RKC INSTRUMENT SRZ Instruction Manual

Page 1

RKC INSTRUMENT INC.
Module Type Controller
SRZ
Instruction Manual
IMS01T04-E6
Page 2
Modbus is a registered trademark of Schneider Electric. Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
Page 3
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of the instrument, carefully read all the instructions in this manual. Please place the manual in a convenient location for easy reference.

SYMBOLS

WARNING

CAUTION
!
: This mark indicates where additional information may be located.
To prevent injury to persons, damage to the instrument and the equipment, a
suitable external protection device shall be required.
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not taken,
damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating procedures.
: This mark indicates supplemental information on installation, handling and operating procedures.
WARNING
!
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to the instrument and the equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to the instrument and the equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction may occur and warranty is void under these conditions.
IMS01T04-E6
i-1
Page 4

CAUTION

This product is intended for use with industrial machines, test and measuring equipment.
(It is not designed for use with medical equipment and nuclear energy plant.)
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take additional measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
Be sure to provide an a pp ropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock to operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
If the equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock, instrument
failure, or incorrect action. The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.
To prevent instrument damage as a result of failure, protect the power line and the
input/output lines from high currents with a suitable overcurrent protection device with adequate breaking capacity such as a fuse, circuit breaker, etc.
A malfunction in this product may occasionally make control operations impossible or prevent
alarm outputs, resulting in a possible hazard. Take appropriate measures in the end use to prevent hazards in the event of malfunction.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
fire or malfunction.
For prop er operation of this instrument, provide adequate ventilation for heat dissipation. Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power sup ply before clea ning the instrument. Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration may occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to the instrument display, do not rub with an abrasive material or push the
front panel with a hard object.

NOTICE

This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for explanation purpose. RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components
have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty, expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
i-2
IMS01T04-E6
Page 5

CONTENTS

1. OUTLINE ........................................................................... 1-1
1.1 Features ...................................................................................................... 1-2
1.2 Checking the Product .................................................................................. 1-3
1.2.1 Z-TIO module .......................................................................................................... 1-3
1.2.2 Z-DIO module .......................................................................................................... 1-3
1.2.3 Optional (sold separately) ....................................................................................... 1-3
1.3 Model Code................................................................................................. 1-4
1.3.1 Z-TIO module .......................................................................................................... 1-4
1.3.2 Z-DIO module .......................................................................................................... 1-7
1.4 Parts Description ......................................................................................... 1-9
1.4.1 Z-TIO module .......................................................................................................... 1-9
1.4.2 Z-DIO module ........................................................................................................ 1-11
Page
2. SETTING PROCEDURE TO OPERATION ....................... 2-1
3. MOUNTING ........................................................................ 3-1
3.1 Mounting Cautions ........................................................................................ 3-2
3.2 Dimensions ................................................................................................... 3-4
3.3 Important Points When Joining Modules ...................................................... 3-5
3.4 DIN Rail Mounting and Removing ................................................................ 3-6
3.5 Panel Mounting ............................................................................................. 3-8
4. WIRING ............................................................................. 4-1
4.1 Wiring Cautions ............................................................................................ 4-2
4.2 Connecting Precautions ............................................................................... 4-4
4.3 Terminal Configuration ................................................................................. 4-5
4.3.1 Z-TIO module .......................................................................................................... 4-5
4.3.2 Z-DIO module ....................................................................................................... 4-10
4.4 Connection to Host Computer .................................................................... 4-12
4.5 Installation of Termination Resistor ............................................................ 4-17
4.6 Connections for Loader Communication .................................................... 4-19
5. SETTINGS BEFORE OPERATION ................................... 5-1
5.1 Module Address Setting ............................................................................... 5-2
5.2 Protocol Selections and Communication Speed Setting ............................... 5-3
5.3 Operating Precautions .................................................................................. 5-4
5.4 Communication Requirements ..................................................................... 5-5
IMS01T04-E6 i-3
Page 6
6. RKC COMMUNICATION ................................................... 6-1
6.1 Polling ........................................................................................................... 6-2
6.1.1 Polling procedures .................................................................................................. 6-2
6.1.2 Polling procedures example .................................................................................... 6-7
6.2 Selecting ....................................................................................................... 6-8
6.2.1 Selecting procedures .............................................................................................. 6-8
6.2.2 Selecting procedures example .............................................................................. 6-11
6.3 Communication Data Structure ................................................................... 6-12
6.4 Communication Data List............................................................................ 6-13
6.4.1 Reference to communication data list ................................................................... 6-13
6.4.2 Communication data of Z-TIO module .................................................................. 6-14
6.4.3 Communication data of Z-DIO module .................................................................. 6-30
Page
7. MODBUS............................................................................ 7-1
7.1 Communication Protocol............................................................................... 7-2
7.1.1 Message format ...................................................................................................... 7-2
7.1.2 Function code ......................................................................................................... 7-3
7.1.3 Communication mode ............................................................................................. 7-3
7.1.4 Slave responses ..................................................................................................... 7-4
7.1.5 Calculating CRC-16 ................................................................................................ 7-5
7.2 Register Read and Write .............................................................................. 7-8
7.2.1 Read holding registers [03H] ................................................................................. 7-8
7.2.2 Preset single register [06H] ................................................................................... 7-9
7.2.3 Diagnostics (Loopback test) [08H] ....................................................................... 7-10
7.2.4 Preset multiple registers [10H] ............................................................................ 7-11
7.3 Data Processing Precautions ..................................................................... 7-12
7.4 How to Use Memory Area Data .................................................................. 7-13
7.5 How to Use Data Mapping .......................................................................... 7-17
7.6 Communication Data List............................................................................ 7-18
7.6.1 Reference to communication data list ................................................................... 7-18
7.6.2 Communication data of Z-TIO module .................................................................. 7-19
7.6.3 Communication data of Z-DIO module .................................................................. 7-39
7.6.4 Memory area data address (Z-TIO)....................................................................... 7-42
7.6.5 Data mapping address (Z-TIO, Z-DIO) .................................................................. 7-44
i-4
IMS01T04-E6
Page 7
8. COMMUNICATION DATA DESCRIPTION ....................... 8-1
8.1 Reference to Communication Data Contents ............................................... 8-2
8.2 Communication Data of Z-TIO Module ......................................................... 8-3
8.2.1 Normal setting data items ....................................................................................... 8-3
8.2.2 Engineering setting data items .............................................................................. 8-61
8.3 Communication Data of Z-DIO Module ..................................................... 8-143
8.3.1 Normal setting data items ................................................................................... 8-143
8.3.2 Engineering setting data items ............................................................................ 8-154
9.
TROUBLESHOOTING ....................................................... 9-1
Page
10. SPECIFICATIONS ......................................................... 10-1
10.1 Z-TIO module ........................................................................................... 10-2
10.2 Z-DIO module ......................................................................................... 10-16
11. APPENDIX ..................................................................... 11-1
11.1 ASCII 7-bit Code Table ............................................................................. 11-2
11.2 Current Transformer (CT) Dimensions ..................................................... 11-3
11.3 Cover ........................................................................................................ 11-4
11.4 Block Diagram of Logic Output Selection Function ................................... 11-6
11.5 Peak Current Suppression Function ......................................................... 11-7
11.6 Example of Using DI/DO........................................................................... 11-9
11.7 Example of Using Unused Heat/Cool Control Channel Inputs ................ 11-12
INDEX .................................................................................... A-1
IMS01T04-E6
i-5
Page 8
MEMO
i-6 IMS01T04-E6
Page 9

OUTLINE

1.1 Features ........................................................................................... 1-2
1.2 Checking the Product ....................................................................... 1-3
1.2.1 Z-TIO module ............................................................................................ 1-3
1.2.2 Z-DIO module ............................................................................................ 1-3
1.2.3 Optional (sold separately) .......................................................................... 1-3
1.3 Model Code ...................................................................................... 1-4
1.3.1 Z-TIO module ............................................................................................ 1-4
1.3.2 Z-DIO module ............................................................................................ 1-7
1.4 Parts Description ............................................................................. 1-9
1.4.1 Z-TIO module ............................................................................................ 1-9
1.4.2 Z-DIO module .......................................................................................... 1-11
IMS01T04-E6 1-1
Page 10
1. OUTLINE

1.1 Features

This chapter describes features, package contents and model code, etc. The module type controller has the following features:
Module type controller SRZ interfaces with the host computer via Modbus or RKC communication protocols. The SRZ sets all of the data items via communication (The communication interface used for both protocols is RS-485.). Therefore before operation, it is necessary to set value of each data item via communication.
Common to both Z-TIO and Z-DIO module
A user can select RKC communication or Modbus. When each module is connected, the power and communication lines are connected internally within the
modules, and thus it is only necessary to wire one module to the power terminal and communication terminal; there is no need to individually wire each module to the terminals. This reduces the amount of wiring needed.
Compact size
Terminal type: depth 85 mm, Connector type: depth 79 mm
Z-TIO module (Z-TIO-A, Z-TIO-B)
The Z-TIO module is a temperature control module equipped with either two or four control channels. The measured input is a universal input that supports thermocouple input, resistance temperature sensor
input, voltage input, current input, and feedback resistance input.
The input type can be specified separately for each channel, and different input types can be combined. Output types are relay contact output, voltage pulse output, voltage output, current output, open collector output, and
triac output. Output types are specified when the order is placed, and a different output type can be specified for each channel.
4CH Z-TIO module can have 4 CT (current transformer) inputs. Up to 16 Z-TIO modules can be connected.
[The maximum number of SRZ modules (including other function modules) on the same communication line is 31.]
Z-DIO module (Z-DIO-A)
The Z-DIO module is an event input/output module equipped with digital inputs and outputs (DI8 points
/DO8 points).
DI signal assignment enables switching of various mode states and memory areas of the Z-TIO module. DO signal assignment enables output of the event result of the Z-TIO module to the event output (DO),
and output of the DO manual output state of the Z-DIO module.
Up to 16 Z-DIO modules can be connected.
[The maximum number of SRZ modules (including other function modules) on the same communication line is 31.]
For reference purposes, the Modbus protocol identifies the host computer as master, each module of SRZ as slave.
For details of the Z-CT module, refer to Z-CT Instruction Manual (IMS01T21-E).
1-2 IMS01T04-E6
Page 11
1. OUTLINE

1.2 Checking the Product

Before using this product, check each of the following:
Model code Check that there are no scratches or breakage in external appearance (case, front panel, or terminal, etc.) Check that all of the items delivered are complete. (Refer to below)
If any of the products are missing, damaged, or if your manual is incomplete, please contact RKC sales office or the agent.

1.2.1 Z-TIO module

Description Q’TY Remarks
Z-TIO-A module or Z-TIO-B module 1  Z-TIO Instruction Manual
[For Host communication] (IMS01T01-E)  Z-TIO Host Communication Quick Instruction Manual
[For Host communication] (IMS01T02-E)  Joint connector cover KSRZ-517A 2 Enclosed with instrument Power terminal cover KSRZ-518A(1) 1 Enclosed with instrument SRZ Instruction Manual
(IMS01T04-E6)
1 Enclosed with instrument
1 Enclosed with instrument
1 This manual (sold separately) *
* This manual can be downloaded from the official RKC website:
http://www.rkcinst.com/english/manual_load.htm

1.2.2 Z-DIO module

Description Q’TY Remarks
Z-DIO module 1  Z-DIO module Instruction Manual
(IMS01T03-E)  Joint connector cover KSRZ-517A 2 Enclosed with instrument Power terminal cover KSRZ-518A(1) 1 Enclosed with instrument SRZ Instruction Manual
(IMS01T04-E6)
1 Enclosed with instrument
1 This manual (sold separately) *
* This manual can be downloaded from the official RKC website:
http://www.rkcinst.com/english/manual_load.htm

1.2.3 Optional (sold separately)

Description Q’TY Remarks
End plate DEP-01 2  Connector SRZP-01 (front screw type) 2 For the connector type module Connector SRZP-02 (side screw type) 2 For the connector type module CT cable W-BW-03-1000 1 For CT input connector (cable length: 1 m) CT cable W-BW-03-2000 1 For CT input connector (cable length: 2 m) CT cable W-BW-03-3000 1 For CT input connector (cable length: 3 m) Current transformer CTL-6-P-N 1 0.0 to 30.0 A Current transformer CTL-12-S56-10L-N 1 0.0 to 100.0 A Terminal cover KSRZ-510A(1) 1 For the terminal type module
IMS01T04-E6 1-3
Page 12
1. OUTLINE

1.3 Model Code

Check that the product received is correctly specified by referring to the following model code list: If the product is not identical to the specifications, please contact RKC sales office or the agent.

1.3.1 Z-TIO module

Suffix code
4-channel type:
Z-TIO-A / □□□/Y
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
2-channel type:
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
Wiring type Terminal type T Connector type C
Relay contact output M Voltage pulse output V Output1 (OUT1) Voltage output, Current output (Refer to Output Code Table) Triac output T Open collector output D Relay contact output M Voltage pulse output V Output2 (OUT2) Voltage output, Current output (Refer to Output Code Table) Triac output T Open collector output D Relay contact output M Output3 (OUT3) Voltage pulse output V [Z-TIO-A type only] Voltage output, Current output (Refer to Output Code Table) Triac output T Open collector output D Relay contact output M Output4 (OUT4) Voltage pulse output V [Z-TIO-A type only] Voltage output, Current output (Refer to Output Code Table) Triac output T Open collector output D Current transformer (CT)
input No quick start code (Configured to factory default) N
Quick start code Specify quick start code 1 1 Specify quick start code 1 and 2 2
Control Method (all channel common) [Quick start code 1]
Measured input and Range (all channel common) [Quick start code 1]
Instrument specification Version symbol /Y
1
Z-TIO-A type: CH2 and CH4 only accept Measured value (PV) monitor and event action.
Z-TIO-B type: CH2 only accepts Measured value (PV) monitor and event action.
2
Z-TIO-A type: Inputs of CH2 and CH4 can be used as FBR input.
Z-TIO-B type: Input of CH2 can be used as FBR input.
Specifications
None N CT (4 points) [4-channel type], CT (2 points) [2-channel type] A
Quick start code 1 is not specified No code PID control with AT (Reverse action) PID control with AT (Direct action) Heat/Cool PID control with AT 1 Heat/Cool PID control with AT (for Extruder [air cooling]) 1 A Heat/Cool PID control with AT (for Extruder [water cooling]) 1 Position proportioning PID control without FBR 2 Quick start code 1 is not specified No code
Refer to range code table. 
Z-TIO-B / N □□□/Y
(1) (2) (3) (6) (7) (8) (9) (10)
Suffix code
Hardware coding only Quick start code1
1-4 IMS01T04-E6
Page 13
Output Code Table
Voltage output (0 to 1 V DC) 3 Voltage output (1 to 5 V DC) 6 Voltage output (0 to 5 V DC) 4 Current output (0 to 20 mA DC) 7 Voltage output (0 to 10 V DC) 5 Current output (4 to 20 mA DC) 8
Range Code Table
[Thermocouple (TC) input, RTD input] [Voltage input, Current input]
Type Code Range (Input span) Code Range (Input span) Type Code Range (Input span)
K02 0 to 400 C KA1 0 to 800 F 0 to 10 mV DC 101 K04 0 to 800 C KA2 0 to 1600 F 0 to 100 mV DC 201 Programmable range K41 200 to 1372 C KC7 328 to 2501 F 0 to 1 V DC 301 19999 to 19999
K K09 0.0 to 400.0 C KA4 0.0 to 800.0 F 0 to 5 V DC 401 [The decimal point position is selectable]
K10 0.0 to 800.0 C 0 to 10 V DC 501 (Factory set value: 0.0 to 100.0) K35 200.0 to 400.0 C 1 to 5 V DC 601 K40 200.0 to 800.0 C 0 to 20 mA DC 701 K42 200.0 to 1372.0 C 4 to 20 mA DC 801 J02 0 to 400 C JA1 0 to 800 F J04 0 to 800 C JA2 0 to 1600 F J15 200 to 1200 C JB9 328 to 2192 F
J J08 0.0 to 400.0 C JB6 0.0 to 800.0 F
J09 0.0 to 800.0 C J27 200.0 to 400.0 C J32 200.0 to 800.0 C J29 200.0 to 1200.0 C
T T19 200.0 to 400.0 C TC5 328 to 752 F
TC6 0.0 to 752.0 F
E E20 200.0 to 1000.0 C EB2 0.0 to 800.0 F
EB1 328 to 1832 F S S06 50 to 1768 C SA7 58 to 3214 F R R07 50 to 1768 C RA7 58 to 3214 F B B03 0 to 1800 C BB1 32 to 3272 F N N07 200 to 1372 C NA8 328 to 2502 F
PLII A02 0 to 1390 C AA2 0 to 2534 F
W5Re/W26Re W03 0 to 2300 C WB1 32 to 4208 F
Pt100 D21 200.0 to 200.0 C DC6 328.0 to 752.0 F
D35 200.0 to 850.0 C DD2 328 to 1562 F
JPt100 P31 200.0 to 649.0 C PC6 328.0 to 752.0 F
PD2 328 to 1200 F
Output type Code Output type Code
1. OUTLINE
IMS01T04-E6
1-5
Page 14
1. OUTLINE
Quick start code 2 (Initial setting code)
Quick start code 2 tells the factory to ship with each parameter preset to the values detailed as specified by the customer. Quick start code is not necessarily specified when ordering, unless the preset is requested. These parameters are software selectable items and can be re-programmed in the field via the manual.
□ □ □ □-□ □
(1) (2) (3) (4) (5) (6)
Specifications
Event function 1 (EV1) 1 None N Event function 1 (Refer to Event type code table) Event function 2 (EV2) 1 None N Event function 2 (Refer to Event type code table) Event function 3 (EV3) 1 None N Event function 3 (Refer to Event type code table) Temperature rise completion 6 Event function 4 (EV4) 1 None N Event function 4 (Refer to Event type code table) Control loop break alarm (LBA) 5 None N CT type 2 CTL-6-P-N P CTL-12-S56-10L-N S Communication protocol RKC communication (ANSI X3.28-1976) 1 Modbus 2
1
If it is desired to specify the deviation action between channels or the deviation using local SV, the settings must be configured by the customer. (Engineering setting data)
2
The CT assignment and Heater break alarm (HBA) type must be configured by the customer. (Engineering setting data)
Event type code table
Code Type Code Type Code Type
A Deviation high H Process high V SV high B Deviation low J Process low W SV low C Deviation high/low K Process high with hold action 1 MV high [heat-side] D Band L Process low with hold action 2 MV low [heat-side] E Deviation high with hold action Q Deviation high with re-hold action 3 MV high [cool-side] F Deviation low with hold action R Deviation low with re-hold action 4 MV low [cool-side] G Deviation high/low with hold action T Deviation high/low with re-hold action
Quick start code 2 (Initial setting code)
(1) (2) (3) (4) (5) (6)
1-6
IMS01T04-E6
Page 15
1. OUTLINE
    
    
    
 
 

