RKI Instruments 12 VDC User Manual

12 VDC Beacon 200
Operator’s Manual
Part Number: 71-0293RK Revision: P1 Released: 10/4/13
www.rkiinstruments.com
RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of sh ipm ent from RKI Instr uments, Inc. Any part s fo und defective within that period will be repaired or replaced, at our option, free of charge. This warranty does not apply to those items, which by their nature, are subject to deterioration or consumption in normal service, and which must be clean ed, rep aired, or replace d on a rout ine basis. Exa mples of such items are as follows:
a) Absorbent cartridges d) Batteries b) Pump diaphragms and valves e) Filter elements c) Fuses
Warranty is voided by abuse including mechanical damage, alteration, rough handling, or repair procedures not in accordance with the operator’s manual. This warranty indicates the full extent of our liability, and we are not responsible for removal or replacement costs, local repair costs, transportation costs, or contingent expenses incurred without our prior approval.
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED, AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF RKI INSTRUMENTS, INC. INCLUDING BUT NOT LIMITED TO, THE WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS, INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR CONSEQUENTIAL LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF ITS PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR OPERATE PROPERLY.
This warranty covers instruments and parts sold to users by authorized distributors, de alers, and r epresenta tives as appo inted by R KI Instrument s, Inc.
We do not assume indemn ification for any accident or damage caused by the operation of this gas monitor, and our warranty is limited to the replacement of parts or our complete goods.
12 VDC Beacon 200 Operator’s Manual
Table of Contents
Chapter 1: Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About the 12 VDC Beacon 200 Gas Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 2: Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
External Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Internal Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chapter 3: Installation and Start Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Mounting the 12VDC Beacon 200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wiring the 12 VDC Beacon 200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Starting Up the 12 VDC Beacon 200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 4: Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Recorder Output Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Alarm Indications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Viewing & Resetting Min/Max Readings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Chapter 5: Channel Control and Setup Program . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Enable/Disable Channel(s) Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Configure Channel Settings Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
View System Information Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
12 VDC Beacon 200 Operator’s Manual
Chapter 6: Input Setup Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Setting up a New Channel or Changing an Existing Channel. . . . . . . . . . . . . . . 33
Chapter 7: Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Calibration Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Replacing the Fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Parts List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
12 VDC Beacon 200 Operator’s Manual
Chapter 1: Introduction
Overview
This chapter briefly describes the 12 VDC Beacon 200. This chapter also describes the 12 VDC Beacon 200 Operator’s Manual (this document). Table 1 at the end of this chapter lists the specifications for the 12 VDC Beacon 200.
About the 12 VDC Beacon 200
The 12 VDC Beacon 200 is a fixed-mou nted, continuous-monitoring ga s detection instru ment. This gas monitor is capable of detecting gas at two locations. The display screen simultaneously displays the gas readings of the active channel or channel s. Both dir ect connect ( internal a mplifier type) detector heads and 4 - 20 mA transmitter (remote amplifier type) detector heads may be used with the 12 VDC Beacon 200.
The 12 VDC Beacon 200 includes aud ibl e an d vi su al a lar m s th at warn you of hazardous gas conditions. The alarm circuit includes two levels of gas alarms. The fail circuit alerts you to failures in the gas detector heads or 12 VDC Beacon 200.
Three instrument programs allow you to display and change channel and calibration settings and change channel types. They are the Channel Control & Setu p Program and the Ca libration P rogram, and the Inp ut Setup Program.
12 VDC Beacon 200 Operator’s Manual
About this Manual
The 12 VDC Beacon 200 Gas Monitor Operator’s Manual uses the following conventions for notes, cautions, and warnings.
NOTE: Describes additional or critical information.
CAUTION: Describes potential dam a ge to equ ipm en t.
WARNING: Describes potential danger that can result in injury or
Caution: refer to accompanying documentation
!
death.
~ Vac (AC voltage)
Vdc (DC voltage)
2 • 12 VDC Beacon 200 Operator’s Manual
Specifications
Table 1 lists specifications for the 12 VDC Beacon 200.
