Electrical
Input Voltage:
Up to 600VAC, 3Ø, 50/60Hz.
Capacitance:
0.47 microfarads, ±10%
Resistance:
100 or 220 ohms, ±5%, 7 watts
Varistors:
Max. Allowable AC Voltage: 625VAC
Max. Clamping Voltage: 1650V @ 50A
Energy: 40 joules
Bleeding Resistor:
1 megohms, 1/2 watt
Power Consumption:
37 watts @ 600VAC
Ordering Information
600VAC
Three Phase
Transient Voltage
Filters
Physical
Mounting: Surface
Termination:
#16 Stranded Wire Leads
Packaging: Dust Cover
Weight: 12 Oz.
Ambient Temperatures
Operating: -40°C to 85°C
Storage: -40°C to 85°C
RCY
• 600 Volt Ratings
• Wye Configuration
• Three Phase (3Ø)
Applications
• Varistor Option
RC Y 6 A - 30
R-K Model
Arrangement
Y - Wye
Voltage Series
2 - 240VAC
6 - 600VAC
DIN Rail Bracket #DRB-4
Resistor
A -220 Ohms
G -100 Ohms
18 - 18 Ohms (Not CSA)
Other Option
C - Multi-Conductor
Cable (CSA only)
R - Bleeding Resistor
Varistor Option
V - Varistor
Lead Length
30 - 30 Inches
__ - Specify Lead Length
Dimensions Connections
RCR
R
C
RCY6_-_
MS
L1
L2
C
OL
1.5"
.75"
3"
2.4"
3.8"
4.75"
4.25"
L3
Hook-Up
Example
M = Motor
MS = Motor Starter
OL = Overloads
C
RCR
V V
R
C
RCY6_-_V
RCY
• Bleeding Resistor
Option
• Single Package
• Stranded Wire Leads
E71902
STANDARD 508
Operation
Transient Voltage Filters
R-C networks (ResistanceCapacitance) are applied to circuits
where transient electrical voltage
spikes can cause a malfunction or
damage in solid state controls or
control systems (PLCs, CNCs,
NCs, Solid State Counters, etc.).
The RCY is typically applied in
parallel with three phase inductive
loads (motors) to absorb the
VV
M
transients generated when the load
is disconnected from the line. It
also absorbs electrical noise while
the load is operating. The Varistor
option provides additional protection by clamping the transients at a
specific voltage level (Max.
Clamping Voltage). The Bleeding
Resistor allows the voltage that
builds up on the capacitor in the
RCY to bleed off after voltage is
removed. The Bleeding Resistor is
typically used in applications where
the control with the RCY may be
operated (tested) without the load
(motor) connected.
LR43414
• •
11/06/02
F9