RKC Instrument Inc THV-1PZ-030-5*HN, THV-1PZ-030-8*NN User manual

Page 1
Single-phase Thyristor Unit
Instruction Manual
IMR01M01-E16
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of the instrument, carefully read all the instructions in this manual. Please place the manual in a convenient location for easy reference.
WARNING
CAUTION
!
An external protection device must be installed if
failure of this instrument could result in damage to the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned
on to prevent electric shock, fire or damage to the instrument and the equipment.
This instrument must be used in accordance with the
specifications to prevent fire or damage to the instrument and the equipment.
This instrument is not intended for use in locations
subject to flammable or explosive gases.
Do not touch high-voltage connections such as
power supply terminals, etc. to avoid electric shock.
When the withstand voltage test or each test is
performed, please contact RKC sales office or the agent. If you make a mistake in the test method, the instrument failure may result.
RKC is not responsible if this instrument is repaired,
modified or disassembled by other than factory-approved personnel. Malfunction may occur and warranty is void under these conditions.
High temperature caution: Do not touch the heat radiation fin while the power is turned on or just after the power is turned off as it may be at high temperatures. If touched, burning may result.
This product is intended for use with industrial machines,
test and measuring equipment. (It is not designed for use with medical equipment and nuclear energy plant.)
This is a Environment A instrument. In a domestic environment,
this instrument may cause radio interference, in which case the user may be required to take additional measures.
All Rights Reserved, Copyright 2002, RKC INSTRUMENT INC.
Find Quality Products Online at: sales@GlobalTestSupply.com
SYMBOLS
: This mark indicates precautions that must be
taken if there is danger of electric shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions
and operating procedures are not taken, damage to the instrument may result.
: This mark indicates that all precautions should
be taken for safe usage.
: This mark indicates important information on
installation, handling and operating procedures.
: This mark indicates supplemental information
on installation, handling and operating procedures.
: This mark indicates where additional
information may be located.
WARNING
!
CAUTION
www.GlobalTestSupply.com
RKC INSTRUMENT INC.
®
Be sure to provide an appropriate surge control circuit
respectively for the following:
If input/output or signal lines within the building are
longer than 30 meters.
If input/output or signal lines leave the building,
regardless the length.
This product is manufactured on the assumption that it is
mounted within a control panel. All high-voltage connections such as power supply terminals must be enclosed in the control panel to avoid electric shock to operating personnel.
All precautions described in this manual should be taken to
avoid damage to the instrument or equipment.
All wiring must be in accordance with local codes and
regulations.
Always use this product at the rated power supply voltage,
load current and power frequency.
All wiring must be completed before power is turned on to
prevent electric shock, instrument failure, or incorrect action.
To prevent instrument damage or failure, protect the power
line and the input/output lines with a protection device such as fuse, etc.
If this product is used for phase control, higher harmonic
noise may be generated. Therefore in this case, take such measures as separating the power line from the high-voltage line for load drive.
Prevent metal fragments or lead wire scraps from falling
inside instrument case to avoid electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found
in the manual to avoid electric shock, fire or malfunction.
For proper operation of this instrument, provide adequate
ventilation for heat dissipation.
Do not connect wires to unused terminals as this will
interfere with proper operation of the instrument. Turn off the power supply before cleaning the instrument. Do not use a volatile solvent such as paint thinner to clean
the instrument. Deformation or discoloration may occur.
Use a soft, dry cloth to remove stains from the instrument. To avoid damage to the instrument display, do not rub with
an abrasive material or push the front panel with a hard
object.
NOTICE
This manual assumes that the reader has a fundamental
knowledge of the principles of electricity, process control,
computer technology and communications. The figures, diagrams and numeric values used in this
manual are only for explanation purpose. RKC is not responsible for any damage or injury that is
caused as a result of using this instrument, instrument
failure or indirect damage. RKC is not responsible for any damage and/or injury
resulting from the use of instruments made by imitating this
instrument. Periodic maintenance is required for safe and proper
operation of this instrument. Some components have a
limited service life, or characteristics that change over time. Every effort has been made to ensure accuracy of all
information contained herein. RKC makes no warranty,
expressed or implied, with respect to the accuracy of the
information. The information in this manual is subject to
change without prior notice. No portion of this document may be reprinted, modified,
copied, transmitted, digitized, stored, processed or
retrieved through any mechanical, electronic, optical or
other means without prior written approval from RKC.
Page 2
1. CHECKING THE PRODUCT
When unpacking your new instrument, please confirm that the following items are included. If any item is missing, damaged, or if your manual is incomplete, please contact RKC sales office or the agent.
THV-1: 1 unit Accessories (optional) Instruction manual (IMR01M01-E16): 1 copy Setter for open loop control (potentiometer, knob and scale plate) Setting of Heater Break Alarm (IMR01M05-E ) Fuse unit (fast-blow fuse [1 piece] and holder)
[For THV-1 with optional function 1]: 1 copy Output voltmeter (150 V span or 300 V span)
Short bar: 1 piece Connector (plug)
The short bar is connected to the input and power supply terminals.
2. CONFIRMATION OF THE MODEL CODE
Check whether the delivered product is as specified by referring to the following model code list. If the product is not identical to the specifications, please contact RKC sales office or the agent.
THV 1 P Z N ( ) *
(1) Power supply
1: Single-phase 100 to 240 V AC
(2) Control method
PZ: Phase control/Zero-cross control (configurable)
(3) Rated current
020: 20 A 045: 45 A 080: 80 A 030: 30 A 060: 60 A 100: 100 A
(4) Input signal
5: Voltage input: 0 to 10 V DC 6: Voltage input: 1 to 5 V DC 8: Current input: 4 to 20 mA DC
(5) Optional function 1
N: No heater break alarm, current limiter, constant
current control and protection function for control of primary side of a transformer functions
H: Heater break alarm, current limiter, constant
current control and protection function for control of primary side of a transformer functions (The current limiter, constant current control and protection function for control of primary side of a transformer functions are not available when the Zero-cross control.)
Accessories (Order Separately)
THVP-S01 Setter (potentiometer, knob and scale plate) THVP-F60 Fast-blow fuse for 60 A (1 circuit type) THVP-F21 Fuse unit for 20 A (fast-blow fuse [1 piece] and holder [3 circuits type]) THVP-FA0 Fast-blow fuse for 80 A/100 A (1 circuit type) THVP-F31 Fuse unit for 30 A (fast-blow fuse [1 piece] and holder [3 circuits type]) THVP-F2B Fast-blow fuse (UL approved instrument) for 20 A THVP-F22 Fuse unit for 20 A (fast-blow fuse [1 piece] and holder [1 circuit type]) (1 circuit type) THVP-F32 Fuse unit for 30 A (fast-blow fuse [1 piece] and holder [1 circuit type]) THVP-F3B Fast-blow fuse (UL approved instrument) for 30 A THVP-F42 Fuse unit for 45 A (fast-blow fuse [1 piece] and holder [1 circuit type]) (1 circuit type) THVP-F62 Fuse unit for 60 A (fast-blow fuse [1 piece] and holder [1 circuit type]) THVP-F4B Fast-blow fuse (UL approved instrument) for 45 A THVP-FA2 Fuse unit for 80 A/100 A (fast-blow fuse [1 piece] and holder [1 circuit type]) (1 circuit type) THVP-F23 Fuse unit (UL approved instrument) for 20 A THVP-F6B Fast-blow fuse (UL approved instrument) for 60 A
THVP-F33 Fuse unit (UL approved instrument) for 30 A THVP-F8B Fast-blow fuse (UL approved instrument) for 80 A
THVP-F43 Fuse unit (UL approved instrument) for 45 A THVP-FAB Fast-blow fuse (UL approved instrument) for 100 A
THVP-F63 Fuse unit (UL approved instrument) for 60 A THVP-V01 Output voltmeter (150 V span) [For Phase control]
THVP-F83 Fuse unit (UL approved instrument) for 80 A THVP-C01 Connector (plug)
THVP-FA3 Fuse unit (UL approved instrument) for 100 A THVP-H02 Fuse holder for 20 A, 30 A and 45 A (1 circuit type)
THVP-F20 Fast-blow fuse for 20 A (3 circuits type) THVP-H04 Fuse holder (UL approved instrument) for 20 A and 30 A THVP-F2A Fast-blow fuse for 20 A (1 circuit type) (1 circuit type) THVP-F30 Fast-blow fuse for 30 A (3 circuits type) THVP-H05 Fuse holder (UL approved instrument) for 45 A, 60 A, 80 A THVP-F3A Fast-blow fuse for 30 A (1 circuit type) and 100 A (1 circuit type) THVP-F45 Fast-blow fuse for 45 A (1 circuit type)
(1) (2) (3) (4) (5) (6) (7)
(6) Optional function 2
N: No function
(7) Accessories
1: Setter for open loop control (potentiometer, knob and scale plate) [1 set]
and Connector (plug)
2: Setter for open loop control (potentiometer, knob and scale plate) [2 sets]
and Connector (plug)
3: Fuse unit for 20 A and 30 A
(fast-blow fuse [1 piece] and holder [3 circuits type]) 4: Output voltmeter (150 V span) [For Phase control] 5: Output voltmeter (300 V span) [For Phase control] 6: Fuse unit for 20 A, 30 A, 45 A, 60 A, 80 A and 100 A
(fast-blow fuse [1 piece] and holder [1 circuit type]) 7: Fuse unit (UL approved instrument) for 20A, 30A, 45A, 60A, 80A, and 100A
(fast-blow fuse [1 piece] and holder [1 circuit type]) 9: Connector (plug)
Combination example of accessories
-1-3: Setter for open loop control [1 set] and Connector (plug) and Fuse unit
*
The code for accessory will be more than one if the product has
more than one accessory.
To control the primary side of the transformer, it is recommended to purchase a THV-1 with a protection function for control of primary side of a transformer.
Code Details Code Details
(fast-blow fuse [1 piece] and holder [1 circuit type]) (1 circuit type)
(fast-blow fuse [1 piece] and holder [1 circuit type]) (1 circuit type)
(fast-blow fuse [1 piece] and holder [1 circuit type]) (1 circuit type)
(fast-blow fuse [1 piece] and holder [1 circuit type]) THVP-V02 Output voltmeter (300 V span) [For Phase control]
(fast-blow fuse [1 piece] and holder [1 circuit type]) THVP-H01 Fuse holder for 20 A and 30 A (3 circuits type)
(fast-blow fuse [1 piece] and holder [1 circuit type]) THVP-H03 Fuse holder for 60 A, 80 A and 100 A (1 circuit type)
Refer to the 10. Accessories (P. 29) for the actual rated current for Fast-blow fuse to confirm the rating between Thyristor unit and Fast-blow fuse.
