater connected.
Failure to follow these instructions can result
in death, injury or property damage.
A gas meter is connected to the service pipe by the
gas supply company. An existing meter should be
checked, preferably by the company, to ensure that
the meter is adequate for the rate of gas supply
required.
Installation pipes must be fitted in accordance with
local and national codes. Pipes of smaller size than
the heater inlet gas connection should not be used.
Gas lines must meet applicable codes:
United States: Flexible stainless steel gas hose
(US models) is certified per the standard for
connectors for gas applications. ANSI Z21.21/CSA
6.10 – latest revision.
Canada: Rubber type 1 gas hose (Canadian
models) is certified as being in compliance with the
20 of 47
standard for elastomeric compostite hose and hose
couplings for conducting propane and natural gas,
CAN/CGA 8.1 – latest revision.
9.1 Connections
Connect the heater to the gas supply ensuring that
the final connections are as follows:
•Gas supply pipe work is run in medium or heavy
gauge tubing in compliance with local and
national codes.
• Meter and service must be large enough to
handle all the burners being installed plus any
other connected load. The gas pipe which feeds
the system must be large enough to supply the
req
uired gas with a maximum pressure drop of
1/2" wc. When gas piping is not included in the
layout drawing, contact the local gas supplier.
• An isolating valve and union connection should
be used and fitted into the supply adjacent to the
heater.
•A minimum 1/8" NPT plugged tapping
accessible for test connection must be installed
immediately upstream of the gas supply
connection to the heater.
•For suspended heaters, an approved metal
flexible connection between the isolating valve
and the heater may be used. To reduce
pressure loss, use one pipe size larger than
the heater gas connection.
IMPORTANT - The complete installation must be
purged and tested for gas soundness in accordance
with local and national codes.
Caution: Do not high pressure (in excess of 1/2 psi
[14" wc]) test the gas piping with the burner
connected. Close manual shut-off valve during any
pressure testing equal to or less than 1/2 psi (14"
wc).
Check the pipe and tubing ends for leaks before
placin
checking for gas leaks, use a soap and water
solution; never use an open flame.
g heating equipment into service. When
Page 29
Figure 14: Gas Connection
• Hold gas
nipple securely
with pipe
wrench when
attaching the
flexible gas
connector.
•Do not twist
flexible gas
connector.
•Ensure all
joints are
gas tight.
• Do not bend
flexible gas
connector
sharply.
CAUTION
Hold gas nipple securely with pip wrench
when attaching flexible gass connector.
Failure to follow these instruction can relsut
in prdouct damage
Product Damage Hazard
SECTION 9: GAS PIPING
21 of 47
Page 30
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be
required to disconnect electric from
equipment.
Equipment must be properly grounded.
Failure to follow these instructions can result
in death or electrical shock.
Electrical
Supply
Terminal
Strip
R
G
W
C
R
W
24 Volt
Thermostat
Gas
Supply
SECTION 10: WIRING
All heater models require constant 120 V/1Ø/ 60 Hz
power supply. Check heater rating plate for electrical
rating for proper circuit sizing. For servicing, a
disconnect switch of proper electrical rating should
be installed in the vicinity of the heater.
All heaters are equipped with thermostat
connections suitable to power a 24 V thermostat.
Heater must be wired and electrically grounded in
accordance with local codes. In the absence of local
codes in accordance with: United States: refer to
National Electrical Code
®
NFPA 70 - latest revision;
Canada: refer to Canadian Electrical Code CSA
C22.1 Part I - latest revision.
10.2 Low Voltage Thermostat with One Heater
10.1 Positioning Thermostats
A room thermostat should be mounted on a
vibration-free wall or column at a height of
approximately 5' (1.5 m) from the floor to measure
the ambient temperature. It should be clear of both
cold drafts and the direct path of warm air from the
heater.
Avoid mounting thermostat on outside walls or in
areas directly exposed to radiant heat or sunlight.
Install wall tag in a visible location near thermostat.
See Page 4, Section 2.1 for wall tag details.
22 of 47
Page 31
10.3 UHD[X][S] Series Internal Wiring Diagram
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater
must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C
(221° F) and 600 V. For supply connections, use No. 14 AWG or larger wires.
BLUE
BLACK
ORANGE
ORANGE
YELLOW
BROWN
WHITE
WHITE
L2
L1
ORANGE
ORANGE
BLACK
BLACK
GREEN
WHITE
BLUE
BLACK
GREEN
BLUE
GREEN
YELLOW
24 VAC
HOT
GROUND
FLAME
BLACK
BLACK
6
3
4
2
1
45
31
SENSE
ELECTRODE
LIMIT SWITCH
PRESSURE SWITCH
GAS VALVE
IGNITION MODULE
TRANSFORMER
LIMIT SWITCH (UHD 300, 350, 400 ONLY)
MANUAL RESET LIMIT SWITCH (UHD 75 ONLY)
THERMOSTAT INPUT: FIELD SUPPLIED
R = 24 VAC TO THERMOSTAT (RED)
G = MANUAL FAN INPUT FROM THERMOSTAT (GREEN)
W = HEAT DEMAND INPUT FROM THERMOSTAT (WHITE)
C = COMMON GROUND TO THERMOSTAT
FLUE
BLOWER
R
G
W
C
ACC
L1
CMB BLOWER
5
SECTION 10: WIRING
23 of 47
Page 32
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater
must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C
(221° F) and 600 V. For supply connections, use No. 14 AWG or larger wires.
