RK Electronics TDR-F Data Sheet

TDR-F
Initiate
Off Delay & One Shot Timer
• 24 to 240VAC/VDC
(Universal Voltage)
• Off Delay & One Shot Functions
• Time ranges up to 24 hrs
• Adjustment Knobs
• Plug-In Package
• DPDT Contacts
• Status LEDs
Listed
42L2
Specications
Electrical
Supply Voltage: 24 to 240VAC/VDC Frequency: 50 to 400Hz
Functions: On Delay & Interval On Time Ranges: 0.1Sec. up to 24 Hrs. Fine Adjustment Pot:
On Top: Adjusts within Range Remote (11Pin): 1KΩ to 20KΩ
Adjusts within Range
Power Consumption: 1.5VA Indicators: 2 LEDs
Output Rating @ 25°C:
Must be used with UL approved socket to satisfy UL Listing.
Ordering Information
TDR - 24/240V - A F 8 -
R-K Model
Voltage
24/240V - 24-240VAC/VDC
Adjustment
A - Adjustable F - Fixed R - Remote X - Special
Part number includes socket and holddown.
5 Amps @ 250VAC (General Purpose) 1/8 HP @ 120VAC 5 Amps @ 30VDC B300 (Pilot Duty) 360 VA 3 Amps @ 120VAC
1.5 Amps @ 240VAC
Physical
Mounting: Plug-In Termination: 8 or 11Pin Packaging: Dust Cover Weight: 8.5 Oz. Approx.
Ambient Temperatures
Operating: 0°C to 65°C Storage: -40°C to 85°C
Option
XXXX
Pin Base
8 - 8 Pin Base
11 - 11 Pin Base
Function
F - Off Delay & One Shot
X - Special
Off Delay & One Shot
Operations
The TDR-F alows you to select between Off Delay and one Shot timing. The universal supply voltage accepts most typical control voltages
By selecting Off Delay with the function pot on the top, with supply voltage ap­plied, when the Initiate Voltage or Contact are activated, the internal relay is en­ergized. When the Initiate Voltage or Contact are de-activated, the internal relay remains energized and the timing begins. After the time delay, the internal relay de-energizes and the timing resets.
If the Initiate Voltage or Contact re-activate before the timing cycle is completed, the timing is reset. The timing will re-start when the Initiate Voltage or Contact is de-activated again.
By selecting One Shot with the function pot on the top, with supply voltage applied, when the Initiate Voltage or Contact is activated, the internal relay is energizes and the timing begins. After the time delay is completed, the internal relay de-energizes and the timing is reset.
Re-activating the Initiate Voltage or Contact dur­ing timing does not interrupt the timing cycle.
2/4/13
Supply Voltage
Initiate Voltage
or Contact
Off Delay Function
One Shot Function
Dimensions
3.6"
Connections
45
1
Supply
6
7
8
3
2
.6" 1.8"
Initiate
Contact
Contact
2.3"
Initiate
Voltage
6
5
1
Supply
11
7
8
9
10
4
3
2
Txx