(2) Notes on load
R
)
a) Load with small current or sensitive load sometimes
disables off-function as the product maintains on-condition resulting from off state leakage current. In such cases, connect shunt resistance (Rp) to be parallel with load and reduce off state leakage current applied on the load.
IR: Load off current RL: Load impedance ILEK: Off state leakage current b) The product is designed for the purpose of controlling
resistance load. If the load has larger inductance, current phase delays comparing to voltage and may cause disoperation when changing the current flow. Please allow your time to pre-check the function.
(3) Operation
a) The product controls output proportional to the input
rating (4 to 20 mA DC) by adopting zero-cross control system.
The product is available for use without analog input by
applying external volume adjuster.
b) The Ramp-up/Ramp-down (Soft start) function can be
used to suppress rapid change in output voltage by changing the output slowly in case of a rapid change in the output due to input signal changes.
Ramp-up time and Ramp-down time (Soft start
Ramp-up time Ramp-down time
100%
Output
Input signal
* The length Ramp-up and Ramp-down time is the same.
(4) Others
Do not connect products in series to raise strength or in parallel to raise the current volume.
IR × RL
ILEK I
SPECIFICATIONS
1. Ratings
Item SSNZ-15F SSNZ-25F
Maximum Input Current 24 mA DC Max. Load Voltage 264 V AC rms Max. Load Current 15 A AC rms 25 A AC rms 1 Cycle Surge Current 146 A 250 A Isolation Resistance Dielectric Strength 2500 V AC rms/1 min * Ambient Temperature
Storage Temperature
* Input ( , ), Ext. Volume ( , ) Output ( , ),
Power Source ( ) Between Cases
100 M and above (500 V DC) *
20 to 60 C
(No Icing and Condensation)
30 to 70 C
(No Icing and Condensation)
2. Electrical Characteristics
Item SSNZ-15F SSNZ-25F
Input Impedance 250 ± 20 % Input Current Range 4 to 20 mA DC Load Voltage Range 85 to 264 V AC rms (Sine wave) Load Current Range On State Voltage Drop Below 1.5 V AC rms
Off State Leakage Current Below 9 mA AC rms
Power Adjustment Range 0 to 100 % Output power accuracy Setting power ± 10 % Load Voltage Frequency Range
Current Consumption
( )
Responding Time Below 1cycle without Soft start *2 Ramp-up/Ramp-down Time Approx 0.5 to 40 seconds *2 Weight Approx. 260 g Standard UL508 category No. NRNT2
*1 Conduction angle tend to be narrower when the load with minute
current applied. Please allow your time to pre-check the function.
*2 The front volume adjuster reach MAX when turned clockwise and
reach ZERO when turned counter-clockwise. The ratings of approx.0.5 to 40 sec. shows changing time of the power from 0 % 100 % or 100 % 0 %.
100 mA AC rms to max. load current *1
(load voltage 200 V AC rms, 60 Hz)
Analog Input
Ext. volume
50 Hz/60 Hz Auto-change
47 to 53 Hz/57 to 63 Hz
(Ta = 25 C)
(at max. output power)
5.1 mA AC rms
(100 V AC rms, 50 Hz)
7.0 mA AC rms
(100 V AC rms, 50 Hz)
3. Input current vs. Output power
4. Load mitigation
The first edition: MAR. 2005 [IMQ00]
The seventh edition: JUN. 2015 [IMQ00]
RKC INSTRUMENT INC.
Single Phase Power Controller Zero-cross Control Type
SSNZ-15F/SSNZ-25F
User's Manual
RKC INSTRUMENT INC. IMR02A02-E7
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place the manual in a convenient location for easy reference. The instruction manual is intended for those who have the knowledge on electronic devices.
SAFETY INSTRUCTION
SYMBOLS
WARNING
CAUTION
1. Risk of electric shock
Power source should be disconnected when wiring. The terminal cover should be attached whenever it is
operating. Do not remove the outer case. Do not touch the product when operating. Do not touch the terminal immediately after it is
switched off. It may cause an electric shock by
electricity charged in the condenser.
2. Risk of fire or fire burn
Do not touch the heat sink while on operation or
immediately after it is switched off. Do not use the product near inflammable gas or
explosive gas. Keep combustibles away from the product. Apply fuse or breaker for safety reason in order to
prevent overcurrent, short circuit, or breakdown. Wiring to terminals must be screwed with adequate
torque. (It may cause excessive heat generation on
terminals.)
3. Others
Use the unit within the specified ratings. Do not drop the product on any of your body parts.
Incorrect application may result in fire or potential hazard to human body.
Incorrect application may result in damage to the unit or other equipment.
WARNING
®
The following accessories may be available from us.
External Volume (Complete with Volume, Scale plate and Knob.)
Rapid blow fuse
Fuse holder * HK1038UL Fuse holder cover * HC10
* Same fuse holder/cover for 15 A, 25 A
Accessories Model code
For 15 A For 25 A
Do not soak the product in water, washing liquid or
chemicals.