FLAME
SENSOR
PRESSURE SWITCH
THERMOSTAT CONNECTION
6
3
4
5
2
1
120 VAC
TRANSFORMER
FLUE BLOWER
GAS
VALVE
ELECTRODE
IGNITION
MODULE
FLAME
SPARK
LIMIT SWITCH
LIMIT SWITCH (UHD 300, 350, 400 ONLY)
MANUAL RESET LIMIT SWITCH
(UHD 75 ONLY)
FLUE BLOWER
10.4 UHD[X][S] Series Ladder Wiring Diagram
24 of 47
Page 33
10.5 Electrical Connection to the Heater
BX Connector
Junction Box
Flexible Conduit
Burner
Connect wires together
with suitable approved
wire connectors.
Green to Ground
White to L2
Black to L1
L1
L2
Ground
Black
White
Green
SECTION 10: WIRING
IMPORTANT: Junction box is not provided with heater.
Conduit can also be attached directly to heater with wire junction made within the heater cabinet.
25 of 47
Page 34
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
Explosion Hazard
Turn off gas supply to
heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric
before service.
Heater must be
connected to a properly
grounded electrical
source.
SECTION 11: OPERATION AND MAINTENANCE
Read this manual carefully before installation,
operation, or service of this equipment. All
components are accessed via the door secured by
sheet metal screws with grounding strap. Opening
the door exposes live electrical connections and hot
components.
11.1 Pre-Start-Up Checks
All pre-start-up checks must be carried out before
lighting the heater.
Ensure that the heater and all controls are suitable
for the gas, pressure and electrical supply to which
they are to be connected.
11.1.1 Electrical Checks
1. Check that all site wiring is connected in
accordance with the appropriate wiring diagram on Page 23, Section 10.3.
11.1.2 Gas Supply
All aspects of the gas installation including the gas
meter must be inspected, tested for gas tightness
and purged in accordance with local and national
codes.
Ensure that the air is fully purged from the heater
inlet pipe up to the main gas valve inlet test nipple.
11.2 Begin Start-Up
11.2.1 Before Operating the Heater
To ensure that all the controls are in safe working
order, operate the heater for the first time with the
isolating gas valve turned off and power supply
turned on.
1. Turn off the isolating gas valve.
2. Turn up the thermostat above room
temperature. The automatic ignition
sequence will now begin as described
on Page 27, Figure 15.
There will be no ignition of the burner and lockout will occur, which proves the controls are operating
correctly.
11.1.3 Mechanical Checks
1. Check that the flue (and air intake for separated
combustion units) is installed in accordance
with the instructions in this manual and local
regulations. See Page 12, Section 7.
26 of 47
Page 35
Figure 15: Automatic Burner Control Sequence
If at any stage the flame fails, the control will retry
for ignition. The control has four trials for ignition
before a one hour lockout.
½PSIIN
C
ON
OFF
Regulator
Outlet
Pressure
Gas Inlet
Inlet Pressure
TOP VIEW
END VIEW
DescriptionPart Number
Gas Valve 75 – 125 NG90032505
Gas Valve 75 – 125 LP90032506
Burner Sequence for Ignition Control
Thermostat 24 V
SECTION 11: OPERATIONAND MAINTENANCE
RUNSTART
SHUT DOWN
Flue Blower
Pressure
Switch
Ignition Spark
Start Gas Valve
Flame Signal
NO
P
C
NC
*Purge time begins at pressure switch change over.
30 Seconds Purge*
ts = 10 Seconds
Required Incoming Signals
Signals Output By Control
Figure 16: Gas Valve for Models UHD[X][S] 75 – 125
30 Seconds Post
27 of 47
Page 36
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
11.2.2 Start-Up the Gas Valve (All Gases)
11.2.2.1 Check Burner Gas Pressure
1. Remove the plug in the outlet (burner) pressure
test point and connect a pressure tap and a
11.3 Complete Start-Up
Ensure that all covers are fitted correctly and all test
points are properly sealed.
manometer.
2. With the burner firing, measure the pressure on
the manometer. To adjust the burner pressure,
remove the regulator cover from the valve and
turn the regulator adjustment screw to set the
required burner pressure as stated in the
Technical Data Table for the correct gas and
model on Page 45, Section 16.3.
11.3.1 Instruction to the User
Explain the controls of the heater to the user
including how to turn it on and off, using the controls
fitted on site.