2
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
IMR01M01-E16
Page 3
3. PARTS DESCRIPTION
r
The 20 A and 30 A types are used in the following figures for explanation, but the same explanations also apply to 45 A, 60 A, 80 A and 100 A types.
Power lamp
Lights when the power is turned on.
Parameter key
Select the desired parameter group or to
call up the desired parameter.
Switch the Setting data lock function.
( P. 11, P. 12)
Connector (socket)
Connect with a setter (potentiometer), external contact or controller. In addition, used to heate break alarm output. ( P. 9)
Short bar
Switch input types: voltage input, voltage pulse input or current input. ( P. 8)
Display
Display the input signal values and parameters.
Set data lock lamp
Set data lock lamp will be lit when key operation is prohibited. [Set data lock function] ( P. 12, P. 23)
UP keys
Change the values. Switch the Setting data lock function.
( P. 12)
Input and power supply terminals
Connect input signal and power supply wires. ( P. 7)
Main circuit terminals
Connect main circuit wires. ( P. 7)
4. MOUNTING
To prevent electric shock or instrument failure, always turn off the power before mounting or removing the instrument.
4.1 Mounting Environment
Avoid the following conditions when selecting the mounting location:
Ambient temperature of less than 0 °C or more than 40 °C.
(The rated current drops when the ambient temperature exceeds 40 °C.)
The temperature inside the control panel increases due to heat generation of this instrument itself. Therefore, take into account
full ventilation by mounting forced ventilation fans on the panel. Ambient humidity of less than 5 % or more than 95 %RH. Rapid changes in ambient temperature which may cause
condensation. Corrosive or inflammable gases. Direct vibration or shock to the mainframe. Water, oil, chemicals, vapor or steam splashes. Excessive dust, salt or iron particles. Excessive induction noise, static electricity, magnetic fields or
noise. Exposure to direct sunlight. Excessive heat accumulation.
!
WARNING
Load current (%)
100
80
60
40
20
0
10 20 30 40 50 55
Temperature characteristic
(Including the closely mounted)
The temperature characteristic is common to the all types (20 A, 30 A, 45 A, 60 A, 80 A and 100 A).
Temperature ( C)
60
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
3
www.GlobalTestSupply.com
Page 4
c
4.2 Dimensions
20 A and 30 A types
160
172
Mounting dimensions Dimensions
Unit: mm
160 0.2 200
45 A and 60 A types
Dimensions
174
188
48
125
133.5 a 2-M5
a
Dimensions when the connector plug (optional) is connected. When connecting the connector plug, install the thyristor by taking enough space for its wiring into account.
b
Minimum space when mounted closely side by side.
c
Some space for heat radiation is required in the vertical
direction between the lower and upper ends of the instruments. Therefore, make a space of at least 200 mm between them.
50 b
Unit: mm
Mounting dimensions
c
200
174 0.2
68
4
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
150
158.5 a 2-M5
a
Dimensions when the connector plug (optional) is connecte d. When connecting the connector plug, install the thyristor by taking enou gh space for its wiring into account.
b
Minimum space when mounted closely sid e by side.
c
Some space for heat radiat ion is required in the vertical direction between the lowe r and upper ends of the instruments. Therefore, make a space of at least 200 mm between them.
70 b
Page 5
80 A and 100 A types
188
200
Mounting dimensions Dimensions
c
200
188 0.2
Unit: mm
104
116
68
150
158.5 a 4-M5
a
b
Minimum space when mounted closely side by side.
c
Some space for heat radiation is required in the vertical direction
104 0.2
b
120
Dimensions when the connector plug (optional) is connected. When connecting the connector plug, install the thyristor by taking enough space for its wiring into account.
between the lower and upper ends of the instruments. Therefore, make a space of at least 200 mm between them.
4.3 Mounting Procedures
The mounting direction of the instrument must be the same as the direction shown in the figure below to provide adequate ventilation space so that heat does not build up.
CAUTION
This unit generates heat. It is cooled by air convection when installed as shown. Failure to observe the instructions in 4.2 and 4.3 could cause damage to the instrument, equipment or injury to personnel. Precautions should be made for heat dissipation in the control cabinet.
1. Prepare the holes as specified in 4.2 Dimensions.
2. Place the instrument in mounting position.
3. Insert the mounting screws into the holes, then tighten them with a screwdriver.
Recommended tighten torque: 1 N m [10 kgf.cm]
Customer must provide the set of screws.
Screw type: Pan-head screws (Size: M5, Length: 10 mm)
20 A, 30 A, 45 A and 60 A types 80 A and 100 A types
Mounting positions (upper)
Heat radiation direction
Mounting screw
Mounting direction
Mounting screw
Mounting positions (lower)
The Figure shows the type of 20 A and 30 A. However, the mounting procedure is the same as for the type of 45 A and 60 A.
Mounting positions (upper)
Mounting screw
Mounting screw
Mounting positions (lower)
Heat radiation direction
Mounting positions (upper)
Mounting direction
Mounting positions (lower)
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
5
www.GlobalTestSupply.com
Page 6
5. WIRING
To prevent electric shock or instrument failure, do not turn on the power until all wiring is completed. Make sure that the wiring is correct before applying power to the instrument.
5.1 Wiring of Main Circuit
CAUTION
Always conduct wiring so that the phase of the main circuit (2/T1) coincides with that of terminal No. 4 and the
phase of the main circuit (1/L1), with that of terminal No. 5. Otherwise the instrument may not function properly or the load may be damaged.
Caution for connecting a transformer to the load side of the instrument
When a protection function for control of primary side of a transformer is provided:
To conduct control of primary side of a transformer, make sure protection function for control of primary side of a control is set. Appropriately adjust the soft-start time for in case of secondary side breakdown depending on the operating condition.
When a protection function for control of primary side of a transformer is not provided:
If the action of the device is influenced by excessive current (inrush current, current due to flux saturation of transformer), use a transformer 1.25 T (magnetic flux density) or less. Make sure soft-start time is appropriately set.
When connecting a transformer to the load side of this product, make sure that the current value of the primary side of the transformer is equal to or more than the minimum load current of this product. When the current value of the primary side of the transformer is less than the minimum load current value of this product, connect a bleeder resistor in parallel with the primary side of the transformer, and allow the current more than the minimum load current to flow. Minimum load current: 0.6 A (20 A type) 1 A (30 A type or more)
When control is started on this instrument without connecting a load to the transformer, it may result in heat generation or failure of the transformer. Control must be always conducted with the load connected.
Caution for connecting a noise filter to the load side of the instrument
When the control of this instrument is started without connecting a load in a configuration where a noise filter is connected to the load side of the instrument, a large surge may occur to the noise filter and a damage of the instrument may result. Control must be always conducted with the load connected.
THV-1 conforms to CE marking by using the noise filter.
The noise filter specified: SOSHIN ELECTRIC CO., LTD.
Power supply
100 to 240 V AC
Power supply
100 to 240 V AC
Power supply
100 to 240 V AC
20 A/30 A: LF2030A-NH 60 A: HF2060A-UP 100 A: HF2100A-UP 45 A: HF2050A-UP 80 A: HF2080A-UP
Noise filter
LINE LOAD
!
THV-1
THV-1
THV-1
WARNING
2 3 4 5 1
2/T1 1/L1
2 3 4 5 1
2/T1 1/L1
2 3 4 5 1
2/T1 1/L1
Load
Fast-blow fuse
Fast-blow fuse
Fast-blow fuse
Resistance
Transformer
Noise
filter
Load
Load
6
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
IMR01M01-E16
Page 7
There are neither fuses nor power switches in the power circuit of this instrument. Therefore install the fuses and
switches near the instrument, if necessary.
Use wires satisfying the rated current capacity. Firmly tighten each terminal screw with the tightening torque specified below. Otherwise, electric shock, fire or
heat generation may result.
When using a solderless terminal lug, use ring type.
Ring type solderless terminal size and tightening torque
D
Ring type solderless terminal
Item
3.2 mm or more 4.3 mm or more 6.4 mm or more 8.4 mm or more D (mm) 5.5 mm or less 9.5 mm or less 13.2 mm or less 22.6 mm or less Recommended
tightening torque
Power terminals
(4, 5)
0.4 N m (4 kgf cm)
Main circuit terminals (
20 A and 30 A 45 A and 60 A 80 A and 100 A
1.6 N m (16 kgf cm)
3.8 N m (38 kgf cm)
2/T1, 1/L1
)
9.0 N m (90 kgf cm)
Make sure that the any wiring such as solderless terminal is not in contact with the adjoining terminals.
Wiring diagram of main circuit
!
Always conduct wiring so that the phase of the main circuit (2/T1) coincides with that of terminal No. 4 and the phase of the main circuit (1/L1), with that of terminal No. 5. Otherwise the instrument may not function properly or the load may be damaged.
Input and power supply terminals
Main circuit terminal (2/T1)
THV-1
Power supply
100 to 240 V AC
(50/60 Hz)
1 2 3 4 5
N L
Terminal screws size
Main circuit
terminals
(2/T1, 1/L1)
Input and power supply terminals
(1 to 5)
Main circuit terminal (1/L1)
20 A/30 A 45 A/60 A 80 A/100 A
M4 size
size
M6
M3 size
M8
Power supply
100 to 240 V AC
(50/60Hz)
Output voltmeter (optional)
Can use it only in Phase control.
V
Load
Instrument power supply line (To terminal No. 4)
Instrument power supply line (To terminal No.5)
Fast-blow fuse
Table of calorific values
20 A 30 A
100 to
240 V AC
30 W 43 W
Rating current
45 A
60 A
63 W
84 W
80 A
112 W
size
100 A
140 W
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
7
www.GlobalTestSupply.com
Page 8
5.2 Wiring of Input Signal
Current input 4 to 20 mA DC, voltage input 0 to 10 V DC, 1 to 5 V DC and voltage pulse input 0/12 V DC
The input signal type can be changed by moving the short bar position. Any parameter change is not required for input type change.
CAUTION
Firmly tighten each terminal screw with the tightening torque specified below. Otherwise, electric shock, fire or
the generation of heat may result.
When using a solderless terminal lug, use ring type.
Ring type solderless terminal size and tightening torque
Item Input terminals (1, 2 and 3)
Ring type
D
solderless terminal
Current input 4 to 20 mA DC Voltage pulse input 0/12 V DC
For current input (4 to 20 mA DC), short terminal No.1 with terminal No.2.