Table 1: 12 VDC Beacon 200 Specifications
Description Specification
Input Power 10.8 - 14.5 VDC, 1.2A VDC Construction (housing) Fiberglass/polyester with lexan window (NEMA 4X) Controller Dimensions 10.5 in. H x 8.5 in. W x 6.25 in. D
(267 mm H x 216 mm W x 158 mm D) Weight 8 lbs. Environmental Conditions -20°C to 50°C (-4°F to 122°F) max. ambient
Maximum humidity of 80% relative
Relays Relay contacts rated for 10A @ 115/220V~ resistive or 10A @ 30V
User Controls Reset switch
resistive
SPDT Form C
Program buttons: ESCAPE, UP/YES, DOWN/NO, and ENTER
WARNING: When using the 12 VDC Beacon 200, you must follow the
instructions and warnings in this manual to assure proper and safe operation of the 12 VDC Beacon 200 and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 12 VDC Beacon 200 as described in this manual.
12 VDC Beacon 200 Operator’s Ma nual • 3
Chapter 2: Description
p
Overview
This chapter describes external and internal components of the 12 VDC Beacon 200.
Mounting F oot, 4 X
Alarm 2
LED
Alarm
1LED
Display
Contra st
AdjustPot
Detector /
Transm itter
Terminal Strip,
Channel 1
Detector/
Transm itter
Terminal Strip,
Channel 2
ConduitHub (3X)
CH1-A1
NO NC C
CH1-A2
NO NC C
CH2- A1
NO NC C
NO NC CNO NC C
Reset Switch
COM-A 2COM-A1CH2-A2
NO NC C
COM-FAIL NO NC C
FACTORY WIRED
Buzzer
MainPCB
Display PC B
Program Button(4)
Display Fail LED Pilot LED
But ton Repeater Buzzer
DC In Terminal Strip
Fuses, DC Power Switch
Controller Terminal Stri
Relays
Alarm Terminal Strip
Figure 1. 12 VDC Beacon 200 Component Location
4 • 12 VDC Beacon 200 Operator’s Manual
External Description
This section describes the housing and all external components of the 12 VDC Beacon 200. For the purposes of this description, the housing door is considered the front of the monitor.
Housing
The 12 VDC Beacon 200’s fiberglass housing is weather- and corrosion­resistant. It is suitable for installation where general purpose equipment is in use. The housing door is hinged on the left side and is secured by two latches on the right side. The display screen and status lights are visible through windows in the housing door. Four mounting feet are attached to the back of the housing (one at each corner). The mounting feet allow you to install the housing to a vertical surface. Three conduit hubs on the bottom of the housing are for external wiring connections.
CAUTION: To avoid electrical inte rference, do not ro ute detect or head and
power wiring through the same conduit hub.
Reset Switch
The reset switch i s on the bottom of th e ho usi ng . I t i s in front of the conduit hubs. The reset switch serves three functions:
Resets the alarm circuits for “latched” alarms after an alarm 1 or alarm 2 condition passes.
You can set each channel for latched or self-resetting alarms in the Channel Control & Setup Program.
Silences the bu zzer d ur ing an alarm 1 or ala rm 2 con di ti o n. You canno t silence failure alarms.
Displays and resets the minimum and maximum gas concentration values.
Buzzer
The buzzer is on the botto m of the housi ng. It is on the far r ight. The buzze r sounds audible alarms to warn you of gas alarms and in strument failures.
12 VDC Beacon 200 Operator’s Ma nual • 5
Internal Description
This section describes the intern al componen ts of the 12 VDC Beaco n 200.
Display Printed Circuit Board (PCB)
The display PCB is mou nted to the p ower supply mo unting plate which is in turn mounted to t he ma in PCB. The power su pply mo unting p late an d main PCB are described below. The display PCB includes the displ ay, the status lights, and the program buttons.
Display
The display simultaneously indicates the channel number, current gas reading, measuring unit, and target gas of all active channels.
The display also indicates messages, settings, and other data when you are operating the instrument programs.
ALARM 2 Light
ALARM 1 Light
Display Contrast Adjust Pot
Display Screen
Display Cable Connector
FAIL Light
J1
PILOT Light
Figure 2. Display Board Component Location
ESCAPE Button
UP/YES Button
DOWN/NO Button
ENTER Button
Button Repeater Buzzer
6 • 12 VDC Beacon 200 Operator’s Manual
Status Lights
The 12 VDC Beacon 200 incl udes four status lights that indicate the current status of the monito r. The status lights a re to the l eft and righ t of the display (see Figure 2).
Pilot Light. The pilot light is on when the 12 VDC Beacon 200 is receiving incomi ng pow er.
