RKC INSTRUMENT X-TIO-G Instruction Manual

Page 1
Module Type Controller SRX
Temperature Control Module for PROFIBUS
X-TIO-G
Instruction Manual
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place the manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
To prevent injury to persons, damage to instrument
and equipment, a suitable external protection device shall be required.
All wiring must be completed before power is turned
on to prevent electric shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the
specifications to prevent fire or dama ge to instrument and equipment.
This instrument is not intended for use in locations
subject to flammable or explosive gases.
Do not touch high-voltage connections such as
power supply terminals, etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired,
modified or disassembled by other than factory-approved personnel. Malfunction can occur and warranty is void under these conditions.
This product is intended for use with industrial machines,
test and measuring equipment. (It is not designed for use with medical equipment and nuclear energy.)
This is a Class A instrument. In a domestic environment,
this instrument may cause radio interference, in which case the user may be required to take additional measures.
All Rights Reserved, Copyright 2003, RKC INSTRUMENT INC.
: This mark indicates precautions that must be
taken if there is danger of electric shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions
and operating procedures are not taken, damage to the instrument may result.
: This mark indicates that all precautions should
!
be taken for safe usage.
: This mark indicates important information on
installation, handling and operating procedures.
: This mark indicates supplemental information on
installation, handling and operating procedures.
: This mark indicates where additional information
may be located.
WARNING
!
CAUTION
RKC INSTRUMENT INC.
®
This instrument is protected from electric shock by
reinforced insulation. Provide reinforced insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit
respectively for the following: If input/output or signal lines within the building are longer
than 30 meters.
If input/output or signal lines leave the building, regardless
the length.
This instrumen t is designed for installation in an enclosed
instrumentation panel. All high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to
avoid damage to the instrument or equipment.
All wiring must be in accordance with local codes and
regulations.
All wiring must be completed before power is turned on to
prevent electric shock, instrument failure, or incorrect action. The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.
To prevent instrument damage as a result of failure, protect
the power line and the input/output lines from high currents with a suitable overcurrent protection device with adequate breaking capacity such as fuse, circuit breaker, etc.
Prevent metal fragments or lead w ire scraps from falling inside
instrument case to avoid electric shock, fire or malfunction.
T ighten each terminal screw to the specified torque found
in the manual to avoid electric shock, fire or malfunction.
For proper operation of this instrument, provide adequate
ventilation for heat dispensation.
Do not connect wires to unused terminals as this will
interfere with proper operation of the instrument.
Turn off the power supply before cleaning the instrument. Do not use a volatile solvent such as paint thinner to clean
the instrument. Deformation or discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an
abrasive material or push front panel with a hard object.
When high alarm with hold act ion/re-hold action is use d for
Event function, alarm does not turn on while hold action is in operation. Take measures to prevent overheating which may occur if the control device fails.
NOTICE
This manual assumes that the reader has a fundamental
knowledge of the principles of electricity, process control, computer technology and communications.
The figures, diagrams and numeric values used in this
manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is
caused as a result of using this instrument, instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting
from the use of instruments made by imitating this instrument.
Periodic maintenance is required for safe and proper
operation of this instrument. Some components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all
information contained herein. RKC makes no warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified,
copied, transmitted, digitized, stored, processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
Page 2
1. OUTLINE
A
r
L
N
L
X
X
The X-TIO-G (temperature control module for PROFIBUS) can send/receive data to/from PROFIBUS compatible programmable controllers (PLC) via PROFIBUS. One X-TIO-G module enables temperature control corresponding to two channels. It has power supply and communication termin als in addition to temperature control input and output terminals. All data are set by communication.
For details, refer to the Module Type Controller SRX
PROFIBUS Communication Instruction Manual (IMS01N10-E) and the Module Type Controller SRX Communication Instruction Manual (IMS01N01-E).
Programmable
controller (PLC)
Accessories
End Plate .......................................................................... 2
Joint connector cover ....................................................... 2
X-TIO-G Instruction Manual (IMS01N09-E4) ................... 1
GSD file (download free) * ................................................ 1
* The GSD file can be downloaded from the official RKC website:
http://www.rkcinst.com/english/download/field_network.htm.