Current input
4 to 20 mA DC
1 2 3 4 5
Short *
THV-1 input impedance: 100
THV-1 Input and power supply terminals
Temperature controller
4 to 20 mA DC output
3.2 mm or more D (mm) 5.5 mm or less Recommended tightening torque 0.4 N m (4 kgf cm)
Voltage input 0 to 10 V DC, 1 to 5 V DC or
For voltage input (0 to 10 V DC, 1 to 5 V DC) and voltage pulse input (0/12 V DC), short terminal No.2 with terminal No.3.
Voltage input 0 to 10 V DC, 1 to 5 V DC
Voltage pulse input 0/12 V DC
1 2 3 4 5
Short *
THV-1 input impedance 1 to 5 V DC, 0/12 V DC: 30 k 0 to 10 V DC: 68 k
THV-1 Input and power supply terminals
Temperature controller
0 to 10 V DC output 1 to 5 V DC output 0/12 V DC pulse output
* The input signal type can be changed by moving the short bar position. Any parameter change is not required for
input type change. However for a voltage input of 1 to 10 V DC, no input signal can be changed.
Application: Current input 4 to 20 mA DC (Series connection)
Main circuit terminal (1/L1)
Main circuit terminal (2/T1)
Power supply 100 to 240 V AC (50/60 Hz)
Temperature controller 4 to 20 mA DC
+
Input and power supply terminals
1 2 3 4 5
Load
THV-1 THV-1
Input and power
supply terminals
1 2 3 4 5
Load
Fast-blow fuse
THV-1 input impedance: 100
THV-1
Input and power supply terminals
1 2 3 4 5
Load
The number of THV-1 that can be connected depends on the allowable load resistance of temperature controller being used. For resistance of controller, refer to specification of the controller instruction manual.
8
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
IMR01M01-E16
Page 9
Application: Voltage input 0 to 10 V DC, 1 to 5 V DC or Voltage pulse input 0/12 V DC
(Parallel connection)
+
Temperature controller 0 to 10 V DC 1 to 5 V DC 0/12 V DC
THV-1 input impedance 1 to 5 V DC, 0/12 V DC: 30 k 0 to 10 V DC: 68 k
Main circuit
terminal (1/L1)
Main circuit
terminal (2/T1)
Power supply 100 to 240 V AC (50/60 Hz)
THV-1
Input and power
supply terminals
1 2 3 4 5
Load
Fast-blow fuse
THV-1 THV-1
Input and power supply terminals
1 2 3 4 5
Load
Input and power supply terminals
1 2 3 4 5
Load
The number of THV-1 that can be connected depends on the allowable load resistance of temperature controller being used. For resistance of controller, refer to specification of the controller instruction manual.
5.3 Wiring for connector
The connector is used for Contact input, Auto/Manual mode selection, External gradient setting, Heater break alarm 1 output or Heater break alarm 2 output. Use the optional connector (plug) for wiring.
Pin number and details
Pin numbers
CAUTION
Use stranded wire of size 0.14 to 0.5 mm2 for the leadwires. Strip off the sheath from 8 mm from the leadwire end.
THV-1 connector
(Socket)
1
2 3
4 5
6
7 8
Pin number Details
1 +5 V output 2 0 V 3 Gradient setting input (0 to 5 V input by the gradient setter) 4 External manual mode input (0 to 5 V input by the manual setter) 5 Auto/Manual mode transfer (contact open: auto mode)
Shorting No.2 pin (0 V) with No.5 pin results in the Manual mode.
6 Open collector output (+):
Used for output of the Heater break alarm 1 or Heater break alarm 2.
7
Open collector output ( ): Used for output of the Heater break alarm 1 or Heater break alarm 2.
8 Unused
8 mm
Stranded wire: size 0.14 to 0. 5 mm2 (AWG28-20)
Connector (plug
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
)
9
Page 10
Contact input ON/OFF control
t
For contact input, short connector pin No.2 with connecto r pin No.5.
To conduct ON/OFF control, set the value of the Output limiter high and the Output limiter low after wiring the contact input.
Contact closed: Output limiter high Contact open: Output limiter low
For ON/OFF control, short connector pin No.2 with connector pin No.5.
To set or change the output range, set High limit setter first. The set value of Low limit output value conforms to the value of High limit setter. The Low limit output value automatically changes when changing the set value of the High limit setter during the operation with the set value of the Low limit setter.
Low limit output value = Set value o f high limit setter Set value of Low limit setter
Example: Set value of the High l imit setter: 80 % Set value of the Low limit setter: 40 %
80 % 40 % = 32 % Low limit output valu e 32 %
Controller
ON/OFF signal
C: Common NO: Normally open
C
NO
THV-1 connector
+5 V output
Short
1 2
4 5
Pin number
Controller
ON/OFF signal
NO
NC
C
NO: Normally open NC: Normally closed C: Common
Low limit setter High limit setter
3
2
1
3
2
1
THV-1 connector
Short
Auto mode* Manual mode (With gradient setter) Auto/Manual mode selection *
*
For manual setting, short connector pin No.2 with connector pin No.5.
THV-1 connector
3
2
1
Manual setter
THV-1 connector THV-1 connector
1
3
2
Short
1
2
4 5
Pin number
Gradient setter
3
2
1
1 2 3
Pin number Pin numbe r
Manual setter
External contact
External contact closed: Manual mode External contact open: Auto mode
For input signal wiring, refer to Current input 4 to 20 mA DC, voltage input 0 to 10 V DC, 1 to 5 V DC and
voltage pulse input 0/12 V DC (P. 8).
Auto/Manual mode selection (With gradient setter) Heater break alarm output
The gradient setting is valid for both Aut o mode and Manual m ode.
3
Gradient setter
Manual setter
2
1
3
2
1
THV-1 connector
1 2 3 4 5
A diode should be used and connected as show in the diagram, when using a relay.
When the pow er is turned on, the Heater break alarm output may be turned on for up to 0.5 ms. When an interlock circuit or any other related circuit is used, take a necessary measure externally for delaying the activation of the circuit more than 0.5 ms.
THV-1 connector
Relay
Diode
1 2
4 5
Pin number
1 2
4 5
External contac
External contact closed: Manual mode External contact open: Auto mo de
Pin number
6 7
Pin number
For input signal wiring, refer to Current input 4 to 20 mA DC, voltage input 0 to 10 V DC, 1 to 5 V DC and voltage pulse input 0/12 V DC (P. 8).
10
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
IMR01M01-E16
Page 11
6. SETTING
A
This chapter describes the display menus on the LED display.
6.1 Display Flowchart for Monitor and Setting Parameters
The instrument has two Monitor/Setting modes.
Parameter group 1 includes parameters for both monitoring and setting such as Input signal monitor 1, Phase angle
monitor, Phase/Zero-cross control selection, and others.
Parameter group 2 includes parameters for monitoring such as Power frequency monitor, Input signal monitor 2, and
others.
Power ON
fter the maximum load current value is displayed on the display, the display will automatically
change to the Input signal monitor 1. (Display for approx. 1 second)
Input signal
monitor 1
8.8.8.0. M.8.8.0
Output limiter
(high)
H.9.9.9
Maximum load current
set value for alarm 1
P.3.0.0. Q.8.2.0
Heater break alarm 2
used/unused 1
K.8.8.0. Z.3.2.0
Phase angle ratio monitor
Output limiter
.
L.8.0.0. B.8.0.0. O.8.8.2. I.8.0.0. J.8.8.0
Heater break
alarm 1 set value
Current limit value
(low)
setting 1
setting
1, 2
Control method Soft-start time
.
.
.
C.8.8.0
Base-up
set value
Number of alarm
delay times 1
.
R.8.3.0. N.8.8.0. T.8.8.0. F.8.1.5.
Alarm output
state selection 1
c.8.8.0.
break on the secondary side
Soft-down time
U.8.0.1
Output mode
for phase control
Heater break
alarm type 1
Protection function for control of primary side
of a transformer 1
.
Internal manual
D.8.0.1. G.1.0.0.
set value
Alarm output
selection 1
Determination set value in case of a
break on the secondary side
of the transformer 1
t.8.8.0. T.8.8.0.
Soft-start time in case of
of the transformer 1
Output limiter setting in case of a
break on the secondary side
of the transformer 1
Internal gradient
set value
Contact input
action
Heater break alarm 2
set value setting 1
h.2.0.0. u.8.8.0.
1
These parameters are not displayed when the Heater break alarm, Current limiter, Constant current control and Protection function for control of primary side of a transformer functions are not provided.
2
Factory set value varies depending on the instrument specification.
: Available for the Set data lock function
: Press the key.
Parameter group 1
Press and hold the key for 2 seconds.
Parameter group 2
Power frequency
monitor
Input signal
monitor 2
External gradient set value monitor
External manual
set value monitor
Contact input state monitor
CT input
1.8.8.0. 2.8.8.0. 3.8.8.0. 4.8.8.0. 5.8.8.0. 6.8.8.0
*
These parameters are not displayed when the Heater break alarm, Current limiter, Constant current control and Protection
function for control of primary side of a transformer functions are not provided.
Parameters other than Input signal monitor 1, Phase angle ratio monitor and CT input monitor return to Input signal monitor 1 if key operation for more than one minute is not performed.
If any error or alarm occurs, the present display is changed to the error or alarm display.
Error or alarm display
E.8.8.2.
: Press the key.
Error display
.
*
.
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
11
www.GlobalTestSupply.com
Page 12
6.2 Display Sequence
r
f
6.2.1 Selecting parameter group
After power-on to the instrument, the display automatically goes to Input signal monitor 1 in Parameter group 1. To go to Parameter group 2 display, press and hold the Parameter Key for 2 seconds.
Parameter key
Parameter group 1
8.8.8.0.
Press and hold the parameter key for 2 seconds.
Parameter group 2
1.8.8.0.
Press and hold the parameter key for 2 seconds.
6.2.2 Changing parameter settings
Parameter key: Used for parameter calling up and set value registration. UP keys: Used to change the numeric value.
Example: Change control method (parameter group 1) from Phase control to Zero-cross control
Parameter group 1
Input signal monitor 1
Control method
Control method
Control method
8.8.8.0. C.8.8.0. C.8.8.0. C.8.8.1.
Press the parameter key twice to display the contro l method.
Setting range (Control method)
0: Phase control
1: Zero-cross control
Other parameters can be set in the same way as the example above.
Press the UP key unde the first digit from the right to change the value to 1.
Soft-start time Control method
U.8.0.1.
When the value is changed, it will be automatically stored after 3 seconds without any key operation. The value will be also stored if the Parameter key is pressed.
C.8.8.1.
Press the Parameter key to go to the next parameter.
6.2.3 Setting method of Set data lock
Example: To validate the Set data lock function
1. Press and hold the Parameter key for 2 seconds to switch the Parameter group 1 to the Parameter group 2.
Parameter group 1
Input signal monitor 1
8.8.8.0.
