Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper
WARNING
All Rights Reserved, Copyright 2009-2018, RKC INSTRUMENT INC.
operation of your new instrument, carefully read all the instructions in this manual. Please place the manual
in a convenient location for easy reference.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity, process
control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components have
a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in this
manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored, processed
or retrieved through any mechanical, electronic, optical or other means without prior written approval
from RKC.
An external protection device must be installed if failure of this instrument could
result in damage to the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned on to prevent electric shock,
fire or damage to instrument and equipment.
Don't use this product in any method not specification by manufacturer. The
protective features of this product may be impaired if it is used in a method not
specified in the operation manual.
This instrument must be used in accordance with the specifications to prevent fire
or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc. to
avoid electric shock.
Do not use in an environment where there is strong electromagnetic interference.
May cause the operation to become unstable.
RKC is not responsible if this instrument is repaired, modified or disassembled by
other than factory-approved personnel. Malfunction can occur and warranty is void
under these conditions.
This product is intended for use with industrial machines, test and measuring equipment.
(It is not designed for use with medical equipment and nuclear energy.)
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take additional measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply, source of
power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All high-voltage
connections such as power supply terminals must be enclosed in the instrumentation panel to avoid
electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock, instrument failure,
or incorrect action.
The power must be turned off before repairing work for input break and output failure including
replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned
on again.
To prevent instrument damage or failure, protect the power line and the input/output lines from high
currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid electric
shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock, fire
or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front panel with
a hard object.
This instrument is intended to be used under the following environmental conditions.
Installation features: Indoor
Altitude: 2000 m or less
Ambient temperature: 0-50 °C
Ambient humidity: 20-80 %RH (Non-condensing)
Overvoltage category: Category II
Allowable pollution degree: Pollution degree 2
Power module that is used in the instruments conform to EN60950-1/A12: 2011.
When installing this instrument, put on a protective gear such as safety shoes, helmet, etc. for your
safety.
Do not put your foot on the installed instrument or get on it, because it is dangerous.
Only our serviceman or persons authorized by RKC are allowed to remove and take the inner
module, the main unit and printed circuit boards apart.
In case of damage or failure, contacting serviceman of our company, instruments should be against
unintended operation.
FOR PROPER DISPOSAL
When disposing of each part used for this instrument, always follows the procedure for disposing of
industrial wastes stipulated by the respective local community.
SYMBOLS USED ON THE INSTRUMENT
The symbols below are used on this instrument for the cautioning information.
This shows “Caution for handling”.
This symbol is used on the parts need to reference the instruction manual for saving
human body and the instrument.
This shows “Protective grounding”.
Be sure to provide protective grounding prior to operate this instrument.
This shows “Risk of electric shock”.
This symbol is used on the parts, which has a risk of electric shock.
Modbus is a registered trademark of Schneider Electric.
Windows is registered trademarks of Microsoft Corporation.
Company names and product names used in this manual are the trademarks or registered
3.1 Installation place ................................................................................................................................. 3-1
3.2 Installation on panel ............................................................................................................................ 3-1
4.1 Terminal stand array and LAN connector ........................................................................................... 4-1
4.2 Wiring for power supply ...................................................................................................................... 4-2
4.3 Wiring for analog input ........................................................................................................................ 4-3
4.4 Wiring for COM ALM ........................................................................................................................... 4-4
4.5 Wiring for LAN cable ........................................................................................................................... 4-4
4.6 Wiring for DI/DO (Option) .................................................................................................................... 4-5
4.7 Wiring for RS-485 (Option) ................................................................................................................. 4-8
4.8 Wiring for relay output (Option) ........................................................................................................... 4-8
5.1 Before operating ................................................................................................................................. 5-1
5.2 Start and stop of record ...................................................................................................................... 5-1
5.3 Output timing of recorded data to SD card .......................................................................................... 5-1
5.4 Recording operation at power failure .................................................................................................. 5-2
6
DISPLAY FUNCTION .................................................................................... 6-1
6.1 Basic composition of data display screen ........................................................................................... 6-1
6.2 Real time trend display of measured data ........................................................................................... 6-4
6.3 Display of measured data in bar graphs ............................................................................................. 6-4
6.4 Digital display of measured data ......................................................................................................... 6-5
7.2 Setting and checking ........................................................................................................................... 7-2
7.3 Outline of parameter setting procedure ............................................................................................... 7-3
7.4 Basic operation of setting screens ...................................................................................................... 7-4
7.5 Setting the input spec ......................................................................................................................... 7-7
7.6 Setting the scaling............................................................................................................................... 7-9
Setting the display method of channel ................................................................................................ 7-11
.
