RKI Instruments 65-2340RK User Manual

65-2340RK
Toxic Gas Transmitter
Operator’s Manual
Part Number: 71-0143RK
Revision: C
RKI Instruments, Inc.
www.rkiinstruments.com
WARNING
Read and understand this instruction manual before operating detector . Improper use of the dete ctor could result in bodily harm or death.
Periodic calibration and maintenance of the detector is essential for proper operation and correct readings. Please calibrate and maintain this detector regularly! Frequency of calibration depends upon the type of use you have and the sensor types. T ypical calibration frequencies for most applications a re between 3 and 6 months, but can be required more often or less often based on your usage.
65-2340RK Toxic Gas Transmitter
Product Warranty
RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year fr o m date of shipment from RKI Instruments, Inc. Any parts found defective withi n tha t period will be repaired or replaced, at our option, free of charge. This warranty does not apply to those items which by their nature are subject to deterioration or consumption in normal ser v ice, and which must be cleaned, repaired, or replaced on a routine basis. Examples of such items are:
W arranty is voided by abuse including mechanical damage, alteration, rough handling, or repair procedures not in accordance with the operator’s manual. This warranty indicates the full extent of our liability , a nd we are not r esponsible for removal or r eplacement costs, local repair costs, transportation costs, or contingent expenses incurred without our prior approval.
a) Absorbent cartridges d) Batteries b) Pump diaphragms and valves e) Filter elements c) Fuses
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED, AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF RKI INSTRUMENTS, INC. INCLUDING BUT NOT LIMITED TO, THE WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS, INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR CONSEQUENTIAL LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF ITS PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR OPERATE PROPERLY.
This warranty covers instruments and parts sold to users by authorized distributors, dealers, and representatives as appointed by RKI Instruments, Inc.
We do not assume inde mn ification for any accident or dama g e c au s e d b y t he op e ration of this gas monitor, and our warranty is limited to the replacement of parts or our complete goods.
65-2340RK Toxic Gas Transmitter
Table of Contents
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Toxic Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Junction Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting the Toxic Gas Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Wiring the Toxic Gas Transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Introducing Incoming Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Setting the Zero Signal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Replacing Components of the Toxic Gas Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Calibration Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Preparing for Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Setting the Zero Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Setting the Response Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Returning to Normal Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
65-2340RK Toxic Gas Transmitter
Overview
This manual describes the 65-2340RK toxic gas transmitter. This manual also describes how to install, start up, maintain, and calibrate the toxic gas transmitter when used with a gas monitoring controller. A parts list at the end of this manual lists replacement parts and accessories for the toxic gas transmitter.
The 65-2340RK toxic gas transmitter can be used for various target gases which are listed in Table 1 below. For a particular target gas, the part number of the toxic transmitter will be of the format 65-2340RK-XXX. For example, 65-2340RK-NH3 is for ammonia (NH
detection.
Specifications
Table 1 lists specifications for the toxic gas transmitt er.
Table 1: Specifications
)
3
Target Gas 65-2340RK-ASH3: Ar sine (AsH
65-2340RK-CL2: Chlorine (Cl 65-2340RK-CL-10: Chlorine (Cl
)
3
)
2
)
2
65-2340RK-HCN: Hydrogen Cyanide (HCN) 65-2340RK-NH3: Ammonia (NH
65-2340RK-SO2: Sulphur Dioxide (SO 65-2340RK-P H3: Phosphine (PH
)
3
)
2
)
3
Sampling Method Diffusion Detection Range AsH
: 0 - 1.50 ppm
3
: 0 - 3.00 ppm
Cl
2
Cl
: 0 - 10.0 ppm
2
HCN: 0 - 15.0 ppm
: 0 - 75.0 ppm
NH
3
: 0 - 6.00 ppm
SO
2
: 0 - 1.00 ppm
PH
3
Accuracy ± 10% of reading or ± 5% of full scale (whichever is greater) Signal Output 4 to 20 mA Response Time • Cl
and NH3: T90 in 90 seconds
2
• All others: T90 in 45 seconds
Operating Temperature & Humidity
W ARNING: When using the 65-2340RK, you must follow the instructions and warnings
• 14°F to 104°F (-10°C to 40°C)
• 20% to 90% Relative Humidity
in this manual to assure proper and safe operation of the 65-2340RK and to minimize the risk of personal injury. Be sure to maintain and period ically calibrate the 65-2340RK as described in this manual.
65-2340RK Toxic Ga s Tra nsm itter • 1
Description
FactoryAdjustPot
Co ntro l lerTer m inal Strip
Amplifier
Mounting Screw
Detector Terminal Strip
Black - Test Point
Red +Test Point
J-Box
Span Pot
Zer o Pot
ZERO
SPAN
TOXIC OXY
SIG/PWR
S
Toxic Detector
This section describes the components of the toxic gas transmitter. The toxic gas transmitter is a 4 - 20 mA type detector head. It consists of the toxic detector, amplifier, and juncti on box.
2 • 65-2340RK Toxic Gas Transmitter
Figure 1: Toxic Transmitter Component Location
Toxic Detector
Splas h Guard (removable)
Sensor (different for each detector type)
Detect or Ho usin g Cap
Cap Gasket
Det e c tor H o us ing Body (different for each detector type)
The toxic detector consists of the detector housing body, detector housing cap, splashguard, cap gasket, and the plug -in sensor.
Figure 2: Toxic Detector Component Location
Detector Housing Body
The detector housing body protects the electronic components within the housing. Use the mounting threads at the top of the housi ng to screw the toxic detector into the 3/4” NPT hub on the bottom of the junction box. Two wires extend from the top of the detector housing body. Use these wires to connect the toxic detector to the amplifier. One of the wires is black and one of the wires is color coded depending on the detector type. See Figure 4 on page 7 for the color code assignments.
The housing body includes a 12 position connector at the bottom of the housing body. The plug-in sensor mates to this connector. A pre-amplifier located between the connector and the two interconnect wires conditions the sensor’s sign al before the signal reaches the controller . Ea ch plug-in sensor type (Cl
there is a different detector housing body for each gas type.
Housing Cap, Cap Gasket, & Splashguard
The housing cap screws onto the detector housing. It retains the plug-in sensor and protects it from damage. A removable splashguard is screwed onto the detector cap to protect the sensor from impact damage, direct water spray, and splashing. Unscrew the detector cap to access the sensor for maintenance or replacement. A cap gasket seals the interface between the housing and cap.
Plug-In Sensor
The plug-in sensor is secured in the detector assembly by the housing cap. There is a different sensor for each target gas. Through a series of chemical and electrical reactions, the sensor produces an electrical output that corresponds to the detection range of the sensor.
Amplifier
The amplifier converts the electrical output from the detector to a 4 to 20 mA signal that
for example) requires a diffe rent pr e-amplifier, so
2
65-2340RK Toxic Ga s Tra nsm itter • 3
Loading...