RK Electronics DPMP Data Sheet

DPMP
DPMP
460 460 460 ON
Digital Phase Monitor
Digital Voltage Monitor
Panel Mounting (On the Door)
Single & Three Phase
200-240VAC, Single Phase
200-600VAC, Three Phase
All Digital Settings
11.16.16
Purpose
The purpose of the DPMP is to monitor the line voltage sup­plying single and three phase systems, providing the oppor­tunity to disconnect equip­ment if the voltages are outside of the selectable operational parameters.
Operation
If the voltages and rotation are within the selectable set-up parameters, the DPMP will en­ergize the internal relays, trans­ferring the output contacts. If the voltages and/or rotation are outside any of the set-up parameters, the DPMP internal relays will not energized.
If the line voltage does not meet all of the set-up param­eters, the Default screen will toggle between the voltage screen showing the actual voltages and words describing the fault.
During transitions to relays en­ergized or relays de-energized, the remaining time in seconds is displayed above the present relay condition (“ON” or “o”).
General Operational Specications
Line Voltages Monitored: 200 to 240VAC, 1Ø, 50/60Hz 200 to 600VAC, 3Ø, 50/60Hz Faults: Overvoltage Undervoltage Phase Loss Phase Rotation Phase Imbalance Frequency Out of Range Set-Up: Membrane Buttons & Digital Display
• Nominal Line Voltage
• Over/Undervoltage percentage (7% to 15%)
• Trip Time Delay (2 seconds to 10 seconds)
• Re-Start Time Delay (Manual Reset to 4 minutes)
• Phase Imbalance Percentage (3% to 10%) Screens: Manufacture Name and Firmware Version Average Voltage, Frequency, Imbalance, Relay Status A-B, B-C & C-A Voltages, Relay Status Nominal Voltage Selection (Pay attention to 1Ø and 3Ø at the end of the voltages) Over/Undervoltage Percentage Selection Trip Time Delay Re-Start Time Delay Phase Imbalance Percentage Selection History with Last 4 Faults (Wraps back to Manufacture Name and Firmware Version)
Default Set-Up
The default set-up for the DPMP as shipped from R-K Electronics is: Line Voltage: 480VAC, 3Ø Over & Undervoltage: ±5% Trip Time Delay: 5 seconds Re-Start Time Delay: 5 seconds Phase Imbalance: 5%
Custom Set-Up
The DPMP uses 4 membrane buttons to allow the customer to change the set-up criteria for their particular line voltage and preferred parameters. The following listings show the arrangement and selections available by moving through the menu choices. The membrane buttons allow for movement right or left with wrap around to selection criteria and up and down within a selection for specic parameters.
You can select the set-up parameters with only the supply voltage connected.
Example: From the Default screen (A-B, B-C & C-A voltages with relay status) pressing the right Arrow will take you to the line voltage selection parameters. If you want to change the nominal voltage to a dierent voltage, press the Up or Down arrows. Once you have the line voltage (and number of phases) that you want displayed on the screen:
1. Pressing either the Right or Left arrow will set the new line voltage parameter into memory and take you to the next screen, or
2. After 30 seconds of no action, the new voltage parameter will be set into memory and the screen will go back to the default screen.
2
Example: If you want to change the Re-Start Delay to 3 minutes (default is 5 seconds) and you are on the Default screen:
1. Press the Right arrow until you get to the Re-Start Delay screen
2. Press the Up button until you have 3 Minutes on the screen
3. Pressing either the Right or Left arrow will set the new Re-Start Delay into memory and take you to the next screen, or
4. After 10 seconds of no action, the new Re-Start Delay will be set into memory and the screen will go back to the Default screen.