7.7
7.8 Setting the scale of channel ................................................................................................................ 7-13
7.9 Setting the alarm value ....................................................................................................................... 7-15
7.10 Setting the alarm action ...................................................................................................................... 7-17
7.11 Setting the REC/CALC ........................................................................................................................ 7-18
7.12 Copy the channel setting .................................................................................................................... 7-21
7.13 Setting the F value .............................................................................................................................. 7-22
7.14 Setting the timer of channel ................................................................................................................ 7-23
7.15 Setting the group name ....................................................................................................................... 7-24
7.16 Setting the displayed channel ............................................................................................................. 7-25
7.17 Select the ON/OFF of graph type........................................................................................................ 7-26
7.18 Setting the automatic change function of a display group ................................................................... 7-27
7.19 Setting the record cycle of main record ............................................................................................... 7-28
7.20 Setting the record cycle of sub record ................................................................................................. 7-30
7.21 Setting the schedule ........................................................................................................................... 7-32
7.22 Setting the unit .................................................................................................................................... 7-33
7.23 Setting the message ........................................................................................................................... 7-34
7.24 Setting the DI function ......................................................................................................................... 7-35
7.25 Counts the progress time .................................................................................................................... 7-36
7.26 Setting the production information ...................................................................................................... 7-37
7.27 Setting the Int. SP DO ......................................................................................................................... 7-38
7.28 Initialization of parameter .................................................................................................................... 7-40
7.29 Using the wizard function .................................................................................................................... 7-42
7.30 “Input CH” list ...................................................................................................................................... 7-43
7.31 “Calc. CH” list ...................................................................................................................................... 7-45
7.32 “Display” list ........................................................................................................................................ 7-47
7.33 “Record” list ........................................................................................................................................ 7-48
7.34 “Others” list ......................................................................................................................................... 7-49
8
SETTING AND CHECKING SYSTEMS ......................................................... 8-1
8.1 Outline of system setting procedure.................................................................................................... 8-1
8.2 Remove the SD card ........................................................................................................................... 8-2
8.3 Format the SD card ............................................................................................................................. 8-3
8.4 Save the set value .............................................................................................................................. 8-4
8.5 Load the set value............................................................................................................................... 8-5
8.7 Setting the IP address ......................................................................................................................... 8-7
8.8 Setting the keep alive function ............................................................................................................ 8-9
8.9 Setting the SNTP client function ......................................................................................................... 8-10
8.10 Setting the time zone and SNTP server function ................................................................................ 8-11
8.11 Setting the FTP user ........................................................................................................................... 8-12
8.12 Setting Modbus1 (RS485 communication setting, timeout, etc.) ......................................................... 8-14
8.14 Setting the Modbus master ................................................................................................................. 8-17
8.15 Setting the remote AI. ......................................................................................................................... 8-19
8.16 Setting the LCD sleep time ................................................................................................................. 8-20
8.17 Setting the clock.................................................................................................................................. 8-21
Setting the FUNC key ......................................................................................................................... 8-22
.
.
8.18
8.19 Setting the file format .......................................................................................................................... 8-24
8.20 Setting the jump menu ........................................................................................................................ 8-25
8.21 Setting the operation mode ................................................................................................................. 8-26
8.22 Setting the language ........................................................................................................................... 8-27
8.23 Display the system information ........................................................................................................... 8-28
8.24 Setting the security mode ................................................................................................................... 8-29
8.25 Setting the key lock function ............................................................................................................... 8-30
8.26 Setting the user ................................................................................................................................... 8-32
8.28 “Comm.” list ........................................................................................................................................ 8-34
8.29 “Device / Other” list ............................................................................................................................. 8-36
8.30 "Security" list ....................................................................................................................................... 8-38
10.2 Measurement range ............................................................................................................................ 10-2
10.3 Display part ......................................................................................................................................... 10-3
10.5 Record function ................................................................................................................................... 10-4
10.6 Alarm function ..................................................................................................................................... 10-5
10.8 Power supply part ............................................................................................................................... 10-6
10.13 Transportation and storage conditions ................................................................................................ 10-7
10.14 Optional function (Option) ................................................................................................................... 10-7
10.15 Support software ................................................................................................................................. 10-9
10.20 List of Security Logs ............................................................................................................................ 10-17
・Place where dust are little.
・
・
・Place where and where steam is a little. Place where moisture is a little.
・Place where direct sunshine doesn't strike. Place that doesn't become high temperature.
・
CAUTION
Externals, the function, and the longevity etc. of the product might be ruined when
keeping it in poor surroundings.
Environment when keeping it
Place that doesn't include flammable gas, firedamp, causticity gas (SO2, H2S).
Place without vibration and impact.
Place that becomes low temperature too much.
www.GlobalTestSupply.com
Page 9
1-2
【Option】
11
1.4 Confirmation of model number and specification
The marking plate to which the model number has been described is on the case. Please confirm this
instrument is a specification the same as the order referring to the table below.
There is no SD card in this equipment. Please buy it in the computer shop etc.
・SD card on the market is sold having formatted it usually, therefore, it is not necessary to
・Please confirm it is a correct direction and the firm insertion when it installs it. The
・
・When the SD card breaks, important recorded data is lost. The data preserved on the card
・
Standard of record
●
CAUTION
format it again.
the format feature of the personal computer standard, it is likely not to operate correctly.
Recorder cannot recognize the SD card when forcibly inserting it in a wrong direction.
Moreover, it causes the breakdown of the SD card and the main body of the Recorder.
Please note that the damage of the equipment when it reversely inserts it becomes off the
subject of the guarantee.
Please do not turn off power in recording of the SD card, and do not detach the SD card.
Data might damage, and delete it.
recommends the backup to be booked once a month.