If any of the products are missing, damaged, or if your manual is incomplete, please contact RKC sales office or the agent.
The manuals can be downloaded from the official RKC website: http://www.rkcinst.com/english/manual_load.htm.
3. PARTS DESCRIPTION
PROFIBUS-DP
Control output
Temperature control
module for PROFIBUS
X-TIO-G
Measured
Power supply input
(24 V DC)
input
Usable modules:
Temperature cont rol module
[Basic type]: X-TIO-A
Temperature cont rol module
[Extension type]: X-TIO- B
Digital input module: X-DI-A/B Digital output module : X-DO-A/B
(Up to 29 modules)
2. PRODUCT CHECK
Before using this product, check each of the following:
Model code Check that all of the accessories delivered are complete. Check that there are no scratch or breakage in external
appearance (case, front panel, or terminal, etc).
X-TIO-G- - / Y
(1) (2) (3) (4) (5) (6) (7) (8)
(1) Type
G: Module for PROFIBUS
(2) Input channel 1, (3) Input channel 2
K: TC K J: TC J T: TC T S: TC S R: TC R A: TC PL N: TC N E: TC E W: TC W5Re/W26Re B: TC B D: RTD Pt100 P: RTD JPt100 1: 0 to 10 mV DC 2: 0 to 100 mV DC 3: 0 to 1 V DC 4: 0 to 5 V DC 5: 0 to 10 V DC 6: 1 to 5 V DC 7: 0 to 20 mA DC 8: 4 to 20 mA DC
(4) Control output 1, (5) Control output 2
M: Relay contact output V: Voltage pulse output 0/12 V DC 4: 0 to 5 V DC 5 0 to 10 V DC 6: 1 to 5 V DC 7: 0 to 20 mA DC 8: 4 to 20 mA DC
(6) CT1 input, (7) CT2 input
N: None P: CTL-6-P-N S: CTL-12-S56-10L-N
(8) Version symbol
No code: For Japanese domestic market /Y: For International market
Heater break alarm (HBA) function can not be used when control output is Voltage/Current output.
*
Indication lamps 2
Address setting
switch 2
PROFIBUS
connecto
(COM.PORT)
FAIL/ RUN RX/TX EVENT1 EVENT2
FAI
ON
RU
TX/R
EVENT3
4
5
6
3
7
2
1
8
EVENT4
0
9
A
F
B
E
D
C
3
2
4
1
5
5 5
0
4
5
6
6
3
7
2
9
7
1
8
8
9
0
A
F
B
E
C
D
3
2
4
1
5
0
6
9
7
8
Terminal cover
Indicat io n lamps 1
ddress settin g
switch 1
Joint connector (Right-side)
Joint connec to r
Terminal cover
(Left-side)
PROFIBUS side Temperature control side
Indication lamps 2
FAIL
FAIL/RUN RX/TX EVENT1 EVENT2
ONL
RUN
TX/R
EVENT3 EVENT4
Indication lamps 1
Temperature control sidePROFIBUS side
[Indication lamps 1] FAIL/RUN (for temperature control side)
When normally: A green lamp turns on (RUN) When abnormally: A red lamp turns on (FAIL)
RX/TX (for RKC communication/Modbus)
During data send and receive: A green lamp turns on
EVENT 1 to 4
Display various states by setting. During ON state: A green lamp turns on
Display contents
Event 1 state, Event 2 state, Comprehensive event state, Output state, Control state, Executing segment state, Time signal state
[Indication lamps 2] FAIL (for PROFIBUS side)
When hardware is normal: A red lamp turns off When hardware is abnormal: A red lamp turns on
RUN (for internal communication)
When normally: A green lamp turns on When abnormally: A green lamp is flashing
ONL
During PROFIBUS connection establishment: A green lamp turns on
RX/TX (for PROFIBUS communication)
During data send and receive: A green lamp turns on
4. COMMUNICATION SETTING
Set communication setting before mounting and wiring of SRX.
CAUTION
Do not separate the module mainframe from the terminal base with the power turned on. If so, instrument failure may result.
