RKI 61-1000RK-05, 61-0140RK-05 Operator's Manual

61-1000RK-05 / 61-0140RK-05
Combustible Gas Detector
Operator’s Manual
Part Number: 71-0087RK Revision: F Released: 10/26/18
www.rkiinstruments.com
WARNING
Read and understand this instruction manual before operating detector. Improper use of the detector could result in bodily harm or death.
Periodic calibration and maintenance of the detector is essential for proper operation and correct readings. Please calibrate and maintain this detector regularly! Frequency of calibration depends upon the type of use you have and the sensor types. Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage.
61-1000RK-05/61-0140RK-05 Combustible Gas Detector
Product Warranty
RKI Instruments, Inc. warranties gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge. This warranty does not apply to those items which by their nature are subject to deterioration or consumption in normal service, and which must be cleaned, repaired, or replaced on a routine basis. Examples of such items are:
Warranty is voided by abuse including mechanical damage, alteration, rough handling, or repair procedures not in accordance with the operator’s manual. This warranty indicates the full extent of our liability, and we are not responsible for removal or replacement costs, local repair costs, transportation costs, or contingent expenses incurred witho u t our prior approval.
a) Absorbent cartridges d) Batteries b) Pump diaphragms and valves e) Filter elements c) Fuses
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED, AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF RKI INSTRUMENTS, INC. IN CLUDING BUT NOT LIMITED TO, THE WARRANTY OF MERCHANTABILITY OR F ITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS, INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR CONSEQUENTIAL LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF ITS PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR OPERATE PROPERLY.
This warranty covers instruments and parts sold to users by authorized d istributors, dealers, and representatives as appointed by RKI Instruments, Inc.
We do not assume indemnification for any a ccident or damage caused by the opera tion of this gas monitor, and our warranty is limited to the replacement of parts or our complete goods.
61-1000RK-05/61-0140RK-05 Combustible Gas Detector
Table of Contents
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
61-0140RK-05 Combustible Gas Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Junction Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mounting the Combustible Gas Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring the Combustible Gas Detector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Introducing Incoming Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Setting the Zero Signal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Replacing the Combustible Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Preparing for Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Setting the Zero Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Setting the Response Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Returning to Normal Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
61-1000RK-05/61-0140RK-05 Combustible Gas Detector
Overview
!
This manual describes the 61-1000RK-05 combustible gas detector (internal amplifier type). This manual also describes how to install, start up, maintain, and calibrate the detector when it is used with a gas monitoring controller. A parts list at the end of this manual lists replacement parts and accessories for the combustible gas detector.
The 61-1000RK-05 combustible ga s detector includes the 61-0140RK-05 combustible gas detector and a junction box. This manual may also be used for the 61-0140RK-05 combustible gas detector which does not include a junction box and is normally mounted in one of a controller’s conduit hubs. If you are using a 61-0140RK-05 combustible gas detector, disregard all references to the junction box and junction box terminal strip.
Specifications
WARNING: Do not use this product in a manner not specified in this instruction
Table 1 lists specifications for the combustible gas detector.
manual.
Table 1: 61-1000RK-05 Specifica tio ns
Target Gas Combustible gas (Methane Calibration Standard) Area Classification Explosionproof for Class I, Groups B, C, and D Sampling Method Diffusion Detection Range 0 to 100% LEL Response Time 90% in 45 seconds Accuracy ± 5% of reading or ± 2% LEL (whichever is greater)
NOTE: The fol l ow i ng sy mbol on the detector label is a caution to the user to refer to this
documentation for installation and operation instructions:
WARNING: When using the 61-1000RK-05, you must follow the instructions and
warnings in this manual to assur e proper and safe operation of the 61-1000RK-05 and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 61-1000RK-05 as described in this manual.
61-1000RK-05/61-0140RK-05 Combustible Gas Detector • 5
Description
Rubber Spacer, 3X
Red
J-Box
Green
Black
White
This section describes the components of the 61-0140RK-05 and 61-1000RK-05 detectors. The 61-1000RK-05 includes the 61-01 40RK-05 combu stible gas dete ctor and a junction box. A four point terminal strip is provided inside the junction box for detector connections. The 61-0140RK-05 does not include a junction box.
Figure 1: 61-1000RK-05 Component Location
61-0140RK-05 Combustible Gas Detector
The combustible gas detector is a catalytic type detector that produces an electrical output that corresponds to the detection range. It is packaged in a 1/2 NPT nipple with a sintered metal flame arrest or on one end allowing ambient air to diffuse into the detector. The flame arrestor also con tains any spark s which may occur wit hin the detector . The 1/2 NPT mounting threads at the top of the detector allow you to mount it into the bottom conduit hub of the junction box. The controller conduit hubs are normally 3/4 NPT, so a 3/4 x 1/2 NPT reducer may be necessary to install the combustible gas detector. A flame arrestor guard is located at the bottom of the detector and is permanently bonded to the detector housing. The flame arrestor guard protects the flame arrestor from impact damage. Four color-coded leads extend from the top of the detector. The leads allow you to connect the detector to the terminal block.