Give this manual to the u
Ensure that the user is shown and understands the
importance of maintaining clearances to
combustibles on Page 6, Figure 3, installer
IMPORTANT: If the correct burner pressure cannot
be reached, then check the inlet pressure to the
valve with the burner firing. See Technical Data
responsibility on Page 4, Section 2, user
instructions on Page 29, Section 12 and all warnings defined in this manual.
Ta bl e on Page 45, Section 16.3 for inlet pressure
requirement.
Do not continue to adjust the regulator if the
pressure is not changing.
ser.
If the inlet pressure is too low to allow correct burner
pressure setting, then the gas inlet pressure must be
corrected before completing the start-up.
Check Gas Rate
1. Af t e r b urner pressure adjustment, allow the
heater to operate for at least 15 minutes and
then re-check settings. Adjust pressure setting
if necessary.
2. Check gas flow rate at gas meter.
3. Turn off heater and electrical supply.
4. Remove the manometer and refit all covers to
the valve and tighten the screw of the outlet
pressure tap.
11.2.3 Pressure Switch
The pressure switch is factory pre-set for each
model and is not adjustable.
11.2.4 Turning Off the Heater
Set the thermostat to the "OFF" position or lowest
setting and the main burner will stop.
11.2.5 External Controls
External controls may include time switch, interlock
switch, room thermostat and frost thermostat.
Operate each control to ensure that they function
correctly. Set the switches (if fitted) and
thermostat(s) to the users’ requirements.
28 of 47
Page 37
SECTION 12: USER INSTRUCTIONS
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
Explosion Hazard
Turn off gas supply to
heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric
before service.
Heater must be
connected to a properly
grounded electrical
source.
SECTION 12: USER INSTRUCTIONS
The UHD[X][S] Series heaters are fully automatic
and operate from the external controls fitted on site.
The only user control at the heater is the Manual
Reset Limit Switch - See Page 30, Section 12.3.
See Page 41, Figure 15.3 for Manual Reset Limit
Switch location inside control housing.
12.1 Heater Operation
When the heater has been switched on by the
thermostat installed on site, the main burner will
automatically turn on.
The burner control box will control the safe ignition
of the flame.
All heaters require a constant gas and electricity
supply which must not be interrupted during the
normal operation of this heater.
12.2 Common User Controls
12.2.1 Manual Reset Limit Switch
Do not make more than one attempt to
restart the heater if manual reset limit switch
locks out.
The vent or heat exchanger may be blocked.
The fault must be traced and repaired.
Failure to follow these instructions can
result in death, injury or property damage.
The limit thermostat is located inside the access
door of the heater. See Page 41, Section 15.3. This
control protects against excessive heat build-up
inside the burner compartment.
WARNING
Explosion Hazard
29 of 47
Page 38
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
Reset Button
To reset manual reset limit switch, press reset
button. NOTE: To reset, the switch must be cool.
DescriptionPart Number
Manual Reset Limit Switch90412106
Figure 17: Manual Reset Limit Switch
12.3 Lighting Instructions
12.3.1 To Turn On Heater
1. E n s ure that the electrical and gas supplies to
the heater are on. Check that the on site
controls are "ON".
IMPORTANT: The thermostat setting must be above
the ambient temperature for the heater to operate.
12.4.1 Simple Troubleshooting (Burner Faults)
If the burner fails to ignite for any reason, it will retry
for ignition (four trials total). After four unsuccessful
ignition trials, the control will put the heater into
lockout for one hour.
Lockout should not occur during normal operation of
the heater and indicates there is a fault condition
which must be corrected. There is an LED light on
the ignition control that flashes codes to assist in
fault correction. See Page 30, Figure 18 for LED
indication codes.
Figure 18: LED Diagnostic Codes
LED INDICATION FAULT MODE
Slow FlashNormal Operation - No call for heat.
Fast FlashNormal Operation - Call for heat.
2 FlashesIgnition Lockout - No flame detected.
3 FlashesAirflow Fault - Pressure switch open or closed.
4 FlashesTemperature Limit or
Manual Reset Limit Switch Open
5 FlashesFlame Sense Error - Gas valve not energized.
Steady OnInternal Control Failure
2. The automatic firing sequence will begin as
described on Page 27, Figure 15. The heater will now operate automatically under the control
of the on site controls.
12.3.2 To Turn Heater Off
Set the thermostat to the "OFF" position.
The burner will turn off immediately.
To re s t a r t , t urn the thermostat above room
temperature.
12.4 Simple Troubleshooting
Some possible reasons for the heater not operating
are:
1. G a s s upply not "ON".
2. Electricity supply not "ON".
3. The time and/or temperature controls are not
"ON".
4. A limit switch may have operated. This may be
caused by an interruption of the electrical
supply, failure of the distribution fan or vent or
heat exchanger blockage.
If a temperature limit switch persistently trips, there
is a fault which must be investigated by a contractor
qualified in the installation and service of gas-fired
heating equipment.
