AC Current Sensing
16 Amp
Connection
2
7
+
-
4 5
1
3
6
8
Energized
Pick-Up
Drop-Out
De-Energized
2%
3.1" .6" 1.8"
2.3"
C-T
C-T
1"
.9"
.5"
CJD
• Thru Hole C-T
• 2 to 50 Amps, 5 Ranges
• 10 Amp Relay
• Noise Filter
Plug-In
Specifications
Electrical
Input Supply Voltage:
24V AC or DC
120 or 240VAC, ±15%, 50/60Hz
Sensitivity Range Connections:
2 to 8 Amps - No Connections
6 to 16 Amps - Connect 7 & 6
9 to 26 Amps - Connect 7 & 5
16 to 42 Amps - Connect 7 & 8
20 to 50 Amps - Connect 7, 6, & 8
Wire Hole Diameter: 0.35 Inch
Pick-up & Drop-out Delays:
1 Sec. Typical
Pick-up & Drop-out Differential: 2%
Power Consumption: 2VA
Output Rating SPDT @ 25°C:
10 Amps @ 250VAC, 30VDC
1/2 Hp @ 250VAC
1/3 Hp @ 125VAC
Ordering Information
Physical
Mounting: Plug-In
Termination: 8 Pin Octal
Packaging: Dust Cover
Weight: 9 Oz.
Ambient Temperatures
Operating: 0°C to 40°C
Storage: -40°C to 85°C
If current being monitored is too low
for adjustment range, multiple passes
through C-T increases effective current.
2 Passes = Double
3 Passes = Triple
• Time Delay
• Adjustable Setpoint
• Compact Design
• Low Cost
Listed
42L2
Operation
AC Current Sensing
An Input voltage must be supplied
to the CJD continuously. With the current adjustment at the desired
set point, the internal relay will energize and transfer the output contacts
when the current through the C-T
on the side of the CJD exceeds the
adjustable set point for the time delay.
When the current drops 2% below the
set point, the internal relay will deenergize after the time delay. Current
ranges on the multi-range CJD are
selected by jumpers on the socket.
CJD - 120A - 5
R-K Model
Supply Voltage
24V - 22 to 28VAC/VDC
120A - 100 to 130VAC
240A - 200 to 250VAC
Connections
Example of CJD hook-up for:
8 to 16 Amp adjustment range
Adjustments
5 - 2 to 50 Amps in five ranges
Dimensions
1 Pass:
1 Amp = 1 Amp
9/20/10
2 Passes:
1 Amp = 2
•
Amps