This manual accords with current technology at the time of writing. As the printed version is not regularly updated, please obtain
the latest version before using it, by downloading from www.robatherm.com or on request from robatherm.
The copyright to this work, including all illustrations, is reserved. No use which exceeds the limits of copyright law is allowable
without our permission, and such use will be prosecuted. This applies, in particular to duplication, translation, microfilming and
storage and processing in electronic systems.
Subject to modifications.
=== Ende der Liste für Textmarke Inhalt3 ===
04 / 2015
Page 3
Contents
Introduction 1
General 1
Safety Instructions 3
Emergency Provisions 4
Maintenance and Cleaning Instructions 4
Installation RMC / RZ / RM / RL 6
Delivery 6
Unloading and Transport 6
Assembly and Installation 8
Sealing of the Roof of Weatherproof Units 17
Commissioning and Maintenance 19
Damper 19
Fan and Motor 21
Filters 28
Silencer 30
Heating Coil (Hot Water, Steam) 31
Electric Heater 35
Cooling Coil (CW – DX Coil) 37
Refrigeration Installations and Heat Pump 40
Rotary Heat Exchanger 42
Plate Heat Exchangers 45
Heat Pipe 46
Desiccant Rotor 47
Combustion Chamber 49
Gas Surface Burner 53
Spray Humidifier 58
High Pressure Spray Humidifier 64
Pressure Relief Damper 66
Controlling Systems 68
Hydraulic Set 71
These installation, commissioning and maintenance instructions must be read and
observed by all people who carry out work on the unit. For components which are not
described, the individual instructions are to be observed (request if required).
robatherm will not be held liable for damage or faults which result from non-observance of
these instructions.
The manufacturer’s warranty and the certificate of installation/conformity do not apply for
unofficial or unapproved conversions and changes to the appliance.
Use for Intended Purpose
The unit supplied by robatherm must only be used for air handling. This includes filtering,
heating, cooling, humidifying, dehumidifying and transporting of air. robatherm expressly
forbids any other use.
Units with the „Ex“-mark (subsequently described as ATEX-units) are to be used in
accordance with the unit identification on the nameplate and on the technical data sheet in
accordance with the ATEX directive. Be sure to observe any restrictions on use.
The requirements of mechanical equipment rooms must be observed in accordance with the
VDI 2050 for operations and maintenance. This also includes sufficient maintenance space,
ventilation as well as compliance with the temperature and humidity requirements.
In front of heating and cooling coils, it is recommended to allow an obstacle-free area, at
least as wide as the AHU’s depth for maintaining those coils.
Transport and Storage
All units and components must be transported and stored in such a way that damage,
adverse effects through weather factors, condensation (ensure sufficient rear ventilation
within the packaging) or contamination are avoided. When storing for over 3 months, loosen
belt drives and turn rotating components such as e.g. on ventilators, motors, pumps, HRS
rotors on a monthly basis.
Installation
If units are supplied in separate sections, these shall be assembled in accordance with these
assembly instructions and professionally connected to the ductwork. All protective devices
shall be applied.
The person responsible for assembly on site and changing non-runable components to
complete ready to operate units is also responsible for issuing the certificate of conformity
and the CE marking.
Before Commissioning
The unit can only be taken into operation if it has been assembled in accordance with these
instructions. All protective devices must be effective. A lockable service switch must be
installed near the fan unit access door.
Possible spreading of fire between supply- and exhaust air sections of the AHU (e.g. via the
heat recovery system or recirculating air) must be prevented by appropriate precautionary
measures in the building site’s system (e.g. fire dampers) by others.
A possibly required down gradient grid, according to DIN EN 1886 and AHU-Guideline 01,
must be installed within the system to prevent any carry-over of flammable parts from filters,
mist eliminators or contact humidifiers into the supply air duct.
Handover
AHUs with integrated control technology may only be taken into operation after to
robatherm’s initial commissioning and after handover and customer’s briefing has been
concluded.
Freeze Protection
In case of ambient temperatures below the freezing point, it can make sense not to switch
down the unit, e.g. in order to prevent dampers from freezing or to avoid any failures during a
later restart.
Serious bodily injuries and even loss of life and material damage can result from nonobservation of the following instructions of the valid national and international safety
regulations.
Even if the unit is switched off, certain regulating functions can lead to sudden switching on
of unit components such as e.g. resumption of power supply, compressor pump-out, fan
overshoot, frost protection, timer programs.
When the fan is in operation, there is perilous voltage on the permanent-magnet
synchronous motor --> danger to life.
Do not commission ATEX units until the following requirements are met:
Conditions of use in accordance with the purpose for which the unit is intended.
No substances nearby that are prone to spontaneous combustion e.g. pyrophoric
substances under EN 1127-1.
Constant and adequate ventilation of the installation site (mechanical equipment room)
in the case of ATEX units without a specified exterior ex zone so that unavoidable
leakage to the exterior of the unit does not result in an explosive atmosphere.
Only enter the unit or work on it when the following conditions are met:
All-pole disconnection of power supply.
Minimum waiting period of frequency converter 15 minutes (due to remaining voltage).
Protected against switching on by installations in accordance with DIN EN 60204 (VDE
0113) (e.g. lockable service switch).
Standstill of all moving parts, especially fan impeller, belt drive, motor, rotary heat
exchanger.
Heat exchanger and hydraulic systems adapted to ambient temperature.
Pressure bearing systems must be free of pressure.
Wear protective clothing.
No explosive atmosphere present. (rinse unit beforehand if necessary)
The following requirements must be met before the unit is switched on:
Protective devices must be fitted and effective in accordance with DIN EN ISO 12100
(e.g. protective grille).
Check that no persons are in the danger area, e.g. inside the unit.
Work must only be carried out by a qualified expert.
The floor loading in the AHU must not exceed 100 kg/m² of floor surface.
Basically, the units’ roof is not designed to any additional load. In case of need, please
contact robatherm directly.
The local fire provisions must generally be complied with. If there is a fire, disconnect all-pole
power supply to the unit immediately. Close dampers and fire dampers in order to stop the
oxygen supply and the spread of fire. Direct fire-fighting and first aid measures immediately.
Inform the fire brigade. Protection of people has priority over protection of property.
Serious damage to health or even loss of life if fire gases are breathed in. In a fire building
materials used may generate toxic substances. Use heavy duty breathing protection!
Serious damage may be caused to health and property by bursting of pressure vessels or
pipelines during a fire. Keep away from danger area!
Pos: 13.4 /Einleitung/Reinigung und Wartung des Gehäuse s @ 0\mod_1256629499461_ 2008.doc @ 2027 @ 4
Equipment
When performing maintenance and cleaning work in explosion hazard zones, only suitable
tools which e.g. prevent sparks may be used in accordance with EN 1127-1 . Conductive
footwear must be used to prevent personnel from accumulating static charge in accordance
with BGR 132.
Maintenance Intervals
AHUs are machines which require regular maintenance. The maintenance intervals given
are approximate and relate to normally polluted air according to VDI 6022. If air is heavily
polluted, the maintenance intervals must be shortened accordingly. Regular maintenance
does not absolve the operator from his duty of care which involves checking the unit for
function and damage on a daily basis.
Cleaning and Maintenance of the Casing (including Pans)
Coarse contamination must be removed dry with an industrial vacuum cleaner.
Other fouling: Use damp cloth; with grease and oil dissolving cleaners if necessary
(neutral cleaner with pH value between 7 and 9 in the concentrate).
To completely clean pans with limited accessibility, (eg. under coils) obstructive elements
might have to be disassembled prior to cleaning.
Treat galvanized parts with preservative spray.
All moving parts such as door handles, hinges must be treated with lubricating spray
regularly.
Check sealings, especially door sealings regularly for damage and function.
Immediately eliminate damage to the coating or traces of corrosion by using touch up
paint.
Remove pollution and dirt in gaps or grooves using damp cloth with applicable cleansers
To prevent danger of ignition due to electrostatic charge, all surfaces of ATEX units may
only be cleaned with a damp cloth.
Disinfectants
Only use disinfectants with an alcohol base with country specific approval (e.g. RKI, VAH,
DGKH).
Recommissioning
After carrying out maintenance or disinfecting measures, ensure the unit is sufficiently clean
before returning to operation. Toxic or odorous substances must not come into the supply
air.
Leak Test
In clean areas where there must be no transfer of particles from exhaust air to supply air, the
relevant parts must be tested for leakage annually or following any servicing (e.g. by means
of a suitable test gas). Observe manufacturer’s safety instructions! If necessary take suitable
measures to eliminate any leaks in consultation with the manufacturer.
Supply of Spare Parts / Customer Service / Repair
Changes to the unit must only be carried out by qualified personnel. After carrying out
changes (e.g. installation of spare parts) a new assessment of conformity must be carried
out in accordance with the health and safety requirements of the ATEX guideline by a
qualified person with the relevant documentation before the unit is switched back on. Spare
parts must meet the specific requirements of the ATEX classification applied (category,
atmosphere, temperature classification). It is preferable to use identical original
components. If inappropriate changes are made to the unit by third parties, the robatherm
declaration of conformity ceases to apply.
On receipt of the goods they must be checked for damage and completeness. Missing parts
and damage must be noted immediately on the consignment note and be confirmed by the
driver. Details relating to procedures when damage is discovered are noted in detail on the
delivery note. If no such procedures are followed, no liability for defects will be accepted.
Pos: 17.1 /Überschriften/__Entladung und Transpor t @ 0\mod_125734136458 7_2008.doc @ 2038 @ 2
Unloading and Transport
Pos: 17.2 /Montage/Entladung und Transport @ 0\mod_1257 499397431_2008.doc @ 2067 @
Pos: 17.4 /Montage/_Kran-Entladung und Transport @ 0\ mod_1257499685775_2008. doc @ 2069 @ 3
Unloading and Transport by Crane
All units are equipped with lifting eyes or transport loops.
