Read and understand this instruction manual before
operating instrument. Improper use of the gas monitor
could result in bodily harm or death.
Periodic calibration and maintenance of the gas
monitor is essential for proper operation and correct
readings. Please calibrate and maintain this instrument
regularly! Frequency of calibration depends upon the
type of use you have and the sensor types. Typical
calibration frequencies for most applications are
between 3 and 6 months, but can be required more
often or less often based on your usage.
65-2610RK-04 M2 Transmitter Operator’s Manual
Product Warranty
RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in
materials, workmanship, and performance for a period of one year fr o m date of shipment
from RKI Instruments, Inc. Any parts found defective withi n tha t period will be repaired
or replaced, at our option, free of charge. This warranty does not apply to those items
which by their nature are subject to deterioration or consumption in normal ser v ice, and
which must be cleaned, repaired, or replaced on a routine basis. Examples of such items
are:
W arranty is voided by abuse including mechanical damage, alteration, rough handling, or
repair procedures not in accordance with the operator’s manual. This warranty indicates
the full extent of our liability , a nd we are not r esponsible for removal or r eplacement costs,
local repair costs, transportation costs, or contingent expenses incurred without our prior
approval.
a) Absorbent cartridgesd) Batteries
b) Pump diaphragms and valvese) Filter elements
c) Fuses
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER
WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED,
AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF
RKI INSTRUMENTS, INC. INCLUDING BUT NOT LIMITED TO, THE
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS,
INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR CONSEQUENTIAL
LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF
ITS PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR
OPERATE PROPERLY.
This warranty covers instruments and parts sold to users by authorized distributors,
dealers, and representatives as appointed by RKI Instruments, Inc.
We do not assume indemnificatio n f o r a n y a c c ident or damage caus e d b y t he op e ration of
this gas monitor, and our warranty is limited to the replacement of parts or our complete
goods.
(Appendix C available from RKI Instruments, Inc. Not included in manual as normally
provided with M2 detector head.)
65-2610RK-04 M2 Transmitter Operator’s Manual
Chapter 1: Introduction
Overview
This chapter briefly describes the 65-2610RK-04 M2 Transmitter. This chapter also
describes the 65-2610RK-04 M2 Transmitter Operator’s Manual (this document). Table 1 at
the end of this chapter lists the specifications for the M2.
About the M2 Transmitte r
The M2 transmitter is a fixed mount, continuous-monitoring detector hea d. All user
adjustable parameters may be accessed using push button switches. In addition,
calibration may be performed non-intrusively by use of a magnetic wand accessory which
activates magnetic switches through a window at the front face of the detector head.
The M2 displays the current gas reading on an LCD display wh ich is visible through the
window in the cover (front face) and provides a 4 - 20 mA signa l which indicates the
target gas reading for use by a gas monitoring controller, recording device, or
programmable controller. The M2 also provides an RS-485 Modbus output. Three sets of
relay contacts, two controlled by the gas alarms and one by the fail alarm, rated at 115
VAC 5 amps are available for controlling devices such as lights or horns or for controlling
higher rated relays.
Four operating modes allow you to display and change setup and calibration settings and
change the gas type. They are Calibration Mode, Configuration Mode, Gas Type Mode,
and Modbus Mode.
About this Manual
The M2 Transmitter Operator’s Manual uses the following conventions for notes, cautions,
and warnings.
NOTE:Describes additional or critical info rmation.
CAUTION:Describes pote ntial damage to equip ment.
WARNING:Describes potential danger that can result in injury or death.
165-2610RK-04 M2 Transmitter Operator’s Manual
Specifications
Table 1 lists specifications for the M2.
Table 1: M2 Specifications
Target Gas/Detection RangeCombustible Gas (methane calibration standard):
0 - 100% LEL, 1% LEL increments
Alarm Settings
(Alarm 1/Alarm 2)
Construction (housing)Explosion-proof Junction Box, NEMA 4
Area ClassificationExplosion-proof for Class I, Groups B, C, and D
Sampling MethodDiffusion
Input Power 19 - 30 VDC
Controls• Three push button switches
Weight5.5 lbs.
Signal Output• 4 to 20 mA, 500 ohms impedance max
Operating Temperature-20°C to 50°C
Accuracy± 5% of reading or ± 2% LEL (whichever is greater)
*
These are the RKI factory settings. You can change the alarm settings in Configuration Mode. See
“Viewing & Changing M2 Parameters” on page 22.