30 of 47
Page 39
SECTION 13: SERVICING
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
Explosion Hazard
Turn off gas supply to
heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric
before service.
Heater must be
connected to a properly
grounded electrical
source.
SECTION 13: SERVICING
13.1 Servicing Instructions
After start-up, the heater will require maintenance to
be carried out, at a minimum, annually. If the heater
is used in a dirty or dusty area, more frequent
maintenance may be required.
IMPORTANT: After any maintenance or repair work,
always test fire the heater in accordance with the
start-up instructions on Page 26, Section 11 through Page 28, Section 11.3.1 to ensure all safety systems
are in working order before leaving the heater to
operate. Minor faults may be traced by using the
troubleshooting charts on Page 34, Section 14 through Page 38, Section 14.5.
IMPORTANT: Check all gas pipes and pipe joints to
ensure there are no cracks or gas leaks. Any cracks
in the pipes or pipe joints must be repaired.
IMPORTANT: Inspect all suspended components
and hardware. Ensure that they are in good
condition, properly tightened, and corrosion free.
13.2 Burner Maintenance
1. Open the door and remove the burner
compartment cover. See Page 40, Section
15.2.
2. Clean any deposits from the main burner which
may have formed in the injectors or venturi of
the bu
3. Remove the ignition electrode and flame probe.
Check condition of ignition electrode and flame
probe. Clean off any deposits which may have
been formed, check condition of ceramic
rner. See Page 40, Section 15.2.1.
insulators. Replace as required. See Page 41, Figure 15.3.
13.3 Heat Exchanger Maintenance
The heat exchanger will remain clean unless a
problem has developed with combustion. Inspect the
heat exchanger. Look for signs of overheating at the
front tubes which may indicate burner over firing or
persistently low air flows.
13.4 Gas Valve Maintenance
No regular maintenance is required on this device.
To change gas control valves, See Page 39, Section
15.1.
Do not repair or disassemble gas valve.
Replace faulty gas valves with replacement parts
sold and supplied by Roberts-Gordon LLC.
13.5 Flue Blower
The flue blower should not require maintenance.
However, if the air pressure switch is causing burner
lockout, then remove the flue blower from the vent
box by unscrewing the three screws at the mounting
plate. Remove the four scre
mounting plate to the fan inlet (See Page 42, Section 15.5). Ensure that the fan is free to run and
that the fan wheel is clean.
13.6 Venting and Air Intake Pipe
Inspect all venting and air intake pipe. Ensure that
all seams are sealed and suspension points secure.
Repair suspension points if any part of the venting
or combustion air pipe is sagging. Check to make
sure any insulation is not missing or in poor
condition. Replace as required. Check all venting
and air intake components to ensure they are in
good condition, gas tight and corrosion-free.
ws attaching the
31 of 47
Page 40
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
13.7 Maintenance Checklist
Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON
®
equipment must be performed by a contractor
qualified in the installation and service of equipment
sold and supplied by Roberts-Gordon LLC and
conform to all requirements set forth in the
ROBERTS GORDON
®
manuals and all applicable
governmental authorities pertaining to the
installation, service, operation and labeling of the
equipment.
To help facilitate optimum performance and safety,
Roberts-Gordon LLC recommends that a qualified
contractor conduct, at a minimum, annual
®
inspections of your ROBERTS GORDON
equipment and perform service where necessary,
using only replacement parts sold and supplied by
Roberts-Gordon LLC.
Annual Fall Start-upFollow entire start-up procedure at this time and check control settings and
operation.
The Vicinity of the HeaterDo not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 5, Section 3.
Vehicles and Other
Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged in between the heat exchanger tubes.
Immediately remove objects in violation of the clearances to combustibles.
See Page 6, Section 4.
Vent Pipe/TerminalsVenting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
If the vent terminal has a screen built in, remove any dirt, dust or deposits
from the screen.
See Page 19, Section 8.
Cabinet ExteriorAfter installation, touch up scratches. Periodic painting should be done there-
after as required. Warning labels and logo labels should be legible and accu-
rate. Please contact Roberts-Gordon LLC or ROBERTS GORDON
®
independant distributor if you need replacement warning labels or logo labels.
See Page 2, Figure 1through Page 3, Figure 2
32 of 47
Page 41
SECTION 13: SERVICING
Combustion Air Intake
Pipe
Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe,
gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Clean and reinstall as required.
See Page 19, Section 8
Heat ExchangerMake sure there are no cracks.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
Gas Line and Shut-off
Valves
Burner Observation
Window
Flue Blower Scroll, Wheel
Check for gas leaks.
See Page 20, Section 9.
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
and Motor
Inshot Burners and
Orifices
Clear obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Direct-Spark IgniterReplace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8" (3.2 mm).
ThermostatThere should be no exposed wire or damage to the device or wiring.
See Page 22, Section 10.
Suspension PointsMake sure the heater is hanging securely.
