RK Electronics MRT Data Sheet

Motor & Line
L1 L2 L3
Direct to the 3Ø Line or to a Motor
1 11/16"
2 5/8"
L1 L2 L3
2"
4 1/8"
5/16"
MAGNET
MRT
• Tests for Motor Rotation (Off Line)
• Tests for Phase Sequence (On Line)
• T
ests Presence of
All Phases
• No Fuses
Rotation Tester
Specifications
Electrical
Line Voltage:
20mVAC to 600VAC, 3Ø
Frequency: Manual Turning* to 400Hz Phase Rotation:
L1, L2, L3 which is A, B, C, Respectively
Rotation Indicator:
Green LED: Correct Rotation
Battery Indicator:
Green LED: Battery OK
Battery Type:
9 Volt DC Alkaline Battery, Included
Connections
Physical
Termination:
Alligator clips w/color coded boots
Cable Length: 9” leads Packaging: Nema 1 enclosure Weight: 6.5 oz. w/batt. & w/o magnet
9.0 oz. w/battery & magnet
Magnet Pull Strength: 30 lbs.
Ambient Temperatures
Operating: 0°C to 50°C Storage: -30°C to 85°C
*Note: Some motors may require turning
faster than others due to the permeability of the motor, which is related to the abil­ity to generate a sinewave signal large enough to test.
Ordering Information
MRT - M
R-K Model
M - Magnet Option Installed
Tests 20mVAC to
600VAC, 3Ø
• Recessed Push Button
• LED Indicators
• Clip Leads for Easy Hook-Up
Operation Warning: Always remove power when connecting
and disconnecting the MRT clip leads!
The MRT is designed to determine which combination of motor leads will provide the desired motor rotation when matched with the three phase electrical system under test. The Correct Rotation LED indicates the phase sequence to obtain the desired motor rotation. Remove power from the circuit to be tested and connect the three MRT (L1, L2, and L3) to the terminals to be tested.
For Line Rotation T
off, re-apply power while depressing the “Rotation Test” push button on the MRT. If the green Correct Rotation LED lights, the three phase rotation sequence matches the MRT sequence. If the LED does not light, remove power and reconnect the MRT by switching two leads. The green Correct Rotation LED should light. Remove power and rewire the control to match the rotation determined by the MRT. If the LED still does not light, one or more phases is missing. Check your fuses and wiring.
For Motor Rotation T
motor by hand while depressing the “Rotation Test” push button on the MRT. If the green Correct Rotation LED lights, then connecting the motor leads to the matching three phase voltage leads will provide the desired rotation. If it does not light, switch two leads and try again.
01.01.08
After the MRT has been connect to the line with power
esting:
esting:
Connect the MRT leads to the motor leads. Rotate the
leads
The magnet option allows you to tem­porarily connect the MRT to your motor, freeing your hands so you can hook up the clip leads without holding on to the MRT. After hook-up is completed, you can then verify rotation with the push of a button. Warning: Do not place MRT-M
Dimensions