Junction Box
The junction box allows you to install the detector at a mounting site that is remote from a controller, and it protects the detector wiring connections. Two conduit hubs allow you to mount the detector to the junction box and connect the wiring from the detector to a controller. Three spacers installed on the back of the junction box control the distance of the junction box from a mounting s urface an d ensure that there is en ough roo m to instal l a calibration cup on the detector during calibration.
The bottom conduit hub incl udes a 3/4 x 1/2 NPT reducer that allows you to screw the detector into the hub. The terminal block within the junction box f acilitates the wiring
6 • 61-1000RK-05/61-0140RK-05 Combustible Gas Detector
Installation
0.382.70
J-Box
.75
3/4 x 1/2 NPT Reducing Bushing
Combust ible Detector
3/4 NPT
Female
3.65
7.50 max
Spacer, 3X
process. A cover on th e front of the junction box allows access to the interior of the junction box.
This section describes procedures to mount the combustible gas detector in the monitoring environment and wire the detector to a controller.
NOTE: The 61-0140RK-05 detector retains its explosion pr oof classification only when
installed in the explosion proof j unction box. The detector is not explosion proof if installed in a controller conduit hub.
Mounting the Combustible Gas Detector
1. Select a mounting site that is representative of the monitoring environment. Consider the following when you select the mounting site.
Select a site where the detector is not likely to be bumped or disturbed. Make sure
there is sufficient room to perform start-up, maintenance, and calibration procedures.
Select a site where the target gas is likely to be found first. For lighter ga ses,
mount the detector near the ceiling; for heavier gases, mount the detector near the floor.
Figure 2: Mounting the Comb ustible Gas Detector
61-1000RK-05/61-0140RK-05 Combustible Gas Detector • 7
2. At the mounting site you select, hang or mount the junction box with the detector
facing down (see Figure 2).
Wiring the Combustible Gas Detector to a Controller
WARNING: Always verify th at the power to the controller is off before you make
wiring connections.
1. Turn off the controller.
2. Turn off power to the controller.
3. If the detector is mounted remotely from a controller using the junction box, proceed to step 4.
If the detector is mounted directly to a controller, it is normally factory wired. Confirm that the detector’s wires are connected to the appropriate controller detector terminals and skip to “Start Up” on page 10. See Figure 3, the controller operator’s manual, and the controller’s detector head specification sheet for the 61-0140 RK -05 detecto r fo r the wiring connection s.
4. Remove the junction box cover.
5. Guide a four-conductor, shielded cable or four wires in conduit through the unused conduit hub of the junction box. Use appropriate conduit fittings and construction technique for the environmental rating and hazardous location classification of the junction box. The junction box is rated NEMA 4X and classified explosion proof f or Class I, Groups B, C, and D.
6. Connect the wires to the terminal block in the junction box.
WARNING: To maintain the explosion proof classification of the LEL det ector/junction
box combination, a conduit seal must be used at the junction box conduit hub used for wiring to the controlle r.
CAUTION: Leave the shield drain wire insulated and disconnected at the detector. You will
connect the opposite end of the cable’s drain wire at the controller.
7. Secure the junction box cover to the junction box.
8. Route the cable or wires leading from the combustible gas detector through one of the conduit hubs at the controller housing. Use appropriate conduit fittings and construction technique for the environmental rating of the controller. RKI controllers are typically rated NEMA 4X.
CAUTION: Do not route power and detector wiring through the same co nduit hub. The power
cable may disru pt the transmission of the detector signal to the controller.
9. Connect the wires to the applicable controller terminal strip. See the controller operator’s manual and the controller’s detector head sp ecif ication sheet for the 61-1000RK-05 detector.
10. If using shielded cable, connect the cable’s drain wire to an available chassis ground at the controller. RKI controllers typically have a ground stud that is a convenient grounding location.
8 • 61-1000RK-05/61-0140RK-05 Combustible Gas Detector
Green
White
Red
Controller
LEL
Detector
Term inals
J-Box
Terminal S trip
Black
Detector Wires
Red
Green White
Combustible Detector
Black
CableShield
Figure 3: Wiring the Combustible Gas Detector to a Controller
61-1000RK-05/61-0140RK-05 Combustible Gas Detector • 9
Start Up
This section describes procedures to start up the combustible gas detector and place the detector into normal operation.