Units without their own base frame are equipped for transportation with expendable pallets.
Only transport unit in usage position (not inclined or lying).
Unloading and transport should preferably be carried out with a crane or fork lift truck.
Caution
Serious bodily damage or material damage may be caused by falling loads.
Observe the safety instructions of the transporting vehicles.
Do not stop under an airborne load!
Only use suitable and approved slinging devices (ropes, chains, lifting belts) for unloading
and transporting the units and only fasten them to the lifting eyes or transportation loops in
accordance with VBG 9a (UVV 18.4).
Unloading by Means of Lifting Eyes (image to left)
Fasten slinging device to lifting eyes. If the angle of inclination between the slinging device
and load is less than 45°, then a lifting harness is to be used.
Unloading by Means of Transport Loops (image to right)
The transport loops must be used for unit parts which are fully mounted on a DIN-frame.
For DIN-frame units with six transport shackles and by means of a suitable onsite lifting
equipment (e.g. cargo gear), it is imperative that an even load distribution on all transport
shackles must be ensured.
Pos: 17.7 /Montage/_Gabelstapler-Entladung und Transport @ 0\mod_125750 0058891_2008.doc @ 2072 @ 3
When unloading and transporting with fork lift trucks, use forks which go fully underneath
the unit. Only transport units on the base frame or on the pallet.
robatherm units must not take on any functions of the building itself.
If a unit is misused, for example by substituting base of unit for building roof or by allocating
static functions to the unit, all warranty obligations on the part of robatherm will lapse.
Observe the notes in VDI 3803.
Foundation
Install units on a firm and flat foundation. Any unevenness, leading to non-parallel frames of
connecting parts, must be flattened out with suitable supports (metal strips or equivalent).
Maximum tolerance to the horizontal is s = 0.5 % (max angle of inclination: 0.3°).
The foundation must conform to the building requirements in terms of statics, acoustics and
proper water drainage (drip pan, air humidifier, etc.). Structural beams must be one single
piece over their entire length. The maximum beam distortion is 1/1000 of the beam length.
The distance between horizontal beams may not exceed 24 modules (2.5 m) (see robatherm
planning recommendations).
The natural frequency of the supporting structure, especially steel supports, must be
separated adequately from the exciter frequency of rotating components of e.g. fans, motors,
pumps, compressors etc,
Standing Safety
Units installed outside must be secured to the foundations in accordance with the expected
wind speed at the place of installation. This applies for all units with integrated motor
extraction device.
Lifting Gear
Only use suitable and permitted lifting gear for assembly. Only apply lifting gear at the top
edge of the base frame to avoid any deformations.
Mechanical Equipment Room
The requirements of mechanical equipment rooms must be observed in accordance with the
VDI 2050 for operations and maintenance. This also includes sufficient maintenance space,
ventilation as well as compliance with the temperature and humidity requirements.
In front of heating and cooling coils, it is recommended to allow an obstacle-free area, at
least as wide as the AHU’s depth for maintaining those coils.
Check arrangement of functional components and unit design in accordance with data sheet
and drawing prior to starting unit installation.
Sound Reduction
In order to adhere to the permissible sound emission values, sound reducing components
are to be installed at suction and pressure points or on the unit housing (e.g. duct sound
damper, sound proofing walls) if they are not or insufficiently integrated into the unit.
Structure Borne Sound Insulation
Unit bases for structure borne sound insulation e.g. Mafund, Silomer or Ilmod Kompri Band
are to be used in a lengthways and downwards direction.
Misalignment of the casing connecting holes through different compression of the decoupling
profile on the basis of weight differences of neighbouring appliance parts must be balanced
out for unit installation e.g. by means of suitable lifting gear.
Lifting Eyes / Transport Loops
Following assembly remove the lifting eyes / transport loops and seal the openings by
means of plugs.
All connecting parts such as screws, sealing tapes and roofing strips (only for weatherproof
units) are included in the units – mostly in the fan unit.
The unit sections are connected by bolts used through the inside. If no access doors are
provided at connection points, the marked covering panels must be removed for better
access.
If unit sections are only accessible from one side, there will be threaded bushes in the frame.
For the stainless steel version only use stainless steel connecting elements.
In order to connect the unit parts, proceed as follows:
Stick self-adhesive sealing along the circumference of the section frame at each division
area of a unit
Note
The sealing must be stuck between the covering panel and the row of holes.
Cut out holes or threaded bushes in the sealing.
If necessary remove marked covering panels.
If necessary press unit parts together with screw clamps.
Connect components.
Refit covering panels which have been removed.
All unit openings (e.g. duct discharge, electrical connecting box etc.) must be sealed or
equipped with weather protection in order to prevent water ingress into the unit. Do not
position the suction and discharge openings in the main wind direction. Plan the installation
height of the unit in accordance with max. snow level. Connected ducts must be drained
professionally on site.
All air ducts shall be installed stress-free. Any flexible connectors must not be extended to
their max length. Adjust its installation length at 100 to 120 mm. Air ducts including
connection profiles and flexible connectors should be professionally insulated and protected
from the elements. Provide the same to the units’ frames.
Flexible Connection
1 – Unit frame, 2 – Flexible connection, 3 – Building duct
Decoupled Section Frame
1 – Unit frame, 2 – Decoupled section frame, 3 – Building duct, 4 – Sealing
To prevent ignition through electrostatic charge all electrically non-conductive connection
points must be by-passed with equipotential bonding, e.g. decoupled section frame, flexible
connections, vibration isolation. All metallic parts of the units must be included in the local
equipotential bonding measures. The unit must be earthed on the base frame in
accordance with current best practice (foundation electrode). For this purpose a bore hole
at the base frame or a rivet on the floor (for units without base frame) is provided for ATEX
units and marked with an earthing sticker. All connections must be secured against coming
loose.
When connecting heating and cooling water piping (inlet and outlet), care must be taken to
ensure that the inlet and outlet connections are not confused (counterflow principle with
water inlet and air outlet side).
Connection of the Heating and Cooling Water Piping – Example
Pos: 29.3 /Sicherheitshinweise/Montage/!Mon tage_Montage&Aufste llung_Anschluss von W ärmeübertragern_Ac htung @ 0\mod_1257770 028125_2008.doc @ 2103 @
Plan and fit pipework to and from the unit so that the heat exchanger is not subject to
stress and strain e.g. as a result of heavy weights, vibration, tensional forces, heat
expansion etc. Use compensators if necessary.
When tightening the threaded connections of the heat exchanger on site use e.g. a pipe
wrench for counter pressure as the inner pipes may otherwise be twisted and damaged.
The pipes must be flanged in such a way that problem free removal of the heat exchangers
for maintenance or exchange purposes is possible.
Connection of Refrigerating Piping
Prior to connection check the heat exchangers and pipes for leaks, i.e. whether the inert gas
charge on the operation side is still under pressure.
Pos: 30.1 /Montage/_Anschluss der Kondensat- sowie Ab- und Überlaufleitungen @ 0\ mod_1257768304534_2 008.doc @ 2090 @ 3
Connection of the Condensate, Discharge and Overflow Piping
Pos: 30.2 /Montage/Anschluss der Kondensat- sowie Ab- und Überlaufleitungen @ 0\ mod_1257770291293_20 08.doc @ 2105 @ 444
Provide all outlets with a siphon (with non-return valve and self-filling device) and remove
waste water appropriately. The height of the siphon must be set in accordance with the low
pressure or overpressure of the ventilation unit so that suction or blowing out of the air in
relation to the connected waste water pipe is prevented.
The water must flow directly from the siphon into a catch pit or funnel. Do not under any
circumstances connect the siphon directly to the sewage network.
Connection Siphon
1 – Opening for recharge, 2 – Do not connect any horizontal extension
Calculation of Siphon Trap
The height of the siphon is determined as follows:
Under pressure in the device:
(mm) = p/10
H
1
H
(mm) = p x 0.075
S
Overpressure in the device:
H
(mm) = 35 mm
1
H
(mm) = (p/10) + 50
S
p = Unit pressure in Pa (always enter positive value)
Electrical work must only be carried out by a qualified expert.
Make sure that the electrical connection of weatherproof units is water tight. Connection
from below or waterproof unions (at least protection rating IP 65, use sealings) with
sufficient cable radius.
Check all electrical connections (switch cabinet, frequency converter, motor etc.) for correct
seating and retighten if necessary (see also DIN 46200).
Electrical components such as electric air heaters, electric motors, actuators, etc. should be
connected and grounded according to manufacturer’s specifications, local electrical
regulations as well as general recommendations concerning the prevention of
electromagnetic interferences (grounding, cable lengths, cable shields, etc.).
The connection tags are attached in the terminal box.
All existing ground straps (equipotential bondings) shall be inspected and, if necessary,
readjusted/retightened.
Electrical safety inspections should take place in accordance with DIN EN 60204 (VDE
0113) and by adhering to all required safety precautions.
The on-site power supply must fulfill the requirements cited in DIN EN 60204, Table 10.
According to nationally valid regulations, the operator is obligated to repeat these inspections
on a regular basis.
In Germany, the periodic intervals of the repeated inspections according to VBG 4 §5 Table
1A (Repeated inspections of stationary electrical units and equipment) must be observed.
Protect motors against overload in accordance with DIN EN 60204 (VDE 0113).
Provide motor protection switch and adjust to the motor nominal current (see nameplate).
A higher set value is not permissible!
Protect motors with integrated PTC thermistor sensors via a PTC release device.
