RKI Instruments 65-2619RK-CH4-4 User Manual

65-2619RK-CH4-4
M2 Transmitter
Operator’s Manual
Part Number: 71-0289RK
Revision: 0
RKI Instruments, Inc.
www.rkiinstruments.com
WARNING
Read and understand this instruction manual before operating instrument. Improper use of the gas monitor could result in bodily harm or death.
Periodic calibration and maintenance of the gas monitor is essential for proper operation and correct readings. Please calibrate and maintain this instrument regularly! Frequency of calibration depends upon the type of use you have and the sensor types. Typical calibration frequencies for most applications are between 6 and 12 months, but can be required more often or less often based on your usage.
65-2619RK-CH4-4 M2 Transmitter Operator’s Manual
Product Warranty
RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year fr o m date of shipment from RKI Instruments, Inc. Any parts found defective withi n tha t period will be repaired or replaced, at our option, free of charge. This warranty does not apply to those items which by their nature are subject to deterioration or consumption in normal ser v ice, and which must be cleaned, repaired, or replaced on a routine basis. Examples of such items are:
W arranty is voided by abuse including mechanical damage, alteration, rough handling, or repair procedures not in accordance with the operator’s manual. This warranty indicates the full extent of our liability , a nd we are not r esponsible for removal or r eplacement costs, local repair costs, transportation costs, or contingent expenses incurred without our prior approval.
a) Absorbent cartridges d) Batteries b) Pump diaphragms and valves e) Filter elements c) Fuses
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED, AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF RKI INSTRUMENTS, INC. INCLUDING BUT NOT LIMITED TO, THE WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS, INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR CONSEQUENTIAL LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF ITS PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR OPERATE PROPERLY.
This warranty covers instruments and parts sold to users by authorized distributors, dealers, and representatives as appointed by RKI Instruments, Inc.
We do not assume indemnificatio n f o r a n y a c c ident or damage caus e d b y t he op e ration of this gas monitor, and our warranty is limited to the replacement of parts or our complete goods.
65-2619RK-CH4-4 M2 Tr ans mitt er Oper a tor ’s Ma nual
Table of Contents
Chapter 1: Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About the M2 Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Chapter 2: Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
External Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Internal Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 3: Installation & Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mounting the M2 Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Wiring the M2 Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Chapter 4: Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Information Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4 - 20 mA Signal Output Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Alarm Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Chapter 5: Configuration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Viewing & Changing M2 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Chapter 6: Gas Type Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Selecting the Gas Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
65-2619RK-CH4-4 M2 Transmitter Operator’s Manual
Chapter 7: Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Calibration Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Replacing the IR LEL Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Chapter 8: RS-485 Modbus Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Wiring the M2 in a Modbus System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Using the M2 in a 4-wire Modbus System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Modbus Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Supported Modbus Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Appendix A: Control Button Quick Reference Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Appendix B: PLC and DCS Device Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Appendix C: Function Code 16 Registers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
(Appendix C available from RKI Instruments, Inc. Not included in manual as normally provided with M2 detector head.)
65-2619RK-CH4-4 M2 Tr ans mitt er Oper a tor ’s Ma nual
Chapter 1: Introduction
Overview
This chapter briefly describes the 65-2619RK-CH4-4 M2 Transmitter. This chapter also describes the 65-2619RK-CH4-4 M2 Transmitter Operator’s Manual (this document). Table 1 at the end of this chapter lists the specifications for the M2.
About the M2 Transmitte r
The M2 transmitter is a fixed mount, continuous-monitoring detector hea d. All user adjustable parameters may be accessed using push button switches. In addition, calibration may be performed non-intrusively by use of a magnetic wand accessory which activates magnetic switches through a window at the front face of the detector head.
The M2 displays the current gas reading on an LCD display wh ich is visible through the window in the cover (front face) and provides a 4 - 20 mA signa l which indicates the target gas reading for use by a gas monitoring controller, recording device, or programmable controller. The M2 also provides an RS-485 Modbus output. Three sets of relay contacts, two controlled by the gas alarms and one by the fail alarm, rated at 115 VAC 5 amps are available for controlling devices such as lights or horns or for controlling higher rated relays.
Four operating modes allow you to display and change setup and calibration settings and change the gas type. They are Calibration Mode, Configuration Mode, Gas Type Mode, and Modbus Mode.
About this Manual
The M2 Transmitter Operator’s Manual uses the following conventions for notes, cautions, and warnings.
NOTE: Describes additional or critical info rmation.
CAUTION: Describes pote ntial damage to equip ment.
WARNING: Describes potential danger that can result in injury or death.