Fail Light. The fail light turns on when the 12 VDC Beacon 200 is experiencing a fa il co nd i tion. A fail condition can be caused by a failure within the 12 VD C Be acon 200 o r d etector he ad(s) wir ed to the 12 V DC Beacon 200. See “C ha pter 7: Maintenance” o n page 37 for instructions to respond to a fail condition.
Alarm 1 Light. The alarm 1 ligh t is on wh en t he 12 V DC Beaco n 200 i s experiencing an alarm 1 gas condition.
Alarm 2 Light. The alarm 2 ligh t is on wh en t he 12 V DC Beaco n 200 i s experiencing an alarm 2 gas condition.
Program Buttons
The 12 VDC Beacon 200 includes four program buttons that allow you to enter the instrument programs, navigate through the programs, update instrument and channel settings, and save changes to the program settings. When a program button is pressed, a buzzer located on the display PCB beeps. The program buttons are near the right edge of the display PCB (see Figure 2).
Table 2: 12 VDC Beacon 200 Program Button Functions
Button Function
ESCAPE Moves back ward through the progr am menus
Cancels changes you make in the program menus
Enters the Channel Control and Setup program (press with the ENTER button)
UP/YES Accepts the displayed setting and proceeds to the next setting
Changes the displayed setting
Enters the Calibration program (press with the ENTER button)
DOWN/NO Allows you to update the displayed setting
Changes the displayed setting
ENTER Saves changes you make in the programs
Enters the Channel Control and Setup program (press with ESCAPE button)
Enters the Calibration program (press with the UP/YES button)
12 VDC Beacon 200 Operator’s Ma nual • 7
Main PCB
The main PCB is mounted inside the housing. The power supply mounting plate is mounted to the main PCB with four standoffs and the display PCB is mounted to the power supply mounting plate with four standoffs. The main PCB includes the terminal strips, relays, fuses, and power switch.
Terminal Strips
The 12 VDC Beacon 200 includes four terminal strips for ext ernal wiring connections. See “Wi ring the 12 VDC B eac on 20 0” on p a ge 13 for detailed wiring procedures.
Detector/Transmitter Terminal Strips. Two detector/transmitter terminal strip s are locate d near the bo ttom lef t corne r of the mai n circuit board (see Figure 1). These two 9-point terminal strips facilitate wiring connections to the detectors or transmitters. Although each terminal strip can accommodate several different detector head models, only one detector h ead at a time ma y be wi red per channel . The top term inal strip is for channel 1 and the bottom terminal strip is for channel 2.
Alarm Terminal Strip. The alarm terminal strip is located along the bottom edge of the main circuit board (see Figure 1). This 21-point terminal strips facilitates wiring connections to external alarm devices (horn, strobe, etc.). Terminals are provided for individual channels as well as common alarm relay contacts.
Controller T e rminal S trip. The 10-point controller terminal strip is near the lower right edge of the main circuit board (see Figure 1). The controller terminal strip facilitates various interna l and external wiring connections. Table 3 lists the function of each terminal.
T able 3: Terminal Assignments for the Controller Terminal Strip
Terminal Connects to:
NOT USED (top terminal) not used NOT USED (bottom terminal) not used + CH1 OUT + connection of 4 - 20 mA output, channel 1
- CH 1 OUT - connection of 4 - 20 mA output, channel 1 + CH2 OUT + connection of 4 - 20 mA output, channel 2
- CH2 OUT - connection of 4 - 20 mA output, channel 2 RESET (2) Reset switch (factory-wired) BUZ-/BUZ+ Internal buzzer (factory-wired)
8 • 12 VDC Beacon 200 Operator’s Manual
DC In T erminal S trip. The DC in terminal strip is a 3-point terminal strip
Channel 2, Alarm 2
located above the controller terminal strip (see Figure 1). It facilitates wiring from a 12 VDC power source. Table 4 lists the function of each terminal.
T a ble 4: Terminal Assignments for the AC In Terminal Strip
Terminal Connects to:
12 VDC + + wire from 12 VDC power source 12 VDC - - wire from 12 VDC power source
Earth ground
Relays
The 12 VDC Beacon 200 includes four channel relays (two per channel) and three common rela ys. Both sets of rela ys are single-p ole, double-thro w (SPDT) and are rated for 10 amps at 250 VAC (resistive).
NOTE: You can select normally energized (NE) or normally de-energized
(NDE) settings for ea ch channel in th e Channel Co ntrol and Setup program. This section describes the default setting : normally de­energized.