Introducing Incoming Power
1. Complete the installation procedures described earlier in this manual.
2. Verify that the power wiring to the controller is correct and secure. Refer to the controller operator’s manual.
3. Turn on power to the controller.
4. Turn on the controller.
5. Verify that the controller is on and operating properly. Refer to the controller operator’s manual.
CAUTION: Allow the de t ect or to warm up for 5 minutes before you continue with the next
section, “Setting the Zero Reading”.
Setting the Zero Reading
WARNING: Do not remove the junction box cover while the circuits are energized
unless the area is determined to be non-hazardous. Keep the junction box cover tightly closed during operation.
CAUTION: If you suspect the prese nce of combustible gas in the monitoring environment, us e
the zero air calibration cylinder to introduce “fresh air” to the detector and verify an accurate zero re a ding.
1. Verify that the detector is in a fresh air environment (environment known to be free of combustible gas and of normal oxygen concentration, 20.9%).
2. Verify a reading of 0% LEL at the controller. If the display reading is 0% LEL, start up is complete. The combustible detector is in
normal operation. If the display reading is not 0% LEL, continue with step 3.
3. Perform a zeroing operation at the controller. See the controller operator’s manual for directions.
10 • 61-1000RK-05/61-0140RK-05 Combustible Gas Detector
Maintenance
This section describes maintenance procedures. It includes preventive maintenance, troubleshooting, and component replacement procedures.
Preventive Maintenance
This section describes a preventive maintenance schedule to ensure the optimum performance of the combustible gas detector. It includes daily and quarterly procedures.
Daily
Verify a display reading of 0% LEL at the controller. Investigate significant changes in the reading.
Quarterly
Calibrate the detector as described in the Calibration section of this manual.
Troubleshooting
The troubleshooting guide describes symptoms, probable causes, and recommended action for problems you may encounter with the combustible gas detector.
NOTE: This troubleshooting guide describes detector problems only. See the controller
operator’s manual for problems you may encounter with the controller.
Table 2:Troubleshooting the Combustible Gas Detector
Condition Symptom(s) Probable Causes Recommended Action
Fail Condition • Controller indicates a
Slow or No Response/ Difficult or Unable to Calibrate
fail condition.
• Unable to accurately set the zero or response reading during calibration.
• Detector requires frequent calibration.
Note: Under “normal” circumstances, the detector requires calibration once every three months.
Some applications may require a more freque nt calibration schedule.
• The detector wiring is disconnected or misconnected.
• The detector zero signal is low enough to cause a fail condition.
• The detector is malfunctioning.
• The calibration cylinder is low, out-dated, or defective.
• The calibration gas is not an appropriate concentration.
• The detector is malfunctioning.
1. Verify that the detector wiring is correct and secure.
2. Calibrate the detector.
3. If the fail condition continues, replace the detector.
4. If the fail condition continues, contact RKI for further instruction.
1. Verify that the calibration cylinder contains an adequate supply of a fresh test sample.
2. Verify that the calibration gas concentration is appropriate for the detector.
3. If the calibration/response difficulties continue, replace the detector.
4. If the calibration/response difficulties continue, contact RKI for further instruction.
61-1000RK-05/61-0140RK-05 Com bus tible Gas De tect or • 11
Replacing the Combustible Detector
1. Turn off the controller.
2. Turn off power to the controller.
3. If the detector is installed directly on a controller, open the controller door. If the detector is installed remotely from a controller in a junction box, remove the
junction box cove r.
4. If the detector is installed directly on a controller, disconnect the detector leads from the detector terminal strip in the controller. Note the position of the color-coded leads as you remove them.
If the detector is installed remotely from a controller in a junction box , disconnect the detector leads from the terminal block in the junction box. Note the position of the color-coded leads as you remove them.
5. Unscrew the detector from the controller conduit hub or junction box conduit hub.
6. Guide the detector leads of the replacement detector through the controller conduit hub or junction box conduit hub, then screw the mounting threads of the detector into the hub. If necessary for environmental conditions, apply thread sealan t or Teflon tape to the hub and/or detector threads to seal them.
7. If the detector is installed directly on a controller, connect the detector leads to the appropriate detector terminal strip terminals. See Figure 3 for wiring to a generic controller. See the controller operator’s manual and the controller’s detector head specification sheet for the 61-0140RK-05 detector for wir ing specif ic to your cont roller.
If the detector is installed remotely from a controller in a junction box, co nnect the detector leads to the terminal block the same way the old detector was wired (see Figure 3). See the controller operator’s manual and the controller’s detector head specification sheet for the 61-1000RK-05 detector to verify the connections to the controller are correct.
8. If the detector is installed remotely from a controller in a junction box, reinstall the junction box cove r.
9. Turn on or plug in power to the controller.
10. Turn on the controller and place into normal operation.
CAUTION: Allow the replacement detector to warm up for 5 minutes before you continue with
the next step.