MiniSD and the microSD card cannot be used. The use of miniSD and the microSD card
adaptor has the possibility that the card doesn't come off,
The standard of the record when the SD card of 2GB is used is as follows. Please note that the
capacity that can be recorded by the situation of the occurrence of warning and the message is
different.
[Condition]
-Number of inputs : 6 point
Recorded data form :Binary
--Record type :Maximum/minimum value record -
There is no event of the alarm, message etc.
1~32GB
1~32GB
Please go with this Recorder when formatting it. When formatting it by
therefore, please do not use it.
※ The record exceeding the product-life cycle is not guaranteed.
● Timing of data writing
For the timing of outputting recorded data to the SD card, refer to Section 5.3.
For the format of the recording file, refer to Section 10.17.
Allow the power ON/OFF, LCD (display) ON/OFF and record status to be displayed.
Lamp ON (highlighted) :Power ON, recording suspended
Lamp blinks(1 sec ON/1 sec OFF) :Power ON, recording in progress
Lamp blinks(high speed) :Power ON, SD card writing
Lamp OFF :Power OFF
④REC button
Used to start or stop recording.
⑤MENU button
Display the menu screen.
Used to the continuance of record when check screen of stops recording.
FUNC button
⑥
The content of operation is allocated, and the operation can be done. It can select the “Change
display”, “Capture”, “Message” and “Addition reset”.
Select “OFF”, when you use as a start/a stop of Sub record.
(Refer to Section 8.17 for FUNC key.)
⑦ SD card slot
Used for inserting the SD card.
To remove the SD card from the slot, press SD card to insert.
CAUTION
CAUTION
⑤
⑥
⑦
Please confirm the direction to the insertion of SD card. When forcibly
inserting it in a wrong direction, SD card and the main body are destroyed.
When you pull out the SD card while recording, it becomes impossible to
record data normally and causes past preservation data to destroy. Please
- If the overwrite function is OFF and the SD card is not inserted, there is a possibility that recording may be
10% or less. For internal special relay, refer to Section 7.27.
[Caution]
OPERATION
5.1 Before operating
Please confirm the installation of SD card (Refer to Section 1.5), wiring (Refer to Section 4) before
it operates.
Afterwards, please confirm the various parameter settings (Refer to Section 7).
5.2 Start and stop of record
The record begins when REC button is pushed.
When the record is stopped, the REC button is pushed again, and it Stop key touches on the
confirmation screen.
5.3 Output timing of recorded data to SD card
The timing of output to the SD card depends on the version. The recorded data is erased from the
internal memory at the timing when it is output to the SD card. The output timing is shown below.
Less than Version 2.00
Version 2.00 or later
(1) When recording stop (SD card inserted)
(2) When SD card removal operation
(3) When the number of files created for each file recording cycle exceeds 50
(4) When an SD card is inserted (when there is record data in internal memory)
(1) When recording stop (SD card inserted)
(2) When SD card removal operation(Not possible in extended security mode)
(3) When an SD card is inserted (when there is record data in internal memory)
(4) Per file recording cycle(When the file recording cycle is 1 day, it is output to
the SD card at 0:00:00 every day. Also, the sub record is the same)
* From version 2.00 onwards, record data is output every file recording cycle.
Therefore, if you move recorded data to the PC during recording, please save
the data currently being recorded in the same folder name. If you don’t do this
operation, you can’t read the recorded file when reading the management file.
stopped due to insufficient free space in the internal memory. It is recommended to insert the SD card and
record it
- If SD card capacity display became 10% or less, please perform operation for transferring recorded data.
There is a function(internal special relay) to perform DO output when SD card capacity display became
If the power is turned off during recording, recording will start again the next time the power returns.
The recording operation at power failure shown below.
Example:When power is turned off two times from the start of recording to the end of recording
Display the screen name (“Display Name”) that was set arbitrarily. The group screen can be
changed by touching.
② Clock display
Upper stage:Displays currently date and time.
Lower stage:Displays date and time in cursor area, when Historical trend display.
When the progress time display is set "ON", and displayed a Realtime trend, progress time is
displayed.
(Refer to Section 7.25 for progress time. (It supports since recorder version 1.30.))
③ Change trend
The type of trend display can be changed by touching.
The name corresponding to the trend screen displayed now is displayed.
REAL:Real time trend display
HIST:Historical trend display
④ Graph type
The type of graph display can be changed by touching.
(“Horizontal trend display”⇒ “Vertical trend display”⇒“Bar graph display”⇒“Digital
display”
⑤ Change display
⇒“Event log”⇒“Horizontal trend display”…)
The displaying method of screen can be changed by touching.
(“Display all ON”⇒“⑥Scale display OFF”⇒“⑥Scale display ON”, “⑧Measured value
display area OFF”
ON” …)
⑥ Scale display
Display scale on the “
the channel is changed, when each channel point of “
③Change trend
SD card loading /
writing status display
⇒“⑥Scale plate OFF”, “⑧Measured value display area OFF” ⇒ “Display all
⑦Data display area”. The scale width and display color corresponding to
Allow the Real time trend display, Historical trend display, Bar graph display, Digital display and
Event history / communication history display to be displayed. (Refer to Section 6.2 to 6.6)
Display measured data at the position of the cursor when Historical trend display.