The alarm 1 and alarm 2 common relays are factory-set as NDE and the fail common relay is factory-set as NE. The alarm 1, alarm 2, and fail common relays’ NE/NDE settings are not user­adjustable.
Channel relays. The four channel relays are above the alarm terminal strip (see Figure 1). These relays are dedicated to specific channels and alarm levels.
For example, the channel 1, alarm 1 relay energizes if channel 1 recognizes an alarm 1 condition. Figure 2 below illustrates the allocation of the channel relays.
Common Alarm 1
Channel 2, Alarm 1 Channel 1, Alarm 2
Channel 1, Alarm 1
Common Alarm 2
Common Fail
K5 K6 K7
K1 K2 K3
K4
Figure 3. 12 VDC Beacon 200 Channel Relay Allocation
12 VDC Beacon 200 Operator’s Ma nual • 9
NOTE: The alarm 2 channel relays may be set to operate as individual
channel fail relays. See “Configure Channel Settings Menu” on page 30 for instructions.
Common relays. The three common relays , alarm 1, alarm 2, and fail, are to the lef t of th e controlle r terminal strip (see Figu re 1). These rela ys are common for both channels.
For example, the al arm 1 common rela y energizes if either channel 1 or channel 2 recognizes an alarm 1 condition.
Fuses
There are two DC fuses that are used in the 12 VDC Beacon 200. They are located directly to the left of the controller terminal strip. They cut off the incoming DC power in the event of a short circuit or other electrical fault which causes a high current draw in the 12 VDC Beacon 200. They are housed in vertical fuse holders and are held in the holder by a quarter turn cover. They are labelled as F2 (top fuse) and F3 (bottom fuse) on the PCB silk-screen and are rated at 3 A, 250 V.
A third fuse located to the left of the power switch is labelled F1. This fuse is not used in this version of the Beacon 200.
Power Switch
The power switch is located above the relays and to the left of the DC fuses (see Figure 1). The power switch turns the incoming DC power source on and off at the 12 VDC Beacon 200. When the switch is up, the power switch is on.
Power Converter
The power converter is mounted to the power supply mounting plate with standoffs. The power supply mounting plate is located behind the display PCB and is mounted to the main PCB with fo ur standoffs. The power converter takes 12 VDC voltage supplied to the 12 VDC Beacon 200 and converts it to 24 VDC which is used to run the 12 VDC Beacon 200.
10 • 12 VDC Beacon 200 Operator’s Manual
Chapter 3: Installation and Start Up
Overview
This chapter de scribes proced ures to mount the 1 2 VDC Beacon 200, make wiring connections to the monitor, and start up the monitor.
WARNING: Perform all installation and start-up procedures in a
“fresh air” environment (known to be free of combustible gas, toxic gas, and of normal oxygen content). The 12 VDC Beacon 200 is not in operation as a gas monitoring system until the start-up procedure is complete.
Mounting the 12 VDC Beacon 200
Perform the following procedure to install the 12 VDC Beacon 200 at the mounting site.
12 VDC Beacon 200 Operator’s Manual • 11
X
.41
8.50
6.00
Mounting Feet, 4X
Ø.31x.50slot, 4
FAIL
10.50
PILOT
10.94
Buzzer
3/4 ConduitHubs (4X)
6.45
ALARM 2
ALARM 1
BEACON 200
Reset Switch
GAS MONITOR
RESET
Figure 4. 12 VDC Beacon 200 Outline and Mounting Dimensions
1. Select the mounting site. When you select the mounting site consider
the following factors:
Is a 12 VDC power source availa ble?
Is there enough room to open the housing door and make wiring
connections through the conduit hubs at the bottom of the housing?
Are the display screen and status lights visible?
2. Close and latch the housing door.
3. Position t he monitor on a vertical surface at e ye level (4 1/2 to 5 feet
from the floor).
4. The 12 VDC Beacon 200 is shipped with the mounting feet positioned
behind the housing. Loosen the screws that se cure the feet to the housing, rotate the feet to their mounting position (as shown in Figure 4), then tighten the screws.
5. Insert 1/4 in. or 5/16 in. screws through the slot s in the mounting fe et at
each corner of the housing to secure the housing to the mounting surface (see Figure 4).
12 • 12 VDC Beacon 200 Operator’s Manual
Loading...
+ 35 hidden pages