RKI Instruments 72-2102-07, Beacon 200 Operator's Manual

72-2102-07
Beacon 200
Operator’s Manual
Part Number: 71-0364 Revision: A Released: 12/11/17
www.rkiinstruments.com
WARNING
Read and understand this instruction manual before operating instrument. Improper use of the 72-2102-07 Beacon 200 could result in bodily harm or death.
Periodic calibration and maintenance of the 72-2102-07 Beacon 200 is essential for proper operation and correct readings. Please calibrate and maintain this 72-2102-07 Beacon 200 regularly! Frequency of calibration depends upon the type of use you have and the sensor types. Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage.
72-2102-07 Beacon 200 Operator’s Manual
Product Warranty
RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge. This warranty does not apply to those items, which by their nature, are subject to deterioration or consumption in normal service, and which must be cleaned, repaired, or replaced on a routine basis. Examples of such items are as follows:
a) Absorbent cartridges d) Batteries
b) Pump diaphragms and valves e) Filter elements
c) Fuses
Warranty is voided by abuse including mechanical damage, alteration, rough handling, or repair procedures not in accordance with the operator’s manual. This warranty indicates the full extent of our liability, and we are not responsible for removal or replacement costs, local repair costs, transportation costs, or contingent expenses incurred without our prior approval.
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED, AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF RKI INSTRUMENTS, INC. INCLUDING BUT NOT LIMITED TO, THE WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS, INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR CONSEQUENTIAL LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF ITS PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR OPERATE PROPERLY.
This warranty covers instruments and parts sold to users by authorized distributors, dealers, and representatives as appointed by RKI Instruments, Inc.
We do not assume indemnification for any accident or damage caused by the operation of this gas monitor, and our warranty is limited to the replacement of parts or our complete goods.
72-2102-07 Beacon 200 Operator’s Manual
Table of Contents
Chapter 1: Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About the Beacon 200 Gas Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 2: Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
External Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Internal Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 3: Installation and Start Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Mounting the Beacon 200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring the Beacon 200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Starting Up the Beacon 200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Chapter 4: Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Recorder Output Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Alarm Indications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Viewing & Resetting Min/Max Readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Chapter 5: Channel Control and Setup Program . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Enable/Disable Channel(s) Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Configure Channel Settings Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
View System Information Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
72-2102-07 Beacon 200 Operator’s Manual
Chapter 6: Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Calibration Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Adjusting Strobe/Horn Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Replacing Components of the Beacon 200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
72-2102-07 Beacon 200 Operator’s Manual
Chapter 1: Introduction
Overview
This chapter briefly describes the 72-2102-07 Beacon 200. This chapter
also describes the 72-2102-07 Beacon 200 Operator’s Manual (this
document). Table 1 at the end of this chapter lists the specifications for the 72-2102-07 Beacon 200.
About the Beacon 200
The 72-2102-07 Beacon 200 is a fixed-mounted, continuous-monitoring gas detection instrument. This gas monitor is capable of detecting gas at two locations. It includes an 8 foot AC power cord and 2 H
heads each on a user-defined length of cable.
S detector
2
The Beacon 200 displays the current gas readings on an LCD display which is visible through the window in the cover (front face) and provides a 4 - 20 mA signal which indicates the target gas reading for use by a recording device or programmable controller. Three sets of relay contacts, two controlled by the gas alarms and one by the fail alarm, rated at 115 VAC 10 amps are available for controlling devices such as lights or horns or for controlling higher rated relays. The alarm 1 relay is factory wired to the strobe/horn and is not available for field use.
Two instrument programs allow you to display and change channel and calibration settings. They are the Channel Control & Setup Program and the Calibration Program.
1 • 72-2102-07 Beacon 200 Operator’s Manual
About this Manual
!
The Beacon 200 Gas Monitor Operator’s Manual uses the following
conventions for notes, cautions, and warnings.
NOTE: Describes additional or critical information.
CAUTION: Describes potential damage to equipment.
WARNING: Describes potential danger that can result in injury or
Caution: refer to accompanying documentation
death.
~ Vac (AC voltage)
Vdc (DC voltage)
72-2102-07 Beacon 200 Operator’s Manual • 2
Specifications
Table 1 lists specifications for the 72-2102-07 Beacon 200.
Description Specification
Table 1: 72-2102-07 Beacon 200 Specifications
Input Power
Construction (housing) Fiberglass/polyester with lexan window (NEMA 4X)
Controller Dimensions 21.0 in. H x 8.5 in. W x 7.00 in. D
Weight 20 lbs.