Motors with a nominal power up to 3 kW can generally be switched on directly (observe
power limitations of the responsible energy supply company). For larger motors provide
star-delta circuit or soft start up.
Permanent-magnet synchronous motors must not be operated directly on the net without
extra motor electronic (e.g. appropriate frequency converter) (net-bypass-operation is not
possible).
Motors which are operated in an explosive atmosphere and with a frequency converter must
be equipped with an ATEX tested PTC control element. The correct connection of the motor
and with it the application of a tested monitoring element must be assured by the
customer/operator.
When assembly is complete all components must be inspected for contamination and
cleaned if necessary in accordance with VDI 6022. Metal swarf in particular must be
removed carefully as it can lead to corrosion.
On completion of the assembly work all access doors must be checked for freedom of
movement. Depending on the operating conditions it can be necessary to align the access
doors accordingly. Bolt torque: 3 Nm.
Hinge side (image left): The long holes in the hinge carrier enable vertical alignment of
Lock side (image right): Following alignment of the door leaf on the hinge side, an
the door leaf, the long holes in the hinge bracket allow horizontal alignment.
adjustment of the outer lock may be necessary. For this purpose the ramp of the closing
cam can be adjusted vertically and the closing housing horizontally.
For rotor housings which are supplied separately the rotor housing must be bolted in position
as instructed by the rotor manufacturer prior to installation of thermal mass.
For this it is necessary to lower the upper rotor housing accordingly.
Assembly of Rotors
In case assembly of a rotor is provided by the customer, the client is responsible that the
connection between rotor and unit casing will be professionally made and tightened (e.g.
with elastic joint seal).
Page 21
Installation RMC / RZ / RM / RL
Pos: 37.1 /Überschriften/__Verschließen des Dac hes von wetterfesten Ger äten @ 0\mod_12573413683 37_2008.doc @ 2040 @ 2
The roofs of the weatherproof units are covered with plastic strips.
If units are supplied separately for easier transportation, division areas must be sealed as
instructed in the following work sequence.
The following material is supplied:
Plastic roofing strips.
Solvent welding material (adhesive).
PVC solution (sealing).
Pieces of coated sheet metal for overlaps.
Pos: 37.5 /Sicherheitshinweise/Montage/!Mon tage_Verschließung d es Daches_Sicherheit _Vorsicht @ 0\mod_125801 7181193_2008.doc @ 2142 @
Caution
Solvent welding material and PVC solution are slightly volatile and flammable. The
following regulations are compulsory while using them:
Injuries caused by fire or deflagration! Naked flame and smoking are forbidden.
Damage to health caused by solvent vapours. Avoid inhaling!
Solvent welding material and PVC solution are to be kept in hermetically sealed vessels
and open containers must be used quickly.
Storage must be frost free and protected from light.
Remove lifting eyes and seal hole with plugs (if required shift the base profile in the roof
panel a little).
Laying temperature ≥+10 °C; pre-heat with industrial blower for temperatures <+10 °C.
The roofing strip must be clean and absolutely dry alongside the division area.
Dry damp roofing strips with industrial blow drier.
Place the overlapping pieces (3) on division area (4) above the drip nose and bolt or rivet
Do not grip into damper as there is a danger of crushing to limbs! Protection devices such
as e.g. duct connection, protective grille etc. must be present in accordance with DIN EN
ISO 12100.
Do not switch on fan before checking that the appropriate damper is open or that its
opening is indicated by a position switch Provide a control linkage so that when a damper
closes, the fans affected are switched off immediately.
robatherm accepts no liability for damage due to incorrect operation.
Provide pressure relief dampers to prevent damage from pressure spikes due to fire
dampers in the system.
Do not grip into damper as there is a danger of crushing to limbs! Protection devices such
as e.g. duct connection, protective grille etc. must be present in accordance with DIN EN
ISO 12100.
Serious bodily injuries or even loss of life and material damage can be caused by the
breakage of the impeller. Do not exceed maximum fan speed as per nameplate and
technical data sheet. Do not operate fan if there are abnormal vibrations.
There is a danger of fire through grinding impeller, belt, hot running bearings.
Danger to health through noise (up to approx. 110 dB).
Only use approved parts with ATEX units. All electrical parts must be earthed.
Transportation Safety Device
Remove transportation safety devices (wooden wedges or locking plates) from base frame of
fan. Avoid pulling vibration isolators.
Attention
Before commissioning check unit and duct system for foreign bodies (tools, small parts,
building dust) and clean if necessary.
Rotate impeller by hand to check for free running.
Plug Fans
During transportation the circumferential gap between the impeller and inlet nozzle may
change. Measure the gap width before commissioning. The gap must be the same width
round the whole circumference; if necessary correct the gap at the vibration damper using
lock nut and adjusting nut (1).
The overlap (R) must be about 1% of the impeller diameter.
There is no need to perform this check for an open impeller with flexible connection.
1 – Adjusting/locking nut; S – Gap width; R – Overlap
Drive
Check friction locking of bushes and hubs (see torque settings).
Check V-belt drive and adjust if necessary
Belt tension (see page 26).
Alignment of belt pulleys (tolerance < 0.4°; d.h. < 7 mm/m).
After a running in phase of 1 to 2 hours:
Retighten V-belt (see page 26). When retightening check for exact alignment of the belt
pulleys and adjust if necessary.
Check the securing screws of bushes and hubs for correct seating and retighten if
necessary (see torque settings).
Direction of Rotation
Check fan direction of rotation is in line with direction arrow on casing by switching on the
motor briefly. If the fan rotates in the wrong direction, reverse polarity of the motor in
accordance with the safety regulations.
Current Consumption
After reaching the fan operating speed immediately measure the current consumption of all
three phases with closed inspection openings.
The measurement values must not exceed the rated values on the nameplate (and with it the
motor nominal power) and only vary slightly from one another. If there is a current overload
switch off immediately and check external pressures, airflow rate and rotational speed. If
phase current is unequal, check motor connection.
In order to avoid any vibration fractures, fans may not be operated at unacceptably high
speeds (see below) and also not in the field of the resonance speed (and multiples of it) of
the fan motor system.
Therefore resonance speeds are to be established on commissioning and blanked at the
frequency converter. Rebalance if necessary.
Fans may not be run outside the operating range stated by the manufacturer.
The manufacturer’s acceleration and delay times must be observed.
There is a danger of fire through grinding impeller, belt, hot running bearings.
During work on fan motor assembly, e.g. bearing replacement, fitting of plug fan etc., the
separate assembly instructions must always be followed (ask for them to be forwarded if
necessary!). After this the vibration speed of the unit must be checked, assessed and
balanced if necessary.
Caution
Serious bodily injuries or even loss of life and material damage can be caused by the
breakage of the impeller. Do not operate fan if there are extreme vibrations or unacceptably
high vibration speeds.
The maintenance interval must be shortened accordingly if there is a multi-shift operation
and/or special operating conditions such as fluid temperature > 40 °C, appearance of dust
etc.
If one or more V-belts fail in a multiple groove drive, then a new V-belt set must be fitted.
Prior to fitting the V-belts, the axle base must be reduced so that the belts can be placed in
the grooves without force. Forcible fitting by means of a screwdriver etc. is in any case not
permitted as it can lead to damage.
Caution
Observe general safety instructions on page 3!
Cleaning Agent
Cleaning agent shall have a pH value between pH 7 – pH 9.
Check fan for hygiene, contamination, damage, corrosion and fastening
Check impeller for imbalance and vibrations; balance if necessary
Check bearings for noise, vibration and heat
Check flexible connection for leaks
Check functioning of vibration dampers
Check function of protective devices
Check function of inlet vane control
Check functioning of dehydration equipment
Check gap width of open impellers (see page 21); correct if necessary
Pollution and dirt on flex connector shall be removed with a vacuum cleaner, and, in a
second step, wiped with a with damp cloth
Fan – Maintenance when necessary
Replace bearings (no later than the end of the theoretical service life)
Grease bearing. Follow manufacturer’s instructions!
Clean fan, rectify any damage and corrosion, retighten fastenings
Electric Motor – Periodic Maintenance
Check electric motor for contamination, damage, corrosion, fastening, smooth running,
heating and direction of rotation
Check bearings for noise, vibration and heat
Clean electric motor and rectify any damage and corrosion
Measure tension, current input and phase symmetry
Check firm seating of terminals in terminal block; retighten if necessary
Check protective conductor; retighten or replace if necessary
Check cable rails. Clean it if necessary with vacuum cleaner and, if necessary with damp
cloth
Electric Motor – Maintenance when necessary
Replace bearings (no later than the end of the theoretical service life)
Grease bearing. Follow manufacturer’s instructions!
Belt Drive – Periodic Maintenance
Check belt drive for contamination, damage, wear, tension, alignment of motor and fan
pulley (tolerance < 0.4°; d.h. < 7 mm/m), check function and fastening (see torque
settings)
Check protective device for damage, fastening and functioning
Belt Drive – Maintenance when necessary
Replace belt set
Adjust alignment of motor and fan pulley
Adjust belt tension (see page 26)
Clean belt drive
When removing the motor only use suitable and permitted load bearing equipment. When
using an integrated motor removal device ensure that the unit is sufficiently stable e.g. by
fixing to the foundation.
Shut Down
Remove V-belts for down times of more than 3 months to avoid concentrated stress on
bearings.
Replace bearings before recommissioning if out of operation for periods of one year or
longer, or remove grease if bearings have a regreasing device and grease bearings again.
Observe fan manufacturer's instructions.
The belt tension is measured with a suitable measuring instrument in line with instructions
(e.g. belt pretensioning force measuring instrument) and adjusted. Observe operating
instructions for measurement instrument.
Measure axle base A of the belt pulleys (in metres).
Multiply axle base by 16. The result is the belt deflection (S) in millimetres.