⑧
Measured value display area
Display the currently measured value. When abnormally occurred, it becomes the following
display.
When you display Real time trend or Historical trend, the trend corresponding to the channel is
displayed by touching channel in the heavy line for 3 second, and displays the currently setting
unit on the channel display area.
The display color of “
⑥Scale display” and the scale width are changed to corresponding what.
When keeps touching channel part for 2 second, the figure below is displayed, and the content of
the channel set can be confirmed.
Check settings:The setting status can be verified. And, a set item that becomes an object is
selected touching, and Change set key can be moved directly to the selected set
screen by touching.
Change set key can only be displayed when the “Mode” is “Advanced”. Refer to Section 7.1 for
Comment:Arbitrary comments can be registered on a trend. (It supports since recorder version
1.20.)
(A comment can be set up only on a historical-trend screen. A comment is not
directly displayed on a trend screen. Refer to Section 6.8 for comment function.)
Scale:The scale can temporarily be changed.
※ It will be reset if a power source is turned OFF.
⑨
Event display area
Event information such as beginning to record is displayed.
⑩ Event flag display area
The time when warning has been generated belt is red; the time when the event of the message etc.
has been generated belt is displayed in green.
⑪ SD card loading / writing status display
It indicates the loading state of the SD card.
Gray display:shows the state where the SD card is not loaded in the slot.
When the SD card becomes removable even if the SD card is installed, it
becomes a gray display.
Aqua display:shows the state where the SD card is loaded in the slot. Red display:shows the state where the SD card is written.
⑫ Memory remainder capacity display
When the SD card is installed, the remainder capacity for which the SD card can be used is
displayed by percent.
When the SD card is non-installed, the remainder capacity for which an internal memory can be
used is displayed by percent.
⑬ Main record display
It indicates the state of the main record.
Green display:shows the state where the main record is not started. Red display:shows the state where the main record is started.
⑭ Sub record display
It indicates the state of the sub record.
Green display:shows the state where the sub record is not started. Red display:shows the state where the sub record is started.
⑮ Internal memory
It indicates the state of the internal memory.
Aqua display:shows the state where the internal memory is not access. Red display:shows the state where the internal memory is access.
Measured value
display of each
channel
(Instantaneous
value)
Trend display
Display division
Time scale display
Time
(H : M : S)
(24
Bar graph
Measured value
display of each
channel
(
value)
6.2 Real time trend display of measured data
Explanation]
The measured data can be display in graph. The vertical or horizontal trend directions can be
selected by touching to GRPH key.
The refreshment cycles of graph synchronizes record cycles.
Horizontal trend
Instantaneous
display in TAG No.
or the unit is also
-hour display)
Vertical trend
6.3 Display of measured data in bar graphs
Explanation]
The measured data can be display in bar graph.
Operation]
The measured data can be changed bar graph by touching the GRPH key several times.
The number of a bar graph changes with the CH number chosen by the group channel.
(Refer to Section 7.16 for Group channel.)
The data saved in the past can be read and displayed.
When you select an arbitrary folder from among the “Folder group”, the file data included in the
folder is displayed in the file group.
the historical trend screen, the data preserved in the past is read and displayed.
The SD key when touching, the SD card can be switched to an internal memory.
The Mng. key when touching, the display of administrative file (.dm) and trend file (.dmt) can be
switched.
The Main key when touching, the Main record file can be switched to the display of the Sub
record file.
(Refer to Section 10.17 for administrative file and trend file.)
⑦ Measured value display of each channel
①Cursor date” for measured value is displayed.
“
When you make the item of the record type “Max /Min”, the display becomes 2 steps.
Upper step:The Maximum value
Lower step:The Minimum value
(Refer to Section 7.11 for record type.)
The following items are displayed on the historical trend display based not on the setting of the
past recording but on the currently selected values.
● Trend direction
● Number of screen partition
● Trend scale display
● Color bar display selection
When select an arbitrary file, and touching the OK key, on
When a specific event is generated in the data recording now, it is possible to make a mark.
history of LAN communication is preserved.
Operation]
The event history display can be displayed by touching the GRPH key several times. And, the
screen can be changed communication history display by touching the DISP key several times.
Clear key when touching, the vita information can be cleared. The Update key when touching, it is
updated to the latest vita information.
It is possible to switch to the communication history display with the DISP key.
This section describes how to display the logs for each setting or operation. You can record up to 1,000 user
operations such as modification of setting values or start/stop of recording as timestamped logs. When the
number of log records exceeds 1,000, the oldest log record is overwritten and updated. Note that security
logs cannot be deleted.
When you change a setting value, the parameter file immediately after change is saved under the
file name synchronized with the log number. The security log and parameter log can be output to
the SD card. For details, refer to Section 8.6.
(It supports since recorder version 2.00.)
Operation
Touch the GRPH key on the real-time trend screen multiple times and touch the DISP key on the event
record screen several times. Touch the Update key to refresh the display with the latest record information.
You can check the whole log by using the vertical and horizontal scroll bars.
(1) Log recording date/time
Displays the date/time when the setting or operation is performed.
(2) Operator
Displays the account name used to perform the setting or operation.
(3) Log number
Displays the number for each setting or operation log ([000] to [999]).
