RKI Instruments 61-1000RK User Manual

61-1000RK
Combustible Gas Detector
Operator’s Manual
Part Number: 71-0067RK Revision: D Released: 1/31/13
www.rkiinstruments.com
WARNING
Read and understand this instruction manual before operating detector . Improper use of the dete ctor could result in bodily harm or death.
Periodic calibration and maintenance of the detector is essential for proper operation and correct readings. Please calibrate and maintain this detector regularly! Frequency of calibration depends upon the type of use you have and the sensor types. T ypical calibration frequencies for most applications a re between 3 and 6 months, but can be required more often or less often based on your usage.
Product Warranty
RKI Instr umen ts, I nc. wa rran ties gas a larm equi pment sold by us to be fr ee f rom def ects in materials, workmanship, and performance for a period of one year fr o m date of shipment from RKI Instruments, Inc. Any parts found defective withi n tha t period will be repaired or replaced, at our option, free of charge. This warranty does not apply to those items which by their nature are subject to deterioration or consumption in normal ser v ice, and which must be cleaned, repaired, or replaced on a routine basis. Examples of such items are:
W arranty is voided by abuse including mechanical damage, alteration, rough handling, or repair procedures not in accordance with the operator’s manual. This warranty indicates the full extent of our liability , a nd we are not r esponsible for removal or r eplacement costs, local repair costs, transportation costs, or contingent expenses incurred without our prior approval.
a) Absorbent cartridges d) Batteries b) Pump diaphragms and valves e) Filter elements c) Fuses
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED, AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF RKI INSTRUMENTS, INC. INCLUDING BUT NOT LIMITED TO, THE WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS, INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR CONSEQUENTIAL LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF ITS PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR OPERATE PROPERLY.
This warranty covers instruments and parts sold to users by authorized distributors, dealers, and representatives as appointed by RKI Instruments, Inc.
We do not assume indemnification fo r any accident or dama g e ca u s e d by the operation of this gas monitor, and our warranty is limited to the replacement of parts or our complete goods.
61-1000RK Combustible Gas Detector
Table of Contents
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
61-0140RK Combustible Gas Detector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Junction Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mounting the Combustible Gas Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Wiring the Combustible Gas Detector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Introducing Incoming Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Setting the Zero Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Replacing the Combustible Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Calibration Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Preparing for Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Setting the Zero Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Setting the Response Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Returning to Normal Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Overview
This manual describes the 61-1000RK combustible gas detector (internal amplifier type). This manual also describes how to install, start up, maintain, and calibrate the detector when it is used with a gas monitoring controller. A parts list at the end of this manual lists replacement parts and accessories for the combustible gas detector.
The 61-1000RK combustible gas detector includes the 61-0140RK combustible gas detector and a junction box. This manual may also be used for the 61-0140RK combustible gas detector which does not include a junction box and is normally mounted in one of a controller’s conduit hubs. If you are using a 61-0140RK combus tible gas detector, disregard all references to the junction box and junction box terminal strip.
Specifications
WARNING: Do not use this product in a manner not specified in thi s instruction
Table 1 lists specifications for the combustible gas detector.
manual.
Table 1: 61-1000RK Specifications
Target Gas Combustible gas (Methane Calibration Standard) Area Classification Explosionproof for Class I, Groups B, C, and D Sampling Method Diffusion Detection Range 0 to 100% LEL Response Time 90% in 45 seconds Accuracy ± 5% of reading or ± 2% LEL (whichever is greater)
W ARNING: When using the 61-1000RK, you must follow the instructions and warnings
in this manual to assure proper and safe operation of the 61-1000RK and to minimize the risk of personal injury. Be sure to maintain and period ically calibrate the 61-1000RK as described in this manual.
