Read and understand this instruction manual before operating
detector . Improper use of the dete ctor could result in bodily harm
or death.
Periodic calibration and maintenance of the detector is essential
for proper operation and correct readings. Please calibrate and
maintain this detector regularly! Frequency of calibration
depends upon the type of use you have and the sensor types.
T ypical calibration frequencies for most applicatio ns are between
3 and 6 months, but can be required more often or less often
based on your usage.
RKI Instruments, Inc. warranties gas alarm equipment sold by us to be free from defects in
materials, workmanship, and performance for a period of one year from date of shipment
from RKI Instruments, Inc. Any parts found defective within that period will be repaired
or replaced, at our option, free of charge. This warranty does not apply to those items
which by their nature are subject to deterioration or consumption in normal service, and
which must be cleaned, repaired, or replaced on a routine basis. Examples of such items
are:
Warranty is voided by abuse including mechanical damage, alteration, rough handling, or
repair procedures not in accordance with the operator’s manual. This warranty indicates
the full extent of our liability, and we are not responsible for removal or replacement costs,
local repair costs, transportation costs, or contingent expenses incurred without our prior
approval.
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER
WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED,
AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF
RKI INSTRUMENTS, INC. INCLUDING BUT NOT LIMITED TO, THE
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS,
INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR CONSEQUENTIAL
LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF
ITS PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR
OPERATE PROPERLY.
Absorbent cartridgesd) Batteries
a)
b) Pump diaphragms and valvese) Filter elements
c) Fuses
This warranty covers instruments and parts sold to users by authorized dist ri butors,
dealers, and representatives as appointed by RKI Instruments, Inc.
We do not assume indemnification for any a ccident or damage caused by the opera tion of
this gas monitor, and our warranty is limited to the replacement of parts or our complete
goods.
This manual describes the 61-1000RK combustible gas detector (internal amplifier type).
This manual also describes how to install, start up, maintain, and calibrate the detector
when it is used with a gas monitoring controller. A parts list at the end of this manual
lists replacement parts and accessories for the combustible gas detector.
The 61-1000RK combustible gas detector includes the 61-0140RK combustible gas detector
and a junction box. This manual may also be used for the 61-0140RK combustible gas
detector which does not include a junction box and is normally mounted in one o f a
controller’s conduit hubs. If you are using a 61-0140RK combustible gas detector,
disregard all references to the junction box and junction box terminal strip.
Specifications
WARNING: Do not use this product in a manner not specified in this instruction
manual.
Table 1 lists specifications for the combustible gas detector.
Table 1: 61-1000RK Specifications
Target GasCombustible gas (Methane Calibration Standard)
Area ClassificationExplosionproof for Class I, Groups B, C, and D
Sampling MethodDiffusion
Detection Range0 to 100% LEL
Response Time90% in 45 seconds
Accuracy± 5% of reading or ± 2% LEL (whichever is greater)
WARNING: When using the 61-1000RK, you must follow the instructions and warnings
in this manual to assure proper and safe operation of the 61-1000RK and to
minimize the risk of personal injur y. Be sure to maintain and periodically
calibrate the 61-1000RK as described in t hi s manual.
61-1000RK/61-0140RK Co mb u s ti b le G a s D e te c t or • 5
This section describes the components of the 61-0140RK and 61-1000RK detectors. The
61-1000RK includes the 61-0140RK combustible gas detector and a junction box. A four
point terminal strip is provided inside the junction box for de tector connections. The
61-0140RK does not include a junction
box.
Figure 1: 61-1000RK Component Location
61-0140RK Combustible Gas Detector
The combustible gas detector is a catalytic type detector that produces an electrical output
that corresponds to the detection range. It is packaged in a 1/2 NPT nipple with a sintered
metal flame arrest or on one end allowing ambient air to diffuse into the detector. The
flame arrestor also con tains any spark s which may occur wit hin the detector . The 1/2 NPT
mounting threads at the top of the detector allow you to mount it into the bottom conduit
hub of the junction box. The controller conduit hubs are normally 3/4 NPT, so a 3/4 x 1/2
NPT reducer may be necessary to install the combustible gas detec tor. A rain shield screws
onto the bottom of the detector (flame arrestor end). The rainshield helps protect the
detector from rain and debris in the monitoring environment. Four color-coded leads
extend from the top of the detector. The leads allow you to connect the detector to the
terminal block.