Apply enough force to the belt in the middle of the axle base (A) so that the calculated
deflection is reached.
Measure deflection force.
Compare deflection force (F) with table values.
Set higher values for the start up phase of new drives. Test deflection force (F) after several
hours of operation and adjust if necessary.
4535
4545
5040
5050
A – Axle base; S – Belt deflection; F – Deflection force
Carefully fix filter elements to the frames with tension springs or anchor wailers
respectively, cartridge filters to be fastened to bayonet joints hand tight.
Do not shut or damage filter cartridges.
Check air proof seating of the filter cartridges in the frame.
Only use approved filter media with ATEX units.
Filter Monitoring
In order to check the degree of contamination of the filters (except activated carbon filters),
the fitting of a differential pressure manometer on the access side of the unit is
recommended.
Filter End Resistances
Filter Class Rec. End resistance
G1 - G4
M5 - M6, F7
F8 - F9
E10 - E12, H13
150 Pa
200 Pa
300 Pa
500 Pa
Roll Filter
For roll filters the operating and servicing instructions supplied by the manufacturer must be
followed.
Allergic reactions on the skin, eyes or breathing organs can be caused by contact with filter
dusts. For maintenance and replacement works on filter cartridges wear protective clothing
and, if necessary, a respirator. Avoid contamination of the surrounding area and new filters.
Replacement Filters
Keep at least one set of replacement filters in stock. Store in a dry and dust free area. Avoid
contamination and damage. Do not use filters beyond minimum durability.
Only use approved filter media with ATEX units.
Filters – Periodic Maintenance
Check filter cartridges for hygiene, contamination, odors, damage and corrosion
Particle filters: Check differential pressure with manometer
Activated carbon filters: Usually, it is enough to check the filter’s odor. (For a reliable
determination of the remaining lifetime, the manufacturer may check the filter coal’s
saturation in his lab in order to appoint proper service intervals.) Weighing of the
cartridges does not deliver feasible results, since most of the additional weight is caused
by the air’s humidity.
Check filter seat for leakage
Filters – Maintenance when necessary
Replace filter cartridges immediately if there is noticeable contamination, odor, damage
or leakage, when reaching the recommended end resistance or time interval:
1. Filter cartridge after 12 months at the latest
2. Filter cartridge after 24 months at the latest
An earlier filter change may be essential if building or conversion measures result in
significant strain on the filter or following a hygiene inspection.
The change of single filter elements is only permissible in the case of damage to individual
elements provided that the last change does not date back more than 6 months.
When changing the filter cartridges observe the local environmental protection regulations.
Do not use any hot medium while filling, bleeding air or removing as there is a danger of
scalding.
Caution
To avoid burns, do not touch hot surfaces.
Caution
Avoid any contact with brine while charging or venting. Danger of poisoning and acid burns!
Observe manufacturer’s instructions.
Attention
Do not exceed permissible pressure range (see design data sheet).
To avoid freezing of the heating coil:
Add anti-freeze agent or install frost protection control on air, water or condensate side
depending on unit design.
To avoid any overheating damage to the unit, run steam coil only when fan is running
Provide air flow control or temperature limiter.
Ensure sufficient distance between max. surface temperature of the heat exchanger due to
temperature of the medium and minimum ignition temperature of any flammable mixture
which may be present in accordance with EN 1127.
Inspection
Check inlet outlet connections for function (counter flow principle).
Charging
The system must be rinsed (removal of contaminations) according to VDI 2035 and should
be filled with the heat exchanger fluid named in the design data sheet to the correct
concentration. Water quality to VDI 2035. Too high a concentration of glycol leads to
reduced performance, too low a concentration of glycol can lead to frost damage.
When charging the system according to VDI 2035 the heating coil and the system should be
vented carefully at the highest point of the system. For this purpose open the venting screw
at the top connection or open separate venting screw.
If incorrect venting takes place, heating coils develop air locks which lead to a reduction in
capacity. Recommendation: Venting recovery system (stop-cock with hose nozzle).
After Commissioning
After commissioning check the screw fittings of the flange for leakage and retighten if
necessary (see page 12).
Before starting work allow components to cool/warm up to the ambient temperature.
Caution
Avoid any contact with brine while charging or venting. Danger of poisoning and acid burns!
Observe manufacturer’s instructions.
Heating Coil – Periodic Maintenance
Check heating coil for hygiene, contamination on air side, damage, leaks and corrosion
Vent heating coil
Check inlet/outlet for function
Check frost protection for function (determine anti-freeze concentration or thermostat by
means of cooling spray)
Heating Coil – Maintenance when necessary
Clean the heating coil on the air side (see below), rectify damage, leakage and corrosion
Cleaning
Clean coils already assembled or if not accessible pull them out for cleaning. Contamination
which has been removed must not enter adjoining unit parts. Remove dirt and contaminated
water carefully.
Observe the following points:
Avoid bending plate fins
Blow out with compressed air in the opposite direction
Do not use a high pressure cleaner or a high pressure steam cleaner
Clean with water and low pressure
Cleaning Agents
Use cleaning agents with a pH-value between 7 and 9 if required.
Shut Down
If out of operation for some time, especially if there is a danger of freezing, the heat
exchanger must be emptied completely if no anti-freezing agent was added. For this purpose
remove all purging and discharging screws. Then for complete emptying blow air
(compressed air, fan etc) through each heat exchanger as up to 50% fluid may remain in the
heat exchanger during free purging which results in a higher danger of damage during frost.
Remove brine following manufacturer information.
Shutdown the coil, and drain it.
Remove connection pipe and hydraulic set.
Remove the coil’s front panel (use Torx T25 or screw driver).
(Cooling coil: Remove the condensate backflow preventer sheet.)
Pull out coil to the front side, support coil if necessary.
Check sealings, replace worn out parts.
Reassemble in reverse order.
Only use approved parts with ATEX units. All electrical parts must be earthed.
Safety Temperature Limiter
Each electric heater must be equipped with a fully tested safety temperature limiter with
manual reset. Test function with hot air drier.
Recommendation
Triple thermostat mounted directly downstream from electric heater:
“Fan” setting: 40 °C.
“Safety temperature limiter” setting: 70 °C.
Attention
Electric heaters may only be operated if flow control is present.
Overheating damage may occur to the electric heater, housing and other fitted parts if the
system is run with insufficient cooling (e.g. system switched off at the main switch when the
electric air heater is still on) or in the event of an emergency system shut down triggered by
safety devices.
Flow Control
The airflow is monitored by measurement of the pressure difference at the fan unit, using an
air pressure gauge Functioning must be checked during commissioning.
Current Consumption
The current consumption is to be checked at all phases by measuring all phases.
For rated data see nameplate.
If the rated values are exceeded, the robatherm Technical Service must be informed.
Avoid any contact with brine while charging or venting. Danger of poisoning and acid burns!
Observe manufacturer’s instructions.
Caution
To avoid burns, do not touch hot/cold surfaces.
Attention
Do not exceed permissible pressure range.
To avoid freezing of the cooling coil:
Add anti-freeze agent or mount the cooling coil downstream from the pre-heater.
Inspection
Check inlet outlet connections for function (counter flow principle).
In the case of direct expansion coils, the nitrogen protection gas must escape with a hissing
noise following opening of the heat exchanger connections. Otherwise there is a leakage;
please inform our technical service.
Charging
The system must be rinsed (removal of contaminations) according to VDI 2035 and should
be filled with the heat exchanger fluid named in the design data sheet to the correct
concentration. Water quality to VDI 2035. Too high a concentration of glycol leads to
reduced performance, too low a concentration of glycol can lead to frost damage.
Venting
When charging the system according to VDI 2035 the air cooler and the system should be
vented carefully at the highest point of the system. For this purpose open the venting screw
at the top connection or open separate venting screw.
If incorrect venting takes place, cooling coils develop air locks which lead to a reduction in
capacity. Recommendation: Venting recovery system (stop-cock with hose nozzle).
After Commissioning
After commissioning check the screw fittings of the flange for leakage and retighten if
necessary (see page 12).
Avoid any contact with brine while charging or venting. Danger of poisoning and acid burns!
Observe manufacturer’s instructions.
Caution
To avoid burns, do not touch hot/cold surfaces.
Caution
Before starting work allow components to cool/warm up to the ambient temperature.
Cooling Coil – Periodic Maintenance
Check cooling coil for hygiene, contamination on air side, damage, leaks and corrosion
Vent cooling coil
Check drip pan for contamination, clean if necessary
Check water outlet and siphon function, clean if necessary
Check water level in siphon refill if necessary
Check inlet / outlet for function
Check frost protection for function (determine anti-freeze concentration or thermostat by
means of cooling spray)
Check direct expansion for icing
Cooling Coil – Maintenance when necessary
Clean the cooling coil on the air side (see below), rectify damage, leakage and corrosion
Drop Eliminator – Periodic Maintenance
Check drop eliminator for hygiene, contamination, encrustation, damage, drip erosion and
corrosion
Drop Eliminator – Maintenance when necessary
Clean and service eliminator: Pull out cassette, disassemble and clean profiles
separately; rectify damage and corrosion
Cleaning
Clean heat exchangers already assembled or if not accessible pull them out for cleaning.
Contamination which has been removed must not enter adjoining unit parts. Remove dirt and
contaminated water carefully.
Observe the following points:
Avoid bending plate fins
Blow out with compressed air in the opposite direction
Do not use a high pressure cleaner or a high pressure steam cleaner
Clean with water and low pressure
Cleaning Agents
Use cleaning agents with a pH-value between 7 and 9 if required.
