RK Electronics MSS Data Sheet

Specifications
Input Voltage: 24 to 220V ±10% Frequency: AC - 50/60Hz
DC - Filtered to Full Wave
Time Delays:
Type: Adjustable, Factory Fixed or Remote Range: 100 Milliseconds to 5 Minutes Repeat Accuracy: ±1% with Fixed Conditions Control Contact Response Times:
During Timing: 135 Milliseconds,Typical After Timing: 12 Milliseconds, Typical
Protection: Varistor and/or R-C Network Power Consumption: 5VA Output Ratings:
Type: Solid State Form: One Normally Open (1NO, Form A)
Non-Isolated
Rating: 1 Amp Continuous @ 25°C
Resistive: 100%PF Inductive: 75-80%PF 15 Amps Inrush, Non-repetitive 30 mA to ensure Turn-on
Ordering Information
MSS - 120A - 3 S -
R-K Model
Input Voltages
24D - 24VDC
24A - 24VAC
120A - 120VAC 220A - 220VAC
DIN Rail Bracket #DRB-2
Dimensions
2"
1.63"
5 6
1.2"
2.7"
One Shot Solid State Timer
Physical
Mounting: Surface, #6 Screws Termination:
Screw or .25" Push-On Tabs
Packaging: Epoxy Filled Weight: 4 Oz.
Ambient Temperatures
Operating: 0°C to 65°C Storage: -30°C to 85°C
Notes:
Remote Timing Resistors - multiples of
2.7 megohms will increase the time delay by 1 minute ±20%.
For adjustment codes 3 & 4 a jumper or resistor must be installed across terminals 5 and 6 to allow the timer to time out.
(Fixed Time)
Termination
S - Screw Terminals
T - .25" Push-OnTabs
Adjustments
1 - Fixed Internally (Specify time in sec.) 2 - Adjustable .1 to 45 sec. with internal pot. 3 - Adjustable .1 to 300 sec. with remote
resistor and internal pot
4 - Remote timing resistor
Connections
Remote Timing Adj.
MS = Load
(Motor Starter)
C1 = Control
Contact
5 6
1 2 3 4
MSS
1 Amp Output, 1NO
Indicating LED
Fixed or Adjustable
Delays
Screw Terminals or Push-On Tabs
Voltages from 24 to 220 Volts
Epoxy Filled
Operation
One Shot
When input voltage is available, closure of the customer supplied contact (C1) will energize the load and begin the timing cycle. At the end of the timed period, the load will be de-energized. Closure of the contact supplying voltage to the MSS may be maintained, momentary or repeated. The load will only remain energized for the time period initiated by the initial closure of the contact. The MSS resets when the timed cycle is complete with the contact open or the input voltage is removed.
Time Delay
1 2 3 4
1.4"
C1
MS
Load
Input Voltage
+
Load De-Energized
Contact Closure (Maintained or Momentary)
4/00
E10