61-1000RK Co m bu st i bl e G a s D e te c to r • 1
Description
J-Box
Rubber Spacer, 3X
Red
Green
Black
Hydrogen Detector
White
This section describes the components of the 61-0140RK and 61-1000RK detectors. The 61-1000RK includes the 61-0140RK combustible gas detector and a junction box. A four point terminal strip is provided inside the junction box for detector connections. The 61-0140RK does not include a junction box.
Figure 1: 61-1000RK Component Location
61-0140RK Combustible Gas Detector
The combustible gas detector is a catalytic type detector that produces an electrical output that corresponds to the detection range. It is packaged in a 1/2 inch NPT nipple with a sintered metal flame arrestor on one end allowing ambient air to diffuse into the detector. The flame arrest or al so co ntai n s any s park s whi ch may occur within the detector. The 1/2 inch NPT mounting threads at the top of the detector allow you to mount it into the bottom conduit hub of t he junction box. The controller conduit hubs are normally 3/4” NPT, so a 3/4 in. x 1/2 in. NPT reducer may be necessary to install the combustible gas detector. A rainshield screws onto the bottom of the detector (flame arrestor end). The rainshield helps protect the detector from rain and debris in the monitoring environment. Four color-coded leads extend from the top of the detector. The leads allow you to connect the detector to the terminal block.
Junction Box
The junction box allows you to install the detector at a mounting site that is remote from a controller, and it protects the detector wiring connections. Two conduit hubs allow you to mount the detector to the junction box and connect the wiring from the detector to a controller. Three spacers insta lled on the back of the junction box control the distance of the junction box from a mounting surface and ensure that there is enough room to install a calibration cup on the detector during calibration.
The bottom conduit hub includes a 3/4 in. x 1/2 in. reducer that allows you to screw the
2 • 61-1000RK Combustible Gas Detector
Installation
J-Box
2.70 0.38
Combustible Detector
3/4x1/2Reducing Bus hing
.75
3/4 NPT Female
3.65
7.50 max Spacer, 3X
detector into the hub. The terminal block within the junction b ox facilita tes the wiring process. A cover on the front of the junction box allows ac c ess to the interior of the junction box.
This section describes procedures to mount the combustible gas detector in the monitoring environment and wire the detector to a controller.
NOTE: The 61-0140RK detector retains its explosion proof classification only when
installed in the explosion proof junction box. The detecto r is not explosion proof if installed in a controller conduit hub.
Mounting the Combustible Gas Detector
1. Select a mounting site that is representative of the monitoring environment. Consider the following when you select the mounting site.
Select a site where the detector is not likely to be bumped or disturbed. Ma ke sur e
there is sufficient room to perform start-up, maintenance, and calibration procedures.
Select a site where the target gas is likely to be found first. For lighter gases,
mount the detector near the ceiling; for heavier gases, mount the detector near the floor.
Figure 2: Mounting the Combustible Ga s Detector
61-1000RK Co m bu st i bl e G a s D e te c to r • 3
2. At the mounting site you select, hang or mount the junction box with the detector
facing down (see Figure 2).
Wiring the Combustible Gas Detector to a Controller
WARNING: Always verify that the power to the controller is off before you make
wiring connections.
1. Turn off the controlle r.
2. Turn off power to the controller.
3. If the detector is mounted remotely from a controller using the junction box, proceed to step 4.
If the detector is mounted directly to a controller, it is normally factory wired. Confirm that the detector’s wires are connected to the appropriat e contr oller det ector termin als and skip to “S tart Up” on page 6. See F igu re 3, the c ontroller operat or’s manual, and the controller’s detector head specification sheet for the 61-0140RK detector for the wiring connection s.
4. Remove the junction box cover.
5. Guide a four-conductor, shielded cable or four wires in conduit through the unused conduit hub of the junction box. Use appropriate conduit fittings and construction technique for the environmental rating and hazardous location classification of the junction box. The junction box is rated NEMA 4X and classified explosion proof for Class I, Groups B, C, and D.