2
IMS01N09-E4
Page 3
4.1 Address Setting
A
X
FAI
N X
A
N
L
R X
PROFIBUS address setting
Set an address of PROFIBUS. For this setting, use a small slotted screwdriver.
High-order digi t sett ing (Set value 10h)
Low-order digit setting (Set value 1h)
ddress setting switch 2
4
5
3
2
1
0
F
E
D
C
4
5
3
2
1
0
F
E
D
C
Setting range: 1 to 125 [01h to 7Dh: hexadecimal] (Factory set value: 00h)
6
7
8
9
A
B
6
7
8
9
A
B
FAIL/RUN RX/T EVENT1
RU
O
EVENT2
TX/R
EVENT3
4
5
6
3
7
2
8
1
EVENT4
9
0
A
F
B
E
D
C
3
2
4
1
5
5 5
0
4
5
6
6
3
7
2
9
7
8
8
1
9
0
A
F
B
E
D
C
3
2
4
1
5
0
6
9
7
8
No communication with PROFIBUS can be conducted with each factory set value (00h) left as it is. Always set the PROFIBUS address.
Module address setting
Set an address of module. For this setting, use a small slotted screwdriver.
ddress setting switch 1
FAIL/RUN RX/TX EVENT1
FAILRU
ON
EVENT2
TX/
EVENT3
4
5
6
3
7
2
8
1
EVTNT4
9
0
A
F
B
E
D
C
3
2
4
1
5
5 5
4
5
0
6
3
6
7
2
9
7
8
1
8
9
0
A
F
B
E
D
C
3
2
4
1
5
0
6
9
7
8
3
2
4
1
5
5 5
High-order digit setting
0
6
9
7
(Set value 10)
8
3
2
4
1
Low-order digit setting
5
0
6
9
7
(Set value 1)
8
Setting range: 0 to 98 (Factory set value: 00)
Do not set address 99. Otherwise, problems or
malfunction may result.
For Modbus, the value obtained by adding “1” to
the set address corresponds to the address used for the actual program.
Set the module address such that it is different to
the other addresses on the same line. Otherwise, problems or malfunction may result.
4.2 Internal Data Bus Termination Resistor Setting (PROFIBUS side)
Set the termination resistor of internal data bus for internal communication. When two or more modules are connected, set the internal data bus termination resistors to ON in modules at both ends. As a rule, as the X-TIO-G module is connected to the left end, set the internal data bus termination resistor to ON (No.8 of DIP switch 1: ON) on the PROFIBUS side and set that to OFF (No.8 of DIP switch 2: OFF) on the temperature control side.
DIP switch 1
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
OFF
4.3 RKC Communication/Modbus Setting (Temperature control side)
With the DIP switch 2 which there is on the right side of module, select communication speed for RKC communication/Modbus, data bit configuration for RKC communication/Modbus, protocol and termination resistor of internal data bus.
Right side view (temperature control side)
1 2 Communication speed
OFF OFF 2400 bps
ON OFF 9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 9600 bps
3 4 5 Data bit configuration
OFF OFF OFF Data 7-bit, without parity, Stop 1-bit * OFF OFF ON Data 7-bit, Even parity, Stop 1-bit * OFF ON ON Data 7-bit, Odd parity, Stop 1-bit *
ON OFF OFF Data 8-bit, without parity, Stop 1-bit ON OFF ON Data 8-bit, Even parity, Stop 1-bit ON ON ON Data 8-bit, Odd parity, Stop 1-bit
* When the Modbus communication protocol is selected, this
setting becomes invalid.
Factory set value: Data 8-bit, without parity, Stop 1-bit
6 Protocol selection
OFF RKC communication
ON Modbus
Factory set value: RKC communication
Internal data bus termination resistor setting
8
(temperature control side)
OFF Termination resistor OFF
ON Termination resistor ON
Factory set value: Termination resistor OFF
Switch No. 7 must be always OFF. Do not set to ON. When two or more modules are connected on the
same communication line, the DIP switch settings (switch 1 to 6) of all modules must be the same positions.
When RKC communication/Modbus is not used,
switches other than switch 8 need not be set.
For RKC communication/Modbus, refer to the Module Type Controller SRX Communication Instruction Manual (IMS01N01-E).