Screens
Manufacturer’s Screen
R-K Electronics DPMP v0.0.00
Average Voltage Screen
VAvg Imb Hz 460 0 60 o
Default – The Default screen shows the real time voltage detected on each of the 3 phases: A-B B-C C-A 460 459 461 ON
Voltage Selection Screen (Vertical Format) 200, 1Ø; 208, 1Ø; 220, 1Ø; 230, 1Ø; 240, 1Ø; 200, 3Ø; 208, 3Ø; 220, 3Ø; 230, 3Ø; 240, 3Ø; 380, 3Ø; 415, 3Ø; 440, 3Ø; 460, 3Ø; 480, 3Ø; 575, 3Ø; 600, 3Ø;
Over/Undervolage Percentage Screen (Vertical Format) 7%, 8%, 9%, 10%, 11%, 12%, 13%, 14% & 15%
Trip Time Delay Screen (Vertical Format) 2S, 3S, 4S, 5S, 6S, 27S, 8S, 9S & 10S
Re-Start Time Delay Screen (Vertical Format) Manual, 2S, 3S, 4S, 5S, 6S, 7S, 8S, 9S,10S, 30S, 1M, 2M, 3M & 4M
Phase Imbalance Percentage Screen (Vertical Format) 3%, 4%, 5%, 6%, 7%, 8%, 9% & 10%
Fault Screen (Vertical Format) “0” most recent fault, “1” previous fault, “2” third oldest fault & “3” fourth oldest fault
Fault words: “Phase A Loss” (There is no voltage sensed on 3-L1/S) “Voltage Low” (Average line voltage is less than selected Undervoltage percentage) “Voltage High” (Average line voltage is more than selected Overvoltage percentage) “Imbalance” (One Phase is lower than the average voltage by more than the Imbalance percentage) “Phase Loss” ( One phase is more than 30% below the Line Voltage selection) “Bad Rotation” (The phase rotation sequence is reversed) “Bad Freq” Line frequency out of allowable range of 45 to 65Hz)
3
DPT
Digital P
ercentage Timer
Specifications
Electrical
Supply 'Voltage:
24VAC, 120VAC & 240VAC,
Frequency; 50/60Hz Display: 16 Character, 2 Line, LCD
Back Lighting
Adjustments: Membrane Buttons & Display Total Cycle Times: 15 & 30 Min On Tme Percentages: 5% to 95%, 5% Increments Manual: On or Off
Running Hours:0 to 99,999 Hrs.
Output Rating @ 25°C: 10 Amps @ 120VAC 6 Amps @ 277VAC 1/8 HP @ 120/277 VAC 5 Amps @ 30 VDC
Digital Dispaly:
- R
emaining Time
- Time & Percentage Settings
- Running Hours
- Output Relay Status
Multiple Mounting Dimensions
SPDT Contacts
Gasketed Cover
DPT - 120A - 15/30 -
Supply Voltage
24A - 24VAC
1
20A - 120VAC
240A - 240VAC
Special xxxx - Special
The DPT is a Digital PercentageTimer. Operational information is displayed for easy viewing: tiime remaining till relay transfer, relay status, running hours & set-up parameters. With the supply voltage active, The DPT will activate the relay output for the percentage of time selected in set-up. For total cycle time, you can select either 15 or 30 minutes. On time can be selected in 5% increments for 5% to 95%. Manual selection of either continuous On or Off is available. Running hours are accumulated based on the output relay being energized.
Operation
Physical
Mounting: Panel Mounting
4 - Inserts for 2 mounting dim
Termination: Pluggable Block Packaging: Gasketed Face Weight: 1 Pound
Am
bient:Temperatures:
Operating : -20°C to 60°C Storage: 40°C to 85°C
Dimensions
Connections
Ready to Submit
Timing
1
5/30 - 15 & 30 Minutes
Gasket
Supply Voltage
NOCNC
MS
.
.
Listed
42L2
Specications
Supply Voltage: 24VAC, 120VAC or 208/240VAC, 1Ø Part Number: 12 VDC Supply: DPMP-12D-B 24 VDC Supply: DPMP-24D-B 24 VAC Supply: DPMP-24A-B 120 VAC Supply: DPMP-120A-B 240 VAC Supply: DPMP-240A-B
Display: 16 Character, 2 line; Back Lighting Voltage Accuracy: Approx ±1% Buttons: (4) Right & Left, Up & Down Line Voltage Ranges: 200 to 240VAC, 1Ø 200 to 600VAC, 3Ø Frequency Range: 45 to 65Hertz for all voltages Over & Undervoltage: 8% to 15% Phase Imbalance: 3% to 10% Phase Loss: ≥30% low voltage in any one phase Phase Rotation: A-B-C Re-Start Time Delay: 1 second to 4 minutes Manual Reset Option Trip Time Delay: 1 second to 30 seconds Output: SPDT Contact, 10A @ 120VAC Mounting: Panel Mounting Body: 2-7/8” Circular Hole (2-1/2” conduit punch) Holes: (4) Mounting Holes, #10 Termination: Pluggable Terminal Blocks Packaging: Approx. 3.88”H x3.88W x3.6”D (Front to back of terminal blocks)
Nema 12
Dimensions
L1 L2 L3 460 460 460 ON
3.88"
Connections
L1 L2 L3
L3
NC
L2
DPMP
L1
NO
0.71"
MS
2"
2.9" 2.81"
2.875"
L1
L2
3.88"
.88"
L3
L1
L2
NC
NO
0.2" Dia.
2.5"
2.5"
2.81"
MS
3" Dia.
2.875"
Supply Voltage
+
MS
4
Supply Voltage
+
MS
Loading...