1 65-2619RK-CH4-4 M2 Transmitter Operator’s Manual
Specifications
Table 1 lists specifications for the M2.
Table 1: M2 Specifications
Target Gas/Detection Range Methane: 0 - 100% LEL, 1% LEL increments Alarm Settings
(Alarm 1/Alarm 2) Construction (housing) Explosion-proof Junction Box, NEMA 4 Area Classification Explosion-proof for Class I, Groups B, C, and D Sampling Method Diffusion Input Power 19 - 30 VDC Controls • Three push button switches
Weight 5.5 lbs. Signal Output • 4 to 20 mA, 500 ohms impedance max
Operating Temperature -20°C to 50°C Accuracy ± 5% of reading or ± 2% of full scale (whichever is greater)
*
These are the RKI factory settings. You can change the alarm settings in Configuration Mode. See
“Viewing & Changing M2 Parameters” on page 21.
10 %LEL/50 %LEL
• Three magnetic switches for non-intrusive calibrati on
• RS-485 Modbus
WARNING: When using the M2, you must follow the instructions and warnings in
this manual to assure proper and safe operation of the M 2 and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the M2 as described in this manual.
WARNING: M2 det ector heads with firmware version 5.0 or later have a different
Modbus register assignment than M2s wi th previous versions of firmware. If you are adding M2s with firmware version 5.0 or l ater to an existing Modbus network installation, confirm what firmware version is installed in the M2s already in the network and if necessary, take all steps required to address the differences in Modbus register assignments. See “Supported Modbus Functions” on page 40 for information on the current Modbus register assignments. The firmware version i s shown on the Information Screen described on page 16.
65-2619RK-CH4-4 M2 Transmitter Operator’s Manual 2
Chapter 2: Description
Overview
The M2 combustible gas transmitter utilizes an infrared type of detector which has some advantages over a catalytic type of combustible detector. The infrared detector will generally have a longer service life than a catalytic detector, it will require calibration less often, and it can detect combustible gas even if there is no oxygen in the sample which allows detection of combus tible gas in an inert atmosphere.
This chapter describes the components of the M2 transmitter. The transmitter is a 4 - 20 mA type detector head. It consists of the combustible gas detector, calibration adapter/ splash guard, terminal PCB, the M2 junction box, and the detector junction box. The two junction box configuration is in tended for situations where the detector needs to be installed at an inaccessible location. The detector junction box can be installed at the inaccessible location and the M2 junction box can be installed in a more readily accessible area.
External Description
This section describes the junction boxes and all external components of the M2 transmitter.
Mounting Slot (2x)
Magnetic Wand
Window
M2 Junction Box
3/4" NPT Conduit Hub
3/4" NPT Conduit Hub
Detector
Junction Box
Terminal Strip
IR LEL Detector
Calibration Adapter/
Splash G uard
Figure 1: M2 External Component s
3 65-2619RK-CH4-4 M2 Transmitter Operator’s Manual
M2 Junction Box
The M2’s cast aluminum junction box protects the terminal PCB and wiring connections made to the terminal PCB. Use the top 3/4’’ conduit hub to connect wiring from the terminal PCB to external power and/or to an external device, typically an RKI controller. Use the bottom 3/4” conduit hub to wire the remotely installed IR LEL detector. Use the junction box’s two mounting slots to mount the M2 to a vertical surface at the monitoring site. The window in the cover on the front of the junction box allows you to view the LCD display and use the magnetic wand to actuate the magnetic control switches so you can perform non-intrusive calibration. Removing the cover allows you to access the interior of the junction box.
Detector Junction Box
The detector junction box is intended to be installed remotely from the M2 junction box. The IR LEL detector is factory installed in the bottom 3/ 4” conduit hub. A terminal st rip is provided for wiring connections and the detector is factory wired to one side of this terminal strip. The other side of the terminal strip is for user-supplied wiring to the detector terminal strip located in the M2 junction box. This wiring should go through the top 3/4” conduit hub. Three spacers installed on the back of the junction box controls the distance of the junction box from a mounting surface.
Infrared LEL Detector
The infrared LEL detector is made up of a miniature infrared combustible gas LEL detector housed and encapsulated in a pipe nipple. The pipe nipple has 3/4” NPT thr eads on each end and a 1 1/4” hex that allows removal or installation of the detector with a wrench. A por ous flame arr e stor t hat is coat ed wit h a hydr o phobic f ilm that re pels liquids is on one end of the detector and al lows samp le gas to enter the detector. Four color coded leads, red, white, green, and black, extend from the other end of the detector. The leads allow you to connect the detector to the terminal strip.