If out of operation for some time, especially if there is a danger of freezing, the heat
exchanger must be emptied completely if no anti-freezing agent was added. For this purpose
remove all purging and discharging screws. Then for complete emptying blow air
(compressed air, fan etc) through each heat exchanger as up to 50% fluid may remain in the
heat exchanger during free purging which results in a higher danger of damage during frost.
Remove brine following manufacturer information.
Disassembly/Reassembly of Coils
Shutdown the coil, and drain it.
Remove connection pipe and hydraulic set.
Remove the coil’s front panel (use Torx T25 or screw driver).
(Cooling coil: Remove the condensate backflow preventer sheet.)
Pull out coil to the front side, support coil if necessary.
Check sealings, replace worn out parts.
Reassemble in reverse order.
Avoid any physical contact with the refrigerant as this may cause frostbite to the skin and
limbs or retinal damage. Use personal protection equipment against effects of refrigerants
VBG 20 (goggles, gloves, etc.)!
Refrigerant (odourless and tasteless) ejects atmospheric oxygen and can cause
suffocation. TLV values (for R407C: 1,000 ppm in 8h) and practical value limit DIN 8960
(for R407C: 0.31 kg/m³ area) must be observed. If refrigerant does escape only enter the
machine room with heavy duty respiratory protective gear. Observe the safety data sheet.
Refrigerants and compressor oil develop toxic, noxious substances in tandem with naked
flame. Do not inhale! Do not smoke in the machine room!
There may be an allergic reaction if compressor oil is touched or swallowed. Avoid physical
contact! Observe safety data sheet.
Only use approved parts with ATEX units. All electrical parts must be earthed.
Attention
Completion and commissioning of refrigeration installations may only be carried out by the
manufacturer or another expert assigned by the manufacturer; maintenance and servicing
work only by qualified personnel.
For all work the requirements of the service booklet (request if required), and the valid
standards and guidelines (e.g. DIN EN 378, BGR 500 and EC-F Gas Directive) must be
adhered to.
Recurring Inspections
According to §15 of the German Industrial Safety Regulation (BetrSichV), the units and unit
parts underlie recurring inspections by an authorized person respectively accredited
inspection agency. Further applicable statutory provisions of the respective location are to be
observed.
Commissioning Requirements
All construction requirements such as access, completed unit and duct installation and
uninterrupted availability of all supply facilities must be met. In addition there must be a
possibility of operating the system in the required working phases.
Basis for Warranty
The basis for the warranty is built on a maintenance contract with a qualified company
specialised in refrigeration engineering together with records of performance of maintenance
work.
Operation of the refrigeration unit is only permissible when the AHU is running.
Breakdowns of faults of the refrigerating unit are displayed on the switch cabinet.
According to the German Industrial Safety Regulation (BetrSichV), such units require special
supervision; including specific operator-related requirements that are to be fulfilled according
to §14 of the German Industrial Safety Regulation. Further applicable statutory provisions of
the respective location are to be observed.
Maintenance and Inspection
For requirements see service booklet for refrigeration installations.
Attention
Only use oil approved by the compressor manufacturer (see information on the
compressor) as there may otherwise be damage to the unit.
Shut Down
For requirements see service booklet for refrigeration installations.
Heed the relevant environmental regulations when disposing of refrigerant or compressor oil.
When current feed is not disconnected at all poles, there is a risk of crushing and scraping
to the limbs through sudden running of the rotor caused by an automatic cleaning run or
automatic re-start after power failure.
Only use approved parts with ATEX units. All electrical parts must be earthed.
Inspection
Before commissioning ensure that no objects obstruct the free running of the rotor. Remove
any foreign bodies and contamination.
Sealing Strips
Check contact pressure of sealing strips. They must be placed as close as possible to the
thermal mass and direct dragging must be avoided even under operating pressure.
Bearing
In principle the bearing of the rotor is aligned in the factory. Depending on installation
conditions some rework may be necessary. Please observe the manufacturer’s instructions.
Drive
Open inspection cover at marked rotor corner and check whether V-belt has enough tension
from tensioning device, shorten V-belt if necessary:
Open hinged lock
Shorten endless belt as required
Close hinged lock
Close inspection cover
As the V-belt is subject to natural stretching, the tension of the V-belt should be regularly
checked in the first 400 operating hours in particular.
Put drive motor into operation. For rotor controller observe the manufacturer’s operating
instructions.
Check pre-defined rotor speed (e.g. 10 rpm for 10 V input signal).
Direction of Rotation
Check rotational direction of rotor (arrow), if necessary change electrical connections of
motor. If a washing zone is installed the storage mass must turn from extract air via the
washing chamber into the supply air.
In order to avoid contamination of the supply air with the extract air, the pressure potential of
the fans should be selected in such a way that the system related leakage from the supply
air side flows into the extract air side.
Adiabatic Humidification of Extract Air
Excessive humidity shall be avoided upstream of the rotor to prevent its matrix from overwetting. If ever possible, permeate from the reverse osmosis should be used to operate the
humidifier.
Zone crossing must be avoided with ATEX units in all circumstances.
When current feed is not disconnected at all poles, there is a risk of crushing and scraping
to the limbs through sudden running of the rotor caused by an automatic cleaning run or
automatic re-start after power failure.
Attention
In order to avoid damage when cleaning, air or water jet should only be directed onto the
surfaces of the heat exchanger at a right angle.
Rotary Heat Exchanger – Periodic Maintenance
Check rotary heat exchanger for hygiene, foreign bodies, contamination, damage and
corrosion
Check sealing strips for contamination, foreign bodies and contact pressure (see above)
Check drive belt for wear and tension, shorten (see above) or change if necessary
Check rotor for imbalance and lateral trueness
Check bearing for incorrect heating, vibrations or running noises and change if necessary
(no later than the end of the theoretical service life)
Check water outlet and siphon function clean if necessary
Check water level of siphon, top up if necessary
Check functioning of rotor control, align sensor if necessary
Rotary Heat Exchanger – Maintenance when necessary
Rectify foreign bodies, contamination, damage and corrosion
Clean rotor body with compressed air or high pressure cleaner (only water without
additives); remove dirty water carefully
Clean sealing strips, change if there is abrasion
Adjust contact pressure of sealing strips (see above)
Balance or align rotor
Shut Down
If rotor is out of action for a longer period (e.g. summer), turn it on intermittently to maintain
self-cleaning function.
In order to avoid damage to the heat exchanger, do not exceed the maximum permissible
pressure drop SUPPLY/EXTRACT (depending on type approx. 1,000 Pa). Observe notes
for closing dampers (see page 19)
There is a danger to life when charging gas under high pressure! Do not damage or
overheat pipes (e.g. by means of welding torch).
Heat Pipe-HRS – Periodic Maintenance
Check heat pipe for hygiene, contamination, damage and corrosion
Check water outlet and siphon function, clean if necessary
Check water level of siphon, top up if necessary
Heat Pipe-HRS – Maintenance when necessary
Clean the heat pipe on the air side (see below), rectify damage and corrosion
Cleaning
Observe the following points:
Avoid bending plate fins.
Blow out with compressed air in the opposite direction.
Do not use a high pressure cleaner or a high pressure steam cleaner.
Clean with water and low pressure.
Cleaning Agents
Use cleaning agents with a pH-value between 7 and 9 if required.
When current feed is not disconnected at all poles, there is a risk of crushing and scraping
to the limbs through sudden running of the rotor caused by an automatic cleaning run or
automatic re-start after power failure.
Attention
If commissioning is not undertaken correctly, overheating, frost damage, erosions of the
rotor body or odor problems may occur depending on the type of rotor. It is compulsory to
observe the rotor manufacturer’s information (request if necessary)!
Do not operate LICI-rotors with e.g. supersaturated air or clean wet.
The commissioning must be carried out in accordance with the rotor manufacturer’s
instructions and the commissioning described by robatherm (see page 42).
Rotor Speed
The desiccant rotor requires a much lower speed during dehumidification than during HRS
operation. The defined rotor speeds have to be checked, e.g. during dehumidification 10 1/h
for 2 V input signal (or the priority contact is closed) and in HRS operation 10 1/min for 10 V
input signal.
Pressure Drop
In order to avoid contamination of the supply air with the humid regeneration air, the
pressure potential of the fans should be selected in such a way that the system related
leakage from the supply air side flows into the regeneration air side.
Zone crossing must be avoided with ATEX units in all circumstances.
When current feed is not disconnected at all poles, there is a risk of crushing and scraping
to the limbs through sudden running of the rotor caused by an automatic cleaning run or
automatic re-start after power failure.
Maintenance Work
The maintenance work must be carried out in line with the instructions of the rotor
manufacturer (ask if required).
Desiccant Rotor HRS – Periodic Maintenance
Check rotor for hygiene, foreign bodies, contamination, damage and corrosion
Check sealing strips for contamination, foreign bodies and contact pressure (see above)
Check drive belt for wear and tension, shorten (see above) or change if necessary
Check rotor for imbalance and lateral trueness
Check bearing for incorrect heating, vibration or running noises and change if necessary
(no later than the end of the theoretical service life)
Check functioning of rotor control, align sensor if necessary
Desiccant Rotor HRS – Maintenance when necessary
Rectify foreign bodies, contamination, damage and corrosion
Clean body of rotor in line with rotor manufacturer's instructions. Depending on the rotor
type, wet cleaning may lead to the destruction of the rotor!
Clean sealing strips, change if there is abrasion
Adjust contact pressure of sealing strips (see above)
Balance or align rotor
Shut Down
If standstill is for a longer period, put the rotor intermittently into operation in line with the
manufacturer’s instructions to maintain self purification of the rotor.
Observe requirements in line with DIN 4794, DIN 4755 and DVGW-worksheet (German
Technical and Scientific Association for Gas and Water) G600.
There is a danger of fire if flammable materials come into contact with the combustion
chamber.