2. Press and hold the Parameter key and the UP key at the right edge for 10 seconds to validate the Set data lock function.
2 seconds
Parameter group 2
Power frequency monitor
Parameter group 2
Power frequency monitor
1.8.8.0.
Input signal monitor 2
It is possible to validate the Set data lock function when the parameters o the Parameter group 2 displays.
1.8.8.0.
1 2
Press and hold the Parameter key and the UP key a t the right edge for 10 seconds.
12
Find Quality Products Online at: sales@GlobalTestSupply.com
To invalidate the Set data lock function
Press and hold the Parameter key and the UP key at the right edge for 10 seconds to invalidate the Set data lock function. It is possible to invalidate the Set data lock function when the Parameter group 1 or the Parameter group 2
displays. The UP key is not available when the Set data lock function is valid. It is possible to monitor the set values by using the Parameter key when the Set data lock function is valid.
www.GlobalTestSupply.com
2.8.8.0.
The Set d ata lock lamp lights when the Set data lock function is valid.
Set data l ock lamp l ights
IMR01M01-E16
Page 13
6.2.4 Setting procedure of protection function for control of primary side of a transformer
The following parameters need to be adjusted to suit your system. (If the factory set values satisfy the requirements, they can be used as they are) After having the following parameters properly adjusted, enable the protection function for primary side of a transformer.
Determination set value in case of a break on the secondary side of the transformer (a)
[Factory set value: 70 % of computed heater current value]
Output limiter setting in case of a break on the secondary side of the transformer (h)
[Factory set value: 20.0 % of phase angle]
Soft-start time in case of break on the secondary side of the transformer (u)
[Factory set value: 0.1 seconds]
Setting procedure
Parameter group 1
Input signal monitor 1
8.8.8.0.
Keep pressing the Parameter key until the determination set value in case of a break on the secondary side of the transformer displays.
Soft-start time in case of
break on the secondary
side of the transformer
u.2.0.1.
Set the soft-start time in case of break on the secondary side of the transformer. (Factory set value: 0.1)
Soft-start time in case of
break on the secondary
side of the transformer
u.2.0.1.
Keep pressing the Parameter key until the protection function for control of primary side of a transformer displays.
For details on changing the numeric value, refer to 6.2.2 Changing parameter settings (P. 12).
Determination set value in case of a
break on the secondary side
of the transformer
C.8.7.0. C.8.7.0.
Set the determination set value in case of a break on the secondary side of a transformer. (Factory set value: 70)
Output limiter setting in case of
a break on the secondary side
of the transformer
h.2.0.0.
Press the Parameter key to go to the soft-start time in case of break on the secondary side of the transformer.
Protection function for control
of primary side of a transformer
t.2.0.0.
Set the set value to 1: Protection function for control of primary side of a transformer enable. (Factory set value: 0)
Determination set value in case of a
break on the secondary side
of the transformer
Press the Parameter key to go to the output limiter setting in case of a break on the secondary side of the transformer.
Output limiter setting in case of
a break on the secondary side
of the transformer
h.2.0.0.
Set the output limiter setting in case of a break on the secondary side of the transformer. (Factory set value: 20.0)
Protection function for control
of primary side of a transformer
t.2.0.1.
Press the Parameter key. This completes manual setting of the determination set value in case of a break on the secondary side of the transformer. When the Parameter key is pressed, the protection function for control of primary side of a transformer is enabled.
Setting end
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
13
www.GlobalTestSupply.com
Page 14
6.2.5 Parameter list
Parameter group 1
Parameter
Symbol
No
parameter
M
(M)
C
(C)
(U)
U
(d)
D
G
(G)
H
(H)
(L)
L
(b)
B
O
(o)
I
(I)
Name
Input signal monitor 1
Phase angle ratio monitor
Control method
Soft-start time
Soft-down time
Internal gradient set value
Output limiter high
Output limiter low 4
Base-up set value 4
Output mode for phase control 6
Internal manual set value
1
If a load generating large rush current is used, thyristor break-down may occur when no soft-start time is appropriately set. Also in Zero-cross control, no rush current can be suppressed even if the soft-start time is set.
2
If the protection function for control of primary side of a transformer is enabled, soft-start function is always operated for 0.1
second regardless of setting of soft-start time (U) at 0.0 seconds.
3
Output limiter high value must be equal or higher than Output limiter low.
4
These function can not be used together.
5
Base-up set value will not exceed the Output limiter high.
6
The Output mode setting is invalid when the Control method is Zero-cross control.
7
These parameters cannot be set when the Heater break alarm, Current limiter, Constant current control and Protection function for control of primary side of a transformer functions are not provided. If the rated current of thyristor differs from that maximum load current flowing through the heater when the Constant current control is selected, compensate for the difference by setting the gradient. Set the gradient so that the maximum heater load current will flow through the heater at an input signal of 100 % from the controller. (Refer to P. 19)
1, 2
Display range or
Setting range
0 to 100 % Displays one of the following values
0 to 100 %
When 0 %:
phase angle 0
When 100 %:
phase angle180
0: Phase control 1: Zero-cross control
0.0 to 99.9 seconds 0.1 Set the Soft-start time. P. 17
0.0 to 99.9 seconds 0.1 Set the Soft-down time. P. 17
0.00 to 1.00
0.00: Internal gradient 0 %
1.00: Internal gradient 100 %
0.0 to 99.9 % 99.9 Set the Output limiter high setting. 3
0.0 to 99.9 % 0.0 Set the Output limiter low.
0.0 to 99.9 %
0: Proportional phase
angle to input
1: Proportional voltage to
input
2: Proportional square
voltage (electric power) to input
3: Constant current
control 7
0.0 to 99.9 %
Factory
set value
depending on the Control mode and the setting of Contact input action.
Input signal from controller External manual set value Internal manual set value
For this selection, refer to item
7.1 Selecting Manual Mode Type and Input Signal Monitor 1.
0 Select the Control method. P. 17
1.00 Set the Internal gradient set value. P. 18
0.0
2
0.0
Phase angle
180
Phase angle
135
Phase angle
90
Phase angle
45
The Base-up set value is effective only when the Output limiter low is set to
0.0. Set the Base-up set value (output bias)
of output. 5 The Base-up set value is effective only when the Output limiter low is set to
0.0. Select the output method for Phase
control with linearity (R: resistor) load. The setting is invalid when Zero-cross control is selected.
Set the Internal manual set value.
Details
100 %
75 %
50 %
25 %
Display this value.
3
Reference
page
P. 17
P. 18
P. 18
P. 18
P. 18
14
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
IMR01M01-E16
Page 15
Parameter group 1
1, 2
1, 5
Parameter
Symbol
J
(J)
P
(P)
Q
(q)
(r)
r
(n)
N
T
(T)
(F)
F
K
(K)
Name
Contact input action
Maximum load current set value for alarm 1
Heater break alarm 1 set value setting
Number of alarm delay times 1
Heater break alarm type
Alarm output selection 1
Heater break alarm 2 set value setting
(Heater deterioration)
Heater break alarm 2 used/unused
1
These parameters are not displayed when the Heater break alarm, Current limiter, Constant current control and Protection function for control of primary side of a transformer functions are not provided.
2
When the Control method is Phase control, RKC recommends:
- Set the Heater break set value to approximately 20 % of the Maximum load current value for heater break alarm Type 1.
- Set the Heater break set value to approximately 10 % of the Maximum load current value for heater break alarm Type 2.
When the Control method is Zero-cross control, RKC recommends:
- Set the Heater break alarm set value to approximately 80 % of the reading of current transformer input.
- Set the Heater break alarm set value to a slightly smaller value to prevent a false alarm when power supply variation is
- Set the Heater break alarm set value to a slightly larger value to detect a failure of one heater when more than one heaters
3
The number for the delay times for Heater break alarm 2 is the set value of Number of alarm delay times multiplied by 10.
4
The setting is invalid when Zero-cross control is selected.
5
When the Control method is Phase control and heater break alarm Type 1 is selected, RKC recommends:
- Set the value must be equal or less than the heater break alarm 1 set value.
When the Control method is Phase control and heater break alarm Type 2 is selected:
- For the type 2, this item is not available. Set the 0: Heater break alarm 2 unused.
When the Control method is Zero-cross control, RKC recommends:
- If the alarm needs to be output before a heater break occurs, set the set value of heater break alarm 2 to any value slightly
- If the alarm needs to be output before thyristor break-down occurs, set the set value of heater break alarm 2 to any value
6
When the heater break alarm type is Type 2:
- For type 2, this item is not used. Set the set value of Heater break alarm 2 to 0: Unused.
1, 4
1, 6
large.
are connected in parallel. But the set value should be less than the maximum reading of current transformer input.
larger than that of heater break alarm 1.
slightly smaller than that of heater break alarm 1.
Display range or
Setting range
0: External manual mode
Auto mode
1: Internal manual mode
Auto mode
2: Internal manual mode
(fixed)
0.0 to 32.0 A
0 to 55 A 0 to 70 A 0 to 90 A 0 to 110 A 0 to 100 %
0: Heater break alarm 1
unused
0 to 99 times 3
0: Type 1 1: Type 2
0: Heater break alarm 1 1: Heater break alarm 2
(heater deterioration)
2: Logical OR of heater
break alarm 1 and heater break alarm 2
(heater deterioration) 0 to 100 % 0: Heater break alarm 2
unused 0: Unused 1: Used
(20 A/30 A)
45
(45 A)
60
(60 A)
(80 A)
80
(100 A)
100
Factory
set value
0 Select the contact input action.
This selection also affects the display of the Input signal monitor 1.
Display of the Input signal monitor 1
Contact
input action
0 Input signal
1 Input signal
2 Internal manual set value
(Refer to P. 14)
30.0
Sets the maximum heater current value. The value is used for the Heater break alarm 1 and Heater break alarm 2.
Set the Heater break alarm 1 set value.
20
(Refer to page 18 for Heater break alarm.)
Set the Number of alarm delay times.
30
This setting is common to both Heater break alarm 1 and Heater break alarm 2.
When the Control method is Phase
0
control, select an appropriate Heater break alarm.
Select the alarm type to be output from
0
the digital output terminal of the connector.
Set the Heater break alarm 2 set value.
15
(Refer to page 18 for Heater break alarm).
Set use/unuse of Heater break alarm 2.
0
If set to 0: Unused, no alarm is output.
Details
Contact
from controller
from controller
open
Contact
close
External Manual set value Internal Manual set value
Reference
page
Refer to
7.1 on
page 17.
