RKC INSTRUMENT SR Mini HG SYSTEM H-PCP-J Instruction Manual

SR Mini HG SYSTEM
Power Supply/CPU Module
PLC Communication
H-PCP-J
Instruction Manual
RKC INSTRUMENT INC.
®
IMS01J06-E1
Modbus is a registered trademark of Schneider Electric. The name of each programmable controller (PLC) means the products of each manufacturer. Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
All Rights Reserved, Copyright 2004, RKC INSTRUMENT INC.
Thank you for purchasing this RKC instrument. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference.
SYMBOLS

WARNING

CAUTION
!
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
: This mark indicates precautions that must be taken if there is danger of electric shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not taken, damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating procedures.
: This mark indicates supplemental information on installation, handling and operating procedures.
: This mark indicates where additional information may be located.
WARNING
!
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can occur and warranty is void under these conditions.
IMS01J06-E1
i-1

CAUTION

This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide
reinforced insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the
instrument or equipment.
All wiring must be in accordance with local codes and regulations. All wiring must be completed before power is turned on to prevent electric shock,
instrument failure, or incorrect action. The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines
from high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric
shock, fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation. Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument. Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration. RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some
components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
i-2
IMS01J06-E1
CONTENTS
1. OUTLINE............................................................................... 1
2. COMMUNICATION SPECIFICATIONS ................................ 3
3. CONNECTIONS .................................................................... 4
4. SETTING ON THE H-PCP-J MODULE SIDE ....................... 6
4.1 PLC Register Address Setting .........................................................................6
Page
4.2 Protocol Selection and Communication Setting...............................................8
4.3 PLC Scanning Time Setting.............................................................................9
5. SETTING ON THE PLC SIDE............................................. 10
6. COMMUNICATION DATA .................................................. 11
6.1 Request Command and Data Transfer..........................................................11
6.2 Data Processing Precautions ........................................................................15
6.3 Communication Data List...............................................................................17
7. DATA MAP.......................................................................... 24
7.1 Reference to Data Map .................................................................................24
7.2 Data Map List ................................................................................................25
7.2.1 GROFA-GM series............................................................................................. 25
7.2.2 MASTER-K series .............................................................................................. 31
IMS01J06-E1 i-3
MEMO
i-4 IMS01J06-E1
r

1. OUTLINE

This manual describes the communication function of the SR Mini HG SYSTEM and the LG Industrial Systems programmable controller (hereafter called PLC).
This manual is attached when the model code of H-PCP-J module is H-PCP-J--D -05E.
For details of the H-PCP-J module, see the Power Supply/CPU Module H-PCP-J Instruction Manual (IMS01J02-E).
The SR Mini HG SYSTEM can be connected to the LG Industrial Systems GLOFA-GM/MASTER-K series link unit without using any program. The SR Mini HG SYSTEM occupies the fixed area in the PLC data memory for each unit address. The control unit for SR Mini HG SYSTEM consists of the H-PCP-J module and temperature control function modules.
LG Industrial Systems
GLOFA-GM/MASTER-K
PLC
series
RS-422A
o
RS-232C
SR Mini HG SYSTEM
control unit
Converter
RS-422A
RS-422A
SR Mini HG SYSTEM
control unit
SR Mini HG SYSTEM
control unit
RS-422A
SR Mini HG SYSTEM
control unit
(Up to 4 units)
IMS01J06-E1 1
1. OUTLINE
Usable modules
(LG Industrial Systems GLOFA-GM series and MASTER-K series)
Name Type
Cnet I/F module G3L-CUEA (GLOFA-GM series and MASTER-K series)
G4L-CUEA (GLOFA-GM series and MASTER-K series) G6L-CUEC (GLOFA-GM series and MASTER-K series) G7L-CUEC (GLOFA-GM series and MASTER-K series) etc.
Usable modules (SR Mini HG SYSTEM)
The following function module data can be used in PLC communication (see “Data map” on page 24). In addition, data on other modules connected (TI, AI, AO, etc.) can be used on one more communication port (RKC communication or Modbus).
Function module Type
Temperature control module H-TIO-A H-TIO-B H-TIO-C H-TIO-D H-TIO-E
H-TIO-F H-TIO-G H-TIO-H H-TIO-J H-TIO-P H-TIO-R
Position proportioning control
H-TIO-K
module *
Speed control module * H-SIO-A
Cascade control module * H-CIO-A
Current transformer input
H-CT-A (Up to 20 points/control unit are available)
module
* There is restriction on usable data. Only data described in 6.3 Communication Data List (P. 17)
can be used.
For the function modules, see the Hardware Instruction Manual (IMSRM15-E).
2
IMS01J06-E1