1.3.2 Z-DIO module

Z-DIO-A □-□ □/□-□□□□□□□
(1) (2) (3) (4) (5) (6) (7) (8)
Wiring type Terminal type T
Connector type C
Digital input (DI) None N 8 points A None N Digital output (DO) Relay contact output (8 points) M Open collector output (8 points) D Quick start code No quick start code (Configured to factory default) N (DI/DO assignments) Specify quick start code 1 1
DI signal assignments Quick start code 1 is not specified No code (DI1 to DI8) None N [Quick start code 1] Refer to DI assignment code table.  DO signal assignments Quick start code 1 is not specified No code (DO1 to DO4) None N [Quick start code 1] Refer to DO assignment code table.  DO signal assignments Quick start code 1 is not specified No code (DO5 to DO8) None N [Quick start code 1] Refer to DO assignment code table.  Communication protocol RKC communication (ANSI X3.28) 1 Modbus 2
DI assignment code table
Code DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
00 No assignment 01 02 REM/LOC 03 Interlock release EDS start signal 1 04 Soak stop 05 RUN/STOP 06 REM/LOC 07 AUTO/MAN EDS start signal 1 08 Operation mode 09 RUN/STOP 10 EDS start signal 1 11 REM/LOC Soak stop 12 RUN/STOP 13 Area set 2 14 15 Soak stop 16 EDS start signal 1 17 REM/LOC Soak stop 18 Interlock release AUTO/MAN RUN/STOP 19 20 21 Soak stop 22 23 AUTO/MAN REM/LOC 24 25 REM/LOC EDS start signal 1 26 Memory area
transfer (1, 2) 27 Memory area transfer (1 to 8) 1 Area set 28 Memory area
transfer (1, 2) 29 EDS start signal 1 EDS start signal 2 Operation mode 3
RUN/STOP: RUN/STOP transfer (Contact closed: RUN) AUTO/MAN: Auto/Manual transfer (Contact closed: Manual mode) REM/LOC: Remote/Local transfer (Contact closed: Remote mode) Interlock release (Interlock release when rising edge is detected) EDS start signal 1 (EDS start signal ON when rising edge is detected [for disturbance 1]) EDS start signal 2 (EDS start signal ON when rising edge is detected [for disturbance 2]) Soak stop (Contact closed: Soak stop)
1
Memory area transfer (:Contact open : Contact closed)
Memory area number
DI1 DI2 DI3
2
Area set becomes invalid prior to factory shipment.
3
Operation mode transfer (:Contact open : Contact closed)
Operation mode
DI5 (DI7) DI6 (DI8)
1
1
1 2 3 4 5 6 7 8
Unused Monitor Monitor
(1) (2) (3) (4) (5) (6) (7) (8)
Suffix code
Specifications
Memory area transfer (1 to 8)
2
Area set
Interlock release RUN/STOP AUTO/MAN REM/LOC Operation mode 3
2
Area set
Interlock release RUN/STOP AUTO/MAN REM/LOC
AUTO/MAN
1
Hardware coding only Quick start code1
2
Operation mode
DI signal will become valid at rising edge after the closed contact is held for 250 ms.
Contact closed
Contact open
Event function Control
3
Soak stop
EDS start signal 1
EDS start signal 1
EDS start signal 1
Soak stop
3
EDS start signal 1 EDS start signal 2
250 ms or more
(Rising edge)
Soak stop
RUN/STOP
Soak stop
RUN/STOP
Soak stop
RUN/STOP
Continued on the next page.
IMS01T04-E6
1-7
Page 16
1. OUTLINE
Continued from the previous page.
DO assignment code table
[DO1 to DO4]
Code DO1 DO2 DO3 DO4
00 No assignment 01
02 Event 1 comprehensive output 1 Event 2 comprehensive output 2 Event 3 comprehensive output 3 Event 4 comprehensive output 4 03 Event 1 (CH1) Event 2 (CH1) Event 3 (CH1) Event 4 (CH1) 04 Event 1 (CH2) Event 2 (CH2) Event 3 (CH2) Event 4 (CH2) 05 Event 1 (CH3) Event 2 (CH3) Event 3 (CH3) Event 4 (CH3) 06 Event 1 (CH4) Event 2 (CH4) Event 3 (CH4) Event 4 (CH4) 07 Event 1 (CH1) Event 1 (CH2) Event 1 (CH3) Event 1 (CH4) 08 Event 2 (CH1) Event 2 (CH2) Event 2 (CH3) Event 2 (CH4) 09 Event 3 (CH1) Event 3 (CH2) Event 3 (CH3) Event 3 (CH4) 10 Event 4 (CH1) Event 4 (CH2) Event 4 (CH3) Event 4 (CH4) 11 HBA (CH1) of Z-TIO module HBA (CH2) of Z-TIO module HBA (CH3) of Z-TIO module HBA (CH4) of Z-TIO module 12 Burnout status (CH1) Burnout status (CH2) Burnout status (CH3) Burnout status (CH4) 13 Temperature rise completion 5 HBA comprehensive output 6 Burnout state comprehensive output 7 DO4 manual output
1
Logical OR of Event 1 (ch1 to ch4)
2
Logical OR of Event 2 (ch1 to ch4)
3
Logical OR of Event 3 (ch1 to ch4)
4
Logical OR of Event 4 (ch1 to ch4)
5
Temperature rise completion status (ON when temperature rise completion occurs for all channels for which event 3 is set to temperature rise completion.)
6
The following signals are output depending on the setting of the DO signal assignment module address.
Logical OR of HBA (ch1 to ch4) of Z-TIO module Logical OR of HBA (ch1 to ch12) of Z-CT module Logical OR of HBA (ch1 to ch4) of Z-TIO module and HBA (ch1 to ch12) of Z-CT module
7
Logical OR of burnout state (ch1 to ch4)
[DO5 to DO8]
Code DO5 DO6 DO7 DO8
00 No assignment 01
02 Event 1 comprehensive output 1 Event 2 comprehensive output 2 Event 3 comprehensive output 3 Event 4 comprehensive output 4 03 Event 1 (CH1) Event 2 (CH1) Event 3 (CH1) Event 4 (CH1) 04 Event 1 (CH2) Event 2 (CH2) Event 3 (CH2) Event 4 (CH2) 05 Event 1 (CH3) Event 2 (CH3) Event 3 (CH3) Event 4 (CH3) 06 Event 1 (CH4) Event 2 (CH4) Event 3 (CH4) Event 4 (CH4) 07 Event 1 (CH1) Event 1 (CH2) Event 1 (CH3) Event 1 (CH4) 08 Event 2 (CH1) Event 2 (CH2) Event 2 (CH3) Event 2 (CH4) 09 Event 3 (CH1) Event 3 (CH2) Event 3 (CH3) Event 3 (CH4) 10 Event 4 (CH1) Event 4 (CH2) Event 4 (CH3) Event 4 (CH4) 11 HBA (CH1) of Z-TIO module HBA (CH2) of Z-TIO module HBA (CH3) of Z-TIO module HBA (CH4) of Z-TIO module 12 Burnout status (CH1) Burnout status (CH2) Burnout status (CH3) Burnout status (CH4) 13 Temperature rise completion 5 HBA comprehensive output 6 Burnout state comprehensive output 7 DO8 manual output
1
Logical OR of Event 1 (ch1 to ch4)
2
Logical OR of Event 2 (ch1 to ch4)
3
Logical OR of Event 3 (ch1 to ch4)
4
Logical OR of Event 4 (ch1 to ch4)
5
Temperature rise completion status (ON when temperature rise completion occurs for all channels for which event 3 is set to temperature rise completion.)
6
The following signals are output depending on the setting of the DO signal assignment module address.
Logical OR of HBA (ch1 to ch4) of Z-TIO module Logical OR of HBA (ch1 to ch12) of Z-CT module Logical OR of HBA (ch1 to ch4) of Z-TIO module and HBA (ch1 to ch12) of Z-CT module
7
Logical OR of burnout state (ch1 to ch4)
DO1 manual output DO2 manual output DO3 manual output DO4 manual output
DO5 manual output DO6 manual output DO7 manual output DO8 manual output
For details of the Z-CT module, refer to Z-CT Instruction Manual (IMS01T21-E).
1-8
IMS01T04-E6
Page 17

1.4 Parts Description

1.4.1 Z-TIO module

Module mainframe
<Terminal type>
FAIL/ UNR RX/TX
C
D
B
LOADER
TIO
E
A
F
9
0
8
1
7
2
6
3
4
5
CT4 CT3
Loader communication
connector
CT1 CT2
Indication lamps
Address setting
CT Input connector
Input/Output terminals
switch
(Optional)
TIO
RX/TX
RNU/LIAF
C
D
B
E
A
F
9
0
8
1
7
2
6
3
5
4
CT1 CT2
Input select switch* (for CH3)
Input select switch* (for CH4)
(Z-TIO-AT: 4-channel type)
* The 2-channel type does not have neither an input select switch (for CH3) and nor an input select switch (for CH4).
<Connector type>
FAIL/ UNR RX/TX
C
D
B
E
A
LOADER
F
9
0
8
1
7
2
6
3
4
5
TIO
CT1 CT2
CN1
CT4 CT3
CN3
CN4
CN2
Loader communication
connector
Indication lamps
Address setting
switch
CT Input connector
(Optional)
Input/Output connector
(Z-TIO-BT: 2-channel type)
RNU/LIAF
RX/TX
C
D
B
E
A
LOADER
F
9
0
8
1
7
2
6
3
5
4
CT1
TIO
CT2
CN3
CN4
CN1
CN2
(Left side)
Input select switch (for CH3)
Input select switch ** (for CH4)
**
(Z-TIO-BC: 2-channel type)(Z-TIO-AC: 4-channel type)
** The 2-channel type does not have neither an input select switch (for CH3) and nor an input select switch (for CH4).
Indication lamps
FAIL/RUN [Green or Red] When normal (RUN): A green lamp is on Self-diagnostic error (FAIL): A green lamp flashes Instrument abnormality (FAIL): A red la mp i s on RX/TX [Green] During data send and receive: A green lamp turns on
Switches
Address setting switch Sets the Z-TIO module address.
(Refer to P. 5-2.)
DIP switch Sets the communication speed, data bit configuration, and communication
protocol. (Refer to P. 5-3.)
Input select switch Selector switch for the measured input type.
(Refer to P. 8-70.)
(Right side) (Left side)
(Right side)
1. OUTLINE
DIP switch
Input select switch (for CH1)
Input select switch (for CH2)
DIP switch
Input select switch (for CH1)
Input select switch (for CH2)
IMS01T04-E6 1-9
Page 18
1. OUTLINE
f
Base
Mounting holes (M3 screw) Holes for screws to fix the base to
a panel, etc. Customer must provide the M3 screws.
Mounting bracket Used to fix the module on DIN rails and
also to fix each module joined together.
(Right side)
(Z-TIO-A: Terminal type)
Base
(Right side)
Base
(Z-TIO-A: Connector type)
(Base: Front)
Joint connector Used to mechanically and electrically connect
each module.
Power supply terminals Supply power to only one of the joined
modules, and all of the joined modules will receive power. (Refer to 4.1 Wiring Cautions)
Communication terminals (RS-485) Connect communication wires to only one o
the joined modules, and all of the joined modules will communicate.
(Base: Rear)
1-10
IMS01T04-E6
Page 19
A
A

1.4.2 Z-DIO module

Module mainframe
<Terminal type>
Loader communication connector
Digital input terminals
<Connector type>
Loader communication connector
Digital input connector
IN OUT
IN OUT
CN3
CN4
LOADER
DIO
LOADER
DIO
FAIL/ UNR RX/TX
FAIL/ UNR RX/TX
1. OUTLINE
(Right side)
D
E
F
0
1
2
3
4
D
E
F
0
1
2
3
4
CN1
CN2
Indication lamps
ddress setting switch
Digital output terminals
Indication lamps
ddress setting switch
Digital output connector
DIP switch
Base
(Right side)
DIP switch
Base
C
B
A
9
8
7
6
5
C
B
A
9
8
7
6
5
Indication lamps
FAIL/RUN [Green or Red] When normal (RUN): A green lamp is on Self-diagnostic error (FAIL): A green lamp flashes Instrument abnormality (FAIL): A red la mp i s on RX/TX [Green] During data send and receive: A green lamp turns on
Switches
Address setting switch Sets the Z-DIO module address.
(Refer to P. 5-2.)
DIP switch Sets the communication speed, data bit configuration, and communication
protocol. (Refer to P. 5-3.)
Terminal configurations of the base are the same as the base of Z-TIO module. (Refer to P. 1-10)
IMS01T04-E6
1-11
Page 20
MEMO
1-12
IMS01T04-E6
Page 21
SETTING
PROCEDURE TO
OPERATION
1.1 ******** .............................................................................................. 1-2
1.2 ******* ................................................................................................ 1-3
1.3 ****** ................................................................................................. 1-4
1.4 *********** .......................................................................................... 1-5
1.4.1 ***** ........................................................................................................... 1-6
1.4.2 ******** ....................................................................................................... 1-7
IMS01T04-E6 2-1
Page 22
2. SETTING PROCEDURE TO OPERATION
Conduct necessary setting before operation according to the procedure described below.
Processing of
the host computer side
Processing of the SRZ side
Preparation of
communication program
Execute it after turning on a power supply of the host computer.
Setting of
communication relation
Set the host computer and SRZ in always the same value.
Communication speed setting
Data bit configuration
Communication protocol selection
Setting of
communication relation
Communication speed setting
Data bit configuration
Communication protocol selection
Communication port setting
Module address setting
Communication line connection
Execute it after turning off a power supply of the host computer.
Refer to 4. WIRING (P. 4-1).
Power-OFF
Power-ON
Turn on the power of the host computer and SRZ.
Communication program start
Engineering setting data
Setting of
Before setting operation data items, always set initial setting data items so as to satisfy the specification used.
Set the Input scale high/low, Input range decimal point position, Control type, Event type etc.
For engineering setting data items, refer to following pages.
 Z-TIO module: 8.2.2 Engineering setting data items (P. 8-61)  Z-DIO module: 8.3.2 Engineering setting data items (P. 8-153)
A
Execute it after turning off a power supply of the SRZ unit.
Refer to 5.2 Protocol Selections and Communication Speed Setting (P. 5-3).
Refer to 5.1 Module Address Setting (P. 5-2).
2-2 IMS01T04-E6
Page 23
2. SETTING PROCEDURE TO OPERATION
A
Control action type?
Position proportioning PID control
PID control or Heat/Cool PID control
Adjustment of the valve positio n
For details, refer to P. 8-118.
Setting of
Normal setting data
Set parameters in Normal setting of data.
For normal setting data items, refer to following pages.
Z-TIO module: 8.2.1 Normal setting data items (P. 8-3) Z-DIO module: 8.3.1 Normal setting data items (P. 8-143)
Control RUN
Set the control RUN/STOP transfer to the “RUN.”
Operation start
IMS01T04-E6
2-3
Page 24
MEMO
2-4 IMS01T04-E6
Page 25

MOUNTING

3.1 Mounting Cautions ........................................................................... 3-2
3.2 Dimensions ....................................................................................... 3-4
3.3 Important Points When Joining Modules .......................................... 3-5
3.4 DIN Rail Mounting and Removing .................................................... 3-6
3.5 Panel Mounting ................................................................................ 3-8
IMS01T04-E6 3-1
Page 26
3. MOUNTING

3.1 Mounting Cautions

This chapter describes installation environment, mounting cautions, dimensions and mounting procedures.
To prevent electric shock or instrument failure, always turn off the power before mounting or removing the instrument.
(1) This instrument is intended to be used under the following environmental conditions.
(IEC 61010-1) [OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following environment conditions:
Allowable ambient temperature: 10 to 50 C Allowable ambient humidity: 5 to 95 %RH
(Absolute humidity: MAX.W.C 29.3 g/m
Installation environment conditio ns: Indoor use
Altitude up to 2000 m
WARNING
!
3
dry air at 101.3 kPa)
(3) Avoid the following conditions when selecting the mounting location:
Rapid changes in ambient temperature which may cause condensation. Corrosive or inflammable gases. Direct vibration or shock to the mainframe. Water, oil, chemicals, vapor or steam splashes. Excessive dust, salt or iron particles. Excessive induction noise, static electricity, magnetic fields or noise. Direct air flow from an air conditioner. Exposure to direct sunlight. Excessive heat accumulation.
(4) Mount this instrument in the panel considering the following conditions:
Provide adequate ventilation space so that heat does not build up. Do not mount this instrument directly above equipment that generates large amount of heat (heaters,
transformers, semi-conductor functional devices, large-wattage resistors).
If the ambient temperature rises above 50 C, cool this instrument with a forced air fan, cooler, etc.
Cooled air should not blow directly on this instrument.
In order to improve safety and the immunity to withstand noise, mount this instrument as far away as
possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel. Power lines: Separate at least 200 mm Rotating machinery: Separate as far as possible
Space required between each module vertically
When the module is mounted on the panel, allow a minimum of 50 mm at the top and bottom of the module to attach the module to the mainframe.
50 mm or more
3-2 IMS01T04-E6
Page 27
3. MOUNTING
Depth for connector mount type module (Connector type)
Space for connectors and cables must be considered when installing.
76.9 mm Approx. 50 mm
Connector
(Plug)
Mounting the joint connector cover
It is recommended to use a plastic cover on the connector on both sides of the mounted modules for protection of connectors.
Joint connector cover
Joint connector cover (Standard equipment)
Parts code Ordering code Q’ty
KSRZ-517A 00433384 2
Installing direction of SRZ unit
Mount the SRZ unit in the direction specified as shown below.
Top
Bottom
(5) If this instrument is permanently connected to equipment, it is important to include a switch or
circuit-breaker into the installation. This should be in close proximity to the equipment and within easy reach of the operator. It should be marked as the disconnecting device for the equipment.
IMS01T04-E6
3-3
Page 28
3. MOUNTING

3.2 Dimensions

Terminal type module
100
5
Connector type module
100
5
Connector type (sold separately): SRZP-01 [Front-screw type]
99
76.9 2.9
30 6.7
Z-TIO-AC: 4-channel type
30 6.7
Z-TIO-AT: 4-channel type
100
5
Z-TIO-BC: 2-channel type
76.9
Connector type (sold separately): SRZP-02 [Side-screw type]
30 6.7
30 6.785
Z-TIO-BT: 2-channel type
89.7
(Unit: mm)
(Unit: mm)
2.9
3-4 IMS01T04-E6
Page 29
3. MOUNTING
3.3

Important Points When Joining Modules

When joining the Z-TIO and Z-DIO modules, note the following:
The maximum number of joined T-TIO-A/B modules that can be connected to one host computer is 16.
Example 1: When joining only Z-TIO-A modules
(Up to 16 modules)
SRZ unit
Example 2: When joining only Z-TIO-B modules
(Up to 16 modules)
SRZ unit
Up to 16 Z-DIO modules can be connected.
Z-DIO modules are used in combination with Z-TIO modules.
When Joining Z-TIO-A and Z-DIO modules
15 Z-TIO-A modules 16 Z-DIO modules
16 Z-TIO-A modules 15 Z-DIO modules
SRZ unit
Example 3: When joining Z-TIO-A and Z-TIO-B modules
(Combination of 16 modules or less)
SRZ unit
The maximum number of SRZ modules (including other function modules) on the same communication line is 31. Therefore, when 16 Z-TIO modules are connected, up to 15 Z-DIO modules can be connected.
SRZ unit
Z-TIO-A/B modules can also be combined with Z-TIO-C/D modules set for “host communication.”
[However, the total number of joined Z-TIO modules must not exceed the maximum (16).]
Host computer
Z-TIO-A or Z-TIO-B modules
(10 modules)
SRZ unit
Z-TIO-C or Z-TIO-D modules*
(6 modules)
*
Temperature control module
(for PLC communication)
Refer to the following manuals for connecting other modules.
Z-TIO-C/D: Temperature Control Module [for PLC Communication] Z-TIO Instruction Manual (IMS01T10-E) Z-TIO-E/F: Temperature Control Module [for PLC Communicat ion] Z-TIO-E/Z-TIO-F Installation Manual (IMS01T17- E).
 Z-CT: Current Transformer Input Module Z-CT Instruction Manual (IMS01T16-E).  Z-COM: Communication Extension Module Z-COM Installation Manual (IMS01T05- E).
IMS01T04-E6 3-5
Page 30
3. MOUNTING
r