P. 20
P. 20
P. 20
P. 20
P. 20
P. 20
P. 20
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
15
www.GlobalTestSupply.com
Page 16
Parameter group 1
1, 4
1, 4
1, 4
Parameter
Symbol
Z
(Z)
c
(c)
(t)
t
A
(a)
(h)
h
u
(u)
Name
Current limit value
1, 2, 3
setting
Alarm output state selection
Protection function for control of primary side of a transformer
Determination set value in case of a break on the secondary side of the transformer
Output limiter setting in case of a break on the secondary side of the transformer
Soft-start time in case of break on the secondary side of the transformer
1
These parameters are not displayed when the Heater break alarm, Current limiter, Constant current control and Protection function for control of primary side of a transformer functions are not provided.
2
If a load through which large rush current flows is used, the Current limit function cannot restrict the above current. In this case, use the Current limit function together with the Soft-start function.
3
The Current limiter function is not available when Zero-cross control is selected.
4
The Protection function for control of primary side of a transformer is not available when Zero-cross control is selected.
1, 4
Display range or
Setting range
0.0 to 32.0 A 0 to 55 A 0 to 70 A 0 to 90 A 0 to 110 A 0: ON at alarm output
1: OFF at alarm output
0: Protection function for
control of primary side of a transformer disable
1: Protection function for
control of primary side of a transformer enable
0 to 100 % of computed heater current value
20.0 to 50.0 % of phase angle
0.1 to 99.9 seconds
(20 A/30 A)
(45 A)
55 70
(60 A)
90
(80 A)
110
(100 A)
Factory
set value
32.0 Set the Current limit value.
20.0
If a current limit value is set to its maximum value, the Current limit function is deactivated. (Factory set value: The Current limiter function OFF)
Select whether the open-collector
0
output is turned on or off when the Heater break alarm is output.
Use to enable/disable protection
0
function for control of primary side of a transformer. This setting must be 1: Protection function for control of primary side of a transformer enable when protection function for control of primary side of a transformer is used.
This is a setting to determine if break
70
(momentary power failure) occurred on the secondary side of the transformer.
Use to set output limiter to suppress control output in case of a break (momentary power failure) on the secondary side of the transformer.
Use to set the soft-start time when the
0.1 instrument is recovered from a break (momentary power failure) on the secondary side of a transformer. This soft-start function is only activated when the instrument is recovered from a break on the secondary side of a transformer.
Details
Reference
page
P. 23
P. 24
P. 24
P. 25
P. 25
Parameter group 2
Name
Power frequency monitor
Input signal monitor 2
External gradient set value monitor
External manual set value monitor
Contact input state monitor
CT input monitor 2
1
When 2: Internal manual mode (fixed) is selected for Contact input action, the Auto/Manual mode is always in Manual mode whichever the contact state is.
2
These parameters are not displayed when the Heater break alarm, Current limiter, Constant current control and Protection function for control of primary side of a transformer functions are not provided.
Parameter
Symbol
1
(1)
2
(2)
3
(3)
4
(4)
(5)
5 6
(6)
Display range Details
0 to 99 Hz Display the power frequency. P. 19
0 to 100 % Display the value of input signal from
0 to 100 % Display the External gradient set value.
0 to 100 % Display the External manual set value.
0: Contact closed (Manual mode) 1: Contact open (Auto mode) 1
0.0 to 40.0 A 0 to 90 A 0 to 120 A 0 to 160 A 0 to 200 A
(45 A)
(60 A)
(80 A)
(100 A)
(20 A/30 A)
Display the input value of current
controller.
Display the state of the Contact input.
transformer.
Reference
page
16
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
IMR01M01-E16
Page 17
7. FUNCTIONS
7.1 Selecting Manual Mode Type and Input Signal Monitor 1
Displays one of the following values depending on the Control mode and the setting of Contact input action selection.
Input signal from controller External manual set value (Input signal from external manual setter) Internal manual set value
, input signal from controller is always displayed on Input signal monitor 1 when the Contact input function is not used.
(The displayed item on Input signal monitor 1)
Contact input
action selection
0: External manual mode
Auto mode
1: Internal manual mode
Auto mode
Contact closed (Manual mode)
External manual set value Input signal from controller
Internal manual set value Input signal from controller
2: Internal manual mode
(fixed)
Select Manual mode type
Example: Select Manual mode with Internal manual set value.
1. Go to the parameter Contact input action in Parameter group 1. Set it to 1: Internal manual mode Auto mode.
2. The input signal from controller is displayed when the contact is open. The Internal manual set value is displayed when the contact is closed.
7.2 Control Method
Phase control
Phase control is to continuously control electric power supplied to a load by changing phase angle of AC voltage applied to the load. Each half-cycle has ON and OFF time.
Zero-cross control (Continuous)
Continuous Zero-cross control is to control electric power supplied to a load by turning the power supply voltage ON and OFF at the point of 0 V AC so that the high frequency noise can be suppressed compared with Phase control. This on and off time is typically measured in milliseconds.
Zero-cross control (Input synchronous type)
Input Synchronous type Zero-cross control is to turn the power supply ON and OFF synchronously with the pulse signal from a controller. This on and off time is typically measured in seconds.
7.3 Ramp Function (Soft-Start/Soft-Down Function)
Soft-start/Soft-down function gradually ramps up/down the output voltage to the demand level over the set time to prevent a sudden change in load or voltage. The Soft-start/Soft-down time sets a period of time from 0 to 100 % or 100 to 0 %.
Output voltage
100%
Soft-start time
Soft-down time
State of external contact
Contact open
(Auto mode)
Internal manual set value
Output voltage
Output limiter (high limit)
J.8.8.1.
50 %
OFF OFF ON
Input signal
Soft-start time Soft-down time
100%
80%
Contact input closed (Manual mode)
Contact input action selection
THV-1
0% 0%
Input signal and setting
Time
Input signal
Time
and setting
Soft-start/Soft-down action diagram
Time
Time
If a load generating large rush current is used, thyristor break-down may occur when no Soft-start time is appropriately set.
In Zero-cross control, no rush current can be suppressed even if the Soft-start time is set.
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
17
www.GlobalTestSupply.com
Page 18
7.4 Gradient Setting Function
Gradient setting is a multiplier to be applied to output to the load to adjust the output value depending on an application.
The following two types of gradient setting are available.
Internal gradient setting set by the THV-1 front keys External gradient setting set by the external gradient setter
(external potentiometer) The output value is adjusted by Gradient setting function as follows.
(Output voltage computed by Auto mode) (Internal gradient
setting) (External gradient set value)
(Output voltage computed by Auto mode) (Internal gradient
set value)
(Output by manual set value) (Internal gradient set value)
(External gradient set value)
If it is necessary to make only the External gradient set value valid, set the Internal gradient set value to 1.00.
External gradient scale
100
80
60
40
Output (%)
20
0 25 50 75 100
Input signal (%)
Gradient output characteristics
100
80
60
40
20
0
Internal gradient set value
1.00
0.80
0.60
0.40
0.20
0.00
7.5 Output Limiter High and Low
This function limits the output range. Output limiter function is related to other functions.
Output limiter high and low has priority to the output value
computed with Gradient setting function.
The maximum output from the instrument will not exceed the
Output limiter high and the minimum output will not go below
the Output limiter low.
Output limiter high has priority to the output value
2
computed with Gradient setting and Base-up setting function. The maximum output from the instrument will not exceed the Output limiter high.
When Output limiter low is not set to zero (0), the Base-up
1
100
80
60
40
Output (%)
20
0 25 50 75 100
Input signal (%)
80.0 % Output limiter high
10.0 % Output limiter low
setting function is invalid.
1
Output = (Input signal or Manual set value) (Gradient set value)
2
Output = (Input signal or Manual set value) (Gradient set value) +
(Base-up set value)
7.6 Base-Up Setting Function
Base-up setting function adds positive bias to the output value computed with Gradient setting function. Set the Base-up set value to a value not exceeding the Output limiter high.
Base-up setting is valid only when Output limiter low is set to
zero (0).
Output limiter high has priority to the output value computed
with Gradient setting and Base-up setting function. The maximum output from the instrument will not exceed the Output limiter high.
*
Output = (Input signal or manual set value) (Gradient set value) +
(Base-up set value)
100
80
60
40
Output (%)
20
0 25 50 75 100
Input signal (%)
Base-up setting 20 %
7.7 Output Mode for Phase Control
When Phase control is selected for a linearity (R: Resistance) load, one of the following four output types can be selected. The factory set value is proportional square voltage (electric power) to input. (The output mode setting is invalid when the Control method is Zero-cross control.)
Proportional phase angle to input
100
Proportional voltage to input
100
Proportional square voltage
(electric power) to input
100
Constant current control
100
50
Phase angle ratio (%)
0
4 12 20
Input signal (mA)
50
Effective voltage (%)
0
4 12 20
Input signal (mA)
50
Electric power (%)
0
4 12 20
Input signal (mA)
50
Current (%)
0
4 12 20
Input signal (mA)
Continued on the next page.
18
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
IMR01M01-E16
Page 19
Continued from the previous page.
Constant current control
This is the function used to keep the output current constant in proportion to the input signal. This function is effective when a heater with large resistance changes caused by temperature variations is used (such as tantalum, superkanthal, tungsten, platinum, or molybdenum). The maximum output current when the Constant current control function is used coincides with the rated current in the thyristor specification.
Operating condition Stability
Power supply voltage variation 10 % Load variation 2 times
Caution for using Constant current control function
If the rated current of thyristor differs from that maximum load current flowing through the heater, compensate for the difference by setting the gradient. If there is the difference, a section where control is disabled may come into existence. A compensation example when there is a difference between the currents flowing through the thyristor and the heater is shown in the following.
Example: When used in the following condition
Rated current of Thyristor: 30 A Input signal from controller: 4 to 20 mA DC Maximum load current of heater: 15 A Soft-start time setting: 0.0 seconds
The Soft-start function is activated during four cycles from load operation start even at a Soft-start time of 0.0 seconds.
When used without setting the gradient, the maximum heater load current becomes 15 A at an input signal of 12 mA. In this case, control is disabled if the input signal exceeds 12 mA.
Constant current control
100
2 % of full scale
Maximum load current (15 A) of heater
50
Current (% )
0
4 12 20
Input signal (mA)
Control is disabled within this section.
In this case, set the gradient to 50 % so that the maximum heater load current will become 15 A at an input signal of 20 mA. The gradient is valid even if internally set or set by the external gradient setter.
Constant current control
100
50
Gradient setting
Current (%)
50 %
0
4 12 20
Input signal (mA)
Maximum load current (15 A) of heater
7.8 Automatic Power Frequency Detection and Power Frequency Monitoring Function
Automatic power frequency detection
The instrument automatically detects a power supply frequency (50 Hz or 60 Hz) when the power is turned on. Displays Error number 32 (Power frequency error 2) at the Error display when failed to detect Power supply frequency.