The parameter log file corresponding to the log number is generated during setting.
For details about the parameter log file, refer to Section 10.19
(4) Setting and operation logs
Displays the performed setting or operation.
For the list of security logs, refer to Section 10.20.
Arbitrary comments are registered to a trend, and it can jump to the time which registered the
comment from the comment list screen. (It supports since recorder version 1.20.)
※ A comment can be registered only on a historical-trend screen. A comment is not directly
displayed on a trend screen.
Moreover, a comment cannot be registered to the old record data (before a main version 1.13).
Operation]
● A comment is registered.
If it continues touching a channel display 2 seconds or more, a channel operation screen (above
figure left side) will be displayed. Next, a Comment key is touched.
(Refer to Section 6.1 for channel operation screen)
A position to input a comment into is touched in a comment point selection screen (above figure
right side).
The Edit key of a "Comment edit" display (above figure) is chosen. And arbitrary comments are
inputted from a "Character entry screen".
(A comment is inputted into a light-blue position.
changed by touching a screen. Refer to Section 7.4 for "Character entry screen".)
Comment that inputted can register by the OK key.
return to a historical-trend screen.
● A comment list is referred to, and it jumps to a comment point.
If the GRPH key of a historical-trend screen is touched, it will move to a comment list screen.
The comment displayed on the comment list screen is touched and chosen, and cursor is moved to a
comment point by touching a Jump key.
(The selected item is displayed at the light-blue. )
※ "Event summary" of Data Viewer can also refer a comment.
(Refer to Section 3.3 of the “DATA VIEWER INSTRUCTION MANUAL”
(WXPVM70mnAR101E) for Event summary.)
nd, production information is displayed, but the current production
[Caution]
6.9 Production information display
Explanation]
Production information can be displayed in the trend display.
The following production information is displayed on the vertical trend and horizontal trend.
(It supports since recorder version 2.00.)
Operation
- Initial setting
1. Set “Products display” ON in the production information display setting. (For production information
2. Set the FUNC key setting to "Product Regist.". (For the setting of FUNC key, refer to Section 8.18.)
- Production information registration
display, refer to Section 7.26.)
On the trend display screen, press the FUNC key. (For production information registration, refer to
Section 8.18.)
* Registration of production information using the network is also possible. For details, refer to the
communication instruction manual.
(2) Registration data
(1) Title
The title for each information No. of the registered production information is displayed.
(2) Registration data
Registered data will be displayed by the production information registration operation.
Registered data is output in the form of "comment" when recording data is output.
The recorded production information can be confirmed in the event summary of the Data Viewer.
In the historical tre
information is displayed.
Past production information is not displayed. When reading the measurement file, the production
information will be hidden.
The capital letters and small letters can be changed.
③ Numerical value key
The numerical value input can be changed.
④ Symbol key
The symbol input can be changed.
⑤ Del key
The character or numerical value of the currently cursor position can be deleted.
⑥ BS key
The character or numerical value of the currently cursor position ahead a character can be deleted,
and the cursor is moved to the left.
⑦ Space key
The space character can be inputted.
⑧ Arrow key
The arrow key can be moved.
⑨ Character input key
It is a key to input the character.
In case where the character string is filled with blank, delete the blank and then enter characters.
You can’t enter characters without deleting blank.
The “voice sound symbol” and “semi voiced sound symbol” uses one character's worth of an area.
They should advance one character with the “
the character allocated in the same button.
⑩ Clear key
It has input character or numerical value can be all deleted.
⑪ List key
The input character can be selected from character string list or input history.
(It supports since recorder version 1.30 for input history function.)
HIST:The inputted character string is registered automatically, and can be used again.
(The history will be initialized if power is OFF.)
List:The character string registered into "String.txt" can be used.
[Char] in a text file means the number of characters which can be inputted.
[Max] means the number of the character strings which can be registered.
(A part to have exceeded is omitted and displayed.)
("String.txt" can be edited by the text editor of a personal computer.)
The "String.txt" is preserved in the “Etc” folder of the SD card.
Refer to Section 10.17 for “Etc” folder.
⑫ OK key
The input contents can be entered.
⑬ Cancel key
The input contents can be canceled.
①Character entry box], an input position is arbitrarily movable.
Setting the Burn Out function.(The record swings over to the 0% side or the 100% side)
Burn Out function can only be set when the input type is “TC” and “mV”.
④ RJC
The method of making amends for the temperature of the terminal of the thermo-couple range is
selected.
Internal:It makes amends with a built-in temperature sensor.
Assignment CH:It makes amends for measurements of the specified channel as a temperature of
OFF:It doesn't make amends for the temperature of the terminal.
⑤ RJC channel
RJC channel can only be set when the “
of a standard point of contact is specified.
⑥ OK, Cancel key
The each setting for changing contents is saved by the OK key. And, the “Parameter” can be
returned not change by the Cancel key.
⑦ No selected range
The gray color is displayed that cannot be selected now. In this case, can be selected by presses
The warning units relay number of the option is specified, and the warning output destination is
set. The selection item changes by connecting the relay and the transistor.
Common : The main body has been equipped normally.
Relay : When the “Relay card (Option)” is selected, can be set.
Transistor: When the “DI/DO card (Option)” is selected, can be set.