3.4 DIN Rail Mounting and Removing

Mounting procedures
1. Pull down the mounting bracket at the bottom of the module (A). Attach the hooks on the top of the
module to the DIN rail and push the lower section into place on the DIN rail (B).
2. Slide the mounting bracket up to secure the module to the DIN rail (C).
DIN rail
Mounting
bracket
(A) Pull down
(B) Push
(C) Locked
3. Mount the modules on the DIN rail. Slide the modules until the modules are closely joined together
and the joint connectors are securely connected.
Front view of module mainframe
(
Joint connecto
)
4. Push in the mounting brackets to lock the modules together and fix to the DIN rail.
Rear view of base
(
)
State where each module is locked.
Mounting bracket
Push in all of the mounting brackets.
3-6 IMS01T04-E6
Page 31
r
5. Connect the required number of function modules.
3. MOUNTING
6. Install a
connectors.
plastic cover on the connector on both sides of the mounted modules for protection of
Joint connector cove
To firmly fix the modules, use end plates on both sides of the mounted modules.
End plate
(sold separately)
*
End plate
(sold separately)
End plate
Parts code Ordering code Q’ty
DEP-01 00434944 2
Removal procedures
1. Pull down a mounting bracket with a slotted screwdriver (A).
2. Lift the module from bottom, and take it off (B).
IMS01T04-E6
(A) Pull down
(B) Lift and take off
3-7
Page 32
3. MOUNTING

3.5 Panel Mounting

Mounting procedures
1. Refer to the mounting dimensions below when selecting the location.
0.2
100
70
(30)
38
300.2
M3
Recommended screw: M3  10
Recommended tightening torque:
0.3 N・m (3 kgf・cm)
Base
Mounting dimensions
(Unit: mm)
2. Remove the base from the module (B) while the lock is pressed (A). (Fig. 1)
Lock
(B)
(A)
(Bottom of the module mainframe)
Fig. 1: Removing the base
3. Join bases. Then, lock them by pushing in the mounting brack ets.
Refer to the 3.4 DIN Rail Mounting and Removing (P. 3-6).
4. Fix the base to its mounting position using M3 screws. Customer must provide the screws.
5. Mount the module on the base. (Fig. 2)
(Top of the module mainframe)
(Base)
Fig. 2: Mounting the module mainframe
3-8 IMS01T04-E6
Page 33

WIRING

4.1 Wiring Cautions ................................................................................ 4-2
4.2 Connecting Precautions ................................................................... 4-4
4.3 Terminal Configuration ..................................................................... 4-5
4.3.1 Z-TIO module ............................................................................................ 4-5
4.3.2 Z-DIO module .......................................................................................... 4-10
4.4 Connection to Host Computer ........................................................ 4-12
4.5 Installation of Termination Resistor ................................................ 4-17
4.6 Connections for Loader Communication ........................................ 4-19
IMS01T04-E6 4-1
Page 34
4. WIRING

4.1 Wiring Cautions

This chapter describes wiring cautions, wiring layout and wiring of terminals.
To prevent electric shock or instrument failure, do not turn on the power until all wiring is completed. Make sure that the wiring is correct before applying power to the instrument.
WARNING
!
For thermocouple input, use the appropriate compensation wire. For RTD input, use low resistance lead wire with no difference in resistance between the three lead wires
(3-wire system).
Signal connected to Voltage input and Current input shall be low voltage defined as “SELV” circuit per
IEC 60950-1.
To avoid noise induction, keep input/output signal wires away from instrument power line, load lines and
power lines of other electric equipment.
If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.
Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise
reduction.
Always install the noise filter on a grounded panel. Minimize the wiring distance between the noise
filter output and the instrument power supply terminals to achieve the most effective noise reduction.
Do not connect fuses or switches to the noise filter output wiring as this will reduce the effectiveness
of the noise filter.
Allow approximately 8 seconds for contact output when the instrument is turned on. Use a delay relay
when the output line is used for an external interlock circuit.
Power supply wiring must be twisted and have a low voltage drop. For an instrument with 24 V power supply input, supply power from a “SELV” circuit defined as IEC
60950-1.
A suitable power supply should be considered in end-use equipment. The power supply must be in
compliance with a limited-energy circuits (maximum available current of 8 A).
Supply the power to only one of the joined modules. When power is supplied to any one of the joined
modules, all of the joined modules will receive power.
Select the power capacity which is appropriate for the total power consumption of all joined modules and
the initial current surge when the power is turned on.
Power consumption (at maximum load): 140 mA max. (at 24 V DC) [Z-TIO module (4CH type)] 80 mA max. (at 24 V DC) [Z-TIO module (2CH type)] 70 mA max. (at 24 V DC) [Z-DIO module] Rush current: 10 A or less
For the terminal type module, use t he specif ied solder less term inals . Only these specified solderless terminals
can be used due to the insulation between the terminals.
Screw Size: M3 7 (with 5.8 5.8 square washer) Recommended tightening torque:
5.5 MAX
3.2 MIN
0.4 Nm (4 kgf・cm)
2
Applicable wire: Solid/Twisted wire of 0.25 to 1.65 mm Specified solderless terminals: Manufactured by J.S.T MFG CO., LTD. Circular terminal with isolation V1.25MS3
5.6 mm
9.0 mm
(M3 screw, width 5.5 mm, hole diameter 3.2 mm)
Make sure that during field wiring parts of conductors cannot come into contact with adjacent conductive
parts.
3.2
4-2 IMS01T04-E6
Page 35
When tightening a screw of the instrument, make sure to fit the screwdriver properly into the screw head mounted tilted or flat as shown in the right figure. Tightening the screw with excessive torque may damage the screw thread.
Tilted terminal
For the connector type modu le, use t he followi ng our conn ector (plu g) [sold separately].
Connector type: SRZP-01 (Front-screw type) SRZP-02 (Side-screw type) Screw size: M2.5 Recommended tightening torque:
0.43 to 0.50 Nm (4.3 to 5.0 kgf・cm) Used cable specifications: Lead wire type: Solid (AWG 28 [cross-section: 0.081 mm Twisted wire (AWG 30 [cross-section: 0.051 mm
2
] to 12 [cross-section: 3.309 mm2]) or
2
] to 12 [cross-section: 3.309 mm2])
Stripping length: 9 to 10 mm (SRZP-01), 7 to 8 mm (SRZP-02)
9 to 10 mm
7 to 8 mm
For isolated device input/output blocks, refer to the following:
(SRZP-01)
(SRZP-02)
: Isolated : Not isolated
Z-TIO module
Power supply Output 1 (OUT1)
1, 2
4. WIRING
Flat terminal
Measured input (CH1) Measured input (CH2) Measured input (CH3) Measured input (CH4)
Output 2 (OUT2)
Output 3 (OUT3)
Communication Output 4 (OUT4)
1
When all outputs are continuous output (current output, voltage output) or voltage pulse output, there is no
need for isolation between outputs. There is also no need for isolation between each output and the power supply, and no need for isolation between each output and communication.
2
When the output type is relay contact output or triac output, isolation is required between this output and
other blocks (power supply, communication, and output).
Z-DIO module
Power supply
Digital output 1 (DO1)
1, 2
1, 2
1, 2
Digital input 1 (DI1) Digital output 2 (DO2) Digital input 2 (DI2) Digital output 3 (DO3) Digital input 3 (DI3) Digital output 4 (DO4) Digital input 4 (DI4)
Digital input 5 (DI5) Digital input 6 (DI6) Digital output 5 (DO5) Digital input 7 (DI7) Digital output 6 (DO6) Digital input 8 (DI8) Digital output 7 (DO7)
Communication
Digital output 8 (DO8)
IMS01T04-E6
4-3
Page 36
4. WIRING

4.2 Connecting Precautions

To prevent electric shock or instrument failure, turn off the power before connecting or disconnecting the instrument and peripheral equipment.
Connect connectors correctly in the right position. If it is forcibly pushed in with pins in the wrong
positions, the pins may be bent resulting in instrument failure.
When connecting or disconnecting the connectors, do not force it too far to right and left or up and down,
but move it on the straight. Otherwise, the connector pins may be bent, causing instrument failure.
When disconnecting a connector, hold it by the connector itself. Disconnecting connectors by yanking on
their cables can cause breakdowns.
WARNING
!
To prevent malfunction, never touch the contact section of a connector with bare hands or with hands
soiled with oil or the like.
To prevent damage to cables, do not bend cables over with excessive force.
4-4 IMS01T04-E6
Page 37
p
p
IN

4.3 Terminal Configuration

4.3.1 Z-TIO module

Input/Output terminals
<Terminal type module>
4. WIRING
Z-TIO-AT
4-channel type
CH1
CH2
Z-TIO-BT
2-channel type
<Common to both 2-channel/4-channel types>
13 14 15
18 19 20
11 12
16 17
Relay contact
output
OUT1
NO
Thermocouple
input
TC
Relay contact
output
OUT2
NO
Thermocouple
input
TC
Open collector
output
OUT1
11 12
Open collector
output
OUT2
16 17
Feedback
resistance input
O
18
W
19
C
20
Triac output
OUT1
Triac
11 12
input
14
IN
15
Triac output
OUT2
Triac
16 17
Voltage/Current
input
19 20
Voltage pulse/
Current/Voltage
output
OUT1
 
RTD input Voltage/Current
A
RTD
B B
Voltage pulse/
Current/Voltage
out
ut
OUT2
 
RTD input
A
RTD
B B
11 12
CH1
14 15
16 17
CH2
19 20
CAUTION
CH3
CH4
Flat terminal
Voltage/Current
input
21
IN
22
Open collector
output
OUT3
24 25
Feedback
resistance input
C
26
W
27
O
28
Open collector
output
OUT4
29 30
Tilted terminal
<4-channel type only>
21 22 23
24 25
26 27
29 30
Thermocouple
input
21
TC
22
Voltage pulse/
Current/Voltage
output
OUT3
24 25
RTD input
B
26
B
27
RTD
A
28
Voltage pulse/
Current/Voltage
output
OUT4
29 30
RTD input
B B
RTD
A
Triac output
OUT3
Triac
Voltage/Current
in
ut
IN
Triac output
OUT4
Triac
Relay contact
output
OUT3
NO
24 25
Thermocouple
input
26
TC
27
Relay contact
output
OUT4
29
NO
30
Z-TIO-AT
4-channel type
IMS01T04-E6 4-5
Page 38
4. WIRING
p
p
IN
IN
<Connecter type module>
Z-TIO-AC
4-channel type
CH1
CH2
Z-TIO-BC
2-channel type
<Common to both 2-channel/4-channel types>
5 4
3 2 1
5 4
3 2 1
Relay contact
output
OUT1
NO
Thermocouple
input
TC
Relay contact
output
OUT2
NO
Thermocouple
input
TC
Open collector
output
OUT1
5 4
Open collector
output
OUT2
5 4
Feedback
resistance input
O
3
W
2
C
1
Triac output
OUT1
Triac
Voltage/Current
5 4
input
2 1
Triac output
OUT2
Triac
5 4
input
2 1
Voltage pulse/
Current/Voltage
output
OUT1
 
RTD input
A
RTD
B B
Voltage pulse/
Current/Voltage
output
OUT2
 
RTD input Voltage/Current
A
RTD
B B
5 4
CH1
2 1
5 4
CH2
2 1
<4-channel type only>
1 2
3
4 5
1 2
4 5
Thermocouple
input
1
TC
2
Voltage pulse/
Current/Voltage
out
ut
OUT3
4 5
RTD input
B
1
B
2
RTD
A
3
Voltage pulse/
Current/Voltage
ut
out
OUT4
4 5
Relay contact
output
OUT3
NO
4 5
Thermocouple
input
1
TC
2
Relay contact
output
OUT4
NO
4 5
CH3
CH4
Voltage/Current
input
1
IN
2
Open collector
output
OUT3
4 5
Feedback
resistance input
C
1
W
2
O
3
Open collector
output
OUT4
4 5
RTD input
B B
RTD
A
Triac output
OUT3
Triac
Voltage/Current
input
IN
Triac output
OUT4
Triac
Z-TIO-AC
4-channel type
4-6
IMS01T04-E6
Page 39
Input/output configurations by control specifications
2-channel
type
module
4-channel
type
module
Control type
PID control
Heat/Cool PID control
Position proportioning
PID control
PID control
Heat/Cool PID control
Position proportioning
PID control
PID control
Heat/Cool PID control
PID control
Position proportioning
PID control
Heat/Cool PID control
PID control
Heat/Cool PID control
Position proportioning
PID control
Position proportioning
PID control
PID control
Position proportioning
PID control
Heat/Cool PID control
CH1 output
terminal
(OUT1)
Control output
(CH1)
Heat-side
output (CH1)
Open-side
output (CH1)
Control output
(CH1)
Heat-side
output (CH1)
Open-side
output (CH1)
Control output
(CH1)
Control output
(CH1)
Heat-side
output (CH1)
Heat-side
output (CH1)
Open-side
output (CH1)
Open-side
output (CH1)
CH2 output
terminal
(OUT2)
Control output
(CH2)
Cool-side
output (CH1)
Cool-side
output (CH1)
Control output
(CH2)
Cool-side
output (CH1)
Cool-side
output (CH1)
Control output
(CH2)
Control output
(CH2)
Cool-side
output (CH1)
Cool-side
output (CH1)
Cool-side
output (CH1)
Cool-side
output (CH1)
CH3 output
terminal
(OUT3)
Control output
(CH3)
Heat-side
output (CH3)
Open-side
output (CH3)
Heat-side
output (CH3)
Open-side
output (CH3)
Control output
(CH3)
Open-side
output (CH3)
Control output
(CH3)
Heat-side
output (CH3)
CH4 output
terminal
(OUT4)
Control output
Cool-side
Cool-side
Cool-side
Cool-side
Control output
Cool-side
Control output
Cool-side
* Only the Measured value (PV) monitor and event action are possible.
“CH” numbers in parentheses indicate the control channel number of the module.
CH3 input terminals (Input3)
CH3 output terminals (OUT3)
CH4 input terminals (Input4)
CH4 output terminals (OUT4)
CH1 output terminals (OUT1)
CH1 input terminals (Input1)
CH2 output terminals (OUT2)
CH2 input terminals (Input2)
CH3 input terminals (Input3)
CH3 output terminals (OUT3)
CH4 input terminals (Input4)
CH4 output terminals (OUT4)
(CH4)
output (CH3)
output (CH3)
output (CH3)
output (CH3)
(CH4)
output (CH3)
(CH4)
output (CH3)
CH1 input
terminal (Input1)
Sensor input
(CH1)
Sensor input
(CH1)
Sensor input
(CH1)
Sensor input
(CH1)
Sensor input
(CH1)
Sensor input
(CH1)
Sensor input
(CH1)
Sensor input
(CH1)
Sensor input
(CH1)
Sensor input
(CH1)
Sensor input
(CH1)
Sensor input
(CH1)
CH2 input
terminal
(Input2)
Sensor input
(CH2)
FBR input
(CH1)
Sensor input
(CH2)
FBR input
(CH1)
Sensor input
(CH2)
Sensor input
(CH2)
FBR input
(CH1)
FBR input
(CH1)
4. WIRING
CH3 input
terminal (Input3)
Sensor input
(CH3)
Sensor input
(CH2)
Sensor input
(CH3)
Sensor input
(CH3)
Sensor input
(CH3)
Sensor input
(CH3)
Sensor input
(CH3)
Sensor input
(CH3)
Sensor input
(CH3)
CH1 output terminals (OUT1)
CH1 input terminals (Input1)
CH2 output terminals (OUT2)
CH2 input terminals (Input2)
CH4 input
terminal (Input4)
Sensor input
(CH4)
FBR input
(CH3)
FBR input
(CH3)
Sensor input
(CH4)
FBR input
(CH3)
Sensor input
(CH4)
IMS01T04-E6
4-7
Page 40
4. WIRING
Power supply terminals, Communication terminals
(Common to both terminal and connector type module)
2 1
3 4 5
Power supply terminals
Description
1 2
24 V DC () 24 V DC ()
Communication terminals (RS-485)
Terminal No.
3 4 5
Description
T/R (A) T/R (B)
SG
Connecting to the base terminals
As an example, the method of connecting to the power terminals (terminal numbers 1 and 2) is shown below.
1. Remove the module mainframe to which the power wiring will be connected.
Remove the mainframe.
Module mainframe
2. Attach the solderless terminals to the power terminals with a Phillips head screwdriver.
(Base)
2 1
3 4 5
3. Return the module mainframe to the base. This completes the wiring work.
Power supply terminals
1 2
DC
+
24 V
Solderless terminals
12
()
()
!
Prior to conducting the wiring, always turn OFF the power.
Return the module mainframe to the base.
Connections to the communication terminals (terminal numbers 3 to 5) are made in the same way.
4-8
IMS01T04-E6
Page 41
CT input connector (Optional)
Pin No. Description
1 2 3 4
CT4 (CH4)
CT3 (CH3)
For the CT input, use the following our CT cable (with socket) and current transformer (CT). [sold separately]
Cable type: W-BW-03- (: Standard cable length [unit: mm]) 1000: 1m, 2000: 2 m, 3000: 3 m
Current transformer (CT): CTL-6-P-N (0.0 to 30.0 A) or CTL-12-S56-10L-N (0.0 to 100.0 A)
2 1
4 3
[Solderless terminal] Blue: CT1 (Pin No. 3, 4), CT3 (Pin No. 3, 4) Yellow: CT2 (Pin No. 1, 2), CT4 (Pin No. 1, 2)
4. WIRING
Pin No. Description
34
12
1 2 3 4
CT2 (CH2)
CT1 (CH1)
IMS01T04-E6
4-9
Page 42
4. WIRING

t

4.3.2 Z-DIO module

Digital input (DI1 to DI8)
<Terminal type module> <Connecter type module>
Voltage
*
contact inpu
DI4 DI3 DI2
DI1
COM
DI8 DI7 DI6
DI5
COM
21 22 23 24 25
26 27 28 29 30
CAUTION
Voltage contact input
Flat terminal
*
24 V DC
Tilted terminal
An external power supply of 24 V DC is required for the voltage contact input.
COM
Voltage
contact input
CN3
Pin No. Description
1 DI4 2 DI3 3 DI2 4 DI1 5 COM
CN4
Pin No. Description
1 DI8 2 DI7 3 DI6 4 DI5 5 COM
*
DI1
DI4
COM
DI5
DI8
Circuit configuration of digital input
4-10
IMS01T04-E6
Page 43
p
put
Digital output (DO1 to DO8)
<Terminal type module> <Connecter type module>
CAUTION
Relay contact output
DO1
Load
Relay
contact out
COM
NO
DO1
NO
DO2
NO
DO3
NO
DO4
COM
NO
DO5
NO
DO6
NO
DO7
NO
DO8
Flat terminal
* An external power supply of 12 to 24 V DC is required for the open collector output.
Open collector
ut
11 12 13 14 15
16 17 18 19 20
out
COM
DO1 DO2 DO3 DO4
COM
DO5 DO6 DO7 DO8
Tilted terminal
*
11 12 13 14 15
16 17 18 19 20
Open collector output
DO1
Relay contact output/ Open collector output
CN1
Pin No. Description
5 COM 4 DO1 3 DO2 2 DO3 1 DO4
CN2
Pin No. Description
5 COM 4 DO5 3 DO6 2 DO7 1 DO8
Load
4. WIRING
*
DO4
DO5
DO8
Load
Load
Load
COM
COM
DO4
DO5
DO8
12 to 24 V DC
Load
COM
Load
Load
COM
Circuit configuration of digital output
Power supply terminals, Communication terminals
(Common to both terminal and connector type module)
Terminal configurations of the base are the same as the base of Z-TIO module. (Refer to P. 4-8)
IMS01T04-E6
4-11
Page 44
4. WIRING
)