Power frequency monitoring function
This function monitors the power supply frequency and when it goes out of the detection range, the error message display appears. Displays Error number 16 (Power frequency error 1). To confirm power supply frequency, switch to the Power frequency monitor by pressing the Parameter key at the Error display. (Only Power frequency monitor is available.)
Detection range: 50 Hz = 45.0 to 54.9 Hz
Error message will be cleared when power supply frequency returns to the detection range during the operation.
60 Hz = 55.0 to 64.9 Hz
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
19
www.GlobalTestSupply.com
Page 20
7.9 Heater Break Alarm Function
The Heater break alarm monitors the current flowing through the load by a dedicated current transformer (CT). The THV compares the measured value with the set values, and detects a fault in the heating or cooling circuit. In addition, there are several types of Heater break alarms depending on control methods and applications of these Heater break alarms. Read this chapter carefully to choose an suitable method and set an appropriate set value.
7.9.1 Common function for all types
Number of alarm delay times
To prevent producing a false alarm, the alarm function waits to produce an alarm status until the measured current by the CT is in an alarm range for the preset number of consecutive sampling cycles. The parameter of the Number of alarm delay times is to change the number of consecutive sampling cycles by 5-cycle increment.
Heater break alarm 1: (5 cycles) (Number of alarm delay times) Heater break alarm 2: (5 cycles) (Number of alarm delay times) 10
7.9.2 Heater break alarm for Phase control
There are two alarm types (type 1 or type 2) available for Phase control.
(1) Type 1
Type 1 can be used as follows by using two Heater break alarm set values. (Refer to Application)
Heater break alarm 1 set value: The alarm can be output when a heater break occurs by setting the Heater break alarm set value. Heater break alarm 2 set value: This alarm set value can be used as an auxiliary alarm. For example, it can be used as a
The Heater break alarm of Type 1 cannot be used for heat generation substances such as noble metals making
large resistance changes with temperature variations. In addition, it cannot be used for heat generation substances such as silicon carbide making resistance changes with temperature variations and a lapse of time.
Type 1 cannot be used for any power supply waveforms other than a sine waveform.
How alarm is activated
When heater current does not flow (Heater break, malfunction of the control device, etc.)
When the phase angle is equal to or more than 15% and the current transformer input value is equal to or less than the Heater break alarm set value for the preset number of consecutive sampling cycles, an alarm status is produced.
However, in order to prevent malfunctioning, it is so designed that no Heater break alarm occurs at an phase angle of less than 15 % (less than 15 % of maximum load current).
When heater current can not be turned off (Thyristor break-down or permanent damage)
When the current transformer input value is equal to or greater than the Heater break alarm set value for the preset number of consecutive sampling cycles, an alarm status is produced.
The alarm will be turned off when the current transformer input value goes in and stays at non-alarm range for five consecutive cycles.
Application (When Heater break alarm 1 is used for detecting any broken heater or Heater break alarm 2,
for detecting any deteriorated heater.)
Refer to the figure below for action by setting the set values for the following parameters:
Maximum load current set value for alarm (P)*: 20 A Heater break alarm 2 set value setting (F): 15 % Heater break alarm 1 set value setting (q): 20 % Heater break alarm 2 used/unused (K): 1: Used Number of alarm delay times (r): 0 times Alarm output state selection (c): 0: ON at alarm output Heater break alarm type (n): 0: Type 1 Alarm output selection (T): 2: Logical OR of heater break alarm 1 and Heater break alarm 2
* Always set the maximum heater current value.
For details of Heater break alarm, refer to the separate Setting Method of Heater Break Alarm (IMR01M05-E ).
Heater break alarm 1 set value
= (Maximum load current set value) (Heater break alarm 1 set value) = 20 A 20 % = 4 A Heater break alarm 1 set value 4 A
Heater break alarm 2 set value
= (Maximum load current set value) (Heater break alarm 2 set value) = 20 A 15 % = 3 A Heater break alarm 2 set value 3 A
The 4 and 3 amperes are set (deviation setting) to the high and low sides of the computed heater current value.
Maximum load current (20 A)
Heater deterioration alarm if set to any value slightly smaller than the Heater break alarm set value to output the alarm before a heater break occurs when the load current decreases due to heater deterioration, etc.
Current (A)
Thyristor break­down side
Alarm range
of heater
break alarm
Operation point of Heater break alarm 1 (upper) Alarm range of Heater deterioration alarm Operation point of Heater break alarm 2 (upper) Computed heater current value
Operation point of Heater break alarm 2 (lower)
Alarm range of Heater deterioration alarm
Operation point of Heater break alarm 1 (lower)
Delays by the same number of cycles as that when the Number of alarm delay times is set at 1 even with the Number of alarm delay times set at 0.
Heater break alarm 1 set value (upper): 20 % (4 A)
Heater break alarm 2 set value (upper): 15 % (3 A)
14.9 % No heater break alarm occurs if within this ran ge. However, the alarm occurs in the case of thyristor break-down.
Alarm range
of heater
break alarm
20
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Heater break alarm 2 set value (lower): 15 % (3 A)
Heater break alarm 1 set value (lower): 20 % (4 A)
Heater break side
100 % 0
Phase angle (%)
IMR01M01-E16
Page 21
How alarm is checked
f
A
If the alarm occurs, the relevant error number is shown on the display unit. Therefore in this case, check the alarm contents.
Error number Description
E.1.2.8.
Error display
128 Heater break alarm 1 256 Thyristor break-down 512 Heater break alarm 2 (heater deterioration)
For the Error display, refer to the 8. ERROR OR ALARM DISPLAY (P. 26).
(2) Type 2
Type 2 corresponds to a Heater break alarm when one heater is used. (Refer to Application) The Heater break alarm of Type 2 is used for heat generation substances such as noble metals making large resistance change with temperature variations.
No type 2 can be used when two or more heaters are used in parallel connection.
How alarm is activated
When heater current does not flow (Heater break, malfunction of the control device, etc.)
When the phase angle is equal to or more than 15 % and the current transformer input value is equal to or less than the Heater break alarm set value for the preset number of consecutive sampling cycles, an alarm status is produced.
However, in order to prevent malfunctioning, it is so designed that no Heater break alarm occurs at an phase angle of less than 15 % (less than 15 % of maximum load current).
When heater current can not be turned off (Thyristor break-down or permanent damage)
When the phase angle is 0 % and the current transformer input value is equal to or greater than the Heater break alarm set value for the preset number of consecutive sampling cycles, an alarm status is produced.
The alarm will be turned off when the current transformer input value goes in and stays at non-alarm range for five consecutive cycles.
Application
Refer to the figure below for action by setting the set values for the following parameters:
Maximum load current set value for alarm (P) Heater break alarm 1 set value setting (q): 10 % Heater break alarm 2 set value setting (F) Number of alarm delay times (r): 0 times Heater break alarm 2 used/unused (K) Heater break alarm type (n): 1: Type 2 Alarm output state selection (c): 0: ON at alarm output
1
Always set the maximum heater current value.
2
Always set the Heater break alarm 2 to 0: Heater break alarm 2 unused.
3
Always set the Heater break alarm 2 used/unused to 0: Unused.
For details of heater break alarm, refer to the separate Setting Method of Heater Break Alarm (IMR01M05-E ).
Heater break alarm 1 set value
= (Maximum load current set value) (Heater break alarm 1 set value) = 20 A 10 % = 2 A Heater break alarm 1 set value 2 A
Set the Heater break alarm 1 set value to approximately 10 % of the maximum load current value. Do not set the Heater break alarm set value to more than 15 %.
(When the maximum load current value is set to 20 A)
Alarm range of Heater break alarm
(Thyristor break-down)
When the phase angle is 0 % and the current transformer input value is equal to or greater than the Heater break alarm set value for the preset number o consecutive sampling cycles, an alarm status is produced.
Heater break alarm 1 set value 10 % (2 A)
1
: 20 A Alarm output selection (T): 0: Heater break alarm 1
Current (A)
14.9 %
No Heater break alarm occurs if within this range. However, the alarm occurs in the case of thyristor break-down.
100 % 0
Phase angle (%)
2
: 0: Heater break alarm 2 unused
3
: 0: Unused
larm range of Heater break alarm
When the phase angle is equal to or more than 15% and the current transformer input value is equal to or less than the Heater break alarm set value for the preset number of consecutive sampling cycles, an alarm status is produced.
How alarm is checked
If the alarm occurs, the relevant error number is shown on the display unit. Therefore in this case, check the alarm contents.
Error number Description
E.1.2.8.
Error display
For the Error display, refer to the 8. ERROR OR ALAMR DISPLAY (P. 26).
128 Heater break alarm 1 256 Thyristor break-down
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
21
www.GlobalTestSupply.com
Page 22
7.9.3 Zero-cross control
The following usage is available in Zero-cross control. (Refer to Application)
Heater break alarm 1 set value: The alarm can be output when a heater break occurs by setting the Heater break alarm set value. Heater break alarm 2 set value: This alarm set value can be used as an auxiliary alarm.
How alarm is activated
When heater current does not flow (Heater break, malfunction of the control device, etc.)
When the control output is ON and the current transformer input value is equal to or less than the Heater break alarm set value for the preset number of consecutive sampling cycles, an alarm status is produced.
When heater current can not be turned off (Thyristor break-down or permanent damage)
When the control output is OFF and the current transformer input value is equal to or greater than the Heater break alarm set value for the preset number of consecutive sampling cycles, an alarm status is produced.
The alarm will be turned off when the current transformer input value goes in and stays at non-alarm range for five consecutive cycles.
Application (When Heater break alarm 1 is used for detecting any broken heater or Heater break alarm 2,
for detecting any deteriorated heater.)
Refer to the figure below for action by setting the set values for the following parameters:
Maximum load current set value for alarm (P)*: 20 A Heater break alarm 2 set value setting (F): 85 % Heater break alarm 1 set value setting (q): 80 % Heater break alarm 2 used/unused (K): 1: Used Number of alarm delay times (r): 0 times Alarm output state selection (c): 0: ON at alarm output Alarm output selection (T): 2: Logical OR of Heater break alarm 1 and Heater break alarm 2
*
Always set the maximum heater current value.
For details of Heater break alarm, refer to the separate Setting Method of Heater Break Alarm (IMR01M05-E ).