Alarm value
④
This item cannot only be set when the “
The alarm value is set.
The decimal point position of the alarm value can be changed by changing the value of Scaling
key ⇒ Decimal point key. (Refer to Section 7.6 for Decimal point key.)
⑤ OK, Cancel key
The each setting for changing contents is saved by the OK key. And, the “Parameter” can be
returned not change by the Cancel key.
⑥ No selected range
The gray color is displayed that cannot be selected now. In this case, can be selected by presses
“Input filter”, “Record type”, “Offset”, and “Gain” of each channel are set.
Note: When the recorder is in recording, the setting cannot be changed.
Operation]
Select the Input CH key
No selected range
Channel No.
①
The set channel is selected. (The selection range becomes CH13
② Input filter
The time constant of the input filter (the first order filter) is set. (0 to 99 sec)
A time constant expresses the time to reach 63.2% of measured value. If the setting values of an
input filter increase, the speed which measured value changes in proportion to it will become
loose.
③ Record type
The method of operating measurements is specified for the record cycle, and the operation result
is recorded on the SD card.
The record cycle can be set from Record key
(Refer to Section 7.19 for Setting (Main) key. Moreover, please refer a next page for the detail of
each record type.)
Instant value :The instant value every record cycle is recorded.
Average :The average value is calculated and recorded.
Max/Min :The Max/Min value is calculated and recorded.
OFF :It doesn't record on the SD card though the trend is recorded.
※ Record data is not created if the record type of all the channels is "OFF".
④ Offset
The value added (Offset) to the input is set. (-32000 to 32000 digit)
The decimal point position of the “Offset” can be changed by changing the value of Scaling key
⇒ Decimal point key. (Refer to Section 7.6 for Decimal point key.)
⑤ Gain
The ratio of I/O (Gain) is set. (-320.00 to 320.00 %)
(Refer "●The specification of offset and a gain" of page 7-20 for Offset and Gain.)
The each setting for changing contents is saved by the OK key. And, the “Parameter” can be
returned not change by the Cancel key.
⑦ No selected range
The gray color is displayed that cannot be selected now. In this case, can be selected by presses
OK key (or Cancel key) returning to “Parameter”.
●The specification of a record type
The following 3 record types can be chosen in this recorder.
①Max / Min
The maximum and the minimum in a "record cycle" are recorded. For example, if a recording cycle
is 1 second. The measured value of a total of ten pieces can be measured in 1 second. (Because, the
measurement cycle in the interior of this recorder is 100 milliseconds (=msec).)
(Measured value is recorded at the time of 0 millisecond of for 1 second.)
If measured value changes a “lower left table”.
The value of the last in a "record cycle" is recorded.
Compared with the Max / Min record, time recordable on an SD card becomes long. (Because, record data
decrease in number to one piece from two piece.)
In the case of the above-mentioned example, "the instant value" becomes "57.0". (following table).
Recored data
Time
14:00:01
msec
③AverageThe average in a "record cycle" is recorded.
Compared with the Max / Min record, time recordable on an SD card becomes long. (Because, record data
decrease in number to one piece from two piece.)
CH02 INS
0
57.0
In the case of the above-mentioned example, "the average" becomes "57.3". (following table).
●The specification of offset and gain
This recorder can set offset (shift value) and gain (inclination).
The graph when setting offset and a gain is shown.(following)
Ex) Channel type: 0-5mV Scaling range: 0-100%
Offset = 50
Offset = 0
Gain = 200%
Gain = 100%
The operation expression about Offset and Gain is as follows.
P’= A calculation result of offset and gain ※1
P’= A * P + B P = Measured value
A = Gain value (inclination) (-320.00~320.00%)
B = Offset value (-32000~32000It is dependent on the decimal point. ※2)
1 The judgment of input error (such as Burnout, Error, and L/H Over) is performed against the input and for
※
the result of offset or gain calculation.
※2 Refer to Section 7.6 for Decimal point.
● If input type is changed or the scaling function is turned ON/OFF, the offset and gain set value for the
To execute reset of the input value at the set interval time, “T1 timer (sec)”, “T2 timer (min)” of
each channel is set.
Note: When the recorder is in recording, the setting cannot be changed.
Operation]
Select the Calc. CH key
T1 timer (sec)
①
The T1 timer (sec) is set. (1 to 9999)
Please input an arbitrary T1 timer (sec) from the numeric input screen, and set it with the OK
key.
② T2 timer (min)
The T2 timer (min) is set. (1 to 9999)
Please input an arbitrary T2 timer (min) from the numeric input screen, and set it with the OK
key.
The content of the timer can be selected according to the following 6 kinds besides the
above-mentioned.
(A set value is fixation, and not changes. Moreover, a set value is set from the parameter loader.
Refer to Section 2.3 of “PARAMETER LOADER INSTRUCTION MANUAL” for details)
Item Content
T3 Reset is executed at twelve o'clock (midnight) every day.
T4 Reset is executed at twelve o'clock (midnight) of Sunday every week.
T5 Reset is executed at twelve o'clock (midnight) of the first every month.
T6 Reset is executed at every o'clock. (※1)
U1 Reset by DI. (※2)
U2 Reset by DI. (※1) (※2)
※1 (It supports since recorder version 1.30.)