Calibration Adapter/Splash Guard
A calibration adapter/splash guard is installed on the IR LEL detector. A fitting at the bottom of the calibration adapter/splash guard allows a length of tubing to be connected for calibration and routed to a more easily accessible location (near the M2 junction box is optimal for ease of calibration). The calibration adapter/splash guard also protects the detector from splashing water or direct water spray.
Magnetic Wand
The magnetic wand is a short plastic rod with a magnet in one end. It is used to actuate the magnetic control switches on the control PCB while the junction box cover is still installed so that non-intrusive calibration can be performed.
65-2619RK-CH4-4 M2 Transmitter Operator’s Manual 4
Internal Description
This section describes the interna l components of the M2. The internal components of the M2 include t he t e rminal PCB which pro v i de s f or all the wiring connections to the M2 and the control PCB which displays the gas reading and has the control buttons.
3/4" NPT Conduit Ope ni n g
Power/Signal
Terminal Strip
Detector Terminal Strip
Detector
Cur rent Po t
(Factory
Adjust)
Programming
Connector
(Factory Use)
Modbus
Terminal Strip
Termination
Jumper
for Wire Entry
- S +
PWR/SIG
- S +
LEL PWR/SIG
LEL
R W G B
R W G B
R S 485
RS 485
A B C
A B C
Display Ribbon Cable Connector
Relay Terminal Strips
FAIL
C NC NO
ALARM 1
C NC NO
ALARM 2
C NC NO
3/4" NPT Conduit Op ening f or Det e cto r J -Box Wiring
Junction Box
Terminal PCB
Control PCB
Magnetic Switches
UP/YES
DOWN/NO
ENTER
Push Button
Contro l Sw itc hes
UP/YES
DOWN/NO
ENTER
Fail LED
Al arm 1 LED
Al arm 2 L ED
RX L ED
TX LED
RKI INS TRUMENTS
M2 TRANSM ITTER
L CD Display
View With Cover and
Control PCB Removed
View With Cover Removed
Figure 2: M2 Internal Component s
Terminal PCB
The terminal PCB is encapsulated in epoxy for protection against moisture and physical damage. It is mounted into the rear of the junction box with three standoffs and rests on a thin layer of foam. A banana jack is screwed into each of the standoffs and used for mounting the control PCB. The terminal PCB converts the electrical output from the detector to a signal which can be displayed by the LCD display, a 4 - 20 mA signal (that is proportional to the detection range), and an RS-485 Modbus output signal. The 4 - 20 mA signal may be used by a recording device, gas monitor controller, or programmable controller. The Modbus output may be used to connect the M2 to a Modbus network. The terminal PCB also controls three relays, one fail and two gas alarm relays.
Two columns of plug-in style terminal strips are used to make all wiring connections to the M2. The column on the left consists of the power/signal, detector, and Modbus terminal strips. The column on the right consists of the relay terminal strips. A 20 position connector at the bottom of the terminal PCB is used to connect the terminal PCB to the
5 65-2619RK-CH4-4 M2 Transmitter Operator’s Manual
control PCB with a ribbon cable. A 5 position connector on the left side of the terminal PCB is used by factory or field service personnel to program the M2. A factory adjust pot just above the programming connector is used to set the detector current.
Power/Sign al Terminal Strip
The power/signal terminal strip is a three position plug-in style terminal strip located at the top of the left terminal column. It is used to connect 24 VDC power to the M2 and to connect the 4 - 20 mA output signal to a device.
The signal output, the S terminal, does not have to be connected for the M2 to function. The S terminal is used if you want to connect the 4 - 20 mA output signal to another device such as a gas monitoring controller, chart recorder, or programmable controller (PLC).
Detector Terminal Strip
The detector terminal strip is a four position plug-in style terminal strip and is the middle terminal strip in the left terminal column. All four terminals are used to connect the detector to the M2.
Detector
Terminal Strip
- S +
PWR/SIG
- S +
LEL
R W G B
RS 4 85
A B C
PWR/SIG
LEL
R W G B
RS 485
A B C
C NC NO
C NC NO
C NC NO
FAIL
ALARM 1
ALARM 2
Figure 3: Detect o r Term inal Strip
NOTE: The detector is factory-wired to the M2. See “Wiring the M2 Transmitter” on
page 11 for all wiring procedures related to M2.
Modbus Terminal Str ip
The Modbus terminal strip is a three position plug-in style terminal strip and is the bottom terminal strip in the left terminal column. It allows connection of the M2 into a Modbus network.