Look for signs of wear on the suspension materials or ceiling.
See Page 10, Figure 5.
Silicone TubingEnsure tight, secure fit on all pressure fittings at pressure switch,
burner partition, and blower outlet.
Gas ValveVerify that cap covering pressure regulator adjustment screw is secure and
has not been tampered with.
Verify all wiring connections.
Condensate Drain
Flush drain and clear any obstructions.
(when installed)
DuctworkConsult an indoor air quality professional for proper cleaning procedures.
Air Circulation BlowerFor a complete inspection, refer to the manufacturers installation, operation
and service manual.
Wall TagIf wall tag is present, make sure it is legible and accurate. Please contact
Roberts-Gordon LLC or your ROBERTS GORDON
®
independent distributor if
you need a wall tag. See Page 4, Section 2.1.
33 of 47
Page 42
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
Explosion Hazard
Turn off gas supply to
heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric
before service.
Heater must be
connected to a properly
grounded electrical
source.
SECTION 14: TROUBLESHOOTING
34 of 47
Page 43
14.1 General
Ensure air flow through the
heat exchanger is
appropriate per the rating
plate.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Heater Operating
TROUBLESHOOT ENDS.
No
Replace limit switch.
The limit switch has
tripped. See Manual Reset
Limit Switch section.
No
Use Troubleshooting for
Automatic Ignition Burner
Systems section to test burner.
Has burner “Locked Out”?
Ye s
No
With external controls (i.e.
thermostat) on, does the
burner continue through the
heating cycle?
No
Yes
Does the flue blower run?
No
Use Troubleshooting for
Flue Blower section to test
fan.
Ye s
Ye s
Burner has locked out due
to ignition failure. Use
Trou bleshooting for Automatic
Ignition Burner Systems
section to test burner.
Is ignition control showing a
"2 flashes" LED code?
Ye s
No
Ye s
Fan and limit switch are
operating normally.
Replace temperature limit
switch.
UHD 75: Press in reset
button on manual reset limit
switch. UHD 100 - 125: Wait
10 - 15 minutes for limit
switch to cool. Does fan
stop running?
No
Is ignition control showing a
"4 flashes" LED code?
Ye s
No
Ye s
Turn on supplies.
Are gas & electrical
supplies on?
No
Ye s
START
SECTION 14: TROUBLESHOOTING
35 of 47
Page 44
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Heater Operating
TROUBLESHOOT ENDS.
No
Trace fault in supervision
system. See
Trou bleshooting
for Flame Supervision
System section.
Ye s
Is ignition control showing
a "2 flashes" LED code?
No
Is the flame current at
least 1 μAmp DC when
the flame ignites?
Ignition control faulty;
replace.
See Ignition Control section.
Is ignition lead okay and
connected?
Is spark electrode okay?
Ye s
Replace valve.
Is the gas valve operating?
To test valve, See
Trou bleshooting for Gas
Valves section.
No
Does the flame light?
No
Ye s
Wait 30 - 40 seconds.
Does ignition spark
operate?
No
Ye s
Flue blower faulty;
replace
Burner control faulty or wiring
connections faulty. Repair
or replace as required
Check for too much vent/air inlet duct. Check for blockage in vent and combustion air circuit. Check for faulty air pressure
switch. Check pressure switch hoses for leaks or cracks.
Do not attempt to circumvent pressure switch circuit to
place unit in operation.See Pressure Switch section for details.
Does air pressure switch
change over?
No
Ye s
Is 120 V supply at fan
connections?
Does flue blower run?
No
Ye s
Ye s
No
Ye s
Fan and limit switch are
operating normally.
Replace temperature limit
switch.
UHD 75: Press in reset
button on manual reset limit
switch. UHD 100 - 125: Wait
10 - 15 minutes for limit
switch to cool. Does fan
stop running?
No
Is ignition control showing a
"4 flashes" LED code?
Ye s
No
Ye s
Turn on controls.
Are external controls
(i.e. Thermostat) on?
No
Ye s
Turn on supplies.
Are gas & electrical
supplies on?
Ye s
START
No
For optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon LLC.
Conduct start-up procedure as shown on Page 26, Section 11.
14.2 Troubleshooting For Automatic Ignition Burner Systems
36 of 47
Page 45
14.3 Troubleshooting for Flame Supervision System
NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.
To m e a sure flame current, connect a 0 - 50 μA DC meter in series with the flame probe. If the meter
reads negative values, then reverse the test leads.
START
Connect a DC ammeter in
series with the flame probe.
SECTION 14: TROUBLESHOOTING
Is the flame present and
at least 1 μA DC flame
current?
Ye s
Is there a current flowing in
the flame probe circuit with
no flame present?
No
No
damaged? Is the flame probe
Ye s
damaged or touching earthed
Does “lockout” occur when
there is a flame present?
No
Heater Operating
TROUBLESHOOT ENDS.
