F018-1902/1000
TWO CHANNEL WALL MOUNT CONTROLLER
Gas Detection For Life
Affordable 2 Point Monitor
Beacon™ 200 Model
Features
• Simultaneous readout on 2 channels
• Two alarm levels per channel
• Discrete and common relays
• Built in audible alarm
• NEMA 4X enclosure
• 4-20 mA outputs
• Proven, long-life sensors for a wide variety of gases
• Accepts any 4-20 mA transmitter input (24 VDC)
• Easy to install, operate and expand
• CSA, C/US classified
Industry Applications
• Petrochemical plants
• Refineries
• Water & wastewater treatment plants
• Pulp & paper mills
• Gas, telephone, & electric utilities
• Parking garages
• Manufacturing facilities
• Steel
• Automotive
• HVAC
The Beacon 200 is a powerful, low cost fixed system controller for two points of gas detection. It is
microprocessor controlled, versatile, simple to install and operate, and priced to be the industry’s
most economical two point controller. It is capable of connecting directly to RKI sensors for LEL level
combustibles, oxygen, CO2 and toxic gas sensors. The Beacon 200 can also accept any 4-20 mA
transmitter (2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beacon 200 housing, or
can be wired remotely from the controller.
The 10 amp rated relays are strong enough to actuate most external alarms and horns without using
slave relays. The digital display has backlighting and simultaneous readout of the gas type and concentration.
The Beacon 200’s housing is rated NEMA 4X for corrosion resistance and a weather tight seal, and
complies with lock out / tag out standards. An external reset switch allows the alarm to be silenced
from outside of the controller housing. The Beacon 200 comes complete with a wall mounting kit for
easy installation.
RKI offers the industry’s widest selection of standard and toxic gas detection sensors, which can be
utilized with the Beacon 200, providing gas monitoring protection for almost any application.
RKI Instruments, Inc. • 33248 Central Ave. Union City, CA 94587 • Phone (800) 754-5165 • (510) 441-5656 • Fax (510) 441-5650
World Leader In Gas Detection & Sensor Technology
www.rkiinstruments.com

Physical
Beacon™ 200 Model
Dimensions
Enclosure Wall mounting grey polycarbonate with hinged cover
Conduit Connection 3/4” NPT conduit hubs, 3 provided. 2 for sensor wiring and 1 for power & relay wiring
Wiring Termination Screw type terminal block, 14 gauge max
Power
Controls 4 internal push buttons for setup, programming, and calibration. 1 external push button for alarm reset
Height: 10.5” (267 mm) x Width: 8.5” (216 mm) x Depth: 6.3” (158 mm)
100-240 VAC or 24 VDC standard. Battery backup option available
Operating Environment
Operating Temperature
Storage Temperature -4°F to 158°F (-20°C to 70°C)
Enclosure Rating
NEMA-4X enclosure, waterproof, chemical, and weather resistant.
-4°F to 122°F (-20°C to 50°C)
Suitable for indoor and outdoor installations.
Inputs
Direct Wired Sensors LEL, Oxygen, and toxic gas sensors. Remote amp required for greater than 500 feet
4-20 mA Sensors
Sampling Methods Accepts diffusion or sample draw heads
Accepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are
available with 4-20 mA signals; (See list of detectable gases.) Wiring distances up to 5,000 feet
Outputs
7 relays - 10 amp rating (at 115 VAC), SPDT isolated contacts. 2 relays for gas alarm levels per channel,
Relays
plus 2 relays for common gas alarm and 1 common relay for malfunction. Relays fully programmable
for: increasing or decreasing alarm, latching or self reset, normally energized or normally de-energized,
time delay for alarm on and alarm off
4-20 mA Signal output, 4-20 mA (into 1,000 ohms impedance maximum), per channel
24 VDC 24 VDC (350 mA max) output provided to operate sample drawing adapters
Display Alphanumeric display with backlighting. 20 characters per line; 4 lines each
Audible
Visual 4 LED’s on the front cover for alarm status indication, pilot, and malfunction
Approvals
Warranty
Specifications subject to change without notice.
Built-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = fail
CSA Certied to CSA C22.2 No. 1010 and ANSI/ISA S82.01
One year material and workmanship
Made in the USA
Authorized Distributor:
Toll Free: (800) 754-5165 • Phone: (510) 441-5656
Fax: (510) 441-5650 • www.rkiinstruments.com