6. Connect the detector leads to the terminal block in the junction box.
CAUTION: Leave the shield drain wire insulated and disconnected at the detector. You will
connect the opposite end of the cabl e’s drain wire at the controller.
7. Secure the junction box cover to the junction box.
8. Route the cable or wires leading from the combustible gas detector through one of the conduit hubs at the controller housing. Use appropriate conduit fittings and construction technique for the environmental rating of the controller. RKI controllers are typically rated NEMA 4X.
CAUTION: Do not route power and detector wiring through the same conduit hub. The power
cable may disru pt the transmission of the detect or signal to the controller.
9. Connect the wires to the applicable controller terminal strip. See the controller operator’ s manual and the controller’s detector head specification sheet for the 61-1000RK detector.
10. If using shielded cable, connect the cable’s drain wire to an available chassis ground at the controller. R KI controllers typically have a ground stud that is a convenient grounding location.
4 • 61-1000RK Combustible Gas Detector
Te rminal Strip
Black
White
J-Box
Combus tible Detector
Controller LEL
Detector Terminals
GREEN BLACK
RED WHITE
Detector Wires
Green
Red
Figure 3: Wiring the Combustible Gas Detector to a Controller
61-1000RK Co m bu st i bl e G a s D e te c to r • 5
Start Up
This section describes procedures to start up the combustible gas detector and place the detector into normal operation.
Introducing Incoming Power
1. Complete the installation procedures described earlier in this manual.
2. Verify that the power wiring to the controller is correct and secure. Refer to the controller operator’s manual.
3. Turn on power to the controller.
4. Turn on the controller.
5. Verify that the controller is on and op erating properly. Refer to the controller operator’s ma nual.
CAUTION: Allow the detector to warm up for 5 minutes before you continue with the next
section, “Setting the Zero Reading”.
Setting the Zero Reading
WARNING: Do not remove the junction box cover while the circuits are energized
unless the area is determined to be non-hazardous. Keep the junction box cover tightly closed during operation.
CAUTION: If you suspect the presence of combustible gas in the monit oring environment, use
the zero air calibration cylinder to introduce “fr e sh air” to the dete ctor and verify an accurate zero reading.
1. Verify that the detector is in a fresh air environment (environment known to be free of combustible gas and of normal oxygen concentration, 20.9%).
2. Verify a reading of 0% LEL at the controller. If the display reading is 0% LEL, start up is complete. The combustible d e tector is in
normal operation. If the display reading is not 0% LEL, continue with step 3.
3. Perform a zeroing operation at the controller. See the contr oller operato r’s manual for directions.
6 • 61-1000RK Combustible Gas Detector
Maintenance
This section describes maintenance procedures. It includes preventive maintenance, troubleshooting, and component replacement procedures.
Preventive Maintenance
This section describes a preventive maintenance schedule to ensure the optimum performance of the combustible gas detector. It includes daily, monthly, and qua r terly procedures.
Daily
Verify a display reading of 0% LEL at the controller. Investigate significant changes in the reading.
Monthly
This procedure describes a test to verify that the combustible gas detector responds properly to the target gas.
WARNING: The controller is not an active gas monitoring device during the response
test procedure.
NOTE: Performing a response te st on the combustible detector may cause alarms. Be
sure to put the controller into its calibration program or disable external alarms before performing this test.
NOTE: The following procedure assumes the use of a calibration kit which includes a
calibration gas cylinder, a 0.5 LPM fixed flow regulator with an on/off knob, a calibration cup for the detector, and a length of sample tubing.
Preparing for the response test
1. Place the controller into its calibration program or disable external alarms.
2. Verify that the controller display reading is 0% LEL. If the controller reading is not 0% LEL, set the zero reading then continue this
procedure. See the controller operator’s manual for directions to set the zero reading.
