RK Electronics CSB Data Sheet

7 9658
3
4
2
1
Customer Contact (C1)
A B
-
Customer Contact (C1)
-
8
6
7
4
5
3
2
1
1
3
4
5
6
7
10
11
-
2
8
9
Customer Contact (C1)
Input
Voltage
Input
Voltage
Input
Voltage
One Shot
One Shot
When input voltage is available, closure
of the customer supplied contact (C1)
will energize the internal relay and begin
the timing cycle. At the end of the timed
period, the relay will be de-energized.
Closure of the contact (C1) may be
maintained, momentary or repeated. The
relay will only remain energized for the
time period initiated by the initial closure
of the contact. The CSB resets when
timed cycle is complete with the contact
open or the input voltage is removed.
Input Voltage
24 or 125VDC ±10%, Filtered to Full Wave
Time Delays:
Type: Adjustable or Factory Fixed
±10Milliseconds, Whichever is Greater
After Timing: 50 Milliseconds, Typical
Varistor and/or R-C Network
5VA
500,000 Full Load Electrical Cycles
50,000,000 Mechanical Cycles
6.5 Amps, 1/3 HP, 125VA @ 240VAC
7 Amps, 1/6 HP, 125VA @ 120VAC
Plug-In
Termination:
Weight:
7 Oz.
-10°C to 40°C
- 115VAC
1 - Fixed (specify time) (DPDT-11 Pin)
- Knob On Top (DPDT-11 Pin)
4 - Fixed (specify time) (SPDT-8 Pin)
5 - Knob On Top (SPDT-8 Pin)
Adj. Code 1B & 5B
Adj. Code 1 & 2
Adj. Code 4 & 5
2.9"
.6"
.6"
3.5"(B)
1.8"
2.3"
Contact Closure (Maintained or Momentary)
Output Contacts De-Energized
Time Delay
Time Delays
1S - 0.05 to 1 Sec.
5S - 0.05 to 5 Sec.
- 0.1 to 10 Sec.
30S - 0.3 to 30 Sec.
1M - 0.6 Sec. to 1 Min.
2M - 1.2 Sec. to 2 Min.
3M - 1.8 Sec. to 3 Min.
5M - 3 Sec to 5 Min.
30M - 18 Sec. to 30 Min.
1H - 36 Sec. to 1 Hr.
5H - 3 Min. to 5 Hr.
24H - 14.4 Min to 24 Hr.
®
CSB
• Digital CMOS Design
• 10 Amp, DPDT
• ±0.2% Repeatability
Plug-In Timer
Specifi cations
Electrical
Physical
Ambient Temperatures
Ordering Information
• Transient Protected
• Timing Ranges Up To 24 Hours
Operation
Dimensions Connections
E11
5/28/07
513.204.6060 or 800.543.4936 •