2. COMMUNICATION SPECIFICATIONS

Interface: Based on RS-422A, EIA standard
Connection method: RS-422A: 4-wire system, multi-drop connection
Synchronous method: Start/stop synchronous type
Communication speed: 9600 bps, 19200 bps, 38400 bps
Communication speed can be selected with switch
Data bit configuration: Start bit: 1 Data bit: 8 Parity bit: Without Stop bit: 1
Protocol: Dedicated communication (LG Industrial Systems special protocol)
Station address 00
Usable command: WSB: Write continuous device RSB: Read continuous device
Specification mode: Mode 1 (Dedicated)
Maximum connections: 4 control units per communication port of PLC
IMS01J06-E1 3

3. CONNECTIONS

RS-422A
Pin layout of modular connector (RS-422A)
COM.PORT1
R (A)
1
R (B)
2
SG
3
T (B)
4
T (A)
5
SG
6
H-PCP-J module
Connector pin number and signal details (RS-422A)
Pin No. Signal name Symbol
1 Receive data R (A)
2 Receive data R (B)
3 Signal ground SG
4 Send data T (B)
5 Send data T (A)
6 Signal ground SG
4 IMS01J06-E1
k
Diagram of RS-422A wiring
H-PCP-J
Pair wire
3. CONNECTIONS
PLC
LG Industrial Systems
RS-422 Port
T (A)
T (B)
SG
R (A)
R (B)
SG
5
4
3
1
2
6
SDB
SDA
SG
RDB
RDA
Shielded twisted pair wire
The 6-pin type modular connector should be used for the connection to the H-PCP-J module. Recommended model: TM4P-66P (Manufactured by HIROSE ELECTRIC CO., LTD.,)
Customer is requested to prepare a communication cable fit for the control unit to be connected by the PLC. Connection cable W-BF-01 * (RKC product) can use to connect PLC.
* Shields of the cable are connected to SG (No. 6 pin) of the H-PCP-J connector.
A wiring example when using our W-BF-01 connection cable is shown in the following.
Cable type: W-BF-01-3000 (RKC product, Sold separately) [Standard cable length: 3 m]
PLC
LG Industrial Systems
RS-422 Port
H-PCP-J
W-BF-01
Connect to the [COM. PORT1]
Blac
Blue
Orange
White
Red
T (B)
T (A)
R (B)
R (A)
SG
The details of the connectable connector for the PLC please also read the instruction manual
SDA
SDB
RDA
RDB
SG
for the used PLC.
IMS01J06-E1
5
4.