Ye s
No
Use General
Trou bleshooting section to
trace the fault.
Is the connecting lead
components?
Is inlet burner gas pressure
correct? Is live and neutral
polarity correct? Is
flame probe circuit correct?
No
Repair or replace as
required.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Ye s
Repair or replace as
required.
Ye s
Replace ignition control.
37 of 47
Page 46
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
Valve faulty.
Replace with one of
correct type.
Fault elsewhere.
Correct pressure problem.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Valve Operating
TROUBLESHOOT ENDS.
No
Yes
Valve or ignition control
faulty. Replace with
one of correct type.
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
No
Ye s
Does gas pressure at outlet
of the valve rise when
valve turns on?
No
Ye s
Is gas pressure at inlet of the
valve correct for gas type?
Note pressure found.
No
Ye s
START
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Blower Operating
TROUBLESHOOT ENDS.
No
Blower motor faulty.
Replace with correct type.
Check blower motor leads
for loose connections.
Correct power
supply problem.
Ye s
START
Does blower turn on and
off while burner is firing
continuously?
No
Ye s
Does flue blower run
automatically when there
is a call for heat?
No
Ye s
For optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon
LLC.
Conduct start-up procedure as shown on Page 26, Section 11.
14.4 Troubleshooting for Gas Valves
14.5 Troubleshooting for Flue Blower
38 of 47
Page 47
SECTION 15: REPLACEMENT PARTS
½PSIIN
C
ON
OFF
Flexible Air Duct
NOTE: Separated combustion
DescriptionPart Number
Gas Valve, NG (Models UHD[X][S] 75 - 125)90032505
Gas Valve, LP (Models UHD[X][S] 75 - 125)90032506
model shown.
SECTION 15: REPLACEMENT PARTS
DANGER
Electrical Shock Hazard
Use only genuine ROBERTS GORDON
Explosion Hazard
®
replacement parts per this installation, operation and
WARNING
Fire Hazard
Carbon Monoxide Hazard
service manual.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
See warnings and notes on Page 31, Section 13
before removing or replacing parts
Burner Components
All serviceable burner parts are accessed by the
door on the side of the heater. Remove the
Replace in reverse order. Verify that the gas flow
direction of the valve is correct. Use a minimum
amount of gas seal on the thread joint. Check that
all the joints are leak free. Reset gas valve. See Page 28, Section 11.2.2.
sheetmetal screws.
15.1 Gas Valve
Remove the gas supply pipe at the heater inlet.
IT IS IMPORTANT THAT ONLY THE CORRECT
GAS VALVE IS USED WHEN REPLACING THESE
CONTROLS.
Follow steps on Page 40, Section 15.2 through
Page 40, Section 15.2.1 to remove gas valve/
manifold.
.
39 of 47
Page 48
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
Remove flexible
air duct from spigot
Viewing port
for flame probe
Flame Probe
Burner
Compartment
Cover
Ignition Electrode
Remove screws and
pull off burner cover
The burner compartment is a sealed
compartment. Following any work,
re-seal the compartment with the
gas pipe rubber seal fully in place
and all screws fitted and tight.
To replace the electrode or flame probe, remove the electrical lead and screw.
Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the
front view of the burner compartment.
SECTION 15: REPLACEMENT PARTS
15.4 Heat Exchanger
The heat exchanger consists of a six-pass design with 1.5" outer diameter [aluminized steel] [409 stainless
steel] tube. The tube plates are made of [aluminized steel] [409 stainless steel]. The tube supports are
made of [galvannealed steel] [409 stainless steel].
41 of 47
Page 50
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
To remove the blower, remove
screws securing the fan and
mounting plate to the vent box.
To remove the blower from the
mounting plate, remove screws.
Refit in reverse order.
To change the vent and air
intake orientation from back to
top, remove the blower and
mounting plate as above.
Remove intake (if applicable)
and exhaust covers from top of
the heater.
Rotate the blower, mounting
plate and gasket clockwise until
the flue adapter lines up with
the top hole. Secure screws.
If applicable, remove the flexible
air duct from the air intake
adapter on the back.
If applicable, remove the air
intake adapter from the back of
the heater and install in the
appropriate hole on top.
Reconnect the flexible air duct.
Install intake and exhaust
covers over the back holes.
NOTE: Separated combustion model shown.
15.5 Flue Blower Vertical Installation
MODELUHD[X][S] 75UHD[X][S] 100UHD[X][S] 125
Flue Blower P/N907104049071040590710405
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED FOR EACH MODEL TYPE
IS USED WHEN REPLACING THESE ITEMS.
Carry out a start-up after working on or changing a flue blower. See Page 26, Section 11.
42 of 47
Page 51
15.6 Pressure Switch
SECTION 15: REPLACEMENT PARTS
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure
switch for model. The pressure switches are color coded for each pressure setting.
Carry out a start-up after working on or changing a pressure switch. See Page 26, Section 11.