10 %LEL/50 %LEL
• Three magnetic switches for non-intrusive calibrati on
• RS-485 Modbus
WARNING:When using the M2, you must follow the instructions and warnings in
this manual to assure proper and safe operation of the M 2 and to
minimize the risk of personal injury. Be sure to maintain and periodically
calibrate the M2 as described in this manual.
WARNING:M2 det ector heads with firmware version 5.0 or later have a different
Modbus register assignment than M2s wi th previous versions of
firmware. If you are adding M2s with firmware version 5.0 or l ater to an
existing Modbus network installation, confirm what firmware version is
installed in the M2s already in the network and if necessary, take all steps
required to address the differences in Modbus register assignments. See
“Supported Modbus Functions” on page 41 for information on the current
Modbus register assignments. The firmware version i s shown on the
Information Screen described on page 17.
65-2610RK-04 M2 Transmitter Opera tor’s Manual2
Chapter 2: Description
3/4" NPT Conduit Hub
Overview
This chapter describes the components of the M2 transmitter. The transmitter is a 4 - 20
mA type detector head. It consists of the combustible gas detector, calibration adapter/
splash guard, terminal PCB, the M2 junction box, and the detector junction box. The two
junction box configuration is in tended for situations where the detector needs to be
installed at an inaccessible location. The detector junction box can be installed at the
inaccessible location and the M2 junction box can be installed in a more readily accessible
area.
External Description
This section describes the junction boxes and all external components of the M2
transmitter.
Mounting Slot (2x)
Magnetic
Wand
Window
M2 Junction Box
Terminal
Strip
3/4" NPT Conduit Hub
Detec tor
Junction Box
Combustible Gas
Detector
Calibration Adapter/
Splash Guard
Figure 1: M2 External Component s
365-2610RK-04 M2 Transmitter Operator’s Manual
M2 Junction Box
The M2’s cast aluminum junction box protects the terminal PCB and wiring connections
made to the terminal PCB. Use the top 3/4’’ conduit hub to connect wiring from the
terminal PCB to external power and/or to an external device, typically an RKI controller.
Use the bottom 3/4” conduit hub to wire the remotely installed combustible gas detector.
Use the junction box’s two mounting slots to mount the M2 to a vertical surface at the
monitoring site. The window in the cover on the front of the junction box allows you to
view the LCD display and use the magnetic wand to actuate the magnetic control
switches so you can perform non-intrusive calibration. Removing the cover allows you to
access the interior of the junction box.
Detector Junction Box
The detector junction box is intended to be installed remotely from the M2 junction box.
The combustible gas detector is factory installed in the bottom 3/4” NPT conduit hub
using a 3/4 in. x 1/2 in. NPT reducer. A terminal strip is provided for wiring connections
and the detector is factory wired to one side of this terminal strip. The other side of the
terminal strip is for user-supplied wiring to the detector terminal strip located in the M2
junction box. This wiring should go through the top 3/4” conduit hub. Three spacers
installed on the back of the junction box controls the di stance of the junction box from a
mounting surface.
Combustible Gas Detector
The combustible gas detector is a catalytic type detector that produces an electrical output
that corresponds to the detection range. It is packaged in a 1/2 inch NPT nipple with a
sintered metal flame arrestor on one end allowing ambient air to diffuse into the detector.
The flame arrest or al so co ntai n s any s park s whi ch may occur within the detector. The 1/2
inch NPT mounting threads at the top of the detector allow you to mount it into the
bottom conduit hub of the junction box. The junction box conduit hub is 3/4” NPT, so a
3/4 in. x 1/2 in. NPT reducer is used to install the combustible gas detector. A rainshield
screws onto the bottom of the detector (flame arrestor end). The rainshield helps protect
the detector from rain and debris in the monitoring environment. Four color-coded leads
extend from the top of the detector. The leads allow you to connect the detector to the
terminal strip.
Calibration Adapter/Splash Guard
A calibration adapter/splash guard is installed on the combustible gas detector. A fitting
at the bottom of the calibration adapter/splash guard allows a length of tubing to be
connected for calibration and routed to a more easily accessible location (near the M2
junction box is optimal for ease of calibration). The calibration adapter/splash guard also
protects the detector from splashing water or direct water spray.
Magnetic Wand
The magnetic wand is a short plastic rod with a magnet in one end. It is used to actuate
the magnetic control switches on the control PCB while the junction box cover is still
installed so that non-intrusive calibration can be performed.
65-2610RK-04 M2 Transmitter Opera tor’s Manual4
Internal Description
This section describes the interna l components of the M2. The internal components of the
M2 include t he t e rminal PCB which pro v i de s f or all the wiring connections to the M2 and
the control PCB which displays the gas reading and has the control buttons.