3. Screw the regulator into the calibration cylinder.
4. Screw the calibration cup onto the bottom of the detector.
5. Use the calibration kit sample tubing to connect the regulator to the calibration cup.
Performing the response test
1. Turn the regulator’s on/off knob counterclockwise to open the regulator. Gas will begin to flow.
2. Allow the gas to flow for one minute.
3. Verify that the reading is within ± 20% of the gas concentration.
61-1000RK Co m bu st i bl e G a s D e te c to r • 7
NOTE: If the readings are not within ± 20% of the gas concentration, calibrate the
detector as described in the Calibration section of this manual.
4. Turn the regulator knob clockwise to close the regulator.
5. Unscrew the regulator from the calibration cylind er.
6. Unscrew the calibration cup from the detector.
7. When the display reading falls below the ala r m setpoints, return the controller to normal operation.
8. Store the components of the calibration kit in a safe place.
Quarterly
Calibrate the detector as described in the Calibration section of this manual.
Troubleshooting
The troubleshooting guide describes symptoms, probable causes, and recommended action for problems you may encounter with the combustible gas detector.
NOTE: This troubleshooting guide describes detector problems only. See the controller
operator’s manual for problems you may encounte r with the controller.
Table 2:Troubleshooting the Combustible Gas Detector
Condition Symptom(s) Probable Causes Recommended Action
Fail Condition • Controller indicates a
Slow or No Response/ Difficult or Unable to Calibrate
fail condition.
• Detector responds slowly or does not respond to response test.
• Unable to accurately set the zero or response reading during calibration.
• Detector requires frequent calibration.
Note: Under “normal” circumstances, the detector requires calibration once every three mont hs.
Some applications may require a more freque nt calibration schedule.
• The detector wiring is disconnected or misconnected.
• The detector zero signal is low enough to cause a fail condition.
• The detector is malfunctioning.
• The calibration cylinder is low, out-dated, or defective.
• The calibration gas is not an appr opriate concentration.
• The detector is malfunctioning.
1. Verify that the detector wiring is correct and secure.
2. Calibrate the det ect or.
3. If the fail condition continues, replace the detector.
4. If the fail condition continues, contact RKI for further instruction.
1. Verify that the calibration cylinder contains an adequate supply of a fresh test sample.
2. Verify that the calibration gas concentration is appropriate for the detector.
3. If the calibration/response difficulties continue, replace the detector.
4. If the calibration/response difficulties continue, contact RKI for further instruction.
8 • 61-1000RK Combustible Gas Detector
Replacing the Combustible Detector
1. Turn off the controlle r.
2. Turn off power to the controller.
3. If the detector is installed directly on a controller, open the controller door. If the detector is installed remotely from a controller in a junction box, remove the
junction box cove r.
4. If the detector is installed directly on a controller, disconnect the detector leads from the detector terminal strip in the controller. Note the position of the color-coded leads as you remove them.
If the detector is installed remotely from a controller in a junction box, disconnect the detector leads from the terminal block in the junction box. Note the position of the color-coded leads as you remove them.
5. Unscrew the detector from the controller conduit hub or junction box conduit hub.
6. Guide the detector leads of the replacement detector through the controller conduit hub or junction box conduit hub, then screw the mounting threads of the detector into the hub. If necessary for environmental conditions, apply thread sealant or teflon tape to the hub and/or detector threads to seal them.
7. If the detector is installed directly on a controller, connect the detector leads to the appropriate detector terminal strip terminals. See Figure 3 for wiring to a generic controller. See the controller operator’s manual and the controller ’s detector head specification sheet for the 61-0140RK detector for wiring specific to your controller.
If the detector is installed remotely from a controller in a junction box, connect the detector leads to the terminal block the same way the old detector was wired (see Figure 3). See the controller operator’ s manual and the controller’s detector head specification sheet for the 61-1000RK detector to verify the connections to the controller are correct.
8. If the detector is installed remotely from a controller in a junction box, reinstall the junction box cove r.
9. Turn on or plug in power to the controller.
10. Turn on the controller and place into normal operation.
CAUTION: Allow the replacement detector to warm up for 5 minutes before you continue with
the next step.