Heater break alarm 1 set value
= (Maximum load current set value) (Heater break alarm 1 set value) = 20 A 80 % = 16 A Heater break alarm 1 set value 16 A
Heater break alarm 2 set value
= (Maximum load current set value) (Heater break alarm 2 set value) = 20 A 85 % = 17 A Heater break alarm 2 set value 17 A
Heater break alarm 2 set value 85 % (17.0 A) [heater deterioration]
Heater break alarm 1 set value 80 % (16.0 A) [heater break]
Heater break alarm 2 set value 85 % (17.0 A) [heater deterioration]
Heater break alarm 1 set value 80 % (16.0 A) [heater break]
For example, it can be used as a Heater deterioration alarm if set to any value slightly larger than the Heater break alarm set value to output the alarm before a Heater break alarm occurs when the load current decreases due to heater deterioration, etc.
20.0 A
18.5 A
16.5 A 16.5 A 16.5 A 16.5 A 16.5 A 16.5 A
Current transformer input value
(Heater current data are updated)
Alarm output
Heater deterioration
Current transformer input value
(Heater current data are updated)
Alarm output
Capture
20.0 A
18.5 A
Capture
Heater break
For the preset number of consecutive sampling cycles
ON OFF
15.5 A 15.5 A 15.5 A 15.5 A 15.5 A 15.5 A
For the preset number of consecutive sampling cycles
ON OFF
20.0 A 20.0 A 20.0 A 20.0 A 20.0 A 20.0 A
Heater break alarm 1 set value 80 % (16.0 A) [heater break]
Current transformer input value
(Heater current data are updated)
Alarm output
Thyristor break-down
0 A 0 A
Capture
Capture
For the preset number of consecutive sampling cycles
ON OFF
This chart shows the case when Control output is 50 %.
How alarm is checked
If the alarm occurs, the relevant error number is shown on the display unit. Therefore in this case, check the alarm contents.
Error number Description
E.1.2.8.
Error display
22
Find Quality Products Online at: sales@GlobalTestSupply.com
For the Error display, refer to the 8. ERROR OR ALARM DISPLAY (P. 26).
www.GlobalTestSupply.com
128 Heater break alarm 1 256 Thyristor break-down 512 Heater break alarm 2 (heater deterioration)
IMR01M01-E16
Page 23
7.10 Current Limiter Function
This is the function of limiting a measured current value to a value not exceeding the preset current limit value. A current value is measured for each constant cycle and then the maximum phase angle not exceeding the Current limit value is computed from the above current value thus measured. If the phase angle at that current output is larger than the maximum phase angle computed, the current is output at the maximum phase angle to restrict that current. The maximum phase angle is computed during a time period of 0.1 seconds from the start of load operation, and the Current limit function is activated after the maximum phase angle is computed.
If a load through which large rush current flows is used, the Current limit function cannot restrict the above current. In this case, use the Current limit function together with the Soft-start function.
Even at a Soft-start time of 0.0 seconds, the Soft-start function is activated in order to compute the maximum phase angle during a time period of 0.1 seconds from the start of load operation.
If a current value exceeds Current limit value + Differential gap (0.5 A or 1 A) * due to voltage variations or load resistance changes while the Current limit function is being activated, the maximum phase angle is immediately re-computed to restrict it within a cycle of 2.5 from the time when it exceeds Current limit value + Differential gap.
* Differential gap 0.5 A: 20 A, 30 A types
Differential gap 1 A: 45 A, 60 A, 80 A and 100 A types
If a Current limit value is set to its maximum value, the Current limit function is deactivated.
The Current limiter function cannot be used when Zero-cross control is selected.
7.11 Set Data Lock Function
It is possible to prohibit the key operation to prevent an operation error. Validate Set data lock function to lock the UP key. The following parameters are available for Set data lock function.
Control method (C) Heater break alarm type (n) Soft-start time (U) Alarm output selection (T) Soft-down time (d) Heater break alarm 2 set value setting (F) Internal gradient set value (G) Heater break alarm 2 used/unused (K) Output limiter high (H) Current limit value setting (Z) Output limiter low (L) Alarm output state selection (c) Base-up set value (b) Protection function for control of primary side of a transformer (t) Output mode for phase control (o) Determination set value in case of a break on the secondary side of Internal manual set value (I) the transformer ( ) Contact input action (J) Output limiter setting in case of a break on the secondary side of Maximum load current set value for alarm (P) the transformer (h) Heater break alarm 1 set value setting (Q) Soft-start time in case of break on the secondary side of Number of alarm delay times (r) the transformer (u)
For the setting method, refer to 6.2.3 Setting method of Set data lock (P. 12).
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
23
www.GlobalTestSupply.com
Page 24
7.12 Protection Function for Control of Primary Side of a Transformer
If momentary power failure occurs during execution of the control of primary side of a transformer, inrush current is generated. Protection function for control of primary side of a transformer is to protect the thyristor from the inrush current. With this protection function enabled, when momentary power failure occurs, the instrument determines that the secondary side of a transformer was disconnected and suppresses the output. When the instrument is automatically reset from the breakdown (momentary power failure), the soft-start function suppresses the inrush current. To use this protection, the following parameters need to be set.
Protection function for control of primary side of a transformer (t)
Determination set value in case of a break on the secondary side of the transformer (a)
Output limiter setting in case of a break on the secondary side of the transformer (h)
Soft-start time in case of break on the secondary side of the transformer (u)
While control of primary side of a transformer is executed, if the current transformer (CT) value goes below the determination set value in case of a break on the secondary side of the transformer, it is judged to be a break (momentary power failure). Below is a formula to convert the determination set value in case of a break on the secondary side of the transformer (a) into the current value (A).
While the phase angle is 20 % or more, when the current goes over the determination set value in case of a break on the secondary side of the transformer by 0.3 A (instrument of 45 A or more: 1 A), it is judged to be a release from a break (momentary power failure).
24
Find Quality Products Online at: sales@GlobalTestSupply.com
For the setting range of parameter, refer to page 16.
For the setting procedure, refer to page 13.
Operation chart
Current (A)
Determination set value in case of a break on the secondary side of the transformer
Operating point of output limiter in case of break on the secondary side of a transformer
When the input value of the current transformer (CT) goes below this point, it is judged to be broken and protection is executed. During the break state, the displayed value flashes.
Effective output voltage (%)
Insensible range of protection function for
control of primary side of a transformer
0
22.1 %
(Phase angle 20.0 %)
Output limiter setting range when secondary side of transformer is disconnected.
When momentary power failure occurs, if the output from the instrument is smaller than the output limiter set value in case of a break on the secondary side of the transformer, control continues with the same level of output kept.
Computed heater current value
Output limiter ON range when the secondary side of the transformer is broken.
70.7 %
(Phase angle 50.0 %)
100.0 %
Determination of break and release of secondary side of transformer
Determination of break
Current value [A] = Maximum load current set value [A] Effective output voltage [%] (100 % Determination set value in
case of a break on the secondary side of the transformer [%])
Determination of release
IMR01M01-E16
www.GlobalTestSupply.com
Page 25
Display in case of break of secondary side of a transformer
When the signal level goes below the determination set value in case of a break on the secondary side of the transformer, the displayed value flashes. (Parameters of input signal monitor 1 and phase angle ratio monitor flash) When the instrument is automatically released from the break (momentary power failure), the display stops flashing and remains lit.
Input signal monitor 1 Phase angle ratio monitor
Flashing Flashing
8.8.8.0. M.8.8.0.
Output limiter setting in case of a break on the secondary side of the transformer
This is a function to limit the phase angle between 20.0 % and 50.0 % when the signal goes below the determination set value in case of a break on the secondary side of the transformer.
Phase angle (%)
100.0
50.0
20.0
0
Output limiter set value in case of a break on the secondary side of the transformer
Output limiter range
Input signal (%)
100
Soft-start function in case of break on the secondary side of the transformer
This is a soft-start function which is activated when the instrument is automatically released from the break (momentary power failure) of the secondary side of the transformer. This function suppresses the inrush current at the time of automatic release from the break (momentary power failure).
While the soft-start function of the soft-start time (U) is working, if break (momentary power failure) of secondary side of a transformer occurs, protection function for control of primary side of a transformer starts working to suppress the output. When released from the break (momentary power failure), the instrument changes the output according to the soft-start time in case of break on the secondary side of the transformer (u). After elapse of the soft-start time in case of break on the secondary side of the transformer (u), the soft-start time (U) takes over, and output is changed in the remaining time of the soft-start time (U).
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
25
www.GlobalTestSupply.com
Page 26
8. ERROR OR ALARM DISPLAYS
When the error or alarm occurs, the display changes to the Error display. When two or more errors occur simultaneously, the error code numbers are totaled and displayed as one number.
When the power frequency error is displayed, the display can be changed only to the power supply frequency monitor.
When any of the errors show below occurs, other displays will not be displayed.
Error display
Error number Description Action Solution
1
2
4
8
16
32
64
* For details of the error, refer to 7.8 Automatic Power Frequency Detection and Power Frequency Monitoring
Function (P. 19).
Alarm display
Error number Description Action Solution
128
256
512
Error display
E.1.2.2.
Board error EEPROM error Data error 1 Calibration data error Data error 2
(1)
(2)
(4)
(8)
(16)
(32)
(64)
(128)
(256)
(512)
Board error Thyristor output OFF Turn off the power at once. If an error occurs after the
Data error 1
Data error 2
EEPROM error
Power frequency error 1 *
Power frequency error 2 *
Calibration data error
Heater break alarm 1
Thyristor break-down
Heater break alarm 2
(heater deterioration)
Display the error number.
Thyristor output OFF
The output can be turned ON when the error is canceled.
Thyristor output OFF Check the value of power supply frequency, and turn off
Thyristor output OFF Turn off the power at once. If an error occurs after the
Control is continued. Turn off the power, and check or replace the heater, etc.
If a load generating large rush current is used, thyristor
Turn off the power, and check or replace the heater, etc.
power is turned on again, please contact RKC sales office or the agent.
Check the stability of power supply frequency, and turn off the power at once. If an error occurs after the power is turned on again, please contact RKC sales office or the agent.
the power at once. If an error occurs after the power is turned on again, please contact RKC sales office or the agent.
power is turned on again, please contact RKC sales office or the agent.
break-down may occur when no Soft-start time is appropriately set. In such a case, make the Soft-start time longer. For any causes other than the above, turn the power off and then contact to your nearest RKC sales agent or our sales office.