※2 To set it, “U1” or “U2” is selected by Others key ⇒ DI key.
Selectable range with version less than 2.00 Selectable range in version 2.00 or later
Record cycle Selectable file record cycle
1sec to 5sec 1hour
10sec to 1min 1hour,1day
2min to 3min 1hour,1day,1week
5min to 30min 1hour,1day,1week,1month
60min 1hour,1day,1week,1month,1year
Record cycle Selectable file record cycle
1sec to 5sec 1hour,1day
10sec to 20sec 1hour,1day,1week
30sec to 5min 1hour,1day,1week,1month
10min to 60min 1hour,1day,1week,1month,1year
* Measurement values being recorded are saved in the internal memory first regardless of whether
the SD card is inserted or not inserted.
● Timing of data writing
For the timing of outputting recorded data to the SD card, refer to Section 5.3.
③ File overwrite function
Select ON / OFF of the file overwrite function at memory FULL.
The following shows the recording operation when overwriting function ON / OFF.
But, when the extended security mode is set, the overwrite function is always OFF.
Selectable range with version less than 2.00
OFF ON
capacity of the SD card is less than about 20 MB.
mount
unmount
It does not contribute to the remaining capacity in
internal memory.
Recording stops even when the internal memory
Recording stops when the remaining capacity in
internal memory reaches 0%.
Recording will not stop. *2
Delete and overwrite oldest recorded file.
Delete and overwrite oldest recorded file in internal
Selectable range in version 2.00 or later
OFF ON
Recording will not stop. *2
Delete and overwrite oldest recorded file.
Recording currently being recorded is not deleted.
If the SD card becomes full with only data currently being
recorded, recording stops. *3
Delete and overwrite oldest recorded file in internal
mount
unmount
Recording stops when the remaining memory
capacity of the SD card is less than about 20 MB.
It does not contribute to the remaining capacity in
internal memory.
Recording stops even when the internal memory
Recording stops when the remaining capacity in
*1 It is the same as less than version 2.00.
*2 If there are a lot of files in a directory other than "SD ¥ Recorder ¥ Data", a deletion error
will occur and the recording will stop. Only the record data in "SD ¥ Recorder ¥ Data"
can be deleted.
※3 Example when recording stops (when all the following events overlap)
· When there is only one folder in "SD ¥ Recorder ¥ Data"
· When 48 days have elapsed from the start of recording and the remaining capacity of the
The sub recorded timing is set. (A sub record alone cannot be recorded. Please confirm it is
previously recording before it records.)
Func key:The sub record begins when the FUNC button is pushed.
※ System Settings “Device / Other” ⇒ “FUNC key” is “OFF” only when you can choose.
(Refer to Section 8.18 for "FUNC key".)
Alarm :The sub record begins when alarm is occurred.
DI :The sub record begins when the DI input is turned on.
Sync. :The sub record begins, too, when main record is begun.
OFF :It doesn't sub record.
④ DI No.
This item can only be set when the “
③Sub record timing” is “DI”.
DI No. used for the sub record to begin is set.
Please select arbitrary DI No. from the DI No. selection screen.
When “alarm is occurred and cleared” or “DI ON/OFF”, the message is displayed.
Note: When the recorder is in recording, the setting cannot be changed.
Operation]
Select the Others key
Message No.
①
The set message No. is selected.
② Message
The message to display is set. (Up to 16 characters can be registered.)
Please input an arbitrary message from the character input screen, and set it with the OK key.
③ Timing
Timing in which the message is displayed is set.
Func key :The message displays when the FUNC button is pushed.
Alarm occurred :The message displays when alarm is occurred.
Alarm cleared :The message displays when alarm is released.
DI ON :The message displays when the DI input is turned on.
DI OFF :The message displays when the DI input is turned off.
The set message is displayed in the “Event log”. (Refer to Section 6.6 for “Event log”.)
Moreover, when the message is displayed with the FUNC button, it is necessary to set
Device/Other key⇒ FUNC key key of System to “Message”. (Refer to Section 8.18 for
Note: When the recorder is in recording, the setting cannot be changed.
Operation]
Select the Others key
DI No.
①
The set DI No. is selected.
② DI function
The DI function is set.
OFF :The DI function is not used.
Record ON/OFF :The record begins at DI ON, and the record is stopped at DI OFF.
LCD ON/OFF :When DI is ON, Regardless of “Sleep time”, “LCD ON” is always used.
U1/U2 :When there is an operation channel by which "U1" and "U2" are set as the
※ "U1" and "U2" can be set up with the calculating formula of a Parameter Loader.
(Refer to Section 2.3 of “PARAMETER LOADER INSTRUCTION MANUAL” for
※ The DI function can set one item only to one “DI No.”. The function of DI No. set ahead
⇒ DI key on the Parameter.
When DI is OFF, LCD is turned OFF in accordance with setting out of
“sleep time”.
※ Even if it turned OFF DI, LCD is not immediately come by OFF.
(Refer to Section 8.16 for “Sleep time”.)
timer type, and when the input of DI is set to "ON", timer operation is
executed.
calculating formula.)
automatically becomes “OFF”, when you set the same DI function as two or more DI No.
