Read and understand this instruction manual before operating
detector . Improper use of the dete ctor could result in bodily harm
or death.
Periodic calibration and maintenance of the detector is essential
for proper operation and correct readings. Please calibrate and
maintain this detector regularly! Frequency of calibration
depends upon the type of use you have and the sensor types.
T ypical calibration frequencies for most applications a re between
3 and 6 months, but can be required more often or less often
based on your usage.
65-2484RK-06 Multi Point De tector
Product Warranty
RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in
materials, workmanship, and performance for a period of one year fr o m date of shipment
from RKI Instruments, Inc. Any parts found defective withi n tha t period will be repaired
or replaced, at our option, free of charge. This warranty does not apply to those items
which by their nature are subject to deterioration or consumption in normal ser v ice, and
which must be cleaned, repaired, or replaced on a routine basis. Examples of such items
are:
W arranty is voided by abuse including mechanical damage, alteration, rough handling, or
repair procedures not in accordance with the operator’s manual. This warranty indicates
the full extent of our liability , a nd we are not r esponsible for removal or r eplacement costs,
local repair costs, transportation costs, or contingent expenses incurred without our prior
approval.
a) Absorbent cartridgesd) Batteries
b) Pump diaphragms and valvese) Filter elements
c) Fuses
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER
WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED,
AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF
RKI INSTRUMENTS, INC. INCLUDING BUT NOT LIMITED TO, THE
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS,
INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR CONSEQUENTIAL
LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF
ITS PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR
OPERATE PROPERLY.
This warranty covers instruments and parts sold to users by authorized distributors,
dealers, and representatives as appointed by RKI Instruments, Inc.
We do no t as su me indemnif ic a t ion for any accident or d amage caused b y t he op e r a t ion of
this gas monitor, and our warranty is limited to the replacement of parts or our complete
goods.
This manual describes the 65-2484RK-06 multi point direct connect detector. This manual
also describes how to install, start up, maintain, and calibrate the detector when it is used
with a gas monitoring controller. A parts list at the end of this manual lists replacement
parts and accessories for the detector.
Specifications
WARNING: Do not use this product in a manner not specified in thi s instruction
manual.
Table 1 lists specifications for the multi-point detect or.
Table 1: Specifications
Target GasLEL/O
S/SO2, methane calibration standard for LEL
2/H2
*Note: Since the 65-2484RK-06 is a direct connect detector, the
calibration is done at the controller.
Sampling MethodDiffusion
Detection RangeLEL: 0 to 100 %LEL (lower explosive limit)
: 0 to 25 %volume
O
2
H
S: 0 to 100 ppm (parts per million)
2
: 0 to 6.00 ppm (parts per million)
SO
2
Response Time90% in 30 seconds
AccuracyCatalytic Combustible Gas
:
± 5% of reading or ± 2% LEL (whichever is greater)
Oxygen
± 0.5% O
:
2
Hydroge n Sulfide:
± 5% of reading or ± 2 ppm H2S (whichever is greater)
Sulphur Dioxide
:
± 10% of reading or ± 5% of full scale (whi chever is greater)
Operating Temperature23°F to 104°F (-5°C to 40°C)
65-2484RK-06 Mult i P o in t D e te c to r • 1
NOTE: The following symbol on the detector label is a caution to the user to refer to this
!
documentation for installation and operation instructions:
WARNING: When using the 65-2484RK-06, you must follow the instructions and
warnings in this manual to assure proper and safe opera tion of the
65-2484RK-06 and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 65-2484RK-06 as described in this
manual.
2 • 65-2484RK-06 Multi Point Detector
Description
This section describes the multi-point detector. It consists of the detectors, the terminal
strips, the conduit seal, and the junction boxes.
Detectors
This section describes the components of the various detectors that are used with each
model of the 65-2484RK-06.