SETTING ON THE H-PCP-J MODULE SIDE

4.1 PLC Register Address Setting

Set the file register address of each control unit using the unit address setting switch at the front of the H-PCP-J module. For this setting, use a small blade screwdriver.
Unit address setting switch
0
1
2
F
3
E
4
D
5
C
6
B
7
A
9
8
Setting range: 0 to 15 (0 to F: hexadecimal)
H-PCP-J module
Up to 4 SR Mini HG SYSTEMs can be connected to a PLC communication port. Therefore the file register address uses the 4 SR Mini HG SYSTEMs as a group. The SR Mini HG SYSTEMs connected to the same PLC communication port sets the address in the same group.
Set unit address of each group including 0, 4, 8 and C by all means. 0, 4, 8 and C work
as a master of communication transfer.
Set unit address within address range of PLC (CPU unit) to use.
Group Unit address
setting switch
Group 1
Group 2
Group 3
Group 4
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
PLC register address
for the GLOFA-GM series
PLC register address
for the MASTER-K series
MW0000 to MW0499 DW0000 to DW0499
MW0500 to MW0999 DW0500 to DW0999
MW1000 to MW1499 DW1000 to DW1499
MW1500 to MW1999 DW1500 to DW1999
MW2000 to MW2499 DW2000 to DW2499
MW2500 to MW2999 DW2500 to DW2999
MW3000 to MW3499 DW3000 to DW3499
MW3500 to MW3999 DW3500 to DW3999
MW4000 to MW4499 DW4000 to DW4499
MW4500 to MW4999 DW4500 to DW4999
MW5000 to MW5499 DW5000 to DW5499
MW5500 to MW5999 DW5500 to DW5999
MW6000 to MW6499 DW6000 to DW6499
MW6500 to MW6999 DW6500 to DW6999
MW7000 to MW7499 DW7000 to DW7499
MW7500 to MW7999 DW7500 to DW7999
6 IMS01J06-E1
4. SETTING ON THE H-PCP-J MODULE SIDE
A
Setting example: When group 2 is used (for the GLOFA-GM series)
PLC
SR Mini HG SYSTEM
control unit
Unit address 4
Register address:
MW2000 to MW2499
SR Mini HG SYSTEM
control unit
Unit address 5
Register address:
MW2500 to MW2999
SR Mini HG SYSTEM
control unit
Unit address 6
Register address:
MW3000 to MW3499
SR Mini HG SYSTEM
control unit
Unit address 7
Register address:
MW3500 to MW3999
ddress in the same group is set
IMS01J06-E1
7
4. SETTING ON THE H-PCP-J MODULE SIDE

4.2 Protocol Selection and Communication Setting

Match the setting of data bit configuration, communication speed and communication protocol with the PLC communication specification by COM.PORT1/COM.PORT2 setting switch (SW2). Setting example to recommend is shown in the following.
COM.PORT1/COM.PORT2
setting switch (SW2)
For the
GLOFA-GM
18765 43 2
series
ON
Data bit configuration
Communication speed (Set the same as PLC.)
Right side view
For the
Data bit configuration
SW2
Data bit configuration
1 2
OFF OFF Data 8-bit, Non parity, Stop 1-bit
Communication speed Set the same as PLC.
SW2
Communication speed
3 4
OFF OFF 9600 bps
Or
MASTER-K
1 8 76 5 4 32
Communication protocol
Factory set value: All OFF
series
ON
Data bit configuration
Communication speed (Set the same as PLC.)
Communication protocol
Factory set value: All OFF
8
ON OFF 19200 bps
OFF ON 38400 bps
ON ON Don't set this one
Continued on the next page.
IMS01J06-E1
4. SETTING ON THE H-PCP-J MODULE SIDE
Continued from the previous page.
Using register selection Select register corresponding to PLC.
SW2
Using register selection
5 6 7 8
OFF ON OFF ON
ON ON OFF ON
M register for the LG Industrial Systems GLOFA-GM series
D register for the LG Industrial Systems MASTER-K series

4.3 PLC Scanning Time Setting

Set the PLC scanning time (time of waiting for a response from the PLC) so as to adapt to the environment used. The PLC scanning time is set via host communication (RKC communication or Modbus).
PLC scanning time setting Setting range: 0 to 3000 ms (Factory set value: 10 ms)
[Setting example]
Set PLC scanning time to any value more than twice as long as the maximum scanning time of PLC.
If PLC scanning time is extremely short (When at a factory set value of 10 ms as an
example), the SR Mini HG SYSTEM may detect the time-out not conducting normal
communication processing.
The maximum scanning time of PLC differs depending on the CPU processing speed, I/O unit configuration and the user program capacity of the PLC.
For the PLC scanning time setting (Identifier ST), see the Power Supply/CPU Module H-PCP-J Instruction Manual (IMS01J02-E).
IMS01J06-E1
9