Operation in explosion hazard zones not permitted. Flush to ensure that no explosive
atmosphere is present before the burner ignites.
Attention
First commissioning of a combustion chamber or the associated system must be carried
out by the manufacturer or a specialist appointed by the manufacturer following DIN 4794.
Flame Pot
Check position of flame pot; it must be positioned vertically by the back wall.
Connection
Installation of oil or gas burner in accordance with manufacturer's instructions. Connect
burner to oil or gas line. The operating instructions of the oil or gas burner manufacturer
must be followed exactly.
Install and wire all sensors and thermostats.
Attention
Every system must be equipped with an emergency switch.
Overheating damage of combustion chamber, casing, components etc. may occur when
the unit is operated with insufficient cooling (e.g. the unit is switched off via crash switch
and burner is still running) or the units are switched off via safety bodies.
There is a danger of fire if flammable materials come into contact with the combustion
chamber.
Check that there is a good distribution of the airflow at the inlet and outlet of the
combustion chamber!
Combustion Air
The required combustion air (environmentally compatible) amounts to approx 1 m³/h per kW
installed burner capacity. The intakes should be designed inside the building following TRGI,
in the unit to a max. of 1 m/s, min. 150 cm².
Pos: 64.11 /Inbetriebnahme und Wartung/Brennkammer /Brennkammer_Regel- und Sicherheitsorgan e @ 0\mod_1258445298181_2 008.doc @ 2203 @ 44
Chimney
Make connection to chimney in accordance with applicable regulations. The exhaust system
must meet the civil engineering and official regulations.
Readiness for Operation
Make ready for operation:
Vent oil or gas line.
Check adjustment values of the triple thermostat:
Burner: approx. 70 °C
Fan: approx. 40 °C
Position of sensor approx. 10 cm downstream from combustion chamber
For 2 stage burner check set values of single thermostat: approx. 60 °C.
Burner
Put burner into operation. The commissioning instructions of the burner manufacturer must
be followed precisely. Please ensure that the fan is in constant operation. The fuel supply
must be set in such a way that the rated capacity Q
is not exceeded. For this it is essential
N
to use a gas meter for a gas burner.
Check the flame; it must not touch the combustion chamber walls. Use flame head
extension or other nozzle angle.
Control and Safety Bodies
Check triple thermostat:
The fan should start at set “fan” value = 40 °C. Functional test by means of e.g. hot air
drier.
The burner should switch off at set “burner” value = 70 °C. Functional test by means of
e.g. hot air drier.
For functional test of the safety temperature limiter, heat the capillary by means of hot air
drier for example. Burner must switch off at approx. 100 °C and the safety temperature
limiter must lock. If this does not happen automatically, stop burner, replace triple
thermostat and repeat whole test.
Unlock safety temperature limiter manually by reset button.
The single thermostat is to be tested in the same way as the triple thermostat. The second
burner stage must be switched on or off at approx. 60 °C.
Damper Regulation
For combustion chambers with bypass, the active direction of the dampers must be checked.
If necessary reverse direction of rotation of servo motor by adjusting the slide switch. For
further information see page 19.
Combustion chamber temperature regulation:
If the heating requirement increases, the combustion chamber damper must open and
the bypass damper close. The dampers do the opposite when there is a reduced heating
requirement.
In order to guarantee adequate cooling of the combustion chamber, the combustion
chamber damper may be closed no further than 10 mm of free opening cross section
between the damper blades. Provide a limit switch to switch off the burner.
Temperature control of flue gas:
When under-running the set minimum temperature of the flue gas the combustion
chamber damper (if present) must close and the bypass damper must open. When the
set flue gas maximum temperature is exceeded, the burner capacity must be reduced.
Establish emission value following DIN 4794.
Maximum emission temperature: approx. 210 °C (protection regulations, observe newest
version).
Minimum emission temperature: approx. 150 °C (to reduce formation of condensate).
Observe minimum operation time of burner.
All settings must be documented and filed in the setting records.
Condensate
Condensate piping must be professionally connected and incidental condensate must be
disposed of in line with the local regulations (e.g. ATV information sheet).
One shift operation: Min. 1 x per year
Two shift operation: Min. 2 x per year
Three shift operation or other modes of operation: Min. 3 x per year
Caution
Observe general safety instructions on page 3!
Caution
To avoid burns, do not touch hot surfaces.
Caution
Before starting work allow components to cool/warm up to the ambient temperature.
Caution
Observe requirements in line to DIN 4794, DIN 4755 and DVGW-worksheet (German
Technical and Scientific Association for Gas and Water) G600.
When working on the flame pot, wear protective clothing (skin, eye and inhalation
protection). Observe safety data sheet (ask if required). There is a danger of fire if
flammable materials come into contact with the combustion chamber.
Combustion Chamber – Periodic Maintenance
Dismantle burner. Check combustion chamber for contamination, damage and leaks. If
damage or leaks are found the manufacturer must be informed immediately in order to
effect appropriate repairs. The burner may not be operated until the damage is rectified.
Combustion Chamber – Maintenance when necessary
Following cleaning of the ancillary surface, vacuum the combustion chamber if
necessary.
Flame Pot – Periodic Maintenance
Check flame pot for damage. Slight cracking is normal. Replace if there is damage or
deformation or after 5,000 operating hours. To do this remove burner plate and cylinder
cover.
Remove inspection cover and cleaning cover of the combustion chamber. Remove all
turbulators and check for general condition. Replace if there is heavy corrosion.
Check drainage device and clean if necessary.
Reheating Surface – Maintenance when necessary
Clean all reheating surface pipes with a stainless steel brush and vacuum the collector.
Burner – Periodic Maintenance
On completion of combustion chamber cleaning, the burner maintenance is to be carried
out in accordance with the instructions of the burner manufacturer (in line with DIN 4755
or DVGW-worksheet G600).
Establish exhaust gas values as per Federal Emissions Protection Act.
A record is to be established of all work and forwarded to the manufacturer automatically.
Check gas pipes, connections and gas control system for leaks and eliminate any leaks
found.
Control and Safety Bodies – Periodic Maintenance
Inspection according to commissioning.
Bypass- and Combustion Chamber Damper – Periodic Maintenance
For maintenance see chapter “dampers”.
Checking of active direction: See commissioning.
In general the chimney sweep is responsible for the maintenance of the exhaust pipe
(chimney).
concentration of the indoor air must not exceed locally prescribed value limits!
2
Recirculation air operation is not permissible! Do not enter running unit due to danger of
burns.
Operation in explosion hazard zones not permitted. Flush to ensure that no explosive
atmosphere is present before the burner ignites.
Attention
First commissioning of a gas surface burner or the associated system must be carried out
by the manufacturer or a specialist appointed by the manufacturer following DIN 4794. This
person must be approved by the DVGW as a gas expert. There is a danger of fire if
flammable materials come into contact with the flame.
Regulations
When the unit is installed, the points here must be followed together with any conditions
imposed by the certifying authority, all local regulations and the DVGW and TRGI
requirements must be adhered to precisely.
Connections
Connect controlled gas system to the gas pipe. Ensure that there is no stress on
connections. Type of gas and gas pressure must be suitable for the control system.
Install blow valve outside the building.
Install and wire all sensors and thermostats (room thermostats etc.).
Leak Test
Check gas pipe, connections and gas control system for leaks via testing instrument.
Attention
Every system must be equipped with an emergency switch.
Overheating damage of combustion chamber, casing, components etc. may occur when
the unit is operated with insufficient cooling (e.g. the unit is switched off via crash switch
and burner is still running) or the units are switched off via safety bodies.
There is a danger of fire if flammable materials come into contact with the combustion
chamber.
Check that there is a good distribution of the airflow at the inlet and outlet of the
combustion chamber!
Readiness for Operation
Make ready for operation:
Vent gas line.
Check setting of limit value of safety temperature limiter: 60 °C as standard. Suction and
Pos: 66.10 /Inbetriebnahme und Wartung/Gasflächenbr enner/Gasflächenbr enner_IBN-und W artungsarbeiten @ 0\mod_12 58447177708_2008. doc @ 2213 @ 4
Burner
Put burner into operation. Observe continuous operation of supply and extract fan without
any recirculation air.
This work is only to be performed by the robatherm customer service unless an alternative
agreement has been made.
The numbers shown below refer to the figures on page 56:
Open stopcock (1), check pressure at manometer (11). It must correspond to the rated
pressure in accordance with nameplate.
Set gas pressure gauge min (9) at lowest value.
Set gas pressure gauge max (10) at highest value.
Set air pressure gauge on burner panel at lowest value.
For units with combustion air blower: Set air pressure gauge of supporting blower at
lowest value.
Set desired value of duct and room sensor and thermostats above the respective ambient
temperature.
Set control switch on switch cabinet to “heating”.
Unit will now start burner.
If there is a fault shutdown repeat start up several times (remaining air).
If there is no flame although there is gas at the burner:
Check correct venting of the gas pipe.
Check control units (6, 9, 10, 15, 16) electrically.
Check fine wire fuse of control unit.
Check electrical wiring in the switch cabinet and wiring of field units, correct if necessary.
Check ignition electrodes.
If there is only a short flame although there is gas at the burner:
Check UV diode for correct connection and discolouring, replace if necessary.
For units with ionisation control: Check ionisation rod. Where appropriate remove
contamination. Rod may not have any contact with metal parts. Check insulation body.
For units with combustion air blowers check direction of rotation of the ventilator and
reverse electrical connections if necessary.
Commissioning and Maintenance Work
The points listed below must also be included in maintenance work.
For testing of the safety temperature limiter (STL), heat the capillary by means of hot air drier
for example. Burner must switch off at set value limit and the safety temperature limiter must
lock. If this does not happen automatically, stop burner, replace STL and repeat whole test.