MODELUHD[X][S] 75UHD[X][S]100UHD[X][S] 125
Pressure Switch Kit P/N
Color Code
Set Point in wc
Pressure Switch Snap Ring P/N
904398109043981090439803
blackblackgray
.35.35.41
904398509043985090439850
15.7 Ignition Control
The control mounts to the heat exchanger plate. Pull out ignition cable and wiring from board, noting their
positions. Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition cable
and all other wiring.
15.8 Limit Switches
15.8.1 Removal and Replacement
1. Remove the electrical connections to the switch.
2. Unscrew the two screws securing the switch.
3. Fit a new switch with two screws.
4. Reconnect the electrical connections and test operation.
43 of 47
Page 52
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
SECTION 16: SPECIFICATIONS
16.1 Dimension Data
TOP VIEW
F
E
F
T
REAR VIEW
B
D
4 x 3/8" Captive Nuts
Provided
Air Intake
UHD[X]S
(
N
Q
P
R
Optional Position)
Flue
(Optional Position)
only;
Duct Flange
F
SIDE VIEW
C
G
Air Intake
Flue
J
M
T
H
(UHD[X]S only)
Thermostat
Connection
UHD[X][S]
75
UHD[X][S]
100
UHD[X][S]
125
Gas Supply
K
Electrical
Supply
S
S
L
A
ModelABCDEFGHJKLMNPQRST
in
28.5
17.6
20.3
17.6
16.6
1. 2 5
6.3
6.1
2.8
1. 6
3.4
6.7
18.2
5.5
4.4
6.8
(cm)
in
(cm)
in
(cm)
72.4
28.5
72.4
28.5
72.4
44.7
22.6
57.4
22.6
57.4
51.6
20.3
51.6
20.3
51.6
44.7
17.6
44.7
17.6
44.7
42.2
16.6
42.2
16.6
42.2
3.2
1. 2 5
3.2
1. 2 5
3.2
16.0
7. 0
17.8
7. 0
17.8
15.5
6.0
15.2
6.0
15.2
7. 1
2.4
6.1
2.4
6.1
4.1
1. 6
4.1
1. 6
4.1
8.6
3.4
8.6
3.4
8.6
17.0
6.7
17.0
6.7
17.0
46.2
18.2
46.2
18.2
46.2
14.0
6.3
16.0
6.3
16.0
11.2
4.4
11.2
4.4
11.2
17.3
6.8
17.3
6.8
17.3
1. 8
4.63281.3
1. 8
4.63794
1. 8
4.63794
44 of 47
Page 53
SECTION 16: SPECIFICATIONS
16.2 General Technical Data Table
ModelUHD[X][S] 75UHD[X][S] 100UHD[X][S] 125
Full Load Amps @ 120 VA122
Minimum Air VolumeCFM8509501020
Te m pe r a t ure Rise @ Minimum Air Volume°F (
Heat Exchanger Pressure Drop @ Minimum Air Volumein wc0.060.050.06
Maximum Air VolumeCFM265036604750
Te m pe r a t ure Rise @ Maximum Air Volume°F (
Heat Exchanger Pressure Drop @ Maximum Air Volumein wc0.360.550.98
Recomended Mounting Height to Heater Baseft (m)12 (3.66)20 (6.10)20 (6.10)
°C)
°C)
68 (37)78 (43)92 (51)
22 (12)22 (12)20 (11)
*Do not exceed the maximum length of flue stated or heater may not operate properly.
16.3 Technical Data Table
ModelUHD[X][S] 75UHD[X][S] 100UHD[X][S] 125
Total Inp ut(Btu/h) x (1000)75100125
Total Output(Btu/h) x (1000)61.582102.5
Efficiency%82-All models
Natural Gas (G20) Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.
Burner Pressurein. wc3.52.6 3.3
LPG / Propane (G31) Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.
Burner Pressurein. wc10.09.1 10.0
45 of 47
Page 54
UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATIONAND SERVICE MANUAL
46 of 47
Page 55
SECTION 17: ROBERTS GORDON® COMBAT® UHD-SERIES WARRANTY
SECTION 17: ROBERTS GORDON
®
COMBAT® UHD-SERIES WARRANTY
ROBERTS-GORDON LLC WILL PAY FOR:
Within 24 months from date of purchase by buyer or 27
months from the date of shipment by Roberts-Gordon
LLC (whichever comes first), replacement parts will be
provided free of charge for any part of the product which
fails due to a manufacturing or material defect.
Roberts-Gordon LLC will require the part in question to
be returned to the factory. Roberts-Gordon LLC will, at its
sole discretion, repair or replace after determining the
nature of the defect and disposition of part in question.
ROBERTS GORDON
®
Replacement Parts are warranted
for a period of 18 months from date of shipment from
Roberts-Gordon LLC or the remaining ROBERTS
GORDON
®
COMBAT® UHD-Series warranty.
ROBERTS-GORDON LLC WILL NOT PAY FOR:
Service trips, service calls and labor charges.