Relay Terminal Strips
The right column of terminal strips consists of, from top to bottom, the fail, alarm 1, and alarm 2 relay terminal strips. The y are three-positio n plug-in style terminal strips. The relay terminal strips are used to connect devices such as lights and horns that are controlled by the relay contacts. The relay contacts are rated at 115 VAC, 5 amps. The relay contacts may also be used to control higher rated relays.
65-2619RK-CH4-4 M2 Transmitter Operator’s Manual 6
Termination Jumper
A two pin header with a termination jumper installed is located below the Modbus terminal strip. The jumper has no function unless the M2 is wired into a Modbus installation. See “Chapter 8: RS-485 Modbus Output” on page 35 for a description of using the M2 in a Modbus system.
Control PCB
The LCD display and control switches are located on the control PCB. It is installed on top of the terminal PCB by lining up its three spacing standoffs with the banana jacks in the terminal PCB mounting standoffs and pushing it ont o the banana jacks. The jacks retain the control PCB.
LCD Display
The LCD display is located at the top of the control PCB. It indicates the current gas reading and displays messages and parameters in the M2’s programs.
Control Buttons
The M2 includes three push button switches that allow you to enter the M2’s operating modes, navigate through the modes, update settings, an d save changes to the settings. The push button switches are located along the bottom edge of the control PCB (see Figure 2). The UP/YES button is on the left, the DOWN/NO button is in the middle, and the ENTER button is on the right.
Table 2: M2 Control Button Functions
Switch Function
UP (YES) Saves settings
Changes the displayed set t ing
Enters th e Calibration Program
Enters Gas Type Mode (press with DOWN/NO button)
Enters Configuration Mode (pres s with EN TER button )
DOWN (NO) Cancels setting changes
Changes the displayed set t ing
Enters Gas Type Mode (press with UP/YES button)
Enters Modbus Mode (press with ENTER button )
Displays the Information Screen
ENTER Initiates operations
Enters Configuration Mode (press with UP/YES button)
Enters Modbus Mode (press w ith DOW N /NO button)
Functions as an alarm reset switc h
Just above each push button switch is a magnetic switch with the same function as th e push button switch below it. The magnetic switches are for use in non-intrusive calibration. They are actuated by bringing the magnetic wand close enough to them to actuate them. Although the magnetic switches have the same functions as the push button switches, it is not practical to use them for operations other than calibration because it is not possible to actuate two magnetic switches at once with only one magnetic wand. Since displaying the Information Screen only requires the use of one switch, the wand may be used to show the Information Screen (see “Information Screen” on page 16).
7 65-2619RK-CH4-4 M2 Transmitter Operator’s Manual
Status LEDs
The M2 includes five status LEDs that are located above the display (see Figure 2).
Fail LED The fail LED turns on when the M2 is experiencing a fa il condition. A fail condition
can be caused by a detector failure or low detector signal.
Alarm 1 LED The alarm 1 LED is on when the M2 is experiencing an alarm 1 condition.
Alarm 2 LED The alarm 2 LED is on when the M2 is experiencing an alarm 2 condition.
RX & TX LED’s These LED’s indicate data being received (RX) and transmitted (TX) when the M2’s
Modbus output is operating.
65-2619RK-CH4-4 M2 Transmitter Operator’s Manual 8
Chapter 3: Installation & Startup
b
Overview
This chapter describes procedures to mount the M2 Transmitter in the monitoring environment and wire it to input power and devices.
Mounting the M2 Transmitter
1. Select a mounting site that is representative of the monitoring environment. Consider the following when you select the mounting site.
For the M2 junction box, select a site where the junction box is not likely to be
bumped or disturbed. Make sure there is sufficient room to perform start-up, maintenance, and calibration procedures. The site should be easily a ccessible.
For the detector junction box, select a site where the target gas is likely to be found
first. For lighter gases, mount the detector near the ceiling; for heavier gases, mount the detector near the floor.
5.86
The junction boxes should be mounted no further than 200 feet from each other.
2. Use #10 screws through the M2 junction box’s two mounting slots to secure the junction box to a vertical surface. Figure 4 shows the outline and mounting dimensions the M2 junction box. Figu re 5 shows the outline and mounting dimensions for the detector junction box. Mount the detector junction box with the detector facing down as shown in Figure 5.