Unlock safety temperature limiter manually by reset button.
Check whether defined nominal airflow is set; adjust if necessary.
Adjust gas supply with on site gas meter by turning the setting screw on the pressure
regulator (3) (control damper with servo motor (7) must be fully open).
At full load (control damper (7) fully open) the pressure on the manometer must match the
rated pressure as per nameplate.
The rated value of the duct sensors or room sensor must be set lower than actual value.
Control damper (7) must close.
Set minimum gas throughput using control damper (7). For this set control signal to 0 % and
to smallest possible throughput by means of limit switch in actuator at which a homogeneous
flame pattern is still available. Check via sight glass.
Set unit back to max. capacity (open control damper (7)).
Turn down gas pressure gauge max. (10) until it switches off.
Set value: Switch off value + approx. 20 %
Gas pressure gauge min. (9) remains at lowest setting.
Check direction of rotation of servo motor (7). If the room sensor is set above t
motor (7) must open the control damper and vice versa.
Test the function of the controls.
Set sensors and thermostats to rated value.
The whole gas piping must be checked carefully for leakages with a leak indicator spray. If
leakages are found, undertake appropriate repair work.
For units with combustion air blower, set combustion air pressure by adjusting suction
restrictor; instructions of burner manufacturer must be followed exactly.
Set air pressure gauge on combustion air blower:
Set value: Switch off value – 20 %
Setting of burner slit: Nominal pressure loss at burner slit should be approx. 180 to 250 Pa.
Set pressure switch on burner slit:
Set value: Nominal pressure drop at burner slit – 40 %
All settings must be documented and filed in the setting records.
One shift operation: Min. 1 x per year
Two shift operation: Min. 2 x per year
Three shift operation or other modes of operation: Min. 3 x per year
Caution
Observe general safety instructions on page 3!
Caution
Do not enter running unit due to danger of burns.
There is a danger of fire if flammable materials come into contact with the flame.
Gas Surface Burner – Periodic Maintenance
Check gas pipes, connections and gas control system for leaks and eliminate any leaks
found.
All maintenance work must be performed as shown for commissioning.
Clean off dirt with a brush; ensure that all air holes are clear. Check gas outlets, clean
with injector needle if necessary. Do not touch with ignition electrode or controls.
Check distance of the ignition electrodes; adjust if necessary.
Pos: 68.2 /Inbetriebnahme und Wartung/Überdruckkla ppe/_Beschaffenhei t von Frisch- und Umlauf wasser @ 0\mod_1258474965 883_2008.doc @ 2220 @ 3
Quality of Fresh and Recirculating Water
Pos: 68.3 /Inbetriebnahme und Wartung/Sprühbefeuch ter/Sprühbefeucht er_Frisch/Umlauf wasser @ 0\mod_125847505 0116_2008.doc @ 2221 @ 44
Before commissioning the quality of fresh and recirculating water must be checked.
Fresh Water
Analysis of fresh water (usually available from local water authority).
Total water hardness under 7° dH.
Water quality following VDI 6022, VDI 3803
Ordinance
Recirculating Water
Limits for quality of recirculating water (recommendation partly based on VDI 3803 and
German Printing Trades Association):
Quality
Elec. conductivity
Normal
Requirement
< 1,000* < 300 < 120**
(µS/cm)
DIN EN 13053 and Drinking Water
,
Data Processing
Sterile and Clean
Areas
Rooms
Pos: 68.4 /Inbetriebnahme und Wartung/Sprühbefeuch ter/Sprühbefeucht er_Eindickungszah l @ 0\mod_1258475685116 _2008.doc @ 2222 @ 4
Carbonate hardness
< 4 < 4 < 4
(° dH)
Chloride (g/m³) < 180 < 180 < 180
Sulphate (g/m³) < 150 < 100 < 100
pH-value 7 to 8.5 7 to 8.5 7 to 8.5
Germ count (KBE/ml) < 1,000 < 100 < 10
Legionella (KBE/100ml) < 100 < 100 < 100
Thickening Count 2 to 4 2 to 6*** 2 to 8***
CBU = Colony Building Units
*) Descaling and part desalination may be necessary; for moistening above 95% r.h.
electrical conductivity max 800 µS/cm.
**) Full desalination necessary
***) Lower value without extra measures for sterilisation; upper value with extra
measures
Thickening Count
Establishment of thickening count from the values of the fresh water analysis and the
recommended value limits for the quality of recirculating water (see table):
Thickening count – recommended value for recirculating water / value for fresh water.
Whereby the thickening count must be calculated for the electrical conductivity, hardness,
chloride content and sulphate content. The lowest value of the calculated thickening counts
should be close to the recommended value limits (see table). For values below 2, additional
measures for water treatment should be taken. Contact a company specialising in water
processing.
Setting values for hygienic monitoring can be established from the lowest thickening count:
Value limit for electrical conductivity =
Lowest thickening count x electrical conductivity of fresh water
(Rated value for blow down device or for monitoring with HYGIENECONTROL)
Cleaning interval =
Sump capacity x (thickening count – 1)/ evaporated water quantity
(Setting value for time clock of HYGIENECONTROL)
Note
These settings values are approximations and do not replace the additional monitoring of
germ counts.
We recommend the use of test systems (Dip-Slides). Follow instructions for use.
Fresh Water Pressure
The ball valve is acceptable up to an operating pressure of max. 6 bar.
We recommend a fresh water pressure of at least 3 bar; if necessary install booster system.
Excessive humidity shall be avoided upstream of the rotor to prevent its matrix from overwetting. If ever possible, permeate from the reverse osmosis should be used to operate the
humidifier.
Only use approved parts with ATEX units. All electrical parts must be earthed.
Cleaning
Clean foreign bodies out of humidifier sump, clean contamination with water and cleaning
agent (non-foaming, pH-value 7 - 9).
Note
Remove swarf thoroughly, otherwise there is a risk of pitting!
Filling
Fill humidifier sump up to 10 to 20 mm below the overflow connector and set ball valve at
this level by adjusting the knurled screw.
Note
When operating the spray humidifier there must be an airflow of at least 1 m/s (related to
inside cross section of casing) against the spraying direction in order to avoid rectifier
breakdown.
Treated water must be removed from galvanized parts immediately. White rust formation!
Pump
Put pump into operation. Follow instructions of the pump manufacturer.
Set dry running protection. The pump must switch off when the water level drops below
20 mm over the suction line, otherwise pull floating switch cables in or out as required.
Ball Valve
Check ball valve. At a maximum water level 10 to 20 mm below the overflow connector the
fresh water supply must switch off.
Adjustability
For adjustable humidifiers the pump must switch off at a nozzle pressure of less than
0.3 bar. Setting of control valve or frequency converter as per manufacturer’s operating
instructions.
Shut Down
The humidifier must be switched off automatically as soon as the AHU is switched off or fails.
Leak Testing
Test external piping for leakage, tighten if necessary.
Brand new eliminator profiles do not reach their full elimination capacity until approx 3
operating days have passed (weathering effect).
Hygiene Control
Sedimentation device: Adjust rated value for conductivity in accordance with manufacturer’s
operating instructions (see page 58).
HYGIENECONTROL: Setting of the cleaning interval (see page 58) and value limit of the
conductivity control.
Disinfection
UV rays (with self-controlling UV selective sensors) may be appropriate for continuous
disinfection.
Only use chemical disinfection agents (biocides) if their harmlessness to health in the
application concentration is proven.
Following commissioning the germ count of recirculating water should be checked on a
weekly basis for a while. If necessary the setting values of the hygiene control may be
adjusted.
Caution
Increased quantities of germs can cause infections or allergic reactions.
If germ counts are over the recommended limits, clean or service system immediately. If in
doubt or if germ counts again rise rapidly, you are recommended to have examination and
advice from a qualified body.
If the results are below limits (see page 58), then see maintenance.
Only fill the humidifier sump with fresh water if humidifying is required. The humidifier sump
must be cleaned and dried when it is not operating and for standstill of over 48 hours.
Spray Humidifier – Weekly Maintenance*
Empty humidifier sump and clean with fresh water**
Spray Humidifier – Two Weekly Maintenance*
Check germ count of recirculating water and compare with permissible values (see page
58). If recommended germ count is exceeded, clean and disinfect immediately***.
Examine inner surface for visible or tangible biological film (slimy covering),
contamination, germs, damage or corrosion; if necessary service, scrub manually with a
high pressure cleaner and disinfect***. If there are deposits through scaling then the
recirculating water must have a commercially available descaling agent ***mixed into it;
with the fan at a standstill, it must be allowed to take effect for several hours, the sump
must then be emptied and cleaned with fresh water. If necessary remove drop eliminator
and straightener profiles for cleaning.
Spray Humidifier – Half Yearly Maintenance
Check mudflap, pump and pipes for dirt, coating, condition and function; if necessary
clean with fresh water; if necessary service
Check pump incl. bearings for quiet, vibration free running, heating and noises; perform
corrective maintenance if necessary
Check proper functioning of and clean the conductivity electrodes in line with
manufacturer’s information, service if necessary
Unscrew caps of atomizer nozzles and examine for deposits, clean with commercially
available descaling agent*** if necessary
Check dry running protection and ball valve and adjust if necessary (see page 60)
Check function of the deconcentration device, water conditioning, sterilisation plant, water
drain and overflow; service if necessary.
Check shut off installations for function; service and adjust if necessary
Spray Humidifier – Maintenance when necessary
Drying by fan slow down **
Lubricate pump motor bearings in line with manufacturer’s instructions. Replace bearings
(no later than the end of the theoretical service life)
If the water conditioning or sterilisation plant breaks down all unit parts must be cleaned.