Junction Box
The junction box allows you to install the detector at a mounting site that is remote from a
controller, and it protects the detector wiring connections. Two conduit hubs allow you to
mount the detector to the junction box and connect the wiring from the detector to a
controller. Three spacers installed on the back of the junction box control the distance of
the junction box from a mounting s urface an d ensure that there is en ough roo m to instal l a
calibration cup on the detector during calibration.
The bottom conduit hub includes a 3/4 x 1/2 NPT reducer that allows you to screw the
detector into the hub. The terminal block within the junction b ox facilitates the wiring
process. A cover on th e front of the junction box allows access to the interior of the
junction box.
This section describes procedures to mount the combustible gas detector in the
monitoring environment and wire the detector to a controller.
NOTE: The 61-0140RK detector retains its explosion proof clas sification only when
installed in the explosion proof j unction box. The detector is not explosion proof
if installed in a controller conduit hub.
Mounting the Combustible Gas Detector
1.Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.
•Select a site where the detector is not likely to be bumped or disturbed. Make sure
there is sufficient room to perform start-up, maintenance, and calibration
procedures.
•Select a site where the target gas is likely to be found first. For lighter ga ses,
mount the detector near the ceiling; for heavier gases, mount the detector near the
floor.
Figure 2: Mounting the Comb ustible Gas Detector
61-1000RK/61-0140RK Co mb u s ti b le G a s D e te c t or • 7
2.At the mounting site you select, hang or mount the junction box with the detector
facing down (see Figure 2).
Wiring the Combustible Gas Detector to a Controller
NOTE: The LEL detector is grounded through the metal-to-metal joint between the
detector and the outlex box or grounded installation during end-use.
WARNING: Always verify th at the power to the controller is off before you make
wiring connections.
1.Turn off the controller.
2.Turn off power to the controller.
3.If the detector is mounted remotely from a controller using the junction box, proceed
to step 4.
If the detector is mounted directly to a controller, it is normally factory wired. Confirm
that the detector’s wires are connected to the appropriate controller detector terminals
d skip to “Start Up” on page 10. See Figure 3, the controller operator’s manual, and
an
the controller’s detector head specification sheet for the 61-0140RK detector for the
wiring connection s.
4.Remove the junction box cover.
5.Guide a four-conductor, shielded cable or four wires in conduit through the unused
conduit hub of the junction box. Use appropriate conduit fittings and construction
technique for the environmental rating and hazardous location classification of the
nction box. The junction box is rated NEMA 4X and classified explosion proof for
ju
Class I, Groups B, C, and D.
6.Connect the wires to the terminal block in the junction box.
CAUTION: Leave the shield drain wire insulated and disconnected at the detector. You will
connect the opposite end of the cable’s drain wire at the controller.
7.Secure the junction box cover to the junction box.
8.Route the cable or wires leading from the combustible gas detector through one of th
conduit hubs at the controller housing. Use appropriate conduit fittings and
construction technique for the environmental rating of the controller. RKI controllers
are typically rated NEMA 4X.
CAUTION: Do not route power and detector wiring through the same conduit hub. The power
cable may disru pt the transmission of the detector signal to the controller.
9.Connect the wires to the applicable controller terminal strip. See the controller
operator’s manual and the controller’s detector head sp ecif ication sheet for the
61-1000RK detector.
10. If using shielded cable, connect the cable’s drain wire to an available chassis ground at
the controller. RKI controllers typically have a ground stud that is a conven
grounding location.
This section describes maintenance procedures. It includes preventive maintenance,
troubleshooting, and component replacement procedures.
Preventive Maintenance
This section describes a preventive maintenance schedule to ensure the optimum
performance of the combustible gas detector. It includes daily and quarterly procedures.