Environmental Conditions -20°C to 50°C (-4°F to 122°F) max. ambient
Relays Relay contacts rated for 10A @ 115/220V~ resistive or10A @ 30V
User Controls Reset switch
Detection Range 0 to 100 PPM (parts per million) H
Alarm 1 Setpoint
Alarm 2 Setpoint
Response Time 90% in 30 seconds
115/220V ~ ±10%, 50/60Hz, 0.5/0.3A or 24 V +10% -8%, 0.6A
(533 mm H x 216 mm W x 178 mm D)
Maximum humidity of 80% relative
resistive
SPDT Form C
Program buttons: ESCAPE, UP/YES, DOWN/NO, and ENTER
2
10 ppm
2
50 ppm
1
S
2
Accuracy ± 5% of reading or ± 2 ppm H
1
The AC voltage input is factory set. The standard input is 115 V~.
*
2
*
The alarm setpoints shown are factory settings but they can be changed in the Channel Control and Setup
Program.
S (whichever is greater)
2
WARNING: When using the Beacon 200, you must follow the
instructions and warnings in this manual to assure proper and safe operation of the Beacon 200 and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the Bea con 200 as de scribed in this manual.
3 • 72-2102-07 Beacon 200 Operator’s Manual
Chapter 2: Description
Figure 1. Beacon 200 Component Location
Buzz er
COM-FAIL
NON C C
CH2-A 1
NO NC CNONC C
COM-A1CH2-A2
NO NC C
CH1-A1
Main P CB
Display PC B
Program Button (4)
AC In Terminal Stri p
Fuses, AC
Fail LED Pilot LE D
NO NC C
COM-A2
Controller Terminal Strip
Alarm Terminal S trip
Rela ys
Detector/
Transmitter
Terminal Strip,
Channel 1
Alarm
1LED
Display Contrast
Adjust Pot
Detector/
Transmitter
Terminal Strip,
Channel 2
Button Repeater Buzz er
Fuse, DC
MountingF oot, 4X
Horn/Strobe
AC PowerC ord
Reset Switch
Conduit H ub ( 3X)
Power Switch
NON C CNO NC C
CH1-A2
Display
Alarm 2
LED
H2S Detector C able Channel 2 ( user-defined cablel ength)
H2S Det ector Cable Channel1
(user-defined cable length)
Overview
This chapter describes external and internal components of the Beacon
200.
72-2102-07 Beacon 200 Operator’s Manual • 4
External Description
This section describes the housing and all external components of the Beacon 200. For the purposes of this description, the housing door is considered the front of the monitor.
Housing
The Beacon 200’s fiberglass housing is weather- and corrosion-resistant. It is suitable for installation where general purpose equipment is in use. The housing door is hinged on the left side and is secured by two latches on the right side. The display screen and status lights are visible through windows in the housing door. Four mounting feet are attached to the back of the housing (one at each corner). The mounting feet allow you to install the housing to a vertical surface. Three conduit hubs on the bottom of the housing are for external wiring connections.
CAUTION: Only use the three facto ry installed condui t hubs on the bottom
of the housing for wire entry into the housing. Do not drill the housing for any reason.
CAUTION: To avoid electrical interferen ce, do not r oute detec tor head a nd
power wiring thro ugh the same conduit hub.
Reset Switch
The reset switch is on the bottom of the housing. It is in front of the conduit hubs. The reset switch serves three functions:
Resets the alarm circuits for “latched” alarms after an alarm 1 or alarm 2 condition passes.
You can set each channel for latched or self-resetting alarms in the Channel Control & Setup Program.
Silences the buzzer during an alarm 1 or alarm 2 condition. You cannot silence failure alarms.
Displays and resets the minimum and maximum gas concentration values.
Buzzer
The buzzer is on the bottom of the housing. It is on the far right. The buzzer sounds audible alarms to warn you of gas alarms and instrument failures.
5 • 72-2102-07 Beacon 200 Operator’s Manual
H2S Detector Junction Boxes and Cables
Cable Bushing
To Beacon 200
Mounting Bracket
H2S Detector
(FactoryWired )
Calibration Cup/
Splash Guard
Terminal Strip
Figure 2. H2S Junction Box Component Location
Each of the two H2S detectors consists of a junction box with a mounting bracket, the detector, and the calibration cup/splash guard.
The two H
S detectors are factory wired through the left and middle cable
2
bushings of the Beacon 200 and has a user-defined length of cable for remote installation. The mounting bracket at the top of each junction box is used to mount the junction box. The junction box protects the detector wiring connections. Three spacers installed on the back of the junction box control the distance of the junction box from a mounting surface and ensure that there is enough room to perform a calibration. A cover on the front of the junction box allows access to the interior of the junction box.