Refill the humidifier sump with fresh water**
*) Quarterly maintenance for extract air humidifiers that do not influence the ventilation
air quality.
**) Is performed automatically in units with HYGIENECONTROL, depending on the
For further information the individual commissioning instructions must be observed!
Only use approved parts with ATEX units. All electrical parts must be earthed.
Fresh Water
Completely desalinated water (permeate from reverse osmosis) with max. 20 µS/cm and
total water hardness max. 1 °dH.
Water quality following VDI 6022, VDI 3803
, DIN EN 13053
and Drinking Water Ordinance
Water supply pressure: 2 to 8 bar
Drinking water connections shall be equipped with pipe isolators according to EN 1717.
High Pressure Connection
Check that high pressure hose is routed so that it is not subject to stretching or chafing;
correct if necessary.
Check threaded connections to humidifier and pump station for leaks; tighten if
necessary. Use a second wrench for counter tightening.
Internal bolts must not be retightened.
Pump Station
Check oil level through sight glass or with a dipstick; if necessary top up with required
type of oil (see information on pump station).
Check tension of drive belt; retension with pulley if necessary.
Check discharging screw for leaks; retighten if necessary. For this use a second wrench
to counter turn.
Set system in motion manually and check basic functions.
Check pump direction of rotation, if it is incorrect swap electrical connections.
Check protective devices as instructed.
Pos: 72.5 /Inbetriebnahme und Wartung/Überdruckkla ppe/Überdruckk lappe_IBN_Einstellun g @ 0\mod_1258478593416_2 008.doc @ 2239 @ 4
Caution
Observe general safety instructions on page 3!
Caution
There is a possibility of damage to persons or property as a result of impact or air jet under
high pressure through unexpected release of the pressure relief damper!
Protective devices must be fitted and effective in accordance with DIN EN ISO 12100.
Setting
The release or application pressure of the pressure relief damper against the unit or duct
wall can be varied by height adjustment , and altering the number and distance of weights
(see characteristics).
The presetting is made by means of the indicated a-dimension.
By simulating maximum pressure in the network by using dampers which are as a rule
present in every system, release pressure must be tested and weights adjusted if necessary.
All construction requirements such as access, completed unit and duct installation and
uninterrupted availability of all supply facilities must be met. In addition there must be a
possibility of operating the system in the required working phases.
The commissioning may only be undertaken by a qualified company which specialises in
process measurement and control technology.
At the start of the commissioning work, the commissioning engineer will be shown the
system specific locations by a person nominated by the customer.
Work
The following work must be carried out:
Check correct installation of the field units
Check the electrical connections on the switchgear cabinet and the field units
Functional test of sensors, transducers and actuators included in the supply package
Configuration of control and/or DDC substations including loading of project specific
Commissioning with all connected data stations
Adjustment of the parameters to the operating conditions of the technical system, setting
Testing of the control programmes
Briefing nominated operating staff during the course of commissioning work
Pos: 74.12 /Inbetriebnahme und Wartung/MSR-Technik/ MSR-Technik_War tung_Regler und Zusatz modul @ 0\mod_1258541799396 _2008.doc @ 2249 @
Switch Cabinets, Control Panels, controls – Periodic Maintenance
Check for proper and functionally correct installation and ambient conditions
Check for contamination, corrosion and damage
Check protective coverings are complete
Check electrical/mechanical function of the connections, especially protective conductors
Check functional elements (e.g. operating - and display devices)
Check input signals (e.g. sensor, reference variable) match with rated value
Check optical and acoustic control devices
Check contactors and relays for wear and damage (e.g. contact erosion)
Check switching and control processes (e.g. anti-freeze function)
Check safety devices (e.g. thermal trips)
Check setting of switch cabinet components (e.g. time relays)
Check manual, automatic and remote control functions
Change switch cabinet filter
Switch Cabinets, Control Panels, Controls – Maintenance as required
Clean to maintain functioning
Set, adjust, tighten functional elements (e.g. operating and display devices)
Compensate signals
Readjust
Transducers, Safety and Monitoring Equipment, – Periodic Maintenance
Check for proper and functionally correct installation and ambient conditions
Check for contamination, corrosion and damage
Check electrical/mechanical function of the connections, especially protective conductors
Measure and record measurable quantities at measurement point
Check electrical, electronic and pneumatic measurement signals
Transducers, Safety and Monitoring Equipment – Maintenance as required
Clean to maintain functioning
Readjust, regenerate
Controllers and Supplementary Modules – Periodic Maintenance
Check for proper and functionally correct installation and ambient conditions
Check for contamination, corrosion and damage
Check natural voltage (e.g. buffer batteries, storage batteries)
Check electrical/mechanical function of the connections, especially protective conductors
Check functional elements (e.g. operating - and display devices)
Check electrical, electronic and pneumatic input signals (e.g. sensors, remote adjustment
devices, reference variables)
Check controller functioning and actuating signal
Check control loop as per setting parameters including all supplementary functions
Controllers and Supplementary Modules – Maintenance when necessary
Exchange storage batteries
Clean to maintain functioning
Set, adjust, tighten functional elements (e.g. operating and display devices)
Compensate signals
Adjust controller functioning and actuating signal
Adjust control loop as per setting parameters including all supplementary functions
Check for proper and functionally correct installation and ambient conditions
Check for contamination, corrosion and damage
Check for external leakage (e.g. valve packing bushes)
Check electrical/mechanical function of the connections, especially protective conductors
Check electrical, electronic and pneumatic input signals and operating range
Check functioning of position sensors, alarm actuators and limit switches
Readjust
Actuators – Maintenance when necessary
Lubricate (e.g. valve stem)
Clean to maintain functioning
Software – Periodic Maintenance
Perform data back up
Keep most recent copies of programmes and data
Pos: 76.9 /Inbetriebnahme und Wartung/Hydraulisc he Regelgruppe/Hydrau lische Regelgruppe_Pr üfungen @ 0\mod_1258546 078597_2008.doc @ 2250 @ 4444
Caution
Observe general safety instructions on page 3!
Caution
Only use fluid with ambient temperature when charging or purging as there is a risk of
scalding/frostbite.
Caution
To avoid burns, do not touch hot/cold surfaces.
Only use approved parts with ATEX units. All electrical parts must be earthed.
Ensure sufficient distance between max. surface temperature of the heat exchanger due to
temperature of the medium and minimum ignition temperature of any flammable mixture
which may be present in accordance with EN 1127.
Attention
Do not exceed permissible pressure range.
Observe design data sheet.
In HRS control equipment (e.g. run around coils heat recovery system) the quantity of antifreeze is to be determined in relation to the lowest outside temperature (note
manufacturer’s information).
Inspections
Check:
Correct installation of all components.
Inlet outlet connections for function (counter flow principle).
Firm seating of all bolts and glands.
Easy movement of all valves, slide dampers and baffles.
Charging
The system must be rinsed (removal of contaminations) according to VDI 2035 and should
be filled with the heat exchanger fluid named in the design data sheet to the correct
concentration. Water quality to VDI 2035. This control equipment charging process can also
occur together with the charging of the piping system. During charging check connection
points for leakage; retighten screws and glands if necessary.
Venting
When charging the system according to VDI 2035 the control equipment and the system
should be vented carefully at the highest point of the system. Open the venting recovery
device provided for this purpose. This is also valid for pumps with venting devices (e.g. high
pressure centrifugal pumps in high efficiency run around heat recovery systems). Observe
manufacturer’s instructions.
In incompletely vented systems with pumps, air pockets may cause capacity reduction and
severe damages of the pump.
Pos: 76.18 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_Kontakt mit Sole @ 0\mod_1258373184 697_2008.doc @ 2156 @
Venting
Pumps with venting devices (e.g. high pressure centrifugal pumps in high efficiency run
around heat recovery systems) shall be vented again 2 weeks after commissioning. Observe
manufacturer’s instructions.
Otherwise, bearings and shaft seals might be damaged.
Maintenance Interval
Every three months. ATEX units every month.
Caution
Observe general safety instructions on page 3!
Caution
To avoid burns, do not touch hot/cold surfaces.
Caution
Before starting work allow components to cool/warm up to the ambient temperature.
Caution
Avoid any contact with brine while charging or venting. Danger of poisoning and acid burns!
Observe manufacturer’s instructions.
Hydraulic Control Equipment – Periodic Maintenance
Check control equipment for contamination, damage, corrosion and leaks
Vent pump and hydraulic set
Check filtering systems, clean if necessary
Check easy movement of all valves, slide dampers and baffles; if necessary lubricate
stems in accordance with manufacturer’s instructions.
Check release pressure of pressure relief devices
Service pumps, control valves and servo motors in accordance with manufacturer’s
information
Hydraulic Control Equipment – Maintenance when necessary
Clean control equipment and rectify any damage, leakage and corrosion
Retighten bolts and glands
Shut Down
If out of operation for some time, especially if there is a risk of freezing, the control
equipment must be emptied completely. For this purpose open all purging and discharging
devices.
Then blow air (compressed air, fan etc) through the control equipment for complete purging.
If the system is to be shut down for a longer period the instructions for the individual
components must be observed. Additionally it is compulsory to observe the individual
component manufacturer’s information (request if necessary)!
Take the risk of freezing in winter into account in particular.
Only an authorised company is allowed to disassemble the unit after the service life has
expired. Please observe the safety regulations for every component as well as the
component manufacturer’s instructions to avoid any damage to persons or property.
All components and resources (e.g. oils, refrigerant, brine, batteries) must be disposed of in
line with local regulations. All metal and plastic parts should be separated and sent for
recycling.
Injection moulding parts are provided with material identification; plastic extrusions are
usually made of polyvinyl chloride (PVC).