4.4 Connection to Host Computer

To prevent electric shock or instrument failure, turn off the power before connecting or disconnecting the instrument and peripheral equipment.
WARNING
!
Configurations that can be connected to a host computer
Examples of configurations of SRZ units that can be connected to a host computer are shown below.
“SRZ unit” refers to a unit consisting of only Z-TIO modules, or a unit in which Z-TIO modules are connected to several other function modules (Z-DIO, Z-CT and Z-COM).
When two or more Z-TIO module are connected
Host
computer
(master)
Module address (Slave address)
RS-485
0
SRZ unit (slave
1 152
Z-TIO module
Internal communication line
(RS-485)
Termination resistor
Power supply (24 V DC)
Up to 16 Z-TIO modules can be connected.
When two or more Z-DIO module are connected to Z-TIO modules
Host
computer
(master)
Module address (Slave address)
RS-485
0 1
Z-TIO module Z-DIO module
Internal communication line (RS-485)
Power supply (24 V DC)
SRZ unit (slave)
15 3016 17
Up to 16 Z-DIO modules can be connected. The maximum number of SRZ modules (Z-TIO, Z-CT and Z-COM) on the same communication line is 31.
Function modules (Z-TIO, Z-DIO, Z-CT and Z-COM) connected inside the same unit can be placed in any position.
For the procedure for connecting modules, refer to 3. WIRING (P. 3-1). For the module address settings, refer to 5. SETTINGS BEFORE OPERATION (P. 5-1).
Termination resistor
4-12 IMS01T04-E6
Page 45
When two or more SRZ units are connected (distributed arrangement)
Module address (Slave address)
0
1 2 3 4 5
Z-TIO module Z-DIO module
Internal communication line (RS-485)
SRZ unit (slave)
computer
(master)
Host
RS-485
Power supply (24 V DC)
Module address (Slave address)
6
7 8 9 10 11
Z-TIO module Z-DIO module
Internal communication line (RS-485)
SRZ unit (slave)
RS-485
Power supply (24 V DC)
Module address (Slave address)
12 13 14
SRZ unit (salve)
Z-TIO module
Internal communication line
(RS-485)
RS-485
Power supply (24 V DC)
Regardless of the number of units, a maximum of 16 SRZ Z-TIO modules and a maximum of 16 SRZ Z-DIO modules can be connected respectively. However, the maximum number of SRZ modules that can be connected overall, including other function modules (Z-DIO, Z-CT and Z-COM), is 31.
16 17 18
19 20 21
15 22 23
Z-DIO module
4. WIRING
Termination resistor
IMS01T04-E6
Function modules (Z-TIO, Z-DIO, Z-CT and Z-COM) connected inside the same unit can be placed in any position.
4-13
Page 46
4. WIRING
t
Terminal number and signal details
(Base)
3 4 5
Terminal No. Signal name Symbol
3 Send data/Receive data T/R (A) 4 Send data/Receive data T/R (B) 5 Signal ground SG
Wiring figure
Connection to the RS-485 port of the host computer (master)
()
()
()
()
SRZ unit
  
Z-TIO module
(Slave)
SG
(Slave)
SG
3 4 T/R (B)
5
3 4 5
T/R (A)
Z-TIO module
T/R (A) T/R (B)
RS-485
Shielded twisted
Connec
ed by the internal communication line
R: Termination resistor (Example: 120  1/2 W )
R
If communication errors occur frequently due to the operation environment or the communication distance, connect termination resistors.
Pair wire
pair wire
Host computer (Master)
R
T/ R ( A) T/ R ( B) SG
()
()
Up to 16 Z-TIO modules can be connected.
The maximum number of SRZ modules (Z-DIO, Z-CT and Z-COM) on the same communication line is 31.
The maximum number of SRZ modules (including other function modules) on the same communication line is 31.
The cable and termination resistors must be provided by the customer. The above figure shows an example of connecting of Z-TIO modules. However, this figure is
also used even when the Z-DIO module is connected instead of the Z-TIO module. For installation method of termination resistor of the SRZ side, refer to 4.5 Installation of
Termination Resistor (P. 4-17).
4-14
IMS01T04-E6
Page 47
y
Connection to the RS-232C port of the host computer (master)
A RS-232C/RS-485 converter is required.
Host computer (Master)
()
SRZ unit
Z-TIO module
(Slave)
T/ R ( A) 3
Pair wire
RS-485
4. WIRING
()
T/ R ( B)
  
Z-TIO module
SG
(Slave)
4 5
Shielded twisted
pair wire
T/R (A) T/R (B)
R
SG
Connected b the internal
RS-232C/RS-485 converter
communication line
()
()
Up to 16 Z-TIO modules can be connected. The maximum number of SRZ modules (including other function modules) on the same communication line is 31.
The maximum number of SRZ modules (Z-DIO, Z-CT and Z-COM) on the same communication line is 31.
T/ R ( A) 3 T/ R ( B)
SG 5
R: Termination resistor (Example: 120
R
4
If communication errors occur frequently due to the operation environment or the communication distance, connect termination resistors.
1/2 W )
When the host computer (master) uses Windows 95 or higher, use a RS-232C/RS-485 converter with an automatic send/receive transfer function. Recommended RS-232C/RS-485 converter: CD485, CD485/Vmanufactured by Data Link, Inc. or equivalent
RS-232C
IMS01T04-E6
The cable and termination resistors must be provided by the customer. The above figure shows an example of connecting of Z-TIO modules. However, this figure is
also used even when the Z-DIO module is connected instead of the Z-TIO module. For installation method of termination resistor of the SRZ side, refer to 4.5 Installation of
Termination Resistor (P. 4-17).
4-15
Page 48
4. WIRING
y
Connection to the USB of the host computer (master)
When the host computer (OS: Windows 98SE or higher) is corresponding to the USB connector, our communication converter COM-K (sold separately) can be used.
()
()
()
()
Up to 16 Z-TIO modules can be connected. The maximum number of SRZ modules (including other function modules) on the same communication line is 31.
The maximum number of SRZ modules (Z-DIO, Z-CT and Z-COM) on the same communication line is 31.
SRZ unit
  
Z-TIO module
(Slave)
T/ R ( A) T/ R ( B)
Z-TIO module
T/ R ( A) T/ R ( B)
3 4
SG 5
(Slave)
3 4
SG 5
Host computer (Master)
RS-485
Pair wire
1 SG
T/R (A)
Shielded twisted
pair wire
Connected b the internal communication line
R R: Termination resistor
(Example: 120 1/2 W ) If communication errors occur frequently due to the operation environment or the communication distance, connect termination resistors.
2
T/R(B)
3 4
Unused
5
USB communication
converter COM-K *
* The termination resistor is built into the COM-K.
Connected to USB port of a personal computer
Connected to USB connector
USB cable (COM -K accessory)
For the COM-K, refer to COM-K Instruction Manual (IMR01Z01-E). The cable and termination resistors must be provided by the customer.
The above figure shows an example of connecting of Z-TIO modules. However, this figure is also used even when the Z-DIO module is connected instead of the Z-TIO module.
For installation method of termination resistor of the SRZ side, refer to 4.5 Installation of Termination Resistor (P. 4-17).
4-16
IMS01T04-E6
Page 49
4. WIRING
r

4.5 Installation of Termination Resistor

When connecting termination resistors to each end of the RS-485 communication line, follow the procedure below to connect the resistor to the SRZ end.
For the termination resistor on the host computer side, connect it so as to satisfy the host computer used.
Mounting position
Connect a termination resistor between the communication terminals (No. 3 and 4) of the module at the end of the communication line from the host computer.
Termination resistor (Example: 120 1/2 W)
T/R(A) T/R(B)
When two or more Z-TIO module are connected
SRZ unit (slave)
Host
computer
(master)
RS-485
Z-TIO module
Internal communication line
(RS-485)
When two or more Z-DIO module are connected to Z-TIO module
Z-TIO module
Host
computer
(master)
RS-485
(Base)
34 5
Recommended tightening torque:
0.4 Nm (4 kgf・cm)
SG
To host computer
Connect the termination resistor to this module.
Termination resisto
Connect the termination resistor to this module.
SRZ unit (slave)
Z-DIO module
Internal communication line (RS-485)
Termination resistor
IMS01T04-E6 4-17
Page 50
4. WIRING
When two or more SRZ units are connected (distributed arrangement)
SRZ unit (Slave)
Z-TIO module Z-DIO module
Host
computer
(master)
RS-485
Internal communication line (RS-485)
SRZ unit (Slave)
Z-TIO module Z-DIO module
Internal communication line (RS-485)
RS-485
SRZ unit (Slave)
Z-TIO module
RS-485
Internal communication line (RS-485)
Termination resistor
Z-DIO module
Connect the termination resistor to this module.
4-18
IMS01T04-E6
Page 51
4. WIRING

4.6 Connections for Loader Communication

Each function module (Z-TIO, Z-DIO) is equipped standard with a Loader communication connector. The module Loader communication connector, our COM-K USB communication converter (sold separately) 1,
and a personal computer can be connected with the appropriate cables, and our communication tool (WinUCI-SRZ, PROTEM2) 2 can be installed on the computer, to enable data management monitoring and settings from the computer.
The only data that can be communicated by Loader communication is data of a module that is connected by a Loader communication cable. (Data of other joined modules cannot be communicated.)
1
A loader communication cable (optional) is required for the connection to the Loader communication connector on the module. USB communication converter COM-K-1 (with Loader communication cable [cable length: 1 m])
2
The communication tool (WinUCI-SRZ, PROTEM2) can be downloaded from the official RKC website: http://www.rkcinst.com/.
Personal computer
USB cable (COM-K accessory)
Connec ted to USB port of a pers onal computer
Connected to USB connecter
Loader communication cable (W-B V-01) [Option]
Connected to loader communication co nnec t or of t he module
Loader communication connecter
Do not unplug the USB cable while the power to the instrument is ON.
Communication tool (WinUCI-SRZ, PROTEM2)
Software operation environment: WinUCI-SRZ: Windows 2000 or higher PROTEM2: Windows XP (Service Pack 2) or higher (PROTEM2 needs Microsoft .NET Framework 4.0 or later)
Communication port of host computer
USB port: Based on USB Ver. 2.0
Communication settings on the computer (Values other than the communication port are fixed.)
Communication speed: 38400 bps Start bit: 1 Data bit: 8 Parity bit: Without Stop bit: 1
The Loader port is only for parameter setup.
The Loader communication corresponds to the RKC communication protocol “Based on ANSI X3.28-1976 subcategories 2.5 and B1.”
For the COM-K, refer to the COM-K Instruction Manual (IMR01Z01-E).
USB communica t ion
converter COM-K
Connected t o loader communication connecter
The module address for Loader communication is fixed at “0.”
The setting of the address setting switch is disregarded.
IMS01T04-E6
4-19
Page 52
MEMO
4-20 IMS01T04-E6
Page 53
SETTINGS
BEFORE
OPERATION
5.1 Module Address Setting ................................................................... 5-2
5.2 Protocol Selections and Communication Speed Setting ................... 5-3
5.3 Operating Precautions ...................................................................... 5-4
5.4 Communication Requirements ......................................................... 5-5
IMS01T04-E6 5-1
Page 54
5. SETTINGS BEFORE OPERAT ION

5.1 Module Address Setting

Set communication setting before mounting and wiring of the Z-TIO module.
To prevent electric shock or instrument failure, always turn off the power
before setting the switch.
To prevent electric shock or instrument failure, never touch any section other
than those instructed in this manual.
CAUTION
WARNING
!
Do not separate the module mainframe from the base with the power turned on. If so, instrument failure may result.
Address setting switches
Set an address for the module using a small blade screwdriver. When using two or more modules, set the desired address to each module.
To avoid problems or malfunction, do not duplicate an address on the same communication line.
Module address number of each module:
Z-TIO module
Z-DIO module
0 to 15: Decimal
16 to 31: Decimal
The value obtained by adding “16” to the set address corresponds to the address used for the actual program.
RKC communication Modbus
number 1 to 16: Decimal number
number
Address setting switch
Setting range: 0 to F [0 to 15: Decimal number] Factory set value: 0
The value obtained by adding “1” to the set address corresponds to the address used for the actual program.
17 to 32: Decimal number
The value obtained by adding “17” to the set address corresponds to the address used for the actual program.
5-2 IMS01T04-E6
Page 55
5. SETTINGS BEFORE OPERAT ION
5.2

Protocol Selections and Communication Speed Setting

Use the DIP switch on the right side of module to select communication speed, data bit, configuration and protocol. The data changes become valid when the power is turned on again or when changed to RUN/STOP.
When two or more modules (Z-TIO, Z-DIO) are connected on the same communication line, the DIP switch settings (switch 1 to 8) of all modules must be the same. Otherwise the module may fail or malfunction.
Module
DIP switch
1234567
ON
mainframe
Z-TIO module Z-DIO module
Right side view
8
ON OFF
(The above figure is for the terminal type. However, the switch positions are the same for the connector type.)
1 2 Communication speed
OFF OFF 4800 bps
ON OFF 9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 19200 bps
3 4 5 Data bit configuration
OFF OFF OFF Data 7-bit, without parity, Stop 1-bit * OFF ON OFF Data 7-bit, Even parity, Stop 1-bit *
ON ON OFF Data 7-bit, Odd parity, Stop 1-bit * OFF OFF ON Data 8-bit, without parity, Stop 1-bit OFF ON ON Data 8-bit, Even parity, Stop 1-bit
ON ON ON Data 8-bit, Odd parity, Stop 1-bit
ON OFF OFF
ON OFF ON
Factory set value: Data 8-bit, without parity, stop 1-bit * When the Modbus communication protocol is selected, this setting becomes invalid.
Do not set this one
Setting range of Modbus
Setting range of RKC communication
6 Protocol
OFF RKC communication
ON Modbus
Factory set value: RKC communication
Switch No. 7 and 8 must be always OFF. Do not set to ON.
IMS01T04-E6 5-3
Page 56
5. SETTINGS BEFORE OPERAT ION

5.3 Operating Precautions

Check the following items before starting operation, then turn on the power.
Power ON
When first powered on, the unit starts with the operation mode set to “Control” and the RUN/STOP switch set to STOP (control is stopped) (FAIL/RUN display lamp: lights green). When the RUN/STOP switch is switched from STOP to RUN, operation begins. [Factory set value: STOP]
Action at input error
If the input signal wiring is disconnected or short-circuited (RTD input and Feedback resistance input only), the instrument determines that burnout has occurred.
Burnout direction
Upscale: Thermocouple Voltage (low) input
1
, RTD input (at input break), Feedback resistance input (at input break),
1
Downscale: Thermocouple 1, RTD input (at short-circuited), Feedback resistance input
(at short-circuited), Voltage (low) input, Voltage (high) input 2, Current input 2
1
For the thermocouple input or the voltage (low) input, upscale or downscale can be selected by Engineering mode. (Factory set value: Upscale)
2
For the voltage (high) input or the current input, the display becomes indefinite (display of about zero value).
Output at input error
Control output: According to the contents set by “Action (high/low) at input error” Event output: According to the contents set by “Event action at input error”
Checking the each parameter
The settings for the SV and all parameters should be appropriate for the controlled system. There are parameters in Engineering setting which can not be changed when the controller is in RUN mode.
Change the RUN/STOP mode from RUN to STOP when a change for the parameters in Engineering setting is necessary.
For details of the each parameter, refer to 8. COMMUNICATION DATA DESCRIPTION
(P. 8-1).
Operation when power failure
A power failure of 4 ms or less will not affect the control action. When a power failure of more than 4 ms occurs the instrument assumes that the power has been turned off. When the power returns, the operation of instrument will be re-starts in accordance with the content selected by Hot/Cold start.
For details of Hot/Cold start, refer to Hot/Cold start (P. 8-92).
Event hold action
The event action is activated when the power is turned on or when transferred from STOP mode to RUN
mode.
The event re-hold action is activated when not only the SV is changed, but also the power is turned on or
when transferred from STOP mode to RUN mode.
5-4 IMS01T04-E6
Page 57
5. SETTINGS BEFORE OPERAT ION

5.4 Communication Requirements

Processing times during data send/receive
When the host computer is using either the polling or selecting procedure for communication, the following processing times are required for controller to send data:
- Response wait time after controller sends BCC in polling procedure
- Response wait time after controller sends ACK or NAK in selecting procedure
RKC communication (Polling procedure)
Procedure details Time
Response send time after controller receives ENQ 50 ms max. Response send time after controller receives ACK 50 ms max. Response send time after controller receives NAK 50 ms max. Response send time after controller sends BCC 2 ms max.
RKC communication (Selecting procedure)
Procedure details Time
Response send time after controller receives BCC 50 ms max. Response wait time after controller sends ACK 2 ms max. Response wait time after controller sends NAK 2 ms max.
Modbus
Procedure details Time
Read holding registers [03H] Response send time after the slave receives the query message
Preset single register [06H] Response send time after the slave receives the query message
Diagnostics (loopback test) [08H] Response send time after the slave receives the query message
Preset multiple registers [10H] Response send time after the slave receives the query message
50 ms max.
30 ms max.
30 ms max.
100 ms max.
IMS01T04-E6 5-5
Page 58
5. SETTINGS BEFORE OPERAT ION
A
RS-485 (2-wire system) send/receive timing
RS-485 communication is conducted through two wires, therefore the transmission and reception of data requires precise timing.
Polling procedure
Host
Send data
(Possible/Impossible)
computer
Sending status
Send data
(Possible/Impossible)
SRZ
Sending status
a: Response send time after the controller receives [ENQ] + Interval time b: Response send time after the controller sends BCC c: Response send time after the controller receives [ACK] + Interval time or Response send time after the controller receives [NAK] + Interval time
Selecting procedure
Host
Send data
(Possible/Impossible)
computer
Sending status
Send data
(Possible/Impossible)
SRZ
Sending status
a: Response send time after the controller receives BCC + Interval time b: Response wait time after the controller sends ACK or Response wait time after the controller sends NAK
To switch the host computer from transmission to reception, send data must be on line.
Possible Impossible
Possible Impossible
Possible Impossible
Possible Impossible
N
- - - - -
- - - - -
E N Q
b
S
- - - - -
T X
B C C
a
C K
B C C
b
N
or
A K
E
O
T
S T X
A
or
A
C
K
K
c a
The following processing times are required for the controller to process data.
- In Polling procedure, Response wait time after the controller sends BCC
- In Selecting procedure, Response wait time after the controller sends ACK or NAK
Fail-safe
A transmission error may occur with the transmission line disconnected, shorted or set to the high-impedance state. In order to prevent the above error, it is recommended that the fail-safe function be provided on the receiver side of the host computer. The fail-safe function can prevent a framing error from its occurrence by making the receiver output stable to the MARK (1) when the transmission line is in the high-impedance state.
5-6
IMS01T04-E6
Page 59
RKC
COMMUNICATION
6.1 Polling .............................................................................................. 6-2
6.1.1 Polling procedures .................................................................................... 6-2
6.1.2 Polling procedures example ...................................................................... 6-7
6.2 Selecting........................................................................................... 6-8
6.2.1 Selecting procedures ................................................................................ 6-8
6.2.2 Selecting procedures example ................................................................ 6-11
6.3 Communication Data Structure ...................................................... 6-12
6.4 Communication Data List ............................................................... 6-13
6.4.1 Reference to communication data list ..................................................... 6-13
6.4.2 Communication data of Z-TIO module .................................................... 6-14
6.4.3 Communication data of Z-DIO module.................................................... 6-30
IMS01T04-E6 6-1
Page 60
6. RKC COMMUNICATION
p

6.1 Polling

RKC communication uses the Polling/Selecting method to establish a data link. The basic procedure is followed ANSI X3.28-1976 subcategories 2.5 and B1 basic mode data transmission control procedure (Fast selecting is the selecting method used in SRZ).
The Polling/Selecting procedures are a centralized control method where the host computer controls the
entire process. The host computer initiates all communication so the controller responds according to queries and commands from the host.
The code use in communication is 7-bit ASCII code including transmission control characters.
Transmission control characters used in SRZ: EOT (04H), ENQ (05H), ACK (06H), NAK (15H), STX (02H), ETB (17H), ETX (03H) ( ): Hexadecimal
Data send/receive sta te c a n b e m onit or ed by us i ng our c ommunication tool (WinUCI-SRZ, PROTEM2).
The communication tool (WinUCI-SRZ, PROTEM2) can be downloaded from the official RKC
website:
http://www.rkcinst.com/.