11. Calibrate the replacement detector as described in the Calibration section of this manual.
12 • 61-1000RK-05/61-0140RK-05 Combustible Gas Detector
Calibration Frequency
Although there is no particular calibration frequency that is correct for all applica tions, a calibration frequency of every 3 to 6 months is adequate for most combustible gas detector applications. Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every 3 months.
If an application is not very demanding, for example detection in a clean, temperature controlled environment where combustible gas is not normally present and calibration adjustments are minimal at calibration, then a calibration freque ncy of every 6 months is adequate.
If an application is very demanding, for example if combustible gas is present often and in significant concentrations or the environment is not well controlled, then more frequent calibration than every 3 months may be necessary. If potential catalyst poisons are known or likely to be present, more frequent calibration than every 3 month s will be necessary.
Calibration
This section describes how to calibrate the combustible gas detector. It includes procedures to prepare for calibration, set the zero reading, set the response reading, and return to normal operation.
WARNING: The controller is not an active gas monitoring device during the calibration
procedure.
NOTE: The following procedure assumes the use of a calibration kit which includes a
calibration gas cylinder, a 0.5 LPM fixed flo w regulator with an on/off knob, a calibration cup for the detector, and a short piece of sample tubing to connect the regulator to the calibration cup.
Preparing for Calibration
WARNING: Do not remove the junction box cover while the circuits are energized
unless the area is determined to be non-hazardous. Keep the junction box cover tightly closed during operation.
1. Screw the calibration cup onto the bottom of the detector.
2. Screw the regulator into the calibration cylinder.
3. Use the calibration kit sample tubing to connect the regulator to the cali bration cup.
4. Place the controller into its calibration program or disable external alarms.
NOTE: Calibrating the combustible detector may cause alarms. Be sure to put the
controller into its calibration program or disable external alarms before continuing.
61-1000RK-05/61-0140RK-05 Com bus tible Gas De tect or • 13
Setting the Zero Reading
CAUTION: If you suspect the monitori n g en vi r onment is not free of combustible vap o rs , us e the
calibration kit and a zero air calibration cylinder to introduc e “fresh air” to the detector and verify an accurate zero setting.
1. Verify that the detector is in a fresh air environment.
2. Follow the directions in the controller’s operator’s manual for setting the zero reading.
Setting the Response Reading
1. Follow the directions in the controller’s operator’s manual for setting the response reading (span).
2. When the directions call for exposing the detector to gas, turn the regula tor’s on/off knob counterclockwise to open it.
3. Allow the gas to flow for one minute before continuing with th e directions.
4. After setting the response reading, turn the regulator’s on/off knob clockwise to close it.
5. Unscrew the regulator from the cylinder.
Returning to Normal Operation
1. Unscrew the calibration cup from the detector.
NOTE: For convenience, leave regulator and calibration cup connected by the sample
tubing.
2. When the controller display reading falls below the alarm points, return the controller to normal o peration.
NOTE: If you do not allow the gas reading to decrease below the alarm points, then
unwanted alarms may occur.
3. Verify that the controller display reading d ecreases a nd stabilizes at 0 %LEL.
4. Store the components of the calibration kit in a safe and convenient place.
14 • 61-1000RK-05/61-0140RK-05 Combustible Gas Detector
Parts List
Table 3 lists replacement parts and accessories for the 61-1000RK-05 combustible gas detector.
Table 3: Parts List
Part Number Description
18-0400RK-01 Junction box with spacers 61-0140RK-05 Replacement combustible gas detector 71-0087RK 61-1000RK-05 Combustible Gas Detector Operator’s Manual (this document) 81-0002RK-01 Calibration cylinder, 50% LEL hydrogen in air, 34 liter steel 81-0002RK-03 Calibration cylinder, 50% LEL hydrogen in air, 103 liter 81-0004RK-01 Calibration cylinder, 50% LEL propane in air, 34 liter steel 81-0004RK-03 Calibration cylinder, 50% LEL propane in air, 103 liter 81-0007RK-01 Calibration cylinder, 15% LEL hexane in air, 34 liter steel 81-0012RK-01 Calibration cylinder, 50% LEL methane in air, 34 liter steel 81-0012RK-03 Calibration cylinder, 50% LEL methane in air, 103 liter 81-0076RK-01 Zero air calibration cylinder, 34 liter steel 81-0076RK-03 Zero air calibration cylinder, 103 liter 81-1050RK Regulator, with gauge and knob, 0.5 liter/minute continuous flow, for 17 liter and 34
liter steel calibration cylinders (cylinders with external threads)
81-1051RK Regulator, with gauge and knob, 0.5 liter/minute continuous flow, for 34 liter alumi-
num/58 liter/103 liter calibration cylinders (cylinders with internal threads)
81-1117RK Calibration cup
61-1000RK-05/61-0140RK-05 Com bus tible Gas De tect or • 15