The combustible gas detector is a catalytic type detector that produces an electrical output
that corresponds to the detection range. It is packaged in a 1/2 inch NPT nipple with a
sintered metal flame arrestor on one end allowing ambient air to diffuse into the detector.
The flame arrest or al so co ntai n s any s park s whi ch may occur within the detect or. The 1/2
inch NPT mounting threads at the top of the detector allow you to install it in the bottom
conduit hub of the junction box with the use of a 3/4 in. x 1/2 in. NPT reducer. A
rainshield screws onto the bottom of the detector (flame arrestor end). The rainshield
helps protect the detector from rain and debris in the monitoring environment. Four colorcoded leads extend from the top of the detector. The leads allow you to connect the
detector to the terminal block.
65-2484RK-06 Mult i P o in t D e te c to r • 3
Oxygen Detector
The detector consists of the oxygen sensor, the detector housing body, detector housing
cap, and cap gasket.
Detector Housing Body
Cap Gasket
Plug-in Oxygen Sensor
Detect or Housing Cap
Flame Arrestor
Guard
Figure 2: Oxygen Detector Component Location
Detector Housing Body
The detector housing body protects the electronic components within the housing. Use the
mounting threads at the top of the housi ng to screw the oxygen detector into the 3/4”
NPT hub on the bottom of the junction box. Two wires extend from the top of the detector
housing body . Use these wires to connect the oxygen detector to the terminal block. One of
the wires is white and one of the wires is green.
The housing includes two sockets installed on a circuit board. These sockets accept the
plug-in sensor’s two pins to provide electrical connection for the sensor. The circuit board
with the sockets conditions the sensor’s signal before the signal reaches the controller.
Housing Cap & Cap Gasket
The housing cap screws onto the detector housing. It retains the plug-in sensor and
protects it from damage. A foam gasket is installed inside the ho using cap that seals
against the sensor face. The housing cap also includes a flame arrestor which contains any
sparks that may occur within the detector and a flam e arrestor guard wh ich protects th e
flame arrestor from damage. Unscrew the detector cap to access the plug-in sensor for
maintenance or replacement. A cap gasket seals the interface between the housing and
cap.
Plug-in Oxygen Sensor
The plug-in sensor is secured in the detector assembly by the housing cap. It has two pins
that mate with the sockets in the detector housing body. Through a series of chemical and
electrical reactions, the sensor produces an electrical output that corresponds to the
detection range of the transmitter.
4 • 65-2484RK-06 Multi Point Detector
H2S Detector
The detector consists of the H
S sensor, the detector housing body, detector housing cap,
2
and cap gasket.
Detector Housing Body
Cap Ga s ket
Pl u g- In H2S Sen sor
Detector Housing Cap
Flame Arrestor
Guard
Figure 3: H
Detector Housing, Housing Cap, & Cap Gasket
The detector housing protects the sensing components within the housing. Use the
mounting threads at the top of the housing to screw the H
Use the removable cap near the bottom of the housing to access the sensor for
maintenance or replacement. The cap protects the sensor from damage and includes a
flame arrestor which contains any sparks which may occur within the detector housing. A
cap gasket seals the interface between the housing and cap. A flame arrestor guard is
permanently bonded to the cap.
S Detector Component Location
2
S detector into a 3/4” NPT hub.
2
Two wires extend from the top of the detector housing. Use these wires to connect the H
2
detector to the multi-point detector. The housing includes a four-socket pattern. This
socket pattern accepts the sensor’s four pins to secure the sensor within the detector
housing. A pre-amplifier, located between the sockets and two interconnect wires,
conditions the sensor’s signal before the signal reaches the controller.
Sensor
The sensor is secured within the sensor housing by the detector housing cap. It has four
pins that mate with the sockets in the detector housing body . Thr ough a series of chemical
and electrical reactions, the sensor produces an electrical output that is proportional to the
detection range of the detector.
65-2484RK-06 Mult i P o in t D e te c to r • 5