6.1.1 Polling procedures

Polling is the action where the host computer requests one of the connected SRZ to transmit data. An example of the polling procedure is shown below:
Host computer send
E
[Address] [ ] [ ID ]
O T
(1)
ID: Identifier
(2)
Memory area number
When polling the data corresponding to the memory area
E N Q
S T X
No res
E
O
T
[ ID ]
SRZ send
onse
(4)
[ Data ]
(3)
(5)
Host computer send
E
E
T
T
[ BCC ]
or
B
X
(8)
No response
(9)
Indefinite
A
(6)
C K
N A K
(7)
SRZ send
Time out
E O
T
Host computer send
E O
T
(10)
6-2 IMS01T04-E6
Page 61
(1) Data link initialization
Host computer sends EOT to the controllers to initiate data link before polling sequence.
(2) Data sent from host computer - Polling sequence
The host computer sends the polling sequence in the following two types of formats:
Format in which no Memory area number is specified, and Format in which the Memory area number is specified.
When no Memory area number is specified
To be sent in this format for any identifier not corresponding to the memory area.
4. 3. 1.
ENQ
IdentifierAddress
When the Memory area number is specified
To be sent in this format for any identifier corresponding to the memory area.
4.3. 2. 1.
K
ENQ
Memory
area
number
Identifier Address
1. Address (2 digits)
This data is a module address of the SRZ for polled and must be the same as the module address set value in item 5.1 Module Address Setting (P. 5-2).
The polling address which transmitted a message once becomes effective so long as data link is not initialized by transmit and receive of EOT.
2. Memory area number (2 digits)
This is the identifier to specify the Memory area number. It is expressed by K1 to K8 to each Memory area number (from 1 to 8). If the Memory area number is assigned with K0, this represents that Control area is specified.
The memory area now used for control is called Control area. If the Memory area number is not specified when polling the identifier corresponding to the
memory area, this represents that the Control area is specified. If any identifier not corresponding to the memory area is assigned with a Memory area
number, this Memory area number is ignored.
Example:
1M01
Example:
1
6. RKC COMMUNICATION
ENQ
S 11 K0
ENQ
IMS01T04-E6
6-3
Page 62
6. RKC COMMUNICATION
3. Identifier (2 digits)
The identifier specifies the type of data that is requested from the SRZ. Always attach the ENQ code to the end of the identifier.
Refer to 6.4 Communication Data List (P. 6-13).
4. ENQ
The ENQ is the transmission control ch aract er that ind icates t he end of the po lling sequen ce. The host computer then must wait for a response from the SRZ.
(3) Data sent from the SRZ
If the polling sequence is received correctly, the SRZ sends data in the following format:
Identifier Data BCCETBSTX
Identifier Data BCCETXSTX
If the length of send data (from STX to BCC) exceeds 136 bytes, it is divided into blocks by ETB.
In this case, the succeeding divided data is sent after STX.
1. STX
STX is the transmission control character which indicates the start of the text transmission (identifier and data).
2. Identifier (2 digits)
The identifier indicates the type of data (measured value, status and set value) sent to the host computer.
3.2. 6.4.1.
or
3.2. 6.5.1.
Refer to 6.4 Communication Data List (P. 6-13).
3. Data
Data which is indicated by an identifier of this instrument, consisting of channel numbers, data, etc. Each channel number and data are delimited by a space (20H). The data and the next channel number are delimited by a comma (2CH).
Channel number: 2-digit ASCII code, not zero-suppressed. Channels without channel numbers
may exist depending on the type of identifier.
Data: ASCII code, zero-suppressed with spaces (20H). The number of digits varies
depending on the type of identifier.
6-4
IMS01T04-E6
Page 63
6. RKC COMMUNICATION
Memory area soak time monitor and Area soak time become the following data:
When data range is 0 hour 00 minute to 99 hours 59 minutes:
Data range is 0:00 to 99:59, punctuation of time unit is expressed in colon “: (3AH).”
When data range is 0 minute 00 second to 199 minutes 59 seconds:
Data range is 0:00 to 199:59, punctuation of time unit is expressed in colon “: (3AH).”
4. ETB
Transmission control character indicating the end of the block.
5. ETX
Transmission control character indicating the end of the text.
6. BCC
BCC (Block Check Character) detects error by using horizontal parity (even number).
Calculation method of BCC: Exclusive OR all data and characters from STX through ETB or ETX, not including STX.
Example:
STX M 1 0 1 1 5 0 . 0 ETX BCC
4DH 31H 30H 31H 20H 20H 31H 35H 30H 2EH 30H 03H
Hexadecimal numbers
BCC = 4DH 31H 30H 31H 20H 20H 31H 35H 30H 2EH 30H 03H = 54H ( : Exclusive OR) Value of BCC becomes 54H
(4) EOT send (Ending data transmission from the SRZ)
In the following cases, the SRZ sends EOT to terminate the data link:
When the specified identifier is invalid When there is an error in the data format When all the data has been sent
(5) No response from the SRZ
The SRZ will not respond if the polling address is not received correctly. It may be necessary for the host computer to take corrective action such as a time-out.
IMS01T04-E6
6-5
Page 64
6. RKC COMMUNICATION
(6) ACK (Acknowledgment)
An acknowledgment ACK is sent by the host computer when data received is correct. When the SRZ receives ACK from the host computer, the SRZ will send any remaining data of the next identifier without additional action from the host computer. When ACK was sent in succession for Z-TIO module, identifier data item down to “Communication
switch for logic” in the communication identifier list are sent.
When ACK was sent in succession for Z-DIO module, identifier data item down to “DO minimum
ON/OFF time of proportioning cycle” in the communication identifier list are sent.
When host computer determines to terminate the data link, EOT is sent from the host computer.
(7) NAK (Negative acknowledge)
If the host computer does not receive correct data from the SRZ, it sends a negative acknowledgment NAK to the SRZ. The SRZ will re-send the same data when NAK is received. This cycle will go on continuously until either recovery is achieved or the data link is corrected at the host computer.
(8) No response from host computer
When the host computer does not respond within approximately three seconds after the SRZ sends data, the SRZ sends EOT to terminate the data link (time-out time: about 3 seconds).
(9) Indefinite response from host computer
The SRZ sends EOT to terminate the data link when the host computer response is indefinite.
(10) EOT (Data link termination)
The host computer sends EOT message when it is necessary to suspend communication with the SRZ or to terminate the data link due lack of response from the SRZ.
6-6
IMS01T04-E6
Page 65
6. RKC COMMUNICATION
A
r
A

6.1.2 Polling procedure example (when the host computer requests data)

Normal transmission
Host computer send
E
0 1 K 1 S 1E
O
T
04H 30H 31H 4BH 31H 53H 31H 05H 06H
S
Memory
ddress
02H 53H 31H 30H 31H 20H 20H 20H 34H 30H 30H 2EH 30H 03H
number
area
Identifier
*1
E
A
N
Q
S
T
1 01 400.0E T
X
Identifier
Channel No.
Host computer send
Data
SRZ send
O T
04H
S
02H 50H 31H 30H 31H 20H 03H 48H
P 1 0 1  E T X
SRZ send
T X
B C C
Error transmission
Host computer send
C K
B C
X
C
Continue to *1
Host computer send Host computer send
E
0 1 K 1 S 1E
O
T
04H 30H 31H 4BH 31H 53H 31H 05H 15H
S
Memory
ddress
02H 53H 31H 30H 31H 20H 20H 20H 34H 30H 30H 2EH 30H 03H
number
area
Identifie
N
N
Q
Error data
S T X
1 0 1 400.0E T
Identifier
Channel No.
Data
SRZ send
X
B C C
A K
Continue to *1
*1
E
04H
S
S 1 0 1  E T X
02H 53H 31H 30H 31H 20H 03H
SRZ resend
Host computer send
O T
B
T
C
X
C
IMS01T04-E6
6-7
Page 66
6. RKC COMMUNICATION

6.2 Selecting

6.2.1 Selecting procedures

Selecting is the action where the host computer requests one of the connected SRZ to receive data. An example of the selecting procedure is shown below:
E
O
T
(1)
[Address]
(2)
Host computer send
S
[ ]
T X
[Identifier]
(3)
Memory area number
When sele cti n g the data corresponding to the memory area
[Data]
E
E T B
[BCC]
T
or
X
SRZ send
No response
(6)
A C K
(4)
N A
(5)
K
Host computer send
E O
T
(7)
(1) Data link initialization
Host computer sends EOT to the SRZ to initiate data link before selecting sequence.
(2) Sending selecting address from the host computer
Host computer sends selecting address for the selecting sequence.
Address (2 digits): This data is a module address of the SRZ to be selected and must be the same as the module address set value in item 5.1 Module Address Setting (P. 5-2).
As long as the data link is not initialized by sending or receiving EOT, the selecting address once sent becomes valid.
(3) Data sent from the host computer
The host computer sends data for the selecting sequence with the following format:
When no Memory area number is specified
Identifier Data BCCETBSTX
or
Identifier Data BCCETXSTX
6-8 IMS01T04-E6
Page 67
When the Memory area number is specified
Memory
area
number
Identifier
Memory
area
number
Identifier
For the STX, Memory area number, Identifier, Data, ETB, ETX and BCC, refer to 6.1 Polling (P. 6-2).
If the length of send data (from STX to BCC) exceeds 136 bytes, it is divided into blocks by ETB. In this case, the succeeding divided data is sent after STX.
Area soak time set data as the following: When data range is 0 hour 00 minute to 99 hours 59 minutes:
Data range is 0:00 to 99:59, punctuation of time unit is expressed in colon “: (3AH).”
When data range is 0 minute 00 second to 199 minutes 59 seconds:
Data range is 0:00 to 199.59, punctuation of time unit is expressed in colon “: (3AH).” In addition to above, when minute and second data are set in more than 60, become as the following:
Example: 1:65 (1 hour 65 minutes) 2:05 (2 hours 05 minutes)
0:65 (0 minute 65 seconds) 1:05 (1 minute 05 seconds) About numerical data:
The data that receipt of letter is possible
Data with numbers below the decimal point omitted or zero-suppressed data can be received.
(Number of digits: Within 7 digits) <Example> When data send with 001.5, 01.5, 1.5, 1.50, 1.500 at the time of 1.5, SRZ can
receive a data.
When the host computer sends data with decimal point to item of without decimal point, the SRZ
receives a message with the value that cut off below the decimal point. <Example> When setting range is 0 to 200, the SRZ receives as a following.
6. RKC COMMUNICATION
Data BCC ETBSTX
or
Data BCC ETXSTX
The SRZ receives value in accordance with decided place after the decimal point. The value below
the decided place after the decimal point is cut off. <Example> When setting range is 10.00 to 10.00, the controller receives as a following.
IMS01T04-E6
Send data
Receive data
Send data
Receive data
0.5 100.5 0 100
.5 .058 .05 0
0.50 0.05 0.05 0.00
6-9
Page 68
6. RKC COMMUNICATION
The data that receipt of letter is impossible
The SRZ sends NAK when received a following data.
 
Plus sign and the data that gained plus sing Only minus sign (there is no figure)
. Only minus sign and decimal point (period)
(4) ACK (Acknowledgment)
An acknowledgment ACK is sent by the SRZ when data received is correct. When the host computer receives ACK from the SRZ, the host computer will send any remaining data. If there is no more data to be sent to the SRZ, the host computer sends EOT to terminate the data link.
(5) NAK (Negative acknowledge)
If the SRZ does not receive correct data from the host computer, it sends a negative acknowledgment NAK to the host computer. Corrections, such as re-send, must be made at the host computer. The SRZ will send NAK in the following cases:
When an error occurs on communication the line (parity, framing error, etc.) When a BCC check error occurs When the specified identifier is invalid When receive data exceeds the setting range When receive data is the identifier of RO (read only)
(6) No response from SRZ
The SRZ does not respond when it can not receive the selecting address, STX, ETB, ETX or BCC.
(7) EOT (Data link termination)
The host computer sends EOT when there is no more data to be sent from the host computer or there is no response from the SRZ.
6-10
IMS01T04-E6
Page 69

6.2.2 Selecting procedure example (when the host computer sends data)

Normal transmission
E
0 1 S
O
T
04H 30H 31H 02H 4BH 31H 53H 31H 30H 31H 20H 20H 20H 34H 30H 30H 2EH 30H 03H
K 1 S 1 0
T
X
A
Address
06H
Memory
area
number
*1
S
T
P 1 0 1 ET
X
02H 50H 31H 30H 31H 20H 03H 04H
A
06H
Error transmission
E
0 1 S
O
T
04H 30H 31H 02H 4BH 31H 53H 31H 30H 31H 20H 20H 20H 34H 30H 30H 2EH 30H 03H
N
Address
15H
*1
K 1 S 1 0
T
X
Memory
area
number
S
T
K 1 S 1 0 1 ET
X
02H 4BH 31H 53H 31H 30H 31H 20H 03H 04H
A
06H
Host computer send
1 400.0ET
Identifier
Host computer send
Channel No.
Host computer send
1 400.0ET
Identifier
Channel No.
Host computer send
B C
X
C
C K
SRZ send
Host computer sendHost computer resend
X
Data
E O
T
Data
B C C
C K
SRZ send
Error data
E
O
T
6. RKC COMMUNICATION
B C
X
C
C K
Continue to *1
Continue to *1
X
SRZ send
B C C
A K
SRZ send
IMS01T04-E6
6-11
Page 70
6. RKC COMMUNICATION

6.3 Communication Data Structure

Data description (Transmission/Receive data structure)
S
E T X
Part of the data above is shown below.
Data for each channel Data length 7 digits
0
Memory area number *
Data length 1 digit
0
Memory area number *
* To select data corresponding to a memory area, specify the number of the appropriate memory area.
If a Memory area number is specified for data that does not correspond to a memory area, the specification will be invalid.
Data for each module address (Without channel) Data length 7 digits Data length 1 digit
Identifier
Data length 32 digits (Model code) Data length 8 digits (ROM version)
I D
Identifier
........................................................................................................
Data
Identifier
1
Channel
No.
Space
1 0 0 . 0 , 0 2
Data
Channel
No.
Comma
Space
,
1
0 2
Identifier
Channel
No.
Data
Space
Channel
Comma
No.
Data
Space
Data
...
Data
V R ...
Identifier
Identifier
Data
Data
...
Data
T X
B C C
6-12 IMS01T04-E6
Page 71
6. RKC COMMUNICATION

6.4 Communication Data List

6.4.1 Reference to communication data list

No. Name
1 Model code ID 32 RO M Model code (character) 2 ROM version VR 8 RO M ROM version 3 Measured value (PV) M1 7 RO C Input scale low to Input scale high
(1) Name: Communication data name (2) Identifier: Communication identifier of RKC communication (3) Digits: The number of communication data digits in RKC communication (4) Attribute: A method of how communication data items are read or written when viewed from
the host computer is described.
(5) Structure: C: Data for each channel
(6) Data range: Read or Write range of communication data
(7) Factory set value: Factory set value of communication data
(1) (2) (3) (4) (5) (6) (7)
Iden-
tifier
RO: Read only data
Attri-
bute
Struc-
ture
Digits
Host computer
Data range
Data direction
SRZ
R/W: Read and Write data
Host computer
Data direction
1, 2
M: Data for each module
1
On a Z-TIO module (2-channel type), the communication data of the CH3 and CH4 becomes invalid.
2
Parameters only used for Heat/Cool PID control or Position proportionin g PID control, therefore data (indica ted by in
the name column) for CH2 and CH4 of Z-TIO modules are unused. [Read is possible (0 is shown), but the result of Write is disregarded.]
For the data structure, refer to 6.3 Communication Data Structure (P. 6-12).
SRZ
ASCII code data (Example: 7 digits)
Most significant digit
Communication data includes both Normal setting data and Engineering setting data. During RUN (control), the attribute of Engineering setting data is RO. To configure
…………
Least significant digit
Engineering setting data, the RUN/STOP switch must be set to STOP (control stopped).
Factory
set value
 
Z-TIO module: Normal setting data No. 1 to 85, Engineering setting data No. 86 to 208 Z-DIO module: Normal setting data No. 1 to 17, Engineering setting data No. 18 to 31
The Engineering setting data should be set according to the application before setting any parameter related to operation. Once the Engineering setting data are set correctly, no further changes need to be made to parameters for the same application under normal conditions. If they are changed unnecessarily, it may result in malfunction or failure of the instrument. RKC will not bear any responsibility for malfunction or failure as a result of improper changes in the Engineering setting.
When attempting to poll non-existing communication data item (invalid identifier), EOT is returned from the SRZ. In case of selecting, NAK is returned from the SRZ.
IMS01T04-E6 6-13
Page 72
6. RKC COMMUNICATION