3/4" NPT Conduit Ope ni n g
Power/Signal
Terminal Strip
Detector Terminal Strip
Detector
Cur rent Po t
(Factory
Adjust)
Programming
Connector
(Factory Use)
Modbus
Terminal Strip
Termination
Jumper
for Wire Entry
- S +
PWR/SIG
- S +
LELPWR/SIG
LEL
R W G B
R W G B
R S 485
RS 485
A B C
A B C
Display
Ribbon Cable
Connector
Relay
Terminal
Strips
FAIL
C NC NO
ALARM 1
C NC NO
ALARM 2
C NC NO
3/4" NPT Conduit
Op ening f or
Det e cto r J -Box
Wiring
Junction Box
Terminal PCB
Control PCB
Magnetic
Switches
UP/YES
DOWN/NO
ENTER
Push Button
Contro l Sw itc hes
UP/YES
DOWN/NO
ENTER
Fail LED
Al arm 1 LED
Al arm 2 L ED
RX L ED
TX LED
RKI INS TRUMENTS
M2 TRANSM ITTER
L CD Display
View With Cover and
Control PCB Removed
View With Cover Removed
Figure 2: M2 Internal Component s
Terminal PCB
The terminal PCB is encapsulated in epoxy for protection against moisture and physical
damage. It is mounted into the rear of the junction box with three standoffs and rests on a
thin layer of foam. A banana jack is screwed into each of the standoffs and used for
mounting the control PCB. The terminal PCB converts the electrical output from the
detector to a signal which can be displayed by the LCD display, a 4 - 20 mA signal (that is
proportional to the detection range), and an RS-485 Modbus output signal. The 4 - 20 mA
signal may be used by a recording device, gas monitor controller, or programmable
controller. The Modbus output may be used to connect the M2 to a Modbus network. The
terminal PCB also controls three relays, one fail and two gas alarm relays.
Two columns of plug-in style terminal strips are used to make all wiring connections to
the M2. The column on the left consists of the power/signal, detector, and Modbus
terminal strips. The column on the right consists of the relay terminal strips. A 20 position
connector at the bottom of the terminal PCB is used to connect the terminal PCB to the
565-2610RK-04 M2 Transmitter Operator’s Manual
control PCB with a ribbon cable. A 5 position connector on the left side of the terminal
PCB is used by factory or field service personnel to program the M2. A factory adjust pot
just above the programming connector is used to set the detector current.
Power/Sign al Terminal Strip
The power/signal terminal strip is a three position plug-in style terminal strip located at
the top of the left terminal column. It is used to connect 24 VDC power to the M2 and to
connect the 4 - 20 mA output signal to a device.
The signal output, the S terminal, does not have to be connected for the M2 to function.
The S terminal is used if you want to connect the 4 - 20 mA output signal to another device
such as a gas monitoring controller, chart recorder, or programmable controller (PLC).
Detector Terminal Strip
The detector terminal strip is a four position plug-in style terminal strip and is the middle
terminal strip in the left terminal column. All four terminals are used to connect the
detector to the M2.
Detector
Terminal Strip
- S +
PWR/SIG
- S +
LEL
R W G B
RS 4 85
A B C
PWR/SIG
LEL
R W G B
RS 485
A B C
C NC NO
C NC NO
C NC NO
FAIL
ALARM 1
ALARM 2
Figure 3: Detect o r Term inal Strip
NOTE:The detector is factory-wired to the M2. See “Wiring the M2 Transmitter” on
page 11 for all wiring procedures related to M2.
Modbus Terminal Str ip
The Modbus terminal strip is a three position plug-in style terminal strip and is the
bottom terminal strip in the left terminal column. It allows connection of the M2 into a
Modbus network.
Relay Terminal Strips
The right column of terminal strips consists of, from top to bottom, the fail, alarm 1, and
alarm 2 relay terminal strips. The y are three-positio n plug-in style terminal strips. The
relay terminal strips are used to connect devices such as lights and horns that are
controlled by the relay contacts. The relay contacts are rated at 115 VAC, 5 amps. The relay
contacts may also be used to control higher rated relays.
65-2610RK-04 M2 Transmitter Opera tor’s Manual6
Termination Jumper
A two pin header with a termination jumper installed is located below the Modbus
terminal strip. The jumper has no function unless the M2 is wired into a Modbus
installation. See “Chapter 8: RS-485 Modbus Output” on page 36 for a description of using
the M2 in a Modbus system.