Do not put any metallic particles or conducting
materials inside the product. Do not overhaul or remodel them. Use correct size of wires according to the current. Do not drop the product, give vibration or physical
shock. Use the power source within the rated frequency
range. Using the product under the following condition may
cause failure, malfunction or degradation.
As the product self-heats while on operation, heat
sink is attached as a radiator. If the heat convection
is obstructed by surrounding equipment and parts, it
will lead to possible cause of fire or damage by
excessive heat generation. Check the polarity of wires and apply adequate
voltage. The load should be within the rated range.
Rapid blow fuse
Fuse holder
Exposed to water, oil or chemicals. Exposed to corrosive gas. In the high heat or high humidity. Exposed to dust or metal powders.
CAUTION
NPZP-S01
660CF15UL 660CF25UL
IMR02A02-E7 JUN. 2015
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 2
NOTICE
o
(
)
(Typ
)
(
)
k
o
The figures, diagrams and numeric values used in this
manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is
caused as a result of using this instrument, instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by imitating this instrument.
Periodic maintenance is required for safe and proper
operation of this instrument. Some components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all
information contained herein. RKC makes no warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified,
copied, transmitted, digitized, stored, processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
Check specifications or any standards if it conforms to the
product when used with other equipment. We are not responsible for the item's conformity if the pre-confirmation is not carried out.
When using the product with the following application, do
not apply the maximum ratings on the item and take safety measures in advance in order to minimize the damage to the product.
a) When using outside, using under the condition with
potential damage by chemicals or electric obstruction or under the condition not specified in the instruction manual or specifications.
b) Any facilities of nuclear power control, incineration,
railways, airways, vehicles, medical devices, safety devices and the facilities regulated by administrative organ or private sectors.
c) Any system or machinery which may endanger person or
property.
d) Any facilities which requires high reliability such as the
suppliers of gas, electricity and water or the system continuously operating 24 hours.
e) Any other application when an advanced security is
required.
HOW TO MOUNT
1. Dimensions and Mounting
This product can be mounted on a DIN-rail and the wall of a panel.
(1) Dimensions
Protective cover
(Unit mm)
Ramp-up/ Ramp-down (soft start) set up volume
(2) Panel Processing
(3) Torque rate against panel
When mounting the product onto the panel, the tightening torque should be 1.18 to 1.47 N m.
(4) Mounting direction
Vertical direction Horizontal direction
Panel
Panel The load current should be below 70 % of the specified ratings.
2. Regarding Wiring and Connection
When a load is not connected rightly, a fault may be happened. Please connect the load according to the connection example.
(1) Example of connection with temperature controller
Heater
Load
2
2
85 t 264 V AC
Input signal indication lamp
Rapid blow fuse
Heater
Load
Load
Load
85 t 264 V AC
Input signal indication lamp
Rapid blow fuse
4 to
Temperature
20 mA DC
controller
(2) Example connection adopting external volume
(Manual setting)
Ext. volume
Numbers printed in white on a dark circle are terminal numbers of ext. volume (potentiometer).
* Please purchase ext. volume (potentiometer), rapid blow fuse
and fuse holder separately (sold separately).
* When used with a temperature controller, this ext. volume
cannot be used as “(Gradient setting).”
: Input terminal (1+) : Input terminal (2-) : Ext. Volume terminal (3) : Ext. Volume terminal (4) : Output terminal (T1) : Output terminal (L1) : Power terminal (L2)
Input impedance of the product is 250 (ohm). Ext. Volume terminal ( ) outputs 5 V, therefore, the input voltage of the product is; 5 V × 250 /(Resistance on ext. volume + 250 ) Choose the ratings of the external volume in compliance with the amount of electric power adjustments. The volume is available as an optional part from us.
(3) Input wiring
a) Wire size
2
e: NPZP-S01
Single wire: 0.14 to 0.5 mm Stranded wire: 0.14 to 0.5 mm AWG: 20 to 26
b) Processing of the tip
c) How to insert
Insert the connector lever as in the illustration and insert the power cord. If the power cord is pushed in coercively without placing the lever, it may become the cause of bad contact or disconnection.
(4) Output wiring
a) Ring terminals
Terminal No. Item A B
/ Output terminal (T1/L1) Below 9.5 mm Above 4.3 mm
Power terminal (L2) Below 6.5 mm Above 3.7 mm
b) Screw torque
Terminal No. Item Max. rate Recommendation
/ Output terminal (T1/L1)
Power terminal (L2)
3. Notes on electric circuit design
(1) Protective circuit on output side
a) The product is composed of semi-conductor elements
and there is a possibility that the unit fails due to surge voltage and overcurrent. Failures are generally caused by short circuit and it becomes uncontrollable when load is at on state. It is, therefore, more secured to use the product with breaker or contactor as the protective circuit.
b) Output element damages if output side has short-current
or overcurrent.
Apply rapid blow fuse within the following range on load
circuit.
Isurge > Iff > Ir
Isurge: 1 cycle surge on current Iff: Fusing current of rapid blow fuse Ir: Inrush current of load
1.47 N m 1.18 to 1.37 N m