6.4.2 Communication data of Z-TIO module

No. Name
1 Model code ID 32 RO M Model code (character) 2 ROM version VR 8 RO M ROM version 3 Measured value (PV) M1 7 RO C Input scale low to Input scale high
4 Comprehensive event state AJ 7 RO C
5 Operation mode state
monitor
6 Error code ER 7 RO M
7 Manipulated output value
(MV) monitor [heat-side]
Manipulated output value
8
(MV) monitor [cool-side]
9 Current transformer (CT)
input value monitor
10 Set value (SV) monitor MS 7 RO C Setting limiter low to Setting limiter high
Remote setting (RS) input
11
value monitor
12 Burnout state monitor B1 1 RO C 0: OFF
13 Event 1 state monitor AA 1 RO C 0: OFF 14 Event 2 state monitor AB 1 RO C 15 Event 3 state monitor AC 1 RO C 16 Event 4 state monitor AD 1 RO C 17 Heater break alarm (HBA)
state monitor
18 Output state monitor Q1 7 RO M
 Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Iden-
tifier
L0 7 RO C
O1 7 RO C PID control or Heat/Cool PID control:
O2 7 RO C 5.0 to +105.0 %
M3 7 RO C CTL-6-P-N: 0.0 to 30.0 A
S2 7 RO C Setting limiter low to Setting limiter high
AE 1 RO C 0: OFF
Digits
Attri-
bute
Struc-
ture
Varies with the setting of the decimal point position.
Least significant digit: Event 1 2nd digit: Event 2 3rd digit: Event 3 4th digit: Event 4 5th digit: Heater break alarm (HBA) 6th digit: Temperature rise completion Most significant digit: Burnout
Data 0: OFF 1: ON Least significant digit: Control STOP
2nd digit: Control RUN 3rd digit: Manual mode 4th digit: Remote mode 5th digit to Most significant digit: Unused Data 0: OFF 1: ON
1: Adjustment data error 2: Data back-up error 4: A/D conversion error 32: Logic output data error
If two or more errors occur simultaneously, the total summation of these error codes is displayed.
5.0 to +105.0 % Position proportioning PID control with feedback
resistance (FBR) input: FBR input value is displayed.
0.0 to 100.0 %
CTL-12-S56-10L-N: 0.0 to 100.0 A
Varies with the setting of the decimal point position.
Varies with the setting of the decimal point position.
1: ON
1: ON
If the Event 3 type is Temperature r ise completion, check the Temperature rise completion state in the Comprehensive event state (Identifier: AJ). (The Event 3 state monitor does not turn ON.)
1: ON Least significant digit: OUT1
2nd digit: OUT2 3rd digit: OUT3 4th digit: OUT4 5th digit to Most significant digit: Unused
Data 0: OFF 1: ON
Valid only for time-proportional control output.
Data range
Factory
set value
Continued on the next page.
6-14 IMS01T04-E6
Page 73
6. RKC COMMUNICATION
p
Continued from the previous page.
No. Name
19 Memory area soak time
Iden-
tifier
TR 7 RO C 0 minutes 00 seconds to 199 minutes 59 seconds:
monitor
20 Integrated operating time
UT 7 RO M 0 to 19999 hours
monitor
21 Holding peak value ambient
Hp 7 RO C 10.0 to +100.0 C (14.0 to 212.0 F)
temperature monitor
22 Backup memory state
EM 1 RO M 0: The content of the backup memory does not
monitor
23 Logic output monitor 1 ED 7 RO M Least significant digit: Logic output 1
24 Logic output monitor 2 EE 7 RO M Least significant digit: Logic output 5
25 PID/AT transfer G1 1 R/W C 0: PID control
26 Auto/Manual transfer J1 1 R/W C 0: Auto mode
27 Remote/Local transfer C1 1 R/W C 0: Local mode
28 RUN/STOP transfer SR 1 R/W M 0: STOP (Control stop)
29 Memory area transfer ZA 7 R/W C 1 to 8 1 30 Interlock release AR 1 R/W C 0: Normal state
31 Event 1 set value (EV1) A1 7 R/W C Deviation action, Deviation action between channels,
32 Event 2 set value (EV2) A2 7 R/W C 50 (50.0)
33 Event 3 set value (EV3) A3 7 R/W C 50 (50.0)
34 Event 4 set value (EV4) A4 7 R/W C 50 (50.0)
35 Control loop break alarm
A5 7 R/W C 0 to 7200 seconds (0: Unused)
(LBA) time
Parameters which can be used in multi-memory area function
Digits
Attri-
bute
Struc-
ture
Data range
0:00 to 199:59 (min:sec) 0 hours 00 minutes to 99 hours 59 minutes:
0:00 to 99:59 (hrs:min)
Data range of Area soak time can be selec ted on the Soak time unit.
coincide with that of the RAM.
1: The content of the backup memory coincides with
that of the RAM.
2nt digit: Logic output 2 3rd digit: Logic output 3 4th digit: Logic output 4 5th digit to Most significant digit: Unused Data 0: OFF 1: ON
2nt digit: Logic output 6 3rd digit: Logic output 7 4th digit: Logic output 8 5th digit to Most significant digit: Unused Data 0: OFF 1: ON
1: Autotuning (AT)
When the Autotuning (AT) is finished, the control will automatically returns to 0: PID control.
1: Manual mode
1: Remote mode
When performing remote control by Remote setting input and also performing Cascade control and Ratio setting, transfer to the Remote mode.
1: RUN (Control start)
1: Interlock release execution
Temperature rise completion range: Input span to +Input span
Varies with the setting of the decimal point position.
Process action, SV action: Input scale low to Input scale high
Varies with the setting of the decimal point position.
MV action: 5.0 to +105.0 %
If the Event type corresponds to “0: None,” set to RO (Only reading data is possible).
When Temperature rise completion is selected at Event 3 action type.
If Event 4 corres the Event 4 set value becomes RO (Only reading data is possible).
onds to “9: Control loop break alarm (LBA),”
Factory
set value
0
0
0
0
0
50 (50.0)
480
Continued on the next page.
IMS01T04-E6 6-15
Page 74
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
Iden-
tifier
36 LBA deadband N1 7 R/W C 0 to Input span
37 Set value (SV) S1 7 R/W C Setting limiter low to Setting limiter high
38 Proportional band
P1 7 R/W C
[heat-side]
39 Integral time [heat-side]
I1 7 R/W C
40 Derivative time [heat-side]
D1 7 R/W C
41 Control response parameter
CA 1 R/W C
42 Proportional band
P2 7 R/W C
[cool-side]
43 Integral time [cool-side]
I2 7 R/W C
44 Derivative time [cool-side]
D2 7 R/W C
45 Overlap/Deadband V1 7 R/W C
Parame ters which can be used in multi-memory area function
Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO modules are unused.
Digits
Attri-
bute
Struc-
ture
Varies with the setting of the decimal point position.
Varies with the setting of the decimal point position.
Data range
TC/RTD inputs: 0 to Input span (Unit: C [F])
Varies with the setting of the decimal point position.
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of input span 0 (0.0): ON/OFF action
(ON/OFF action for both heat and cool actions in case of a Heat/Cool PID control type.)
PID control or Heat/Cool PID control: 0 to 3600 seconds or 0.0 to 1999.9 seconds (0, 0.0: PD action)
Position proportioning PID control: 1 to 3600 seconds or 0.1 to 1999.9 seconds
Varies with the setting of the Integral/Derivative time decimal point position selection.
0 to 3600 seconds or 0.0 to 1999.9 seconds (0, 0.0: PI action)
Varies with the setting of the Integral/Derivative time decimal point position selection.
0: Slow 1: Medium 2: Fast
When the P or PD action is selected, this setting becomes invalid.
TC/RTD inputs: 1 (0.1) to Input span (Unit: C [F])
Varies with the setting of the decimal point position.
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of input span
If control is other than Heat/Cool PID control, set to RO (Only reading data is possible).
0 to 3600 seconds or 0.0 to 1999.9 seconds (0, 0.0: PD action)
Varies with the setting of the Integral/Derivative time decimal point position selection.
If control is other than Heat/Cool PID control, set to RO (Only reading data is possible).
0 to 3600 seconds or 0.0 to 1999.9 seconds (0, 0.0: PI action)
Varies with the setting of the Integral/Derivative time decimal point position selection.
If control is other than Heat/Cool PID control, set to RO (Only reading data is possible).
TC/RTD inputs: Input span to +Input span (Unit:C [F])
Varies with the setting of the decimal point position.
Voltage (V)/Current (I) inputs: 100.0 to +100.0 % of input span
Minus () setting results in Overlap. However, the overlapping range is within the proportional range. If control is other than Heat/Cool PID control, set to RO
(Only reading data is possible).
Continued on the next page.
Factory
set value
0 (0.0)
TC/RTD: 0 (0.0)
V/I: 0.0
TC/RTD:
30 (30.0) V/I: 30.0
240
60
PID control,
Position proportioning PID control: 0
Heat/Cool PID
control: 2 TC/RTD:
30 (30.0) V/I: 30.0
240
60
0 (0.0)
6-16 IMS01T04-E6
Page 75
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
Iden-
tifier
46 Manual reset MR 7 R/W C
47 Setting change rate limiter
(up)
48 Setting change rate limiter
(down)
HH 7 R/W C 0 to Input span/unit time *
HL 7 R/W C 0 (0.0)
49 Area soak time TM 7 R/W C
50 Link area number LP 7 R/W C 0 to 8
51
Heater break alarm (HBA)
A7 7 R/W C
set value
52
Heater break determination
NE 7 R/W C
point
53
Heater melting
NF 7 R/W C
determination point
54 PV bias PB 7 R/W C Input span to +Input span
55 PV digital filter F1 7 R/W C 0.0 to 100.0 seconds
56 PV ratio PR 7 R/W C 0.500 to 1.500 1.000 57 PV low input cut-off DP 7 R/W C
58 RS bias * RB 7 R/W C Input span to +Input span
59 RS digital filter * F2 7 R/W C 0.0 to 100.0 seconds
60 RS ratio * RR 7 R/W C 0.001 to 9.999 1.000 61
Output distribution
DV 1 R/W C
selection
* Data on RS bias, RS ratio and RS digital filter is that in Cascade control or Ratio setting.
Parameters which can be used in multi-memory area function
Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Digits
Attri-
bute
Struc-
ture
Data range
100.0 to +100.0 %
If the Integral function is valid, set to RO (Only reading data is possible).
When Integral action (heating or c ooling side) is zero, manual reset value is added to the control output.
0: Unused
Varies with the setting of the decimal point position. * Unit time: 60 seconds (factory set value)
0 minutes 00 seconds to 199 minutes 59 seconds: 0:00 to 199:59 (min:sec)
0 hours 00 minutes to 99 hours 59 minutes: 0:00 to 99:59 (hrs:min)
Data range of Area soak time can be selec ted on the Soak time unit.
(0: No link) When CT is CTL-6-P-N:
0.0 to 30.0 A (0.0: Not used) When CT is CTL-12-S56-10L-N:
0.0 to 100.0 A (0.0: Not used)
If there is no Current transf ormer (CT ) or CT is assi gned to “0: None,” set to RO (On ly read ing dat a is poss ible).
0.0 to 100.0 % of HBA set value (0.0: Heater break determination is invalid)
If there is no Current transf ormer (CT ) or CT is assi gned to “0: None,” set to RO (On ly read ing dat a is poss ible).
If Heater break alarm (HBA) corresponds to “0: Type A,” set to RO (Only reading data is possible).
0.0 to 100.0 % of HBA set value (0.0: Heater melting determination is invalid)
If there is no Current transf ormer (CT ) or CT is assi gned to “0: None,” set to RO (On ly read ing dat a is poss ible).
If Heater break alarm (HBA) corresponds to “0: Type A,” set to RO (Only reading data is possible).
Varies with the setting of the decimal point position.
(0.0: Unused)
0.00 to 25.00 % of input span
If the Square root extraction corresponds to “0: Unused,” set to RO (Only reading data is possible).
Varies with the setting of the decimal point position.
(0.0: Unused)
0: Control output 1: Distribution output
set value
Continued on the next page.
Factory
0.0
0 (0.0)
0:00
0
0.0
30.0
30.0
0 (0.0)
0.0
0.00
0 (0.0)
0.0
0
IMS01T04-E6 6-17
Page 76
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
62 Output distribution bias DW 7 R/W C 100.0 to 100.0 % 0.0 63 Output distribution ratio DQ 7 R/W C 9.999 to 9.999 1.000 64 Proportional cycle time T0 7 R/W C 0.1 to 100.0 seconds
65 Minimum ON/OFF time of
proportioning cycle
66
Manual manipulated output value
67
Area soak time stop function
68 EDS mode
(for disturbance 1)
69
EDS mode (for disturbance 2)
Iden-
tifier
VI 7 R/W C
ON 7 R/W C
RV 1 R/W C
NG 1 R/W C 0: No function
NX 1 R/W C 0
Digits
Attri-
bute
Struc-
ture
This item becomes RO (Only reading data is possible) for the Voltage/Current output specification.
This parameter is valid when “0: control output” has been selected at No. 95 “Output assignment.”
0 to 1000 ms
This item becomes RO (Only reading data is possible) for the Voltage/Current output specification.
PID control: Output limiter low to Output limiter high
Heat/Cool PID control: Cool-side output limiter (high) to Heat-side output limiter (high)
Position proportioning PID control: When there is Feedback resistance (FBR) input and it does not break: Output limiter low to Output limiter high
When there is no Feedback resistance (FBR) input or the Feedback resistance (FBR) input is disconnected: 0: Close-side output OFF, Open-side output OFF 1: Close-side output ON, Open-side output OFF 2: Close-side output OFF, Open-side output ON
0: No function 1: Event 1 2: Event 2 3: Event 3 4: Event 4
1: EDS function mode 2: Learning mode 3: Tuning mode
EDS function: External disturbance suppression function
Data range
Factory
set value
Relay contact
output: 20.0
Voltage pulse
output, Triac
output and
Open collector
output: 2.0
0
0.0
0
0
70
EDS value 1 (for disturbance 1)
71
EDS value 1 (for disturbance 2)
72
EDS value 2 (for disturbance 1)
73 EDS value 2
(for disturbance 2)
74 EDS transfer time
(for disturbance 1)
75
EDS transfer time (for disturbance 2)
76
EDS action time (for disturbance 1)
77
EDS action time (for disturbance 2)
78 EDS action wait time
(for disturbance 1)
79 EDS action wait time
(for disturbance 2)
 Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
NI 7 R/W C 100.0
NJ 7 R/W C 0.0
NK 7 R/W C 100.0 to 100.0 % 0.0
NM 7 R/W C 0.0
NN 7 R/W C 0 to 3600 seconds or 0.0 to 1999.9 seconds 0
NO 7 R/W C 0
NQ 7 R/W C 1 to 3600 seconds 600
NL 7 R/W C 600
NR 7 R/W C 0.0 to 600.0 seconds 0.0
NY 7 R/W C 0.0
to 100.0 % 0.0
Continued on the next page.
6-18 IMS01T04-E6
Page 77
Continued from the previous page.
No. Name
80 EDS value learning times NT 7 R/W C 0 to 10 times
81 EDS start signal NU 1 R/W C 0: EDS start signal OFF
82 Operation mode EI 1 R/W C 0: Unused
83 Startup tuning (ST) ST 1 R/W C 0: ST unused
84 Automatic temperature rise
learning
85 Communication switch for
logic
Set data No. 86 or later are for engineering setting [Writable in the STOP mode]
86 Input type XI 7 R/W C 0: TC input K
Iden-
tifier
Y8 1 R/W C 0: Unused
EF 7 R/W M
Digits
Attri-
bute
Struc-
ture
(0: No learning mode)
1: EDS start signal ON (for disturbance 1) 2: EDS start signal ON (for disturbance 2)
1: Monitor 2: Monitor  Event function 3: Control
1: Execute once * 2: Execute always
* When the Startup tuning (ST) is finished, the setting will
automatically returns to “ 0: ST unused.”
The Startup tuning (ST) function is activated according to the ST start condition selected.
If control is Position proportioning PID control, set to RO (Only reading data is possible).
1: Learning *
* When the automatic temperature rise learning is finished,
the setting will automatically returns to “0: Unuse d.”
Least significant digit: Communication switch 1 2nd digit: Communication switch 2 3rd digit: Communication switch 3 4th digit: Communication switch 4 5th digit to Most significant digit: Unused
Data 0: OFF 1: ON
1: TC input J 2: TC input R 3: TC input S 4: TC input B 5: TC input E 6: TC input N 7: TC input T 8: TC input W5Re/W26Re 9: TC input PLII 12: RTD input Pt100 13: RTD input JPt100 14: Current input 0 to 20 mA DC 15: Current input 4 to 20 mA DC 16: Voltage (high) input 0 to 10 V DC 17: Voltage (high) input 0 to 5 V DC 18: Voltage (high) input 1 to 5 V DC 19: Voltage (low) input 0 to 1 V DC 20: Voltage (low) input 0 to 100 mV DC 21: Voltage (low) input 0 to 10 mV DC 22: Feedback resistance input 100 to 150 23: Feedback resistance input 151 to 6 k
If changed to Voltage (high) input from TC/RTD/Current/Voltage (low)/Feedback resistance input, select the hardware by the input selector switch at the side of the module. (Ref e r t o P. 8 - 7 0 )
Data range
6. RKC COMMUNICATION
Factory
set value
1
0
3
0
0
0
Based on
model code
When not
specifying: 0
Continued on the next page.
IMS01T04-E6 6-19
Page 78
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
87 Display unit PU 7 R/W C
88 Decimal point position XU 7 R/W C 0: No decimal place
89 Input scale high XV 7 R/W C TC/RTD inputs:
90 Input scale low XW 7 R/W C TC/RTD inputs:
91 Input error determination
point (high)
92 Input error determination
point (low)
93 Burnout direction BS 1 R/W C 0: Upscale
94 Square root extraction XH 1 R/W C 0: Unused
95 Output assignment
(Logic output selection function)
96 Energized/De-energized
(Logic output selection function)
Iden-
tifier
AV 7 R/W C Input error determination point (low) to
AW 7 R/W C (Input range low 5 % of input span)
E0 1 R/W C 0: Control output
NA 1 R/W C 0: Energized
Digits
Attri-
bute
Struc-
ture
0: C 1: F
Use to select the temperature unit for Thermocouple (TC) and RTD inputs.
1: One decimal place 2: Two decimal places 3: Three decimal places 4: Four decimal places
TC input: K, J, T, E Only 0 or 1 can be set. R, S, B, N, PLII, W5Re/W26Re Only 0 can be set. RTD input: Only 0 or 1 can be set.
V/I inputs: From 0 to 4 can be set.
Input scale low to Maximum value of the
selected input range
Voltage (V)/Current (I) inputs:
19999 to +19999 (However, a span is 20000 or less.)
Varies with the setting of the decimal point position.
Minimum value of the selected input range to Input scale high
Voltage (V)/Current (I) inputs:
19999 to +19999 (However, a span is 20000 or less.)
Varies with the setting of the decimal point position.
(Input range high 5 % of input span)
Varies with the setting of the decimal point position.
to Input error determination point (high)
Varies with the setting of the decimal point position.
1: Downscale
Valid only when the TC input and Voltage (low) input are selected.
1: Used
1: Logic output result 2: FAIL output
1: De-energized
Data range
Factory
set value
Based on
model code
When not
specifying: 0
Based on
model code
If input range
code is not
specified: 1
TC/RTD:
Maximum value
of the selected
input range
V/I: 100.0
If input range
code is not
specified: 1372.0
TC/RTD:
Minimum value
of the selected
input range
V/I: 0.0
If input range
code is not
specified: 200.0 Input range high
(5 % of input
span)
Input range low
(5 % of input
span)
0
0
0
0
Continued on the next page.
6-20 IMS01T04-E6
Page 79
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
Iden-
tifier
97 Event 1 type XA 7 R/W C
98 Event 1 channel setting FA 1 R/W C
99 Event 1 hold action WA 1 R/W C 0: OFF
100 Event 1 interlock LF 1 R/W C 0: Unused
101 Event 1 differential gap HA 7 R/W C Deviation, Process, Set value, or Deviation action
102 Event 1 delay timer TD 7 R/W C 0 to 18000 seconds 0 103 Force ON of Event 1 action OA 7 R/W C
Digits
Attri-
bute
Struc-
ture
Data range
0: None 1: Deviation high (Using SV monitor value) 2: Deviation low (Using SV monitor value) 3: Deviation high/low (Using SV monitor value) 4: Band (Using SV monitor value) 5: Process high 6: Process low
1
1
7: SV high 8: SV low 9: Unused 10: MV high [heat-side] 11: MV low [heat-side] 12: MV high [cool-side] 13: MV low [cool-side]
1, 2
1, 2
1
1
14: Deviation high (Using local SV) 1 15: Deviation low (Using local SV) 16: Deviation high/low (Using local SV) 17: Band (Using local SV)
1
18: Deviation between channels high 19: Deviation between channels low 20: Deviation between channels high/low 21: Deviation between channels band
1
Event hold action is available.
2
If there is Feedback resistance (FBR) input in Position proportioning PID control, set to the Feedback resistance (FBR) input value.
1: Channel 1 2: Channel 2 3: Channel 3 4: Channel 4
This function is valid when “Deviation between channels” is selected.
1: Hold action ON (when power turned on; when transferred from STOP to RUN) 2: Re-hold action ON (when power turned on; when transferred from STOP to RUN; SV changed)
This function is valid when input value, deviation or manipulated value action has been selected.
In case of a deviation action, this function is not available while in Remote mode and while Setting changing rate limiter is working.
1: Used
between channels: 0 to Input span (Unit: C [F])
Varies with the setting of the decimal point position.
MV: 0.0 to 110.0 %
Least significant digit:
Event output turned on at input error
occurrence 2nd digit: Event output turned on in Manual mode 3rd digit: Event output turned on during the
Autotuning (AT) function is being
executed 4th digit: Event output turned on during the
Setting change rate limiter is being
operated 5th digit to Most significant digit:
Unused Data 0: Invalid 1: Valid
1
1
1
1
1
1
1
1
1
1
Continued on the next page.
specifying: 0
specifying: 0
: 1 (1.0) : 1.0
Factory
set value
Based on
model code
When not
1
Based on
model code
When not
0
0
IMS01T04-E6 6-21
Page 80
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
Iden-
tifier
104 Event 2 type XB 7 R/W C
105 Event 2 channel setting FB 1 R/W C
106 Event 2 hold action WB 1 R/W C 0: OFF
107 Event 2 interlock LG 1 R/W C 0: Unused
108 Event 2 differential gap HB 7 R/W C Deviation, Process, Set value, or Deviation action
109 Event 2 delay timer TG 7 R/W C 0 to 18000 seconds 0 110 Force ON of Event 2 action OB 7 R/W C
Digits
Attri-
bute
Struc-
ture
Data range
0: None 1: Deviation high (Using SV monitor value) 2: Deviation low (Using SV monitor value) 3: Deviation high/low (Using SV monitor value) 4: Band (Using SV monitor value) 5: Process high 6: Process low