DIP switch 2
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
OFF
5. MOUNTING
Left side view (PROFIBUS side)
Internal data bus termination resistor setting
8
(PROFIBUS side)
OFF Termination resistor OFF
ON Termination resistor ON
Factory set value: Termination resistor ON
Switch No. 1 to 7: OFF fixed (Do not change this one)If the X-TIO-G module is used independently, the
internal data bus termination resistors on the PROFIBUS and temperature control sides also need to be set to ON (No. 8 of DIP switches 1 and 2: ON).
IMS01N09-E4
To prevent electric shock or instrument failure, always turn off the power before mounting or removing the instrument.
WARNING
!
5.1 Mounting Cautions
(1) This instrument is intended to be used under the following
environmental conditions. (IEC61010-1) [OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
3
Page 4
(2) Use this instrument within the following environment conditions:
Allowable ambient temperature: 10 to 50 C Allowable ambient humidity: 5 to 95 %RH
(Absolute humidity: MAX. W. C 29 g/m
3
dry air at 101.3 kPa)
Installation environment conditions: Indoor use
Altitude up to 2000 m
(3) Avoid the following when selecting the mounting location:
Rapid changes in ambient temperature, which may cause
End Plate mounting
Hold tight both ends of the modules jointed together with the end plates and then fix the end plates with screws. Even if only one X-TIO-G module is used, also hold tight both ends of the module with the end plates.
End Plate
X-TIO-G module
condensation.
Corrosive or inflammable gases. Direct vibration or shock to the mainframe. Water, oil, chemicals, vapor or steam splashes. Excessive dust, salt or iron particles. Excessive induction noise, static electricity, magnetic fields or noise. Direct air flow from an air conditioner. Exposure to direct sunlight. Excessive heat accumulation.
(4) Mount this instrument in the panel considering the following
conditions:
Provide adequate ventilation space so that heat does not bu ild up. Do not mount this instrument directly above equipment that
generates large amount of heat (heaters, transformers, semi-conductor functional devices, large-wattage resistors.)
If the ambient temperature rises above 50 C, cool this instrument
with a forced air fan, cooler, etc. Cooled air should not blow
* For the conservation of the contact of connector, install a joint
connector cover in module of both ends.
Removing procedures
Pull down a mounting bracket with a slotted screwdriver (A). Lift the module from bottom, and take it off (B).
Joint connector cover *
directly on this instrument.
In order to improve safety and the immunity to withstand noise,
mount this instrument as far away as possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel. Power lines: Separate at least 200 mm. Rotating machinery: Separate as far as possible.
Ensure at least 50 mm space on top and bottom of the
(B) Lift and take off
control unit for maintenance and environmental reasons.
(5) In case this instrument is connected to a supply by means of a
permanent connection a switch or circuit-breaker shall be included in the installation. This shall be in close proximity to the equipment and within easy reach of the operator. It shall be marked as the disconnecting device for the equipment.
5.2 Dimensions
(Unit: mm)
125
110 6.8 40.5
6
78
5.4 Panel Mounting
Mounting procedures
1. Pull down the mounting bracket (A) until locked and that a
mounting hole appears.
2. Prepare one mounting bracket per module (B) sold
separately (KSRX-55) and then insert it in the rear of the terminal board at top of the module until locked but a mounting hole does not disappear.
3. Mount each module directly on the panel with screws which
are inserted in the mounting holes of the top and bottom mounting brackets.
5
(A) Pull down
Recommended tightening torque: 0.3 Nm (3 kgfcm)
The customer needs to provide the M3 size screws. Select the screw length that matches the mounting panel.
(B) Insert
Mounting bracket (Sold separately)
(KSRX-55)
5.3 DIN rail Mounting
Mounting procedures
1. Pull down the mounting bracket at the bottom of the module (A). Attach the hooks on the top of the module to the DIN rail and push the lower section into place on the DIN rail (B). [Fig. 1]
2. Slide the mounting bracket up to secure the module to the DIN rail.[Fig. 2]
DIN rail
Mounting bracket
Fig. 1 Fig. 2
(B) Push
(A) Pull down
Locked
Mounting dimensions
(A) Pull down
35.25  0.2
M3
Module of 40.5 mm wide Module of 30 mm wide
30 0.2
130.5 0.2
End Plate
Mounting
holes
(Unit: mm)
4
IMS01N09-E4
Page 5
5.5 Jointing Each Module
A
A
Up to 29 modules (X-TIO-A/B, X-DI-A/B or X-DO-A/B) can be connected to one X-TIO-G module. according to the following procedure.
