480VAC
Single Phase
Transient Voltage
Filters
Specifications
Electrical
Input Voltage: Up to 480VAC, 1Ø, 50/60Hz.
Capacitance: 0.47 microfarads, ±10%
Resistance: 18 to 220 ohms, ±10%, 7 watts
Varistors:
Voltage Max. Allowable Max. Clamping Energy
Code AC Voltage Voltage (Joules)
5625VAC 1650V @ 50A 130
Power Consumption: 10VA @ 480VAC
Physical
Termination: #16 Stranded Wire
Packaging: Epoxy Filled
Weight: 6 Oz.
Ambient Temperatures
Operating: -40°C to 85°C
Storage: -40°C to 85°C
Ordering Information
RCS5
• 480 Volt Rating
• Single Phase (1Ø)
Applications
RC S 5 A - 30
R-K Model
Arrangement
S - Single Phase
Voltage Series
5 - 480VAC Nom.
DIN Rail Bracket #DRB-2
Connections
R
Without Varistor
R
C
C
V
Varistor Option
V - Varistor
Lead Length
30 - 30 Inches
__ - Specify Lead Length
Resistor
A - 220 Ohms
G - 100 Ohms
18 - 18 Ohms
Hook-Up Example
MS = Motor Starter
SV = Solenoid Valve
C1 = Contact
C2 = Contact
RCS = R-C Network
Voltage
C1
MS
• Varistor Options
• Stranded Wire Leads
Operation
Transient Voltage Filters
R-C networks (Resistance-Capacitance) are applied to circuits where
transient electrical voltages can
cause a malfunction or damage in
solid state controls or control
systems (PLCs, CNCs, NCs, Solid
State Counters, etc.). The RCS5s
are typically applied in parallel with
single phase inductive loads (motor
starter coils, contactor coils,
solenoid valves, etc.) to absorb the
transients generated when the load
is de-energized.
Dimensions
2"
1.63"
1.3"
With Varistor
C2
• •
SV
RCS
RCS
4/00
2.7"
1.4"
F4