1
1
7: SV high 8: SV low 9: Unused 10: MV high [heat-side] 11: MV low [heat-side] 12: MV high [cool-side] 13: MV low [cool-side]
1, 2
1, 2
1
1
14: Deviation high (Using local SV) 15: Deviation low (Using local SV) 16: Deviation high/low (Using local SV) 17: Band (Using local SV)
1
18: Deviation between channels high 19: Deviation between channels low 20: Deviation between channels high/low 21: Deviation between channels band
1
Event hold action is available.
2
If there is Feedback resistance (FBR) input in Position proportioning PID control, set to the Feedback resistance (FBR) input value.
1: Channel 1 2: Channel 2 3: Channel 3 4: Channel 4
This function is valid when “Deviation between channels” is selected.
1: Hold action ON (when power turned on; when transferred from STOP to RUN) 2: Re-hold action ON (when power turned on; when transferred from STOP to RUN; SV changed)
This function is valid when input value, deviation or manipulated value action has been selected.
In case of a deviation action, this function is not available while in Remote mode and while Setting changing rate limiter is working.
1: Used
between channels: 0 to Input span (Unit: C [F])
Varies with the setting of the decimal point position.
MV: 0.0 to 110.0 %
Least significant digit:
Event output turned on at input error
occurrence 2nd digit: Event output turned on in Manual mode 3rd digit: Event output turned on during the
Autotuning (AT) function is being
executed 4th digit: Event output turned on during the
Setting change rate limiter is being
operated 5th digit to Most significant digit:
Unused Data 0: Invalid 1: Valid
1
1
1
1
1
1
1
1
1
1
1
Continued on the next page.
specifying: 0
specifying: 0
: 1 (1.0) : 1.0
Factory
set value
Based on
model code
When not
1
Based on
model code
When not
0
0
6-22 IMS01T04-E6
Page 81
Continued from the previous page.
No. Name
Iden-
tifier
111 Event 3 type XC 7 R/W C
112 Event 3 channel setting FC 1 R/W C
113 Event 3 hold action WC 1 R/W C
114 Event 3 interlock LH 1 R/W C 0: Unused
115 Event 3 differential gap HC 7 R/W C
116 Event 3 delay timer TE 7 R/W C 0 to 18000 seconds
117 Force ON of Event 3 action OC 7 R/W C
Digits
Attri-
bute
Struc-
ture
0: None 1: Deviation high (Using SV monitor value) 2: Deviation low (Using SV monitor value) 3: Deviation high/low (Using SV monitor value) 4: Band (Using SV monitor value) 5: Process high 6: Process low 7: SV high 8: SV low 9: Temperature rise completion 10: MV high [heat-side] 11: MV low [heat-side] 12: MV high [cool-side] 13: MV low [cool-side] 14: Deviation high (Using local SV) 1 15: Deviation low (Using local SV) 16: Deviation high/low (Using local SV) 17: Band (Using local SV) 18: Deviation between channels high 19: Deviation between channels low 20: Deviation between channels high/low 21: Deviation between channels band
1
Event hold action is available.
2
If there is Feedback resistance (FBR) input in Position proportioning PID control, set to the Feedback resistance (FBR) input value.
1: Channel 1 2: Channel 2 3: Channel 3 4: Channel 4
This function is valid when “Deviation between channels” is selected.
0: OFF 1: Hold action ON (when power turned on; when transferred from STOP to RUN) 2: Re-hold action ON (when power turned on; when transferred from STOP to RUN; SV changed)
This function is valid when input value, deviation or manipulated value action has been selected.
In case of a deviation action, this function is not available while in Remote mode and while Setting changing rate limiter is working.
1: Used Deviation, Process, Set value, Deviation action
between channels or Temperature rise completion: 0 to Input span (Unit: C [F])
Varies with the setting of the decimal point position.
MV: 0.0 to 110.0 %
If Event 3 corresponds to “9: Temperature rise completion,” the Event 3 delay timer becomes the Temperature rise completion soak time.
Least significant digit:
2nd digit: Event output turned on in Manual mode 3rd digit: Event output turned on during the
4th digit: Event output turned on during the
5th digit to Most significant digit:
Data 0: Invalid 1: Valid
6. RKC COMMUNICATION
Data range
1
1
1
1
1
1, 2
1, 2
1
1
1
Event output turned on at input error
occurrence
Autotuning (AT) function is being executed
Setting change rate limiter is being operated
Unused
1
1
1
1
1
1
Continued on the next page.
1
: 1 (1.0) : 1.0
Factory
set value
Based on
model code
When not
specifying: 0
1
Based on
model code
When not
specifying: 0
0
0
0
IMS01T04-E6 6-23
Page 82
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
Iden-
tifier
118 Event 4 type XD 7 R/W C
119 Event 4 channel setting FD 1 R/W C
120 Event 4 hold action WD 1 R/W C
121 Event 4 interlock LI 1 R/W C
122 Event 4 differential gap HD 7 R/W C
123 Event 4 delay timer TF 7 R/W C 0 to 18000 seconds 0 124 Force ON of Event 4 action OD 7 R/W C
Digits
Attri-
bute
Struc-
ture
Data range
0: None 1: Deviation high (Using SV monitor value) 2: Deviation low (Using SV monitor value) 3: Deviation high/low (Using SV monitor value) 4: Band (Using SV monitor value) 5: Process high 6: Process low
1
1
7: SV high 8: SV low 9: Control loop break alarm (LBA) 10: MV high [heat-side] 11: MV low [heat-side] 12: MV high [cool-side] 13: MV low [cool-side]
1, 2
1, 2
1
1
14: Deviation high (Using local SV) 1 15: Deviation low (Using local SV) 16: Deviation high/low (Using local SV) 17: Band (Using local SV)
1
18: Deviation between channels high 19: Deviation between channels low 20: Deviation between channels high/low 21: Deviation between channels band
1
Event hold action is available.
2
If there is Feedback resistance (FBR) input in Position proportioning PID control, set to the Feedback resistance (FBR) input value.
1: Channel 1 2: Channel 2 3: Channel 3 4: Channel 4
This function is valid when “Deviation between channels” is selected.
0: OFF 1: Hold action ON (when power turned on; when transferred from STOP to RUN) 2: Re-hold action ON (when power turned on; when transferred from STOP to RUN; SV changed)
This function is valid when input value, deviation or manipulated value action has been selected.
In case of a deviation action, this function is not available while in Remote mode and while Setting changing rate limiter is working.
0: Unused 1: Used
Deviation, Process, Set value, or Deviation action
between channels: 0 to Input span (Unit: C [F])
Varies with the setting of the decimal point position.
MV: 0.0 to 110.0 %
Becomes invalid when the Event 4 type corresponds to “9: Control loop break alarm (LBA).”
Least significant digit:
Event output turned on at input error
occurrence 2nd digit: Event output turned on in Manual mode 3rd digit: Event output turned on during the
Autotuning (AT) function is being executed
4th digit: Event output turned on during the
Setting change rate limiter is being operated
5th digit to Most significant digit:
Unused
Data 0: Invalid 1: Valid
Becomes invalid when the Event 4 type corresponds to “9: Control loop break alarm (LBA).”
1
1
1
1
1
1
1
1
1
1
Continued on the next page.
specifying: 0
specifying: 0
: 1 (1.0) : 1.0
Factory
set value
Based on
model code
When not
1
Based on
model code
When not
0
0
6-24 IMS01T04-E6
Page 83
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
125 CT ratio XS 7 R/W C 0 to 9999 CTL-6-P-N: 800
126 CT assignment ZF 1 R/W C
127 Heater break alarm (HBA)
type
128 Number of heater break
alarm (HBA) delay times
129 Hot/Cold start XN 1 R/W C
130 Start determination point SX 7 R/W C
131 SV tracking XL 1 R/W C
MV transfer function
132
[Action taken when changed to Manual mode from Auto mode]
133 Control action XE 1 R/W C
134 Integral/Derivative time
decimal point position
135 Derivative action KA 1 R/W C 0: Measured value derivative
136 Undershoot suppression
factor
137 Derivative gain DG 7 R/W C 0.1 to 10.0 6.0 138 ON/OFF action differential
gap (upper)
139 ON/OFF action differential
gap (lower)
 Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Iden-
tifier
ND 1 R/W C
DH 7 R/W C 0 to 255 times 5
OT 1 R/W C
PK 1 R/W C 0: 1 second setting (No decimal place)
KB 7 R/W C 0.000 to 1.000
IV 7 R/W C
IW 7 R/W C
Digits
Attri-
bute
Struc-
ture
0: None 3: OUT3 1: OUT1 4: OUT4 2: OUT2
0: Heater break alarm (HBA) type A (Time-proportional control output) 1: Heater break alarm (HBA) type B (Continuous control output)
Time-proportional control output:
Relay, Voltage pulse, Triac, or Open collector output
Continuous control output:
Voltage/Current continuous output
0: Hot start 1 1: Hot start 2 2: Cold start
0 to Input span (The unit is the same as input value.) 0: Action depending on the Hot/Cold start selection
Varies with the setting of the decimal point position.
0: Unused 1: Used
0: MV in Auto mode is used.
[Balanceless-bumpless fu nction]
1: MV in previous Manual mode is used.
0: Brilliant II PID control (Direct action) 1: Brilliant II PID control (Reverse action) 2: Brilliant II Heat/Cool PID control [Water cooling type] 3: Brilliant II Heat/Cool PID control [Air cooling type] 4: Brilliant II Heat/Cool PID control [Cooling gain linear type] 5: Brilliant II Position proportioning PID control
Odd channel: From 0 to 5 can be se t. Even channel: Only 0 or 1 can be set. *
* In Heat/Cool PID control and Positio n proportioning
PID control, control action is not performed. Only PV monitor and event action is performed.
1: 0.1 seconds setting (One decimal place)
1: Deviation derivative
TC/RTD inputs: 0 to Input span (Unit: C [F])
Varies with the setting of the decimal point position.
Voltage (V)/Current (I) inputs:
0.0 to 100.0 % of input span
Data range
Factory
set value
CTL-12-S56-10L
-N: 1000 CH1: 1
CH2: 2 CH3: 4 CH4: 4
Set value is based
on the Output
type specified at
ordering.
0
Based on
specification
1
0
Based on
model code
When not
specifying: 1
0
0
Water cooling:
0.100
Air cooling:
0.250
Cooling gain
linear type:
1.000
TC/RTD: 1 (1.0)
V/I: 0.1
TC/RTD: 1 (1.0)
V/I: 0.1
Continued on the next page.
IMS01T04-E6 6-25
Page 84
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
140
Action (high) at input error
Iden-
tifier
WH 1 R/W C
141
Action (low) at input error
WL 1 R/W C
142 Manipulated output value at
OE 7 R/W C
input error
143 Manipulated output value at
OF 7 R/W C
STOP mode [heat-side]
144 Manipulated output value at
OG 7 R/W C
STOP mode [cool-side]
145 Output change rate limiter
PH 7 R/W C
(up) [heat-side]
146 Output change rate limiter
PL 7 R/W C
(down) [heat-side]
147 Output limiter high
OH 7 R/W C
[heat-side]
148 Output limiter low
OL 7 R/W C
[heat-side]
149 Output change rate limiter
PX 7 R/W C
(up) [cool-side]
150 Output change rate limiter
PY 7 R/W C
(down) [cool-side]
151 Output limiter high
OX 7 R/W C
[cool-side]
152 Output limiter low
OY 7 R/W C
[cool-side]
153 AT bias  GB 7 R/W C
154 AT cycles  G3 1 R/W C
155 Output value with AT turned
OP 7 R/W C on
156 Output value with AT turned
OQ 7 R/W C
off
 Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Digits
Attri-
bute
Struc-
ture
Data range
0: Normal control 1: Manipulated output value at input error
105.0 to 105.0 %
Actual output values become those restricted by the output limiter.
Position proportioning PID control: If there is no Feedback resistance (FBR) input or the Feedback resistance (FBR) input is disconnected, an action taken when abnormal is in accordance with the value action setting during STOP.
5.0 to 105.0 %
Position proportioning PID control: Only when there is Feedback resistance (FBR) input and it does not break, the Manipulated output value [heat-side] at STOP is output.
0.0 to 100.0 % of manipulated output /seconds (0.0: OFF)
Becomes invalid when in Position proportioning PID control.
Output limiter low to 105.0 %
Position proportioning control: Becomes valid only when there is Feedback resistance (FBR) input and it does not break.
5.0 % to Output limiter high
Position proportioning PID control: Becomes valid only when there is Feedback resistance (FBR) input and it does not break.
0.0 to 100.0 % of manipulated output /seconds (0.0: OFF)
Becomes invalid when in Position proportioning PID control.
Output limiter low [cool-side] to 1 0 5. 0 % 105.0
5.0 % to Output limiter high [cool-side] 5.0
Input span to +Input span
Varies with the setting of the decimal point position.
0: 1.5 cycles 1: 2.0 cycles 2: 2.5 cycles 3: 3.0 cycles
Output value with AT turned off to 105.0 %
Actual output values become those restricted by the output limiter.
Position proportioning PID control: Becomes valid only when there is Feedback resistance (FBR) input and it does not break (high limit of feedback resistance input at AT).
105.0 % to Output value with AT turned on
Actual output values become those restricted by the output limiter.
Position proportioning PID control: Becomes valid only when there is Feedback resistance (FBR) input and it does not break (low limit of feedback resistance input at AT).
Continued on the next page.
set value
Factory
0
0
0.0
5.0
5.0
0.0
0.0
105.0
5.0
0.0
0.0
0 (0.0)
1
105.0
105.0
6-26 IMS01T04-E6
Page 85
Continued from the previous page.
No. Name
Iden-
tifier
157 AT differential gap time GH 7 R/W C 158 Proportional band adjusting
KC 7 R/W C 0.01 to 10.00 times 1.00
factor [heat-side]
159 Integral time adjusting factor
KD 7 R/W C 0.01 to 10.00 times 1.00
[heat-side]
160 Derivative time adjusting
KE 7 R/W C 0.01 to 10.00 times 1.00
factor [heat-side]
161 Proportional band adjusting
KF 7 R/W C 0.01 to 10.00 times 1.00 factor [cool-side]
162 Integral time adjusting factor
KG 7 R/W C 0.01 to 10.00 times 1.00
[cool-side]
163 Derivative time adjusting
KH 7 R/W C 0.01 to 10.00 times 1.00
factor [cool-side]
164 Proportional band limiter
P6 7 R/W C TC/RTD inputs:
(high) [heat-side]
165 Proportional band limiter
P7 7 R/W C
(low) [heat-side]
166 Integral time limiter (high)
I6 7 R/W C PID control or Heat/Cool PID control:
[heat-side]
167 Integral time limiter (low)
I7 7 R/W C
[heat-side]
168 Derivative time limiter
D6 7 R/W C (high) [heat-side]
169 Derivative time limiter
D7 7 R/W C 0 (low) [heat-side]
170 Proportional band limiter
P8 7 R/W C TC/RTD inputs:
(high) [cool-side]
171 Proportional band limiter
P9 7 R/W C TC/RTD: 1 (0.1)
(low) [cool-side]
Digits
Attri-
bute
Struc-
ture
6. RKC COMMUNICATION
Data range
0.0 to 50.0 seconds 10.0
0 to Input span (Unit: C [F])
Varies with the setting of the decimal point position.
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of input span 0 (0.0): ON/OFF action
(ON/OFF action for both heat and cool actions in case of a Heat/Cool PID control type.)
0 to 3600 seconds or 0.0 to 1999.9 seconds Position proportioning PID control:
1 to 3600 seconds or 0.1 to 1999.9 seconds
Varies with the setting of the Integral/Derivative time decimal point position selection.
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the Integral/Derivative time decimal point position selection.
1 (0.1) to Input span (Unit: C [F])
Varies with the setting of the decimal point position.
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of input span
Factory
set value
TC/RTD:
Input span
V/I: 1000.0
TC/RTD: 0 (0.0)
V/I: 0.0
3600
PID control,
Heat/Cool PID
control: 0
Position proportioning PID control: 1
3600
TC/RTD:
Input span
V/I: 1000.0
V/I: 0.1
172 Integral time limiter (high)
[cool-side]
173 Integral time limiter (low)
[cool-side]
174 Derivative time limiter
(high) [cool-side]
175 Derivative time limiter
(low) [cool-side]
176 Open/Close output neutral
I8 7 R/W C 0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the Integral/Derivative time decimal
I9 7 R/W C 0
point position selection. If control is other than Heat/Cool PID control, set to RO
(Only reading data is possible).
D8 7 R/W C 0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the Integral/Derivative time decimal point position selection.
D9 7 R/W C 0
If control is other than Heat/Cool PID control, set to RO (Only reading data is possible).
3600
3600
V2 7 R/W C 0.1 to 10.0 % of output 2.0
zone
 Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Continued on the next page.
IMS01T04-E6 6-27
Page 86
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
177 Action at feedback
resistance (FBR) input error
178 Feedback adjustment  FV 1 R/W C 0: Adjustment end
179 Control motor time TN 7 R/W C 5 to 1000 seconds 10 180 Integrated output limiter OI 7 R/W C 0.0 to 200.0 % of control motor time
181 Valve action at STOP VS 1 R/W C
182 ST proportional band
adjusting factor
183 ST integral time adjusting
factor
184 ST derivative time
adjusting factor
185 ST start condition SU 1 R/W C
186 Automatic temperature rise
group
187 Automatic temperature rise
dead time
188 Automatic temperature rise
gradient data
189 EDS transfer time decimal
point position
190 Output average processing
time for EDS
191 Responsive action trigger
point for EDS
192 Setting change rate limiter
unit time
193 Soak time unit RU 1 R/W C
194 Setting limiter high SH 7 R/W C Setting limiter low to Input scale high
195 Setting limiter low SL 7 R/W C Input scale low to Setting limiter high
 Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Iden-
tifier
SY 1 R/W C 0: Action depending on the valve action at STOP
KI 7 R/W C 0.01 to 10.00 times 1.00
KJ 7 R/W C 0.01 to 10.00 times 1.00
KK 7 R/W C 0.01 to 10.00 times 1.00
Y7 7 R/W C 0 to 16
RT 7 R/W C 0.1 to 1999.9 seconds 10.0
R2 7 R/W C 1 (0.1) to Input span/minutes
NS 1 R/W C 0: 1 second setting (No decimal place)
NV 7 R/W C 0.1 to 200.0 seconds 1.0
NW 7 R/W C 0 to Input span
HU 7 R/W C 1 to 3600 seconds 60
Digits
Attri-
bute
Struc-
ture
1: Control action continued
1: During adjustment on the open-side 2: During adjustment on the close-side
(0.0: OFF)
Becomes invalid when there is Feedback resistance (FBR) input.
0: Close-side output OFF, Open-side output OFF 1: Close-side output ON, Open-side output OFF 2: Close-side output OFF, Open-side output ON
Becomes valid when there is no Feedback resistance (FBR) input or the Feedback resistance (FBR) input is disconnected.
0: Activate the Startup tuning (ST) function when the
power is turned on; when transferred from STOP to RUN; or when the Set value (SV) is changed.
1: Activate the Startup tuning (ST) function when the
power is turned on; or when transferred from STOP to RUN.
2: Activate the Startup tuning (ST) function when the
Set value (SV) is changed.
(0: Automatic temperature rise function OFF)
Varies with the setting of the decimal point position.
1: 0.1 seconds setting (One decimal place)
Varies with the setting of the decimal point position.
0: 0:00 to 99:59 (hrs:min) [0 hours 00 minutes to 99 hours 59 m inutes]
1: 0:00 to 199:59 (min:sec) [0 minutes 00 seconds to 199 minutes 59 seconds]
Set the data range of Memory area soak time monitor and Area soak time.
Varies with the setting of the decimal point position.
Varies with the setting of the decimal point position.
Data range
set value
TC/RTD: 1 (1.0)
Input scale high
Input scale low
Continued on the next page.
Factory
0
150.0
0
0
0
1 (1.0)
0
V/I: 1.0
1
6-28 IMS01T04-E6
Page 87
6. RKC COMMUNICATION
Continued from the previous page.
No. Name
196 PV transfer function
197 Operation mode
assignment 1 (Logic output selection function)
Logic output 1 to 4
198 Operation mode
assignment 2 (Logic output selection function)
Logic output 5 to 8
199 SV select function KM 1 R/W C 0: Remote SV function
200 Remote SV function
master channel module address
201 Remote SV function
master channel selection
202 Output distribution master
channel module address
203 Output distribution master
channel selection
204 Address of interacting
modules
205 Channel selection of
interacting modules
206 Selection switch of
interacting modules
207 Control RUN/STOP holding
setting
208 Interval time ZX 7 R/W M 0 to 250 ms 10
Iden-
tifier
TS 1 R/W C 0: Unused
EA 7 R/W C 0: No assignment
EB 7 R/W C 0: No assignment
MC 7 R/W C
MN 7 R/W C 1 to 99 1
DY 7 R/W C
DZ 7 R/W C 1 to 99 1
RL 7 R/W C
RM 7 R/W C
RN 7 R/W C Least significant digit: Memory area number
X1 1 R/W M 0: Not holding (STOP start)
Digits
Attri-
bute
Struc-
ture
1: Used
1: Operation mode (Monitor/Control) 2: Operation mode (Monitor  Event function/Control) 3: Auto/Manual 4: Remote/Local 5: Unused (Do not set this one)
1: Operation mode (Monitor/Control) 2: Operation mode (Monitor  Event function/Control) 3: Auto/Manual 4: Remote/Local 5: Unused (Do not set this one)
1: Cascade control function 2: Ratio setting function 3: Cascade control 2 function
1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other modules)
1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other modules)
1 (Interact with its own module address)
0 to 99
(Interact with the addresses of ot her modules)
1 to 99
Becomes valid when the selec ted module is “Z-TIO module.”
2nd digit: Operation mode 3rd digit: Auto/Manual 4th digit: Remote/Local 5th digit EDS start signal 6th digit Interlock release Most significant digit: Suspension of area soak time
Data 0: No interaction 1: Interact with other channels
1: Holding (RUN/STOP hold)
Data range
set value
Factory
0
0
0
0
1
1
1
1
0
1
IMS01T04-E6 6-29
Page 88
6. RKC COMMUNICATION