72-2102-07 Beacon 200 Operator’s Manual • 6
The detector housing body protects the sensing components within the
Cap Gasket
Detector HousingBody
Calibration Cup/ Splash Guard
Flame Arrestor Guard
Detector HousingCap
H2S Plug-in Sensor
Rubber Boot
Spacer
Figure 3. H2S Detector Component Location
housing body. Use the removable cap near the bottom of the housing body to access the sensor for maintenance or replacement. The cap protects the sensor from damage and includes a flame arrestor which contains any sparks which may occur within the detector housing body. A cap gasket seals the interface between the housing body and cap. A flame arrestor guard is permanently bonded to the cap.
The calibration cup/splash guard is screwed onto the bottom of the flame arrestor guard.
The sensor is secured within the sensor housing by four pins. Through a series of chemical and electrical reactions, the sensor produces an electrical output that corresponds to the detection range of the detector. A pre-amplifier, located between the sockets and two interconnect wires, conditions the sensor’s signal before the signal reaches the controller. A rubber boot and spacer are installed on the sensor face to ensure that the sensor remains plugged into the detector housing body.
AC Power Cord
An 8 foot AC power cord is factory-wired through the right cable bushing of the Beacon 200. One end of the cable is connected to the AC In terminal strip.
7 • 72-2102-07 Beacon 200 Operator’s Manual
Internal Description
J1
UP/YES Button
ENTE R Button
DOWN/NO Button
Display Cable Connector
PILOT Light
FAIL Light
Displ ay Scree n
Button Repe ater Buzzer
ALARM 2 Li gh t
ESCAPE Bu t to n
ALARM 1 Li gh t
Display Contrast Adjust Pot
Figure 4. Display Board Component Location
This section describes the internal components of the Beacon 200. See Figure 1 on page 4 for a view of the internal components.
Display Printed Circuit Board (PCB)
The display PCB is mounted to the power supply mounting plate which is in turn mounted to the main PCB. The power supply mounting plate and main PCB are described below. The display PCB includes the display, the status lights, and the program buttons.
Display
The display simultaneously indicates the channel number, current gas reading, measuring unit, and target gas of all active channels.
The display also indicates messages, settings, and other data when you are operating the instrument programs.
72-2102-07 Beacon 200 Operator’s Manual • 8
Status Lights
The Beacon 200 includes four status lights that indicate the current status of the monitor. The status lights are to the left and right of the display (see Figure 4).
Pilot Light. The pilot light is on when the Beacon 200 is receiving incoming power.
Fail Light. The fail light turns on when the Beacon 200 is experiencing a fail condition. A fail condition can be caused by a failure within the Beacon 200 or detector head wired to the Beacon 200. See “Chapter 6: Maintenance” on page 37 for instructions to respond to a fail condition.
Alarm 1 Light. The alarm 1 light is on when the Beacon 200 is experiencing an alarm 1 gas condition.
Alarm 2 Light. The alarm 2 light is on when the Beacon 200 is experiencing an alarm 2 gas condition.
Program Buttons
The Beacon 200 includes four program buttons that allow you to enter the instrument programs, navigate through the programs, update instrument and channel settings, and save changes to the program settings. When a program button is pressed, a buzzer located on the display PCB beeps. The program buttons are near the right edge of the display PCB (see Figure 4).
Table 2: Beacon 200 Program Button Functions
Button Function
ESCAPE Moves backward through the program menus
Cancels changes you make in the program menus
Enters the Channel Control and Setup program (press with the ENTER button)
UP/YES Accepts the displayed setting and proceeds to the next setting
Changes the displayed setting
Enters the Calibration program (press with the ENTER button)
DOWN/NO Allows you to update the displayed setting
Changes the displayed setting
ENTER Saves changes you make in the programs
Enters the Channel Control and Setup program (press with ESCAPE button)
Enters the Calibration program (press with the UP/YES button)
9 • 72-2102-07 Beacon 200 Operator’s Manual
Main PCB
The main PCB is mounted inside the housing. The power supply mounting plate is mounted to the main PCB with four standoffs and the display PCB is mounted to the power supply mounting plate with four standoffs. The main PCB includes the terminal strips, relays, fuses, and power switch.
Terminal Strips
The Beacon 200 includes four terminal strips for external wiring connections. See “Wiring the Beacon 200” on page 17 for detailed wiring procedures.
Detector/Transmitter Terminal Strips. Two detector/transmitter terminal strips are located near the bottom left corner of the main circuit board (see Figure 1). These two 9-point terminal strips facilitate wiring connections to the detectors. Only one detector head at a time may be wired per channel. The top terminal strip is for channel 1 and the bottom terminal strip is for channel 2. The H2S detectors are factory wired to
these terminal strips.
Alarm Terminal Strip. The alarm terminal strip is located along the bottom edge of the main circuit board (see Figure 1). This 21-point terminal strips facilitates wiring connections to external alarm devices (horn, strobe, etc.). Terminals are provided for individual channels as well as common alarm relay contacts. The horn/strobe is factory wired to this terminal strip.