Jointing procedure
1. Mount the modules on the DIN rail and then joint these modules together with the joint connector while sliding the relevant module.
2. Lift each of the joint tabs located at the top and bottom of the module and then insert it in the slot of the adjacent module to fix these two modules.
For panel mounting, first joint each module and then mount it on the panel.
Joint connector
Joint these modules
When viewed from top
In the maximum configuration (extension up to 30 modules) the
24 V DC supplied equipment may draw up to 4 A. The power supply shall be capable of delivering at least 4 A.
Use the solderless terminal appropriate to the screw size.
- Screw size: M3 x 6
- Recommended tightening torque: 0.4 Nm [4 kgfcm]
- Specified solderless terminals: With isolation
5.9 mm or less
3.2 mm or more
Make sure that during field wiring parts of conductors cannot
come into contact with adjacent conductive parts.
6.2 Terminal Configuration
Communication
RS-485
T/R(A)
T/R(B)
16
SG
17
CT input Control output 1 Control output 2
CT1
15
3
CT2
67
Voltage pulse/
Current/ Voltage
OUT1
2
5
Relay contact
OUT1
NO
2
5
Voltage pulse/
Current/ Voltage
OUT2
1
4
Relay contact
OUT2
NO
1
4
Joint tab
There is one joint tab at each of the top and bottom of on module. Therefore, fix two adjacent modules with these two joint tabs.
Joint tab insertion slot
6. WIRING
To prevent electric shock or instrument failure, do not turn on the power until all wiring is completed. Make sure that the wiring is correct before applying power to the instrument.
6.1 Wiring Cautions
For thermocouple input, use the appropriate compensation wire. For RTD input, use low resistance lead wire with no difference
in resistance between the three lead wires.
To avoid noise induction, keep input signal wire away from
instrument power line, load lines and power lines of other electric equipment.
Signal connected to Voltage input and Current input shall be
low voltage defined as “SELV” circuit per IEC 60950-1.
If there is electrical noise in the vicinity of the instrument that
could affect operation, use a noise filter.
- Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction.
- Always install the noise filter on a grounded panel. Minimize the wiring distance between the noise filter output and the instrument power supply terminals to achieve the most effective noise reduction.
- Do not connect fuses or switches to the noise filter output wiring as this will reduce the effectiveness of the noise filter.
Instrument power
Power supply wiring must be tw isted an d have a lo w voltag e drop. For an instrument with 24 V power supply input, supply power
from "SELV" circuit defined as IEC 60950-1.
A suitable power supply should be considered in end-use
equipment. The power supply must be in compliance with a limited-energy circuits (maximum available current of 8 A).
Shorten distance between pitches
WARNING
!
Twist these leadwires
IN
Noise filter
OUT
Minimize distance
Instrument power terminals
16 15 3 2 1
17 7 6 5 4
18 11 10 9 8
20 19 14 13 12
20
FG
Power supply
18
19
DC
24 V
Input channel 1
10
B
14 13
RTD1
RTD
10
B
Thermocouple
10
Voltage/
Voltage/
Current
Current
TC1
IN1
13
13
Ground
Heater break alarm (HBA) function cannot be used when control output is Voltage/Current output.
Terminal No. 11 is not used.
Input channel 2 can be used as remote setting input (only for Voltage/Current input). In this case, control output 2 and CT input 2 become unused.
6.3 Pin Layout of Connector
PROFIBUS connector
(COM. PORT)
9
6
5
1
Upper-side terminal
Lower-side terminal
Input channel 2
9
Thermocouple
9
Voltage/
Current
TC2
IN2
9
B
12
12
RTD
12
B
RTD2
8
IMS01N09-E4
5
Page 6
A
Pin No. Signal name Symbol
1 2 3
Receive data/transmission data (plus)
4 5 Signal ground DGND 6
Termination resistor supply voltage (5 V)
7 8
Receive data/transmission data (negative)
9
The PROFIBUS cable (a connection cable of PLC and SRX) is provided by customer. As for the PROFIBUS cable, there is a case prepared by a PLC manufacturer.