Progress time is counted according to conditions. The counted time can be outputted as a value, if
"PASS function" is used.
(Refer to Section 2.3 of “PARAMETER LOADER INSTRUCTION MANUAL” for "PASS
function".)
Note: When the recorder is in recording, the setting cannot be changed.
Operation]
Select the Others key
Progress time
①
ON/OFF of a progress time display is chosen. If it selects “ON”, it will be displayed on the lower
of the clock display part of a realtime trend screen. (Refer to Section 6.1 for clock display.)
Even if “OFF” is chosen, when conditions are fulfilled, progress time counts.
② Condition
The conditions which start or stop the count of progress time are chosen.
※When a count is stopped and it starts again, a count is started after resetting a value.
Record:A count of progress time is started when record is started, and a count is stopped when
Alarm:A count of progress time is started when alarm occurs, and a count is stopped when
DI :A count of progress time is started when DI is ON, and a count is stopped when DI is OFF.
③ CH No. / DI No.
This item can only be set when the “
CH number or DI number used for “
④ Alarm No.
This item can only be set when the “
Alarm number used for “
⑤ Manual reset
The count of progress time is reset by manual operation.
※ "All" in the selection item of CH number and alarm number means the thing of all the CH
Ex) CH number is "CH01", Alarm number is "All".
⇒ Progress time key on the Parameter.
①
②
③
④
⑤
record is stopped.
alarm recovered.
②Condition” is “Alarm” or “DI”.
②Condition” is set up.
②Condition” is “Alarm”.
②Condition” is set up.
number and alarm number.
A count of progress time is started when an alarm occurs in either of "alarm number 1
of "CH 01". Moreover a count is stopped when an alarm recovered all of "alarm number 1
4" of "CH 01".
The operator sets the output relay.
Common : The main body has been equipped normally.
Relay : When the “Relay card(option)“ is selected, can be set.
Transistors: When the “DI/DO card(option)“ is selected, can be set.
[Note]
③ Exposition
This Paperless recorder display the Exposition that the operator determines function
of “Int. SP DO”.
The function become OR output when the operator determines same the output relay.
・Input CH Group CH Selected CH :CH01~12
Input Input type :±10V (All group)
Scaling Scaling :ON Graph display Horizontal trend :ON
Meas. range(L) :-10.00 Vertical trend :ON
Meas. range(H) :10.00 Bar graph :ON
Scale range(L) :0.00 Digital display :ON
Scale range(H) :100.00 Decimal point :2 Auto display Auto display :OFF
Unit :% Change cycle :5sec
Display TAG :TAGnn (nn=ch) ・Record Description :Blank Setting(Main) Record cycle :1sec
Display color :Purple(CH01) File rec cycle :1hour
:Red(CH02) File overwrite :OFF
:Green(CH03) Setting(Sub) Sub rec cycle :100ms
Scale Range of scale(L):0.00 Sub pre rec :OFF
Range of scale(H):100.00 Sub rec timing :OFF
Scale No. :No.1 Partitions :4 Schedule Schedule :OFF
Start time :00:00:00
Alarm value Act. :OFF End time :00:00:00
OUT :OFF Value :L1 100.00 :L2 100.00 ・Others :L3 0.00 Unit Unit :Blank
:L4 0.00 Message Message :Blank
Alarm action Hysteresis(%) :0.5 Timing :OFF
Alarm delay(sec) :0 DI Function :OFF
Progress time Progress time :OFF
REC/CALC Input filter :0 Condition :Record
Record type :Max/Min (CH01~12) ProductsDisplay Products Display :ON
:OFF(CH13~48) Information No. :No.1~8
Offset :0.00 Title :Model (No.1)
Gain (%) :100.00 :Batch (No.2)
:Serial (No.3)
・Calc. CH :Operator (No.4)
F value Reference temp. :0.0 :Note1 (No.5)
Z value :0.0 :Note2 (No.6)
Start temp. :0.0 :Note3 (No.7)
:Note4 (No.8)
Timer T1 timer(sec) :1 Display :0N (No.1~5)
T2 timer(min) :1 0FF(No.6~8)
Use the SNTP client function to receive the time data from the time server on a regular basis to correct the
recorder's time.
[Operation]
On the system setting screen, select Comm. key
screen.
① Current time and date
Displays the current time and date.
② Selection of SNTP client function
Select ON/OFF of the SNTP client function.
ON: Receives the time data from the SNTP server and calibrates the time. OFF: The SNTP function is not used.
When the correction of the time is attempted using the SNTP function during the recording
process, the correction is not performed if there is a difference of ±5 minutes or more from the
current time. If the difference is 5 minutes or less, the correction is performed by reducing the
difference little by little so that the time approaches the current time.
③ Setting of SNTP server address
Set the SNTP server address.
Input a SNTP server address on the character input screen, and then touch the OK key to set it.
④ Calibration cycle time
Set the time calibration cycle for the SNTP server. (1 to 200 hours)
Input a time calibration cycle on the numerical value input screen and touch the OK key to set it.
⑤ Calibration start
By touching and selecting the key for ⑤" Calibration start ", the time calibration starts
immediately regardless of the setting in ④"Calibration cycle time".
Note) During the recording process, manual calibration cannot be implemented.