RK Electronics CJD Data Sheet

AC Current Sensing
16 Amp Connection
2
7
+
-
4 5
1
3
6
8
Energized
Pick-Up
Drop-Out
De-Energized
2%
3.1" .6" 1.8"
2.3"
C-T
C-T
1"
.9"
.5"
L
o
o
p
I
t
!
CJD
• Thru Hole C-T
• 2 to 50 Amps, 5 Ranges
• 10 Amp Relay
• Noise Filter
Plug-In
Specifications
Electrical
24V AC or DC 120 or 240VAC, ±15%, 50/60Hz
Sensitivity Range Connections:
2 to 8 Amps - No Connections 6 to 16 Amps - Connect 7 & 6 9 to 26 Amps - Connect 7 & 5 16 to 42 Amps - Connect 7 & 8 20 to 50 Amps - Connect 7, 6, & 8
Wire Hole Diameter: 0.35 Inch Pick-up & Drop-out Delays:
1 Sec. Typical
Pick-up & Drop-out Differential: 2% Power Consumption: 2VA Output Rating SPDT @ 25°C:
10 Amps @ 250VAC, 30VDC 1/2 Hp @ 250VAC 1/3 Hp @ 125VAC
Ordering Information
Physical
Mounting: Plug-In Termination: 8 Pin Octal Packaging: Dust Cover Weight: 9 Oz.
Ambient Temperatures
Operating: 0°C to 40°C Storage: -40°C to 85°C
If current being monitored is too low for adjustment range, multiple passes through C-T increases effective current. 2 Passes = Double 3 Passes = Triple
• Time Delay
• Adjustable Setpoint
• Compact Design
• Low Cost
Listed
42L2
Operation
AC Current Sensing
An Input voltage must be supplied to the CJD continuously. With the cur­rent adjustment at the desired set point, the internal relay will ener­gize and transfer the output contacts when the current through the C-T on the side of the CJD exceeds the adjustable set point for the time delay. When the current drops 2% below the set point, the internal relay will de­energize after the time delay. Current ranges on the multi-range CJD are selected by jumpers on the socket.
CJD - 120A - 5
R-K Model
Supply Voltage
24V - 22 to 28VAC/VDC 120A - 100 to 130VAC 240A - 200 to 250VAC
Connections
Example of CJD hook-up for: 8 to 16 Amp adjustment range
Adjustments
5 - 2 to 50 Amps in five ranges
Dimensions
1 Pass: 1 Amp = 1 Amp
9/20/10
2 Passes: 1 Amp = 2
Amps