Daily
Verify a display reading of 0% LEL at the controller. Investigate significant changes in the
reading.
Quarterly
Calibrate the detector as described in the Calibration section of this manual.
Troubleshooting
The troubleshooting guide describes symptoms, probable causes, and recommended
action for problems you may encounter with the combustible gas detector.
NOTE: This troubleshooting guide describes detector problems only. See the cont roller
operator’s manual for problems you may encounter with the controller.
Table 2:Troubleshooting the Combustible Gas Detector
3.If the detector is installed directly on a controller, open the controller door.
If the detector is installed remotely from a controller in a junction box, remove the
junction box cove r.
4.If the detector is installed directly on a controller, disconnect the detector leads from
the detector terminal strip in the controller. Note the position of the color-coded leads
as you remove them.
If the detector is installed remotely from a controller in a junction box, disconne c t the
detector leads from the terminal block in the junction box. Note the position of the
color-coded leads as you remove them.
5.Unscrew the detector from the controller conduit hub or junction box conduit hub.
6.Guide the detector leads of the replacement detector through the controller condui
hub or junction box conduit hub, then screw the mounting threads of the detector into
the hub. If necessary for environmental conditions, apply thread sealan t or Teflon tape
to the hub and/or detector threads to seal them.
7.If the detector is installed directly on a controller, connect the detector leads to th
appropriate detector terminal strip terminals. See Figure 3 f or wiring to a generic
controller. See the controller operator’s manual and the controller’s detector head
specification sheet for the 61-0140RK detector for wiring specific to your controller.
If the detector is installed remotely from a controller in a junction box, connect the
detector leads to the terminal block the same way the old detector was wired (see
Figure 3). See the controller operator’s manual and the controller’s detector head
specification sheet for the 61-1000RK detector to verify the connections to
controller are correct.
8.If the detector is installed remotely from a controller in a junction box, reinstall th
junction box cove r.
9.Turn on or plug in power to the controller.
10. Turn on the controller and place into normal operation.
CAUTION: Allow the replacement detector to warm up for 5 minutes before you continue with
the next step.
11. Calibrate the replacement detector as described in the Calibration section of this
manual.
the
t
e
e
12 • 61-1000RK/61-0140RK Combus tible Gas Detector
Although there is no particular calibration frequency that is correct for all applica tions, a
calibration frequency of every 3 to 6 months is adequate for most combustible gas detector
applications. Unless experience in a particular application dictates otherwise, RKI
Instruments, Inc. recommends a calibration frequency of every 3 months.
If an application is not very demanding, for example detection in a clean, temperature
controlled environment where combustible gas is not normally present and calibration
adjustments are minimal at calibration, then a calibration frequency o f every 6 months is
adequate.
If an application is very demanding, for example if combustible gas is present often and in
significant concentrations or the environment is not well controlled, then more frequent
calibration than every 3 months may be necessary. If potential catalyst poisons are known
or likely to be present, more frequent calibration than every 3 month s will be necessary.
Calibration
This section describes how to calibrate the combustible gas detector. It includes
procedures to prepare for calibration, set the zero reading, set the response reading, and
return to normal operation.
WARNING: The controller is not an active gas monitoring device during the calibration
procedure.
NOTE: The following procedure assumes the use of a calibration kit which includes a
calibration gas cylinder, a 0.5 LPM fixed flo w regulator with an on/off knob, a
calibration cup for the detector, and a short piece of sample tubing to connect the
regulator to the calibration cup.
Preparing for Calibration
1.Screw the calibration cup onto the bottom of the detector.
2.Screw the regulator into the calibration cylinder.
3.Use the calibration kit sample tubing to connect the regulator to the cali bration cup.
4.Place the controller into its calibration program or disable external alarms.
NOTE: Calibrating the combustible detector may cause alarms. Be sure to put the
controller into its calibration program or disable external alarms before
continuing.
61-1000RK/61-0140RK Co m bu s ti b l e G a s D e te c to r • 13