Shipment of replacement parts.
Claims where the total price of the goods have not
been paid.
Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the
ROBERTS GORDON
®
COMBAT® UHD-Series in any
way.
• Use of the ROBERTS GORDON
®
COMBAT® UHD-
Series for other than its intended purpose.
• Incorrect gas or electrical supply, accident, fire, floods,
acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or
accessories not specified by Roberts-Gordon LLC.
• Failure to install or maintain the ROBERTS GORDON
COMBAT
®
UHD-Series as directed in the Installation,
Operation and Service manual.
• Relocation of the ROBERTS GORDON
®
COMBAT®
UHD-Series after initial installation
• The use of the ROBERTS GORDON
®
COMBAT®
UHD-Series in a corrosive atmosphere containing
contaminants.
• The use of the ROBERTS GORDON
®
COMBAT®
UHD-Series in the vicinity of a combustible or
explosive material.
• Any defect in the ROBERTS GORDON
®
COMBAT®
UHD-Series arising from a drawing, design, or
specification supplied by or on behalf of the
consumer.
• Damage incurred during shipment. Claim must be
filed with carrier.
WARRANTY IS VOID IF:
The ROBERTS GORDON® COMBAT® UHD-Series is not
installed by a contractor qualified in the installation and
service of gas-fired heating equipment.
Yo u cannot prove original purchase date and required
annual maintenance history.
The data plate and/or serial number are removed,
defaced, modified or altered in any way.
The ownership of the ROBERTS GORDON
®
COMBAT®
UHD-Series is moved or transferred. This warranty is
nontransferable.
Roberts-Gordon LLC is not permitted to inspect the
damaged controller and/or component parts.
READ YOUR INSTALLATION, OPERATION AND
SERVICE MANUAL
If you have questions about your controller, contact your
installing professional. Should you need Replacement
Parts or have additional questions, call or write:
Roberts-Gordon LLC
1250 William Street
P. O . B o x 4 4
Buffalo, New York 14240-0044
+1.716.852.4400
On the web at:
www.robertsgordon.com
www.rg-inc.com
Roberts-Gordon LLC' liability, and your exclusive
remedy, under this warranty or any implied warranty
(including the implied warranties of merchantability
and fitness for a particular purpose) is limited to
providing replacement parts during the term of this
warranty.
Some jurisdictions do not allow limitations on
how long an implied warranty lasts, so this limitation may
not apply to you. There are no rights, warranties or
conditions, expressed or implied, statutory or otherwise,
other than those contained in this warranty.
Roberts-Gordon LLC shall in no event be responsible
for incidental or consequential damages or incur
liability for damages in excess of the amount paid by
®
you for the ROBERTS GORDON
Series. Some jurisdictions do not allow the exclusion or
®
COMBAT® UHD-
limitation of incidental or consequential damages, so this
limitation or exclusion may not apply to you. This warranty
gives you specific legal rights, and you may also have
other rights which vary from jurisdiction to jurisdiction.
Roberts-Gordon LLC shall not be responsible for failure to
perform under the terms of this warranty if caused by
circumstances out of its control, including but not limited
to war, fire, flood, strike, government or court orders, acts
of God, terrorism, unavailability of supplies, parts or
power. No person is authorized to assume for RobertsGordon LLC any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF
REPRESENTATIVES:
No representative of Roberts-Gordon LLC, other than an
Executive Officer, has authority to change or extend these
provisions. Changes or extensions shall be binding only if
confirmed in writing by Roberts-Gordon LLC's duly
authorized Executive Officer.
Model#:_______________________ Serial #:___________________________ Fuel:____________ Installation Date:__________
Type of Installation (check one):
o Automotive o Manufacturing o Warehouse o Recreational o Aircraft
o Public Building o Office o Retail o Agricultural o Other______________
Mail or Fax to:
Roberts Gordon LLC • 1250 William Street, P.O. Box 44 • Buffalo, NY 14240-0044 • Phone: 716-852-4400 • Fax: 716-852-0854
Toll Free: 800-828-7450 • www.rg-inc.com
Installation Code and Annual Inspections: All installation and service of ROBERTS GORDON® equipment must be performed by a
contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon LLC and conform to all
requirements set forth in the ROBERTS GORDON
®
manuals and all applicable governmental authorities pertaining to the
installation, service, operation and labeling of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon
LLC recommends that a qualified contractor conduct, at a minimum, annual inspections of your ROBERTS GORDON
®
equipment
and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon LLC.
Further Information: Applications, engineering and detailed guidance on systems design, installation and equipment performance is
available through ROBERTS GORDON
®
representatives. Please contact us for any further information you may require, including
ny form or by any means – graphic, electronic, or mechanical, including photcopying,
recording, taping, or information storage and retrieval systems – without written permission of Roberts Gordon LLC.
Printed in the U.S.A.
Warm Air Heating
Page 58
Page 59
Page 60
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.