Controller Terminal Strip. The 10-point controller terminal strip is near the lower right edge of the main circuit board (see Figure 1). The controller terminal strip facilitates various internal and external wiring connections. Table 3 lists the function of each terminal.
72-2102-07 Beacon 200 Operator’s Manual • 10
Table 3: Terminal Assignments for the Controller Terminal Strip
Terminal Connects to:
BAT -
BAT +
+ CH1 OUT + connection of 4 - 20 mA output, channel 1
- CH 1 OUT - connection of 4 - 20 mA output, channel 1
+ CH2 OUT + connection of 4 - 20 mA output, channel 2
- CH2 OUT - connection of 4 - 20 mA output, channel 2
RESET (2) Reset switch (factory-wired)
BUZ-/BUZ+ Internal buzzer (factory-wired)
1 If DC power is used as the primary power source, do not make wiring connections to the AC terminal strip.
- connection from 24 VDC power source
+ connection from 24 VDC power source
1
(or 24 V backup battery)
1
(or 24 V backup battery)
AC In Terminal Strip. The AC In terminal strip is a 3-point terminal strip located above the controller terminal strip (see Figure 1). It facilitates wiring from the AC power source. The 8 foot AC power cord is factory wired to this terminal strip. Table 4 lists the function of each terminal.
Table 4: Terminal Assignments for the AC In Terminal Strip
Terminal Connects to:
LINE Hot wire from AC power source.
NEUT Neutral wire from AC power source.
GND Earth ground
Relays
The Beacon 200 includes four channel relays (two per channel) and three common relays. Both sets of relays are single-pole, double-throw (SPDT) and are rated for 10 amps at 250 VAC (resistive).
NOTE: You can select normally energized (NE) or normally de-energized
(NDE) settings for each channel in the Channel Control and Setup program. This section describes the default setting: normally de­energized.
The alarm 1 and alarm 2 common relays are factory-set as NDE and the fail common relay is factory-set as NE. The alarm 1, alarm 2, and fail common relays’ NE/NDE settings are not user­adjustable.
11 • 72-2102-07 Beacon 200 Operator’s Manual
Channel relays. The four channel relays are above the alarm terminal
K1 K2 K3
Common Alarm 1 Common Alarm 2
Common Fail
K5 K6 K7
K4
Channel 2 , Ala rm 2 Channel 2 , Ala rm 1
Channel 1 , Ala rm 2 Channel 1 , Ala rm 1
Figure 5. Beacon 200 Channel Relay Allocation
strip (see Figure 1). These relays are dedicated to specific channels and alarm levels.
For example, the channel 1, alarm 1 relay energizes if channel 1 recognizes an alarm 1 condition. Figure 4 below illustrates the allocation of the channel relays.
NOTE: The alarm 2 channel relays may be set to operate as individual
channel fail relays. See “Configure Channel Settings Menu” on page 34 for instructions.
Common relays. The three common relays, alarm 1, alarm 2, and fail, are to the left of the controller terminal strip (see Figure 1). These relays are common for both channels.
For example, the alarm 1 common relay energizes if either channel 1 or channel 2 recognizes an alarm 1 condition. The common alarm 1 relay is factory wired to the strobe/horn and is not available for customer use.
Fuses
There are three fuses that are used in the Beacon 200. Two of them are AC fuses and one of them is a DC fuse.
AC Fuses. The two fuses located directly to the left of the controller terminal strip are the AC fuses. They cut off the incoming AC power in the event of a short circuit or other electrical fault which causes a high current draw in the Beacon 200. They are housed in vertical fuse holders and are held in the holder by a quarter turn cover. They are labelled as F2 (top fuse) and F3 (bottom fuse) on the PCB silk-screen and are rated at 3 A, 250 V.
DC Fuse. The fuse located to the left of the power switch is the DC fuse. It cuts off incoming DC power in the event of a short circuit or
72-2102-07 Beacon 200 Operator’s Manual • 12
other electrical fault which causes a high current draw in the Beacon
200. It is also housed in a vertical fuse holder and is held in the holder by a quarter turn cover. It is labelled as F1 on the PCB silk-screen and is rated at 6A, 250 V.
Power Switch
The power switch is located above the relays and to the left of the DC fuses (see Figure 1). The power switch turns the incoming AC power source on and off at the Beacon 200. When the switch is up, the power switch is on.
NOTE: The DC power input has no on/off switch and is not affected by the
position of this switch.
Power Supply
The power supply is mounted to the power supply mounting plate which is located behind the display PCB. The power supply mounting plate is mounted to the main PCB with four standoffs. The power supply receives the AC input from the external power source and converts it to a DC voltage that is usable by the Beacon 200 circuitry.
13 • 72-2102-07 Beacon 200 Operator’s Manual
Loading...
+ 39 hidden pages