The details except the above are connected to a home page of PROFIBUS International, and obtain necessary information. http://www.profibus.com/
Unused Unused
RxD/TxD-P
Unused
VP
Unused
RxD/TxD-N
Unused
7. SPECIFICATIONS
Inputs
Number of inputs: 2 points (Isolated between each channel) Input type:
Thermocouple: K, J, T, S, R, E, B, N (JIS-C1602-1995) PLII (NBS) W5Re/W26Re (ASTM-E988-96) RTD: Pt100 (JIS-C1604-1997) JPt100 (JIS-C1604-1989, Pt100 of JIS-C1604-1981)
Voltage (low): 0 to 10 mV DC, 0 to 100 mV DC, 0 to 1 V DC Voltage (high): 0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC Current: 0 to 20 mA DC, 4 to 20 mA DC
(Input impedance: 250 ) Sampling cycle: 25 ms PV bias: Input span to Input span CT input: 2 points
Outputs
Number of outputs: 2 points
Output type:
Relay contact: 250 V AC, 3 A (Resistive load)
1a contact
Electrical life 300,000 times or more
(Rated load)
Voltage pulse: 0/12 V DC
(Load resistance 600 or more)
Current: 0 to 20 mA DC, 4 to 20 mA DC
(Load resistance 600 or less)
Voltage: 0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC
(Load resistance 1 k or more)
Control action
Number of controls: 2 points Control method: Brilliant PID control
Additional function: Autotuning function
0.0 to 30.0 A (CTL-6P-N) or
0.0 to 100.0 A (CTL-12-S56-10L-N)
(Isolated between input and output, and between output and power supply)
Reverse action or direct action is selectable
Output limiter function Output change rate limiter function
Events
Number of events: 2 points/channel Event type: Temperature event:
Deviation high, Deviation low, Deviation high/low, Band, Process high, Process low
Heater break alarm (HBA) function
Number of HBA: 2 points Setting range: 0.0 to 100.0 A (0.0 A: OFF) Additional function: Number of event delay times:
1 to 255 times
Control loop break alarm (LBA) function
Number of LBA: 2 points LBA time: 1 to 7200 seconds LBA deadband (LBD) setting:
0 to Input span
Program control
Number of patterns: 16 patterns max. Number of segments: 16 segments/pattern max.
Time signal output: 16 points/pattern
(With pattern link function)
Communications
Communication interface: Based on RS-485, EIA standard Communication protocol:
PROFIBUS-DP (EN50170) RKC communication
(ANSI X3.28-1976 subcategories 2.5 and
A4) or Modbus Maximum connections: 31 instruments maximum including a host computer
Others
Power supply voltage: 21.6 to 26.4 V DC
Current consumption: 0.25 A max. Allowable ambient temperature range:
Allowable ambient humidity range:
Installation environment conditions:
Weight: Approx. 300 g
(Including power supply volt age var iation) Rating: 24 V DC
10 to 50 C 5 to 95 %RH (Non condensing)
Absolute humidity: MAX.W.C 29.3 g/m
Indoor use Altitude up to 2000 m
3
dry air at 101.3 kPa
Standard
Safety standard: UL: UL61010-1 CE marking: LVD: EN61010-1
C-Tick: EN55011
cUL: CAN/CSA-C22.2 No.61010-1 OVERVOLTAGE CATEG ORY II,
POLLUTION DEGREE 2, Class II (Reinforced insulation) EMC: EN61326-1
Modbus is a registered trademark of Schneider Electric. Company names and product names used in this manual are the trademarks or registered trademarks
of the respective companies.
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN
RKC INSTRUMENT INC.
®
Website: http://www.rkcinst.com/
IMS01N09-E4
UG. 2013
PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jp FAX: 03-3751-8585 (+81 3 3751 8585)
The first edition: JUN. 2003 [IMQ00] The fourth edition: AUG. 2013 [IMQ00]
Loading...