RK Electronics TDR-A Data Sheet

TDR-A
21
Supply
21
-+
C1
Input Voltage
+
-
Alternating Relay Local or Remote
• Sequence Switch
• 24 to 240VAC/VDC (Universal Voltage)
• Float or Contact Input
• Local or Remote Selector Switch
• Plug-In Package
• Status LEDs
Specications
Electrical
Supply Voltage: 24VAC/VDC
to 240VAC/VDC
Frequency: 50 to 400Hz Pick-Up/Drop-Out Delay: 0.5 Sec Pump Select: Pump #1-Auto-Pump #2 Switch Select: Local-Remote Power Consumption: 1.5VA Indicators: 2 LEDs
Output Relay: Green-On; Red-Off Float Input: Green-Closed; Red-Open
Output Rating @ 25°C:
5 Amps @ 250VAC (General Purpose) 1/8 HP @ 120VAC 5 Amps @ 30VDC B300 (Pilot Duty) 360 VA 3 Amps @ 120VAC
1.5 Amps @ 240VAC
Ordering Information
TDR - 24/240V - A A 8
R-K Model
Voltage
24/240V - 24-240VAC/VDC
Physical
Mounting: Plug-In Termination: 8 or 11Pin Packaging: Dust Cover Weight: 8.5 Oz. Approx.
Ambient Temperatures
Operating: 0°C to 65°C Storage: -40°C to 85°C
Must be used with UL approved socket to satisfy UL Listing.
Option
X - Cross-Wired
Txx
Listed
42L2
Operation
Alternator Function
The TDR-A provides an alternating func­tion, based on the opening of the remote contact “C” (Float Switch).
With supply power applied when the remote contact C closes, the output relay stays in its existing condition. When con­tact C opens, the output relay changes state. Each subsequent opening of the contact C changes the state of the output contacts and provides the alternating function.
Selecting “Adjustable” option provides a Local-Remote pump selection switch on the TDR-A.
• Local - “Pump 1-Auto-Pump 2” switch
is on the TDR-A
• Remote - A remote selector switch can
be wired into the socket
Relay LED: Red - De-energized Green - Energized Input LED: Red - No Input Signal Green - Closed Input
7/17/12
Adjustment
A - Adjustable F - Fixed
Part number includes socket and holddown.
Connections
Supply
-
Remote
Switch
A
21
45
3
2
1
Function & Base: AA8-X
+
Function & Base: AA8
C
6
7
8
Remote
Switch
45
3
C
2
1
Function
A - Alternator X - Special
A
6
.
7
8
Dimensions
3.6"
Supply
+
Remote
Switch
C
5
4
3
2
1
Function & Base: AA11
-
A
6
7
8
9
10
11
Pin Base
8 - 8 Pin Base
11 - 11 Pin Base
.6" 1.8"
2.3"
Example: TDR-24/240V-AA8 MS1 = Load #1 (Motor Starter) MS2 = Load #2 Motor Starter C1 = Control Contact