6.4.3 Communication data of Z-DIO module

No. Name
Model code
1
ROM version
2
3 Digital input (DI) state 1 L1 7 RO M
4 Digital input (DI) state 2 L6 7 RO M
5 Digital output (DO) state 1 Q2 7 RO M
6 Digital output (DO) state 2 Q3 7 RO M
Error code
7
8
Integrated operating time monitor
9
Backup memory state monitor
10 RUN/STOP transfer SR 1 R/W M
11 DO manual output 1 Q4 7 R/W M
12 DO manual output 2 Q5 7 R/W M
13 DO output distribution
selection DO output distribution bias
14
Iden-
tifier
ID 32 RO M Model code (character)
VR 8 RO M ROM version
ER 7 RO M 2: Data back-up error
UT 7 RO M 0 to 19999 hours
EM 1 RO M
DO 1 R/W C 0: DO output
O8 7 R/W C 100.0 to 100.0 % 0.0
Digits
Attri-
bute
Struc-
ture
Data range
Least significant digit: DI1 2nd digit: DI2 3rd digit: DI3 4th digit: DI4 5th digit to Most significant digit: Unused
Data 0: Least significant digit: DI5
2nd digit: DI6 3rd digit: DI7 4th digit: DI8 5th digit to Most significant digit: Unused
Data 0: Contact open 1: Contact closed Least significant digit: DO1
2nd digit: DO2 3rd digit: DO3 4th digit: DO4 5th digit to Most significant digit: Unused
Data 0: OFF 1: ON Least significant digit: DO5
2nd digit: DO6 3rd digit: DO7 4th digit: DO8 5th digit to Most significant digit: Unused
Data 0: OFF 1: ON
0: The content of the backup memory does not coincide with that of the RAM. 1: The content of the backup memory coincides with that of the RAM.
0: STOP (Control stop) 1: RUN (Control start)
Least significant digit: DO1 manual output 2nd digit: DO2 manual output 3rd digit: DO3 manual output 4th digit: DO4 manual output 5th digit to Most significant digit: Unused
Data 0: OFF 1: ON Least significant digit: DO5 manual output
2nd digit: DO6 manual output 3rd digit: DO7 manual output 4th digit: DO8 manual output 5th digit to Most significant digit: Unused
Data 0: OFF 1: ON
1: Distribution output
Contact open 1: Contact closed
Continued on the next page.
Factory
set value
0
0
0
0
6-30 IMS01T04-E6
Page 89
Continued from the previous page.
No. Name
DO output distribution ratio
15
DO proportional cycle time V0 7 R/W C 0.1 to 100.0 seconds
16
DO minimum ON/OFF
17
time of proportioning cycle
Set data No. 18 or later are for engineering setting [Writable in the STOP mode]
18 DI function assignment H2 7 R/W M 0 to 29
19 Memory area setting signal E1 1 R/W M 0: Valid
20 DO signal assignment
module address 1
21 DO signal assignment
module address 2
22 DO output assignment 1
[DO1 to DO4]
23 DO output assignment 2
[DO5 to DO8]
24 DO energized/de-energized NB 1 R/W C 0: Energized
25 DO output distribution
master channel module address
26 DO output distribution
master channel selection
27 DO manipulated output
value (MV) at STOP mode DO output limiter (high)
28
DO output limiter (low)
29
30 Control RUN/STOP
holding setting Interval time
31
Iden-
tifier
O9 7 R/W C 9.999 to 9.999 1.000
VJ 7 R/W C 0 to 1000 ms
LQ 7 R/W M 1, 0 to 99
LR 7 R/W M 1, 0 to 99
LT 7 R/W M 0 to 13
LX 7 R/W M 0 to 13
DD 7 R/W C
DJ 7 R/W C 1 to 99 1
OJ 7 R/W C 5.0 to 105.0 % 5.0
D3 7 R/W C DO output limiter (low) to 105.0 % 105.0
D4 7 R/W C 5.0 % to DO output limiter (high) 5.0
X1 1 R/W M 0: Not holding (STOP start)
ZX 7 R/W M 0 to 250 ms 10
Digits
Attri-
bute
Struc-
ture
(Refer to page 8-154)
1: Invalid
When “1” is selected, all of the signals of the same type (except temperature rise completion and DO manual output value) are OR-operated and produced as outp uts from DO.
When “1” is selected, all of the signals of the same type (except temperature rise completion and DO manual output value) are OR-operated and produced as outp uts from DO.
(Refer to page 8-158)
(Refer to page 8-158)
1: De-energized 1
(Master channel is selected from itself)
(Master channel is selected from other modules)
0 to 99
1: Holding (RUN/STOP hold)
Data range
6. RKC COMMUNICATION
Factory
set value
Relay contact
output: 20.0
Open collector
output: 2.0
0
Depends on model code
When not
specifying: 0
1
1
1
Depends on model code
When not
specifying: 0
Depends on model code
When not
specifying: 0
0
1
1
IMS01T04-E6 6-31
Page 90
MEMO
6-32 IMS01T04-E6
Page 91

MODBUS

7.1 Communication Protocol .................................................................. 7-2
7.1.1 Message format ........................................................................................ 7-2
7.1.2 Function code ........................................................................................... 7-3
7.1.3 Communication mode ............................................................................... 7-3
7.1.4 Slave responses ....................................................................................... 7-4
7.1.5 Calculating CRC-16 .................................................................................. 7-5
7.2 Register Read and Write .................................................................. 7-8
7.2.1 Read holding registers [03H] ................................................................... 7-8
7.2.2 Preset single register [06H] ..................................................................... 7-9
7.2.3 Diagnostics (Loopback test) [08H] ........................................................ 7-10
7.2.4 Preset multiple registers [10H] .............................................................. 7-11
7.3 Data Processing Precautions ......................................................... 7-12
7.4 How to Use Memory Area Data ...................................................... 7-13
7.5 How to Use Data Mapping .............................................................. 7-17
7.6 Communication Data List ............................................................... 7-18
7.6.1 Reference to communication data list ..................................................... 7-18
7.6.2 Communication data of Z-TIO module .................................................... 7-19
7.6.3 Communication data of Z-DIO module.................................................... 7-39
7.6.4 Memory are a data addr e ss (Z-TIO) ......................................................... 7-42
7.6.5 Data mappin g address (Z-TIO, Z-DIO) .................................................... 7-44
IMS01T04-E6 7-1
Page 92
7. MODBUS

7.1 Communication Protocol

The master controls communication between master and slave. A typical message consists of a request (query message) sent from the master followed by an answer (response message) from the slave (SRZ). When master begins data transmission, a set of data is sent to the slave in a fixed sequence. When it is received, the slave decodes it, takes the necessary action, and returns data to the master.
Data send/receive state can be monitored by using our communication tool (PROTEM2). The communication tool (PROTEM2) can be downloaded from the official RKC website: http://www.rkcinst.com/.

7.1.1 Message format

The message consists of four parts: slave address, function code, data, and error check code which are always transmitted in the same sequence.
Slave address Function code
Data
Error check CRC-16
Message format
Slave address
The slave address is a number from 0 to F manually set at the module address setting switch located at the front of the function module (Z-TIO, Z-DIO, Z-CT and Z-COM).
For details, refer to 5.1 Module Address Setting (P. 5-2).
Although all connected slave units receive the query message sent from the master, only the slave with the slave address coinciding with the query message will accept the message.
Function code
The function codes are the instructions set at the master and sent to the slave describing the action to be executed. The function codes are included when the slave responds to the master.
For details, refer to 7.1.2 Function code (P. 7-3).
Data
The data to execute the function specified by the function code is sent to the slave and corresponding data returned to the master from the slave.
For details, refer to 7.2 Register Read and Write (P. 7-8), 7.3 Data Processing Precautions (P. 7-12) and 7.6 Communication Data List (P. 7-18).
Error check
An error checking code (CRC-16: Cyclic Redundancy Check) is used to detect an error in the signal transmission.
For details, refer to 7.1.5 Calculating CRC-16 (P. 7-5).
7-2 IMS01T04-E6
Page 93

7.1.2 Function code

Function code contents
Function code (Hexadecimal)
03H Read holding registers Measured value, control output value, current transformer
06H Preset single register Set value, PID constants, event set value, etc. 08H Diagnostics (loopback test) Loopback test 10H Preset multiple registers Set value, PID constants, event set value, etc.
Message length of each function (Unit: byte)
Function code (Hexadecimal)
03H Read holding registers 8 8 7 255
Function Contents
Function
7. MODBUS
input measured value, Event status, etc.
Query message Response message
Min Max Min Max
06H Preset single register 8 8 8 8 08H Diagnostics (loopback test) 8 8 8 8 10H Preset multiple registers 11 255 8 8

7.1.3 Communication mode

Signal transmission between the master and slaves is conducted in Remote Terminal Unit (RTU) mode.
Items Contents
Data bit length 8-bit (Binary) Start mark of message Unused End mark of message Unused Message length Refer to 7.1.2 Function code Data time interval Less than 24-bit time * Error check CRC-16 (Cyclic Redundancy Check)
* When sending a command message from the master, set intervals of data configuring one message to time shorter than the 24-bit
time. If time intervals become time longer than the 24-bit time the relevant slave assumes that message sending from the master is terminated to deform the message format. As a result, the slave does not make a response.
IMS01T04-E6
7-3
Page 94
7. MODBUS

7.1.4 Slave responses

(1) Normal response
In the response message of the Read Holding Registers, the slave returns the read out data and the
number of data items with the same slave address and function code as the query message.
In the response message of the Preset Single Register, the slave returns the same message as the query
message.
In the response message of the Diagnostics (Loopback test), the slave returns the same message as the
query message.
In the response message of the Preset Multiple Registers, the slave returns the slave address, the function
code, starting number, and number of holding registers in the multi-query message.
(2) Defective message response
If the query message from the master is defective, except for
transmission error, the slave returns the error response message without any action.
If the self-diagnostic function of the slave detects an error, the slave
will return an error response message to all query messages.
The function code of each error response message is obtained by adding
80H to the function code of the query message.
Error code Contents
1 Function code error (An unsupported function code was specified) 2 When the mismatched address is specified. 3
4 Self-diagnostic error response
When the specified number of data items in the query message exceeds the maximum number of
data items available
When the data written exceeds the setting range
(3) No response
Slave address Function code
Error code
Error check CRC-16
Error response message
The slave ignores the query message and does not respond when:
The slave address in the query message does not coincide with any slave address settings. The CRC code of the master does not coincide with that of the slave.
Transmission error such as overrun, framing, parity and etc., is found in the query message. Data time interval in the query message from the master exceeds 24-bit time.
7-4
IMS01T04-E6
Page 95
7. MODBUS

7.1.5 Calculating CRC-16

The Cyclic Redundancy Check (CRC) is a 2 byte (16-bit) error check code. After constructing the data message, not including start, stop, or parity bit, the master calculates a CRC code and appends this to the end of the message. The slave will calculate a CRC code from the received message, and compare it with the CRC code from the master. If they do not match, a communication error has occurred and the slave does not respond.
The CRC code is formed in the following sequence:
1. Load FFFFH to a 16-bit CRC register.
2. Exclusive OR () the first byte (8 bits) of the message with the CRC register. Return the result to the
CRC register.
3. Shift the CRC register 1 bit to the right.
4. If the carry flag is 1, exclusive OR the CRC register with A001 hex and return the result to the CRC
register. If the carry flag is 0, repeat step 3.
5. Repeat step 3 and 4 until there have been 8 shifts.
6. Exclusive OR the next byte (8 bits) of the message with the CRC register.
7. Repeat step 3 through 6 for all bytes of the message (except the CRC).
8. The CRC register contains the 2 byte CRC error code. When they are appended to the message, the
low-order byte is appended first, followed by the high-order byte.
IMS01T04-E6
7-5
Page 96
7. MODBUS
The flow chart of CRC-16
START
FFFFH CRC Register
CRC Register next byte of the message
0 n
Shift CRC Register 1 bit to the right
Carry flag is 1
Yes
CRC Register
No
A001H CRC Register
n + 1  n
n 7
No
CRC Register
7-6
Yes
No
Reverse with high-order byte and low-order byte of CRC register
Is message
complete ?
Yes
END
The symbol indicates an exclusive OR operation. The symbol for the number of data bits is n.
IMS01T04-E6
Page 97
7. MODBUS
Example of a CRC calculation in the ‘C’ language
This routine assumes that the data types ‘uint16’ and ‘uint8’ exists. Theses are unsigned 16-bit integer (usually an ‘unsigned short int’ for most compiler types) and unsigned 8-bit integer (unsigned char). ‘z_p’ is a pointer to a Modbus message, and ‘z_messaage_length’ is its length, excluding the CRC. Note that the Modbus message will probably contain NULL characters and so normal C string handling techniques will not work.
uint16 calculate_crcbyte *z_p, unit16 z_message_length
/* CRC runs cyclic Redundancy Check Algorithm on input z_p */ /* Returns value of 16 bit CRC after completion and */ /* always adds 2 crc bytes to message */ /* returns 0 if incoming message has correct CRC */
{
uint16 CRC= 0xffff; uint16 next; uint16 carry; uint16 n; uint8 crch, crcl;
while (z_messaage_length--) {
next = (uint16) *z_p; CRC ^= next; for (n = 0; n < 8; n++) {
carry = CRC & 1; CRC >>= 1; if (carry) {
CRC ^= 0xA001;
} } z_p++;
} crch = CRC / 256; crcl = CRC % 256 z_p [z_messaage_length++] = crcl; z_p [z_messaage_length] = crch; return CRC;
}
IMS01T04-E6
7-7
Page 98
7. MODBUS
N
7.2 Register Read and Write

7.2.1 Read holding registers [03H]

The query message specifies the starting register address and quantity of registers to be read. The contents of the holding registers are entered in the response message as data, divided into two parts: the high-order 8-bit and the low-order 8-bit, arranged in the order of the register num bers.
Example: The contents of the four holding registers from 0000H to 0003H are the read out from slave
address 2.
Query message
Slave address 02H Function code 03H Starting No. High 00H
Quantity High 00H
CRC-16 High 44H Low 3AH
Normal response message
Slave address 02H Function code 03H Number of data 08H First holding register contents High 01H
Next holding register contents High 01H
Next holding register contents High 01H
Next holding register contents High 01H
CRC-16 High AAH Low F3H
Error response message
Slave address 02H 80H Function code Error code 03H CRC-16 High F1H Low 31H
Low 00H
Low 04H
Low
Low
Low
Low
24H
1BH
2BH
22H
83H
First holding register address
The setting must be between 1 (0001H) and 125 (007DH).
umber of holding registers  2
7-8 IMS01T04-E6
Page 99
7. MODBUS

7.2.2 Preset single register [06H]

The query message specifies data to be written into the designated holding register. The write data is arranged in the query message with high-order 8-bit first and low-order 8-bit next. Only R/W holding registers can be specified.
Example: Data is written into the holding register 008EH of slave address 1.
Query message
Slave address 01H Function code 06H Holding register number High 00H
Low
Write data High 00H
Low CRC-16 High E8H Low 0AH
Normal response message
Slave address 01H Function code 06H Holding register number High 00H
Low Write data High 00H
Low CRC-16 High E8H Low 0AH
Error response message
Slave address 01H 80H Function code Error code 02H CRC-16 High C3H Low A1H
8EH
64H
8EH
64H
86H
Any data within the range
Contents will be the same as query message data.
IMS01T04-E6
7-9
Page 100
7. MODBUS

7.2.3 Diagnostics (Loopback test) [08H]

The master’s query message will be returned as the response message from the slave. This function checks the communication system between the master and slave.
Example:
Query message
Slave address 01H Function code 08H Test code High 00H
Data High 1FH Low 34H CRC-16 High E9H Low ECH
Normal response message
Slave address 01H Function code 08H Test code High 00H Low 00H Data High 1FH Low 34H CRC-16 High E9H Low ECH
Error response message
Slave address 01H 80H Function code Error code 03H CRC-16 High 06H Low 01H
Loopback test for slave address 1
Low
00H
88H
Test code must be set to 00.
Any pertinent data
Contents will be the same as query message data.
7-10
IMS01T04-E6
Loading...