RK Electronics RCY Catalog Page

Specifications
Electrical
Input Voltage:
Up to 600VAC, 3Ø, 50/60Hz.
Capacitance:
0.47 microfarads, ±10%
Resistance:
100 or 220 ohms, ±5%, 7 watts
Varistors:
Max. Allowable AC Voltage: 625VAC Max. Clamping Voltage: 1650V @ 50A Energy: 40 joules
Bleeding Resistor:
1 megohms, 1/2 watt
Power Consumption:
37 watts @ 600VAC
Ordering Information
600VAC Three Phase Transient Voltage Filters
Physical
Mounting: Surface Termination:
#16 Stranded Wire Leads
Packaging: Dust Cover Weight: 12 Oz.
Ambient Temperatures
Operating: -40°C to 85°C Storage: -40°C to 85°C
RCY
• 600 Volt Ratings
• Wye Configuration
• Three Phase (3Ø) Applications
• Varistor Option
RC Y 6 A - 30
R-K Model
Arrangement
Y - Wye
Voltage Series
2 - 240VAC 6 - 600VAC
DIN Rail Bracket #DRB-4
Resistor
A -220 Ohms
G -100 Ohms 18 - 18 Ohms (Not CSA)
Other Option
C - Multi-Conductor Cable (CSA only) R - Bleeding Resistor
Varistor Option
V - Varistor
Lead Length
30 - 30 Inches
__ - Specify Lead Length
RCR
R C
RCY6_-_
MS
L1
L2
C
OL
1.5" .75"
3"
2.4"
3.8"
4.75"
4.25"
L3
Hook-Up Example
M = Motor MS = Motor Starter OL = Overloads
C
RCR
V V
R C
RCY6_-_V
RCY
• Bleeding Resistor Option
• Single Package
• Stranded Wire Leads
E71902 STANDARD 508
Operation
Transient Voltage Filters
R-C networks (Resistance­Capacitance) are applied to circuits where transient electrical voltage spikes can cause a malfunction or damage in solid state controls or control systems (PLCs, CNCs, NCs, Solid State Counters, etc.). The RCY is typically applied in parallel with three phase inductive loads (motors) to absorb the
VV
M
transients generated when the load is disconnected from the line. It also absorbs electrical noise while the load is operating. The Varistor option provides additional protec­tion by clamping the transients at a specific voltage level (Max. Clamping Voltage). The Bleeding Resistor allows the voltage that builds up on the capacitor in the RCY to bleed off after voltage is removed. The Bleeding Resistor is typically used in applications where the control with the RCY may be operated (tested) without the load (motor) connected.
LR43414
11/06/02
F9