R & M Int'l. CGC-1e User Manual

CGC-1e Complete Greenhouse Controller
OVERVIEW
The CGC-1e Complete Greenhouse Controller from C.A.P. controls all of the main devices required in today’s modern hydroponic garden.
WORD TO THE WISE...
Before attempting to operate the CGC-1e, you should at least take the time to look at the Example Connection diagram on page 2 and read the “Start­up Procedure on page 3 of this manual. To get the most out of the CGC-1e, familiarize yourself with this manual. It contains many useful hints; examples and a troubleshooting guide.
IMPORTANT STUFF TO REMEMBER
The CGC-1e is designed to operate from a 120vac, 15-amp power source. It can safely control up to 15-amps of equipment including up to 1000 watts of HID lights. If required, additional lights and larger equipment can be connected to the CGC-1e by using our HPR, MLCs or UPM “Universal Remote Power Modules”. In addition to lights, the CGC-1e also maintains the temperature and humidity by controlling your exhaust fan(s). CO coordinated with your exhaust fans and function only when the lights are ON. Or you can upgrade later to PPM Part-Per­Million control by adding the PPM-1c CO perfect for controlling your hydroponic pumps and more!
CGC-1e
levels can be controlled with the built-in timers, which are
2
monitor. And to complete the package, the built in Adjustable Recycling Timer is
2
PROTECTION & SAFETY
The CGC-1e is overload protected a main 15-amp fuse. Do not exceed the maximum rating of the CGC-1e. IMPORTANT: Replace blown fuses with fuses of the same rating ONLY!
Note: A surge suppressor power strip is always
WARRANTY
The CGC-1e is protected by our 3-year limited warranty. All components are warranted by R & M Supply against defects in workmanship and materials under normal use for 3-years from the date of purchase. The CGC-1e is 100% maintenance-free and does not require service.
INSTALLATION / START-UP
There are a few requirements for a successful installation and start-up.
1) The CGC-1e must be mounted in a vertical position.
2) The CGC-1e requires “free air movement” to maintain temperature and humidity accuracy.
enclosure has ventilation slots to provide air flow through the unit however, we greatly recommended using an oscillating fan in the growing area to provide fresh air for the internal humidity sensor and provide adequate ventilation for the internal electrical components.
3) A dedicated 120 VAC, 15-amp power supply is recommended.
Do not use 2-wire adapters or cords to operate the CGC-1e.
4) The CGC-1e must be protected from water. Do not
5) Read the rest of the manual!!! It has been designed to take you through step-by-step to make start-up a breeze.
recommended when operating electrical equipment such as the CGC-1e.
Mounting feet are included to allow you to secure the unit to a wall.
mount the unit where it can be exposed directly to water.
The top and bottom of the
A ground wire (3-wire outlet) must be used.
Page 1
“FRONT PANEL”
@
000
OVERVIEW
“The CGC-1e is a self-contained greenhouse control system designed for people who want a reasonable, simple to
operate, complete greenhouse controller.
Humidity
controller
Temperature
controller
(2) Exhaust
outlets
(2) Light
outlets
24-hour
timeclock
Hydro mode
selector switch
Hydro “ON”
timer
Night device
outlet
CO2 device
outlet
Hydro “OFF”
timer
(2) Hydro pump
outlets
Control up to (2)
Exhaust Fan(s) or
A/C units
Fan, heater, or
dehumidifier
CO2 Valve or Generator
CO2 “ON”
timer
Optional PPM–1c
quick connect
EXAMPLE CONNECTION DIAGRAM
DO NOT EXCEED 15 AMPS TOTAL
CGC-1e
Exhaust Lights
Night
Hydro
CO
2
PPM Option
24-hour
Timeclock
Fuse protected 15-amps
Control multiple HID lights
with a MLC or UPM
CO2 “OFF”
timer
120 volts
1
Control (2) pumps. Selectable 24-hour operation or daytime only.
Optional CO2
PPM sensor
1250
PPM-1c
15-amp fuse
protected
Page 2
START-UP PROCEDURE
OVERVIEW
“There is no substitute for reading and understanding the operating manual however... You can use the
instructions on this page for a trouble -free start-up”.
HOW TO START-UP THE CGC-1e
1) Locate a suitable source for power. A “3-wire”, grounded, 15-amp dedicated circuit is recommended.
2) Secure the enclosure to a wall using the enclosed mounting “feet”. The CGC-1e requires a vertical orientation for proper
internal ventilation. If proper ventilation is not provided, the thermostat may not be able to properly control the temperature & humidity of the growing area.
3) Plug the CGC-1e into the power source. Do not connect your lights until you have set the “ON and “OFF” times on the
24-hour timeclock.
4) If you are using a PPM-1c CO
sensor, connect it by removing the “jumper-plug” provided with the CGC-1e and
2
connecting the PPM-1c quick-disconnect. Plug the PPM-1c into a source of constant 120-volt power. Refer to the PPM-1c instructions for information on how to operate the PPM-1c properly.
* Note: The pre-wired “jumper plug” must be connected if the PPM-1c is not being used!
5) You can now set the thermostat and de-humistat to the approximate settings you would like to use. A small, inexpensive
combination thermometer and hygrometer works just fine to “dial in” the exact settings. Just compare the reading on the thermometer to what the CGC-1e is set at and adjust as required.
6) You can now select the Hydro mode you would like to use. Choose between operating the Hydro outlet during the
“Daytime” only or, 24-hours a day. Move the Hydro mode switch to the appropriate position. Moving the switch to the center “OFF” position momentarily will reset the timer.
7) There are 4 timers on the CGC-1e, which are used to control a hydroponics pump and a CO
valve or generator. To fully
2
understand the timers that control the CGC-1e, refer to the Timers section of this manual. Set the Hydro and CO2 timers to your desired settings before continuing. (Refer to Timers)
8) The 24-hour timeclock can now be set. Push in the trip levers on the front face of the timer dial for the time you want your
lights to be “ON”. Rotate the dial to the current time to set the timer.
9) You can now plug the equipment you will be using into the appropriate receptacles. Remember that the CGC-1e can
handle a combined load up to 15-amps. A single 1000-watt HID ballast needs over 9-amps alone. Select and size your pumps and fans appropriately or use our UPM-1 or MLCs to increase power capacity.
*Note: We highly suggest NOT plugging in your HID ballast just yet.
10) When the “day” cycle begins, the “Lights” indicator will light up to confirm power is going to the (2) light receptacles. If
you have selected the “Daytime” setting on the Hydro mode, the “Hydro Pumps” indicator will also light up to indicate your pump is powered for the amount of time you selected
11) You can manually override the timeclock to switch from “night” to “day” or back to Night by rotating the outer dial of the
timeclock slowly clockwise. At night, the Lights and CO
are disabled while the thermostat and humistat continue to
2
control the temperature and humidity.
* NOTE: The Hydro outlet will also be disabled if the “Daytime” mode is selected on the Hydro mode switch.
12) When all settings have been confirmed, the HID lights or UPMs can be plugged into the “Lights” receptacles. If more than
1000 watts are to be controlled, use our Universal Power Modules or the MLCs.
* IMPORTANT: Do not plug in more than 1000 watts worth of lighting into the CGC-1e receptacles.
13) Monitor the equipment connected to the CGC-1e to ensure proper operation. Small adjustments are likely to be made until
you find the right combination of controls. Once you are happy with the settings sit back and enjoy the show!
For more details concerning any of the CGC-1e functions, refer to the appropriate section of this manual.
Page 3
Loading...
+ 7 hidden pages