Control PCB
The LCD display and control switches are located on the control PCB. It is installed on top
of the terminal PCB by lining up its three spacing standoffs with the banana jacks in the
terminal PCB mounting standoffs and pushing it ont o the banana jacks. The jacks retain
the control PCB.
LCD Display
The LCD display is located at the top of the control PCB. It indicates the current gas
reading and displays messages and parameters in the M2’s programs.
Control Buttons
The M2 includes three push button switches that allow you to enter the M2’s operating
modes, navigate through the modes, update settings, an d save changes to the settings.
The push button switches are located along the bottom edge of the control PCB (see
Figure 2). The UP/YES button is on the left, the DOWN/NO button is in the middle, and
the ENTER button is on the right.
Table 2: M2 Control Button Functions
SwitchFunction
UP (YES)•Saves settings
•Changes the displayed set t ing
•Enters th e Calibration Program
•Enters Gas Type Mode (press with DOWN/NO button)
•Enters Configuration Mode (pres s with EN TER button )
DOWN (NO)•Cancels setting changes
•Changes the displayed set t ing
•Enters Gas Type Mode (press with UP/YES button)
•Enters Modbus Mode (press with ENTER button )
•Displays the Information Screen
ENTER•Initiates operations
•Enters Configuration Mode (press with UP/YES button)
•Enters Modbus Mode (press w ith DOW N /NO button)
•Functions as an alarm reset switc h
Just above each push button switch is a magnetic switch with the same function as th e
push button switch below it. The magnetic switches are for use in non-intrusive
calibration. They are actuated by bringing the magnetic wand close enough to them to
actuate them. Although the magnetic switches have the same functions as the push button
switches, it is not practical to use them for operations other than calibration because it is
not possible to actuate two magnetic switches at once with only one magnetic wand. Since
displaying the Information Screen only requires the use of one switch, the wand may be
used to show the Information Screen (see “Information Screen” on page 17).
765-2610RK-04 M2 Transmitter Operator’s Manual
Status LEDs
The M2 includes five status LEDs that are located above the display (see Figure 2).
•Fail LED
The fail LED turns on when the M2 is experiencing a fa il condition. A fail condition
can be caused by a detector failure or low detector signal.
•Alarm 1 LED
The alarm 1 LED is on when the M2 is experiencing an alarm 1 condition.
•Alarm 2 LED
The alarm 2 LED is on when the M2 is experiencing an alarm 2 condition.
•RX & TX LED’s
These LED’s indicate data being received (RX) and transmitted (TX) when the M2’s
Modbus output is operating.
65-2610RK-04 M2 Transmitter Opera tor’s Manual8
Chapter 3: Installation & Startup
b
Overview
This chapter describes procedures to mount the M2 Transmitter in the monitoring
environment and wire it to input power and devices.
Mounting the M2 Transmitter
1.Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.
•For the M2 junction box, select a site where the junction box is not likely to be
bumped or disturbed. Make sure there is sufficient room to perform start-up,
maintenance, and calibration procedures. The site should be easily a ccessible.
•For the detector junction box, select a site where the target gas is likely to be found
first. For lighter gases, mount the detector near the ceiling; for heavier gases,
mount the detector near the floor.
5.86
•The junction boxes should be mounted no further than 200 feet from each other.
2.Use #10 screws through the M2 junction box’s two mounting slots to secure the
junction box to a vertical surface. Figure 4 shows the outline and mounting
dimensions the M2 junction box. Figu re 5 shows the outline and mounting
dimensions for the detector junction box. Mount the detector junction box with the
detector facing down as shown in Figure 5.
3.Install 3/16 inch I.D. flexible po lyurethane tubing to the fitting at the bottom of the
calibration adapter/splash guard and route it to an accessible area that is close to the
M2 junction box. See the “Parts List” on page 46 for available tubing.
65-2610RK-04 M2 Transmitter Opera tor’s Manual10
Wiring the M2 Transmitter
WARNING :Always verify that the power to the M2 is off before you make wiring
connections.
1.Confirm that no power is being applied to the M2.
2.Remove the detector junction box’s cover from the junction box.
3.Remove the M2 junction box’s cover from the junction box.
4.Grasp the control PCB by its edges.
5.Gently pull until the control PCB is pulled away from the banana jacks. Take care not
to pull too hard and damage the cable which connects the control and terminal PCBs.
6.Let the control PCB hang by the cable. The terminal strips are now visible on the
terminal PCB. The control PCB may be left hanging while wiring is done. If desired,
the control PCB may be disconnected from the cable and set aside while wiring.