4.59
2.41
5.23
5.00
3/4 NPT Conduit Hu
1.02 .47 (2X)
Figure 4: Outline & Mounting Dimensions, M2 Junction Box
9 65-2619RK-CH4-4 M2 Transmitter Operator’s Manual
.30 (2X)
r
,
3/4 NPT
Female
3.65
9.00 MA X
.382.70
Rubb e Spacer 3X
J-Box
IR LEL
Detector
5.25 Cali bration
Adapt er/
Splash Guard
.75
Figure 5: Outline & Mounting Dimensions, Detector Junction Box
3. Install 3/16 inch I.D. flexible po lyurethane tubing to the fitting at the bottom of the calibration adapter/splash guard and route it to an accessible area that is close to the M2 junction box. See the “Parts List” on page 45 for available tubing.
65-2619RK-CH4-4 M2 Transmitter Operator’s Manual 10
Wiring the M2 Transmitter
WARNING : Always verify that the power to the M2 is off before you make wiring
connections.
1. Confirm that no power is being applied to the M2.
2. Remove the detector junction box’s cover from the junction box.
3. Remove the M2 junction box’s cover from the junction box.
4. Grasp the control PCB by its edges.
5. Gently pull until the control PCB is pulled away from the banana jacks. Take care not to pull too hard and damage the cable which connects the control and terminal PCBs.
6. Let the control PCB hang by the cable. The terminal strips are now visible on the terminal PCB. The control PCB may be left hanging while wiring is done. If desired, the control PCB may be disconnected from the cable and set aside while wiring.
7. Guide a four-conductor, shielded cable or four wires in conduit through the top conduit hub of the detector junction box. To make wiring more convenient, use wire colors that correspond to the detector wire colors: red, white, green, and black.
NOTE: Consult RKI Instruments, Inc. for cable lengths longer than 200 feet.
8. Connect the detector leads to the terminal block in the detector junction box.
9. Secure the detector junction box’s cover to the junction box.
10. Guide the other end of the four-conductor, shielded cable or four wires in conduit through the bottom conduit hub of the M2 junction box.
11. To gain access to a plug-in termi nal strip for wiring, pull it out of its socket by grasping the wall between two terminal positions with needle nose pliers and pulling. Be careful not to exert too much force on the wall to avoid damage to the terminal strip. The detector terminal strip and th e alarm 1 r elay t ermi nal strip ma y be r emo ved by grasping them with your fingers if the adjacent terminal strips have been removed.
WARNING: If the M 2 is installed in a hazardous location, use app ropriatel y rated
conduit, conduit fittings, and appropriate construction technique that complies with the local electrical code. In addition, use appropriately rated conduit, conduit fittings, and appropriate construction technique to maintain the NEMA 4 environmental rating of the junction box and avoid water entering the junction box at the conduit hubs.
12. Pull out the detector terminal strip and connect the four wires to the terminal strip as follows (see Figure 6).
Connect the wire corresponding to the detector ’s red wire to the LEL “R”
terminal.
Connect the wire corresponding to the detector’s white wire to the LEL “W”
terminal.
Connect the wire corresponding to the detector’s green wire to the LEL “G”
terminal.
11 65-2619RK-CH4-4 M2 Transmitter Operator’s Manual
Detector
Terminal
Strip
Connect the wire corresponding to the detector’s black wire to the LEL “B”
terminal.
CAUTION: If shielded cable is used, leave the cable shield ’s drain wire disconnected and
insulated at the detector junction box. You will connect the opposite end of the cable’s drain wire to the M2 junction box’s chassis (earth) ground.
Cable
Shield
FAIL
- S +
PWR/SIGRS 485
- S +
LEL
R W G B
A B C
C NC NO
LEL PWR/SIGRS 485
C NC NO
R W G B
ALARM 2 ALARM 1
C NC NO
A B C
Black Green White Red
Black M2 J-Box
Green
White
Red
DetectorJ-Box
IRLELDetector
Calibration Adapter/Splash Guard
Figure 6: Wiring the Detector to the M2
13. Reinstall the detector terminal strip into its socket.
14. If shielded cable is used between the detector junction box and the M2 junction box, connect the cable’s drain wire to an available chassis (earth) ground at the M2 junction box. Do not connect the shield drain wire at the detector junction box.
15. Guide multi conductor shielded cable or cables or wires in conduit through the top conduit hub of the M2 junction box. The number of cables or wires needed will depend on whether the M2 is wired to a gas monitoring controller or just to power, whether any relays are used, and whether the Modbus output is used.
NOTE: If the M2 is being wired to a PLC or DCS device, see “Appendix B: PLC and
DCS Device Wiring” on page 47, then continue with step 8.
65-2619RK-CH4-4 M2 Transmitter Operator’s Manual 12
Loading...
+ 39 hidden pages