11. Calibrate the replacement detector as described in the Calibration section of this manual.
Calibration Frequency
Although there is no particular calibration frequency that is correct for all applications, a calibration frequency of every 3 to 6 months is adequate for most combustible gas detector applications. Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every 3 months.
If an application is not very demanding, for example detection in a clean, temperature controlled environment where combustible gas is not normally present and calibration adjustments are minimal at calibration, then a calibration frequency of every 6 months is
61-1000RK Co m bu st i bl e G a s D e te c to r • 9
Calibration
adequate. If an application is very demanding, for example if combustible gas is present often and in
significant concentrations or the environment is not well controlled, then more frequent calibration than e v ery 3 mo nt h s m ay be n e ces s ary. If potential catalyst poisons are known or likely to be present, more frequent ca libration than every 3 months will be necessary.
This section describes how to calibrate the combustible gas detector. It includes procedures to prepare for calibration, set the zero reading, set the response reading, and return to normal operation.
W ARNING: The controller is not an active gas monitoring device during the calibration
procedure.
NOTE: The following procedure assumes the use of a calibration kit which includes a
calibration gas cylinder, a 0.5 LPM fixed flow regulator with an on/off knob, a calibration cup for the detector, and a short piece of sample tubing to connect the regulator to the calibration cup.
Prepari ng for Ca libration
1. Screw the calibration cup onto the bottom of the detector.
2. Screw the regulator into the calibration cylinder.
3. Use the calibration kit sample tubing to connect the regulator to the calibration cup.
4. Place the controller into its calibration program or disable external alarms.
NOTE: Calibrating the combustible detector may cause alarms. Be sure to put the
controller into its calibration program or disable external alarms before continuing.
Setting the Zero Reading
CAUTION: If you suspect the mon itoring environment is not free of co mbustible vapors, use the
calibration kit and a zero air calibration cylinder to introduce “fresh air” to the detector and verify an accurate zero setting.
1. Verify that the detector is in a fresh air environment.
2. Follow the directions in the controller’s operator’s manual for setting the zero reading.
Setting the Response Reading
1. Follow the directions in the controller’s operator’s manual for setting the response reading (span).
2. When the directions call for exposing the detector to gas, turn the regulator’s on/off knob counterclockwise to open it.
3. Allow the gas to flow for one minute before continuing with the directions.
10 • 61-1000RK Combustible Gas Detector
4. After setting the response reading, turn the regulator’s on/off knob clockwise to close it.
5. Unscrew the regulator from the cylinder.
Returning to Normal Operation
1. Unscrew the calibration cup from the detector.
NOTE: For convenience, leave regulator and calibration cup connected by the sample
tubing.
2. When the controller display reading falls below the alarm points, return the controller to normal o peration.
NOTE: If you do not allow the gas reading to decrease below the alarm points, then
unwanted alarms may occur.
3. Verify that the controller display reading decreases and stabilizes at 0 %LEL.
4. Store the components of the calibration kit in a safe and convenient place.
Parts List
Table 3 lists replacement parts and accessories for the 61-1000RK combustible gas detector.
Table 3: Parts List
Part Number Description
18-0400RK-01 Junction box with spacers 61-0140RK Replacement combustible gas detector 71-0067RK 61-1000RK Combus tible Gas Detector Operator’s Manual (this document) 81-0007RK-01 Calibration cylinder (15% LEL Hexane in air, 34 liter) 81-0012RK-01 Calibration cylinder (50% LEL Methane in air, 34 liter) 81-0076RK-01 Zero air calibration cylinder (34 liter) 81-1003RK Regulator, 0.5 liter/minute; continuous flow (for 17 and 34 liter calibra tion cylinders) 81-1117RK Calibration c up
61-1000RK Combustible Gas Detector • 11
Loading...