7.Guide a four-conductor, shielded cable or four wires in conduit through the top
conduit hub of the detector junction box. To make wiring more convenient, use wire
colors that correspond to the detector wire colors: red, white, green, and black.
NOTE: Consult RKI Instruments, Inc. for cable lengths longer than 200 feet.
8.Connect the detector leads to the terminal block in the detector junction box.
9.Secure the detector junction box’s cover to the junction box.
10. Guide the other end of the four-conductor, shielded cable or four wires in conduit
through the bottom conduit hub of the M2 junction box.
11. To gain access to a plug-in termi nal strip for wiring, pull it out of its socket by
grasping the wall between two terminal positions with needle nose pliers and pulling.
Be careful not to exert too much force on the wall to avoid damage to the terminal
strip. The detector terminal strip and th e alarm 1 r elay t ermi nal strip ma y be r emo ved
by grasping them with your fingers if the adjacent terminal strips have been removed.
WARNING:If the M 2 is installed in a hazardous location, use app ropriatel y rated
conduit, conduit fittings, and appropriate construction technique that
complies with the local electrical code.
In addition, use appropriately rated conduit, conduit fittings, and
appropriate construction technique to maintain the NEMA 4
environmental rating of the junction box and avoid water entering the
junction box at the conduit hubs.
12. Pull out the detector terminal strip and connect the four wires to the terminal strip as
follows (see Figure 6).
•Connect the wire corresponding to the detector ’s red wire to the LEL “R”
terminal.
•Connect the wire corresponding to the detector’s white wire to the LEL “W”
terminal.
•Connect the wire corresponding to the detector’s green wire to the LEL “G”
terminal.
1 165-2610RK -04 M2 Transmitter Operator’s Manual
Detector
Termina l
Strip
•Connect the wire corresponding to the detector’s black wire to the LEL “B”
terminal.
CAUTION: If shielded cable is used, leave the cable shield ’s drain wire disconnected and
insulated at the detector junction box. You will connect the opposite end of the cable’s
drain wire to the M2 junction box’s chassis (earth) ground.
Cable
Shield
- S +
PW R/SIGR S 485
- S +
LEL
R W G B
A B C
FAIL
C NC NO
L ELPW R /S IGR S 485
C NC NO
R W G B
ALARM 2ALARM 1
C NC NO
A B C
Black
Green
White
Red
M2
J-Box
Green
White
Red
Detector J-Box
Combustible G as
Detector
Calibration Adapter /Splash Guard
Figure 6: Wiring the Detector to the M2
13. Reinstall the detector terminal strip into its socket.
14. If shielded cable is used between the detector junction box and the M2 junction box,
connect the cable’s drain wire to an available chassis (earth) ground at the M2 junction
box. Do not connect the shield drain wire at the detector junction box.
15. Guide multi conductor shielded cable or cables or wires in conduit through the top
conduit hub of the M2 junction box. The number of cables or wires needed will
Black
65-2610RK-04 M2 Transmitter Opera tor’s Manual12
depend on whether the M2 is wired to a gas monitoring controller or just to power,
whether any relays are used, and whether the Modbus output is used.
NOTE:If the M2 is being wired to a PLC or DCS device, see “Appendix B: PLC and
DCS Device Wiring” on page 48, then continue with step 8.
Use the following recommendations to determine how to wire the M2:
•If Modbus connections will not be used and only the PWR/SIG connections will
be used, use a two or three conductor shielded cable or two or three wires in
conduit for connections to the power/signal terminal strip depending on whether
or not the signal (S) terminal is used. The S terminal has a 4 - 20 mA output, but if
you do not need to monitor this signal and do not connect to th e S termi na l to
access this signal, the M2 will still function completely.
Table 3: Wire Size for PWR/SIG Connections
Max Distance to Controller
w/18 Gauge Wire
Max Distance to Controller
w/16 Gauge Wire
Max Distance to Controller
w/14 Gauge Wire
2,500 ft.5,000 ft.8,000 ft.
•If the PWR/SIG connections and one or more relays are used, route the
connections to the M2 in conduit. Use shielded cable in the conduit for the PWR/
SIG connections and unshielded cable or individual wires for the relay
connections. Make sure any wire or cable used for relay wiring is appropriately
rated for the power that it will carry.
CAUTION:If shielded cable is used for the PWR/SIG connections, leave the cable shield’s drain
wire insulated and disconnected at the M2 junction box. You will connect the
opposite end of the cable’s drain wire at the controller or device.
•If the M2 will be wired into a Modbus network, see “Chapter 8: RS-485 Modbus
Output” on page 36.
1 365-2610RK -04 M2 Transmitter Operator’s Manual
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.