RLE RA1x2 User Manual

RA1x2 Quick Start Guide
T
hank you for purchasing the Raptor RA1x2. This guide describes how to install the RA1x2.
If you need further assistance, contact RLE Technologies on our
website at http://www.rletech.com/ (go to the Support Link) or by calling
970.484.6510, Option 2.
1Installation
Electrical Connections
2 Connect the alarm input (dry contact) to J1 pin 7 and pin 8.
Alarm Relay Output Wires Input Wires
Relay 1 - Common (COM) J1 pin 5
Relay 1 - Normally Open (NO) J1 pin 4
Relay 1 - Normally Closed (NC) J1 pin 6
Relay 2 - Common (COM) J1 pin 2
Relay 2 - Normally Open (NO) J1 pin 1
Relay 2 - Normally closed (NC) J1 pin 3
104 Racquette Drive
Fort Collins, CO 80524
970.484.6510
www.rletech.com
2Operation and Testing
The RA1x2 reports the closure of a dry contact change of state. When a change is detected, the audible alarm sounds and the alarm LED illuminates.
Silence and Reset
1 Silence the audible alarm by pushing the Silence button.
2 Select the Reset push button to immediately reset.
Testing
Once the unit has been installed and all electrical connections have been made, test the RA1x2 for proper operation:
1 Push the Reset (Test) button, or cause an alarm on the device being
monitored.
If the RA1x2 is in proper working order, the alarm LED illuminates, and the audible alarm sounds.
2 While the alarm is on, push the Silence button to verify that the audible
alarm is silenced.
3 If the alarm does not sound and the LEDs do not illuminate, check the
power connections, and verify that the power-on LED is illuminated.
© Raymond & Lae Engineering, Inc. 2011. All rights reserved. RLE® is a registered trademark and Seahawk™, Falcon™, and Raptor™ are trademarks of Raymond & Lae Engineering, Inc. The products sold by Raymond & Lae Engi neering, Inc. are subject to the limited warranty, limited liability, and other terms and conditions of sale set forth at http://rletech.com/RLE-Terms-and-Conditions.html. 5150 2/2011
Loading...