26
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
IMR01M01-E16
Page 27
9. SPECIFICATIONS
Number of phase: Single-phase Rated current: 20 A AC, 30 A AC, 45 A AC, 60 A AC, 80 A AC and 100 A AC
Minimum load current: 0.6 A (20 A type), 1 A (30 A, 45 A, 60 A, 80 A and 100 A types) Power supply voltage: 90 to 264 V AC [Including power supply voltage variation] (Rating: 100 to 240 V AC) Power frequency: 50/60 Hz (Automatic discriminating) Allowable power frequency variations:
Input signal: Current input 4 to 20 mA DC (Input impedance: 100 )
Output voltage range: 0 to 98 % of rating voltage Applicable load: Phase control: Linearity (R: resistor) load
Corresponding utilization category:
Overload current profile and duty cycle or OFF-time:
Comprising the rating index:
Control method: Phase control (No feedback) Zero-cross control (No feedback) Output setting range: Internal manual set value: 0.0 to 99.9 % (Set by theTHV-1 front keys)
Output mode: Proportional phase angle to input
Power off leakage current:
Ramp (Soft-start/Soft-down) function:
Auto/Manual mode selection:
Heater break alarm function (optional):
Protection function for control of primary side of a transformer:
For the ambient temperature characteristic, refer to temperature characteristic graph. (P. 3)
1 Hz (Performance guarantee) 2 Hz (Operation guarantee)
Voltage input 0 to 10 V DC (Input impedance: 68 k ) Voltage input 1 to 5 V DC (Input impedance: 30 k ) Voltage pulse input 0/12 V DC (Input impedance: 30 k ) Dry contact input (Input impedance: 47 k )
Control of primary side of a transformer
The magnetic flux density must be 1.25 T [12,500 Gauss] or less when the protection function for control of primary side of a transformer is not provided.
Zero-cross control: Linearity (R: resistor) load
AC-51
1.1 x Ie  60 s
50 - 60
External manual set value: 0 to 100 % (Set by the setter 1) External gradient set value: 0 to 100 % (Set by the setter 1) Internal gradient set value: 0 to 100 % (0.00 to 1.00) (Set by the THV-1 front keys) Output limiter high set value: 0.0 to 99.9 % (Set by the THV-1 front keys) Output limiter low set value: 0.0 to 99.9 % (Set by the THV-1 front keys) Base-up set value: 0.0 to 99.9 % (Set by the THV-1 front keys)
2
Proportional voltage to input Proportional square voltage (electric power) to input Constant current control (optional)
2
When the Phase control use the linearity (R: resistor) load
2
2
2
1
Optional
27 mA AC rms or less (load voltage 200 V rms, 60 Hz, Ta=25 C)
Setting range: 0.0 to 99.9 seconds (Set by the THV-1 front keys)
External dry contact External contact closed: Manual mode External contact open: Auto mode
When the power source ripples of main circuit is sine-wave Input: Current transformer (built-in) Measured accuracy: Within 2 A (20 A and 30 A types) Within 10 % of maximum load current (45 A, 60 A, 80 A and 100 A types) Output: 1 point, open collector output 24 V DC, Max. 100 mA Output ON/OFF at alarm is selectable.
Applicable control method: Phase control Setting range: Protection function for control of primary side of a transformer: 0 (disable)/1 (enable) Determination set value in case of a break on the secondary side of the transformer: 0 to 100 % of computed heater current value (Deviation setting against the computed heater current value.) Output limiter setting in case of a break on the secondary side of the transformer:
20.0 to 50.0 % of phase angle Soft-start time in case of break on the secondary side of the transformer:
0.1 to 99.9 seconds Abnormity judgment conditions: Phase angle 20 % or more Sampling cycle: 0.5 of power cycle Action at the time of automatic release from the break (momentary power failure) of secondary side of the transformer: Output by soft-start function at the time of the break (momentary power failure) of secondary side of transformer.
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
27
www.GlobalTestSupply.com
Page 28
Current limiter function (optional):
Ambient temperature: 0 to 40 C (Performance guarantee range)
Ambient humidity: 5 to 95 %RH (Non-condensing) Power consumption: 6 VA max. Withstand voltage: Between main circuit, power terminals and radiation fins: 1 minute at 2000 V AC Insulation resistance: Between main circuit, power terminals and radiation fins: 20 M or more at 500 V DC Rated conditional short-circuit current:
Cooling method: Natural convection Mounting method: Vertical mounting Dimensions: Refer to 4.2 Dimensions (P. 4). Weight: Approx. 0.9 kg (20 A and 30 A types)
Standard: Safety standards: UL: UL508 (file No. E177758)
EMC test standards: Emissions
28
Find Quality Products Online at: sales@GlobalTestSupply.com
Setting range 20 A, 30 A: 0.0 to 32.0 A
45 A: 0 to 55 A 60 A: 0 to 70 A 80 A: 0 to 90 A 100 A: 0 to 110 A If a current limit value is set to its maximum value, the current limit function is deactivated.
15 to +55 C (Operation guarantee range)
1500 A
20 A fast-blow fuse for 1 circuit type: Breaking capacity 100 kA 20 A fast-blow fuse for 3 circuits type: Breaking capacity 100 kA 30 A fast-blow fuse for 1 circuit type: Breaking capacity 100 kA 30 A fast-blow fuse for 3 circuits type: Breaking capacity 100 kA 45 A fast-blow fuse for 1 circuit type: Breaking capacity 100 kA 60 A fast-blow fuse for 1 circuit type: Breaking capacity 100 kA 80 A fast-blow fuse for 1 circuit type: Breaking capacity 100 kA 100 A fast-blow fuse for 1 circuit type: Breaking capacity 100 kA
Approx. 1.4 kg (45 A and 60 A types) Approx. 1.9 kg (80 A and 100 A types)
cUL: C22.2 No.14 (file No. E177758) CE marking: THV-1 conforms to CE marking by using the noise filter. (Refer to P. 6) LVD: EN 60947-4-3 (Form 4) EMC: EN 60947-4-3 (Form 4)
The EMC emissions test standards required by the standard EN 60947-4-3 Contactors and motor-starters
- AC semiconductor motor controllers and contactors for non-motor loads are presented in table 1.
Table 1: EMC emissions standards compliance
Emission type Test standard
Conducted disturbance CISPR 11 Environment A Group 2
Radiated EM field CISPR 11 Environment A
Immunity The EMC immunity test standards required by the standard EN 60947-4-3 Contactors and motor-starters - AC semiconductor motor controllers and contactors for non-motor loads are presented in table 2.
Table 2: EMC immunity standards compliance
Test type Test standard Test level
Electrostatic discharge EN 61000-4-2 Contact: 4 kV
Radiated, radio frequency electromagnetic field
Electrical fast transient/burst EN 61000-4-4 AC Power port: 2 kV
Surge EN 61000-4-5 AC Power port:
Conducted disturbances induced by radio frequency fields
Voltage dips EN 61000-4-11 AC Power port:
Voltage interruptions EN 61000-4-11 AC Power port:
EN 61000-4-3 Enclosure port:
EN 61000-4-6 AC Power port
Air: 8 kV
80 - 1000 MHz: 10 V/m
1.4 GHz - 2 GHz: 3 V/m 2 GHz - 2.7 GHz: 1 V/m
Signal port: 1 kV
1 kV (line to line)
Signal port:
0.15 - 80 MHz: 10 V
0 % during 0.5 cycle * 0 % during 1 cycle * 40 % during 10/12 cycles * 70 % during 25/30 cycles * 80 % during 250/300 cycles *
* Rated operational voltage
0 % during 250/300 cycles (Rated operational voltage)
IMR01M01-E16
www.GlobalTestSupply.com
Page 29
10. ACCESSORIES (OPTIONAL)
Setter (Potentiometer, Knob and Scale plate)
Unit: mm
10
6
2.8
18.7
16.1
Knob
2 M9 0.75
24
13.5
10 10
(Resistance 5 k , variation characteristic: B)
Potentiometer
Output voltmeter (150 V span or 300 V span)
80
67
V
14 29.5
10
2-M3
16
52
Fuse unit (Holder: 3 circuits type)
For 20 A and 30 A
6-M6
74
63
75
62
86
41
4
8
5
12
Fuse unit (Holder: 1 circuit type)
For 20 A, 30 A and 45 A
2-M6
4
8
5
50
40
60
30
20
10
Scale plate
Insert the fuse as follows.
0
48
64
2-M4
35
100
70
80
90
Fuse
holder
For 60 A, 80 A and 100 A
10
48
0
Set the potentiometer full counter clockwise and combine with a scale plate. When setting the knob on the scale plate, align the arro w on the knob with 0 on the scale plate.
Panel cutout dimensions
32 32
48
18.5 29 .5
Unit: mm
Fast-blow fuse
54
2-4 (hole )
Rated current of fast-blow fuse
Details Rating Fast-blow fuse for 20 A Fast-blow fuse for 30 A
6
2-M10
11
+0.5
0
6
Unit: mm
20 A
30 A
Unit: mm
94
82
105
102
131
116
54
30
12
48
Insulation
cover
72
13
35
35
Insulation
cover
Rated current of fast-blow fuse
Details Rating Details Rating
Fast-blow fuse for 20 A 20 A Fast-blow fuse for 60 A 75 A
Fast-blow fuse for 30 A 30 A Fast-blow fuse for 80 A 100 A
Fast-blow fuse for 45 A 50 A Fast-blow fuse for 100 A 100 A
IMR01M01-E16
Find Quality Products Online at: sales@GlobalTestSupply.com
29
www.GlobalTestSupply.com
Page 30
Fuse holder (UL approved instrument) for 20 A and 30 A (1 circuit type) THVP-H04
79.5
61
56
17.8
71.2
53.4
35.6
2.5
10
43
Rated current of fast-blow fuse (UL approved instrument)
Details Rating
Fast-blow fuse (UL approved instrument) for 20 A
Fast-blow fuse (UL approved instrument) for 30 A
Unit: mm
Fuse holder (UL approved instrument) for 45A, 60 A, 80 A and 100 A (1 circuit type) THVP-H05
110.5
87.5
75.5 53
40
16
53
Replacement method of the fuse
Open a front lid. Take fuse out of the holder.
Fuse
Wiring method of fuse holder
Loosen a screw of holder front.
The Figure shows the type of 20 A and 30 A. However, the replacing procedure or wiring procedure is the same as for the type of 45 A to 100 A.
27
8
2.5
35.6
71.2
106.8
142.4
Insert the new fuse.
Rated current of fast-blow fuse (UL approved instrument)
Fast-blow fuse (UL approved instrument) for 45 A
Fast-blow fuse (UL approved instrument) for 60 A
Fast-blow fuse (UL approved instrument) for 80 A
Fast-blow fuse (UL approved instrument) for 100 A
Details Rating
Close a front lid to finish the work.
Confirm the location and insert a leadwire.
Tighten a screw of holder front. Wire the leader to the bottom side in the same way as in 1, 2 and 3.
Leadwire of main circuit (1/L1)
The first edition: JUN. 2002 [IMQ00] The sixteenth edition: JUL. 2020 [IMQ00]
Unit: mm
20 A
32 A
50 A
63 A
80 A
100 A
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Loading...