5. SETTING ON THE PLC SIDE

Set the PLC as follows. (Recommend setting example)
Item Description
Mode 1
Channel RS422 side
Station 00
Type RS422
Data bit 8
Parity bit Without
Stop bit 1
Transmission speed 38400 bps
Termination resistor Termination resistor is inserted
The setting item varies depending on the PLC. The details of the setting procedure for the PLC please also read the instruction manual for the used PLC.
10 IMS01J06-E1

6. COMMUNICATION DATA

6.1 Request Command and Data Transfer

Data transfer between PLC and SR Mini HG SYSTEM are executed by request command.
Request command “0: Monitor (PLC SR Mini HG SYSTEM)”
Command which requests the SR Mini HG SYSTEM to write data such as temperature measured values, etc. (attribute: RO) to the PLC side. The SR Mini HG SYSTEM always repeats data writing until “1: Setting” or “2: Set value monitor” is set to the request command. The PCP communication status is set to “1: Writing on monitor data” during data transfer.
Request command “1: Setting (PLC SR Mini HG SYSTEM)”
Command which requests the SR Mini HG SYSTEM to read data such as temperature set values, etc. (attribute: RW or WO) from the PLC side. Just when “1: Setting” is set to the request command, the SR Mini HG SYSTEM starts reading the data from the PLC side. The PCP communication status is set to “2: Reading out setting data” during data transfer. After the data is transferred, the request command and PCP communication status returns to “0: Monitor” and “1: Writing on monitor data,” respectively.
Request command “2: Set value monitor (PLC SR Mini HG SYSTEM)”
Command which requests the SR Mini HG SYSTEM to write data such as temperature set values, etc. (attribute: RW) to the PLC side. Just when “2: Set value monitor” is set to the request command, the SR Mini HG SYSTEM starts writing the data to the PLC side. The PCP communication status is set to “3: Writing on setting data” during data transfer. After the data is transferred, the request command and PCP communication status returns to “0: Monitor” and “1: Writing on monitor data,” respectively.
IMS01J06-E1 11
6. COMMUNICATION DATA
p
p
R
t
t
R
Data transfer procedures
Change each set value of SR Mini HG SYSTEM from the PLC after the initial settings
are made.
If each set value of SR Mini HG SYSTEM is changed from the PLC without setting the initial values, it is re-written to 0 with each set value of the PLC at that time set to 0.
Initial Setting (When transmit data of temperature setting values from SR Mini HG
SYSTEM to PLC)
Set “2” to the request command
NO
PCP communication
NO
PCP communication
Start
Turn on power of
each instrument
state = 3 ?
YES
Wait time
state = 1 ?
YES
End
When 2 (Set value monitor) is set to request command, the
SR Mini HG SYSTEM starts writing the data items
such as temperature set value, etc. (attribute: R/W) to the PLC side.
If 3 (Writing on setting data) is set to PCP communication state in the PLC, this indicates that
Mini HG SYSTEM data items such as temperature se
value, etc. (attribute: R/W) are being written into the PLC.
Reserve data write time as wait time. In addition,
rocess data in each item as indefinite during this eriod.
Waiting time (for 38400 bps):
1 second/control unit
If 1 (Writing on monitor data) is set to PCP communication state in the PLC, this indicates tha SRV data items such as temperature set value, etc. (attribute: R/W) have been written to start writing
Mini HG SYSTEM data items such as temperature
measured values (PV), etc. (attribute: RO) into the PLC.
S
S
12
IMS01J06-E1
6. COMMUNICATION DATA
R
t
t
t
t
p
p
Data setting (When transmit data of temperature setting values from PLC to SR Mini
HG SYSTEM)
Start
Set temperature set value (SV) and other setting data to each register (memory) in the PLC.
Set “1” to the request command
[Data setting]
When 1 (Setting) is set to request command, the
Mini HG SYSTEM starts reading the temperature se
value data set to the register (memory) on the PLC side.
NO
PCP communication
state = 2 ?
YES
If 2 (Reading out setting data) is set to PCP communication state in the PLC, this indicates tha temperature set values data are being read from the PLC.
Wait time
Reserve data read time as wait time. In addition,
rocess data in each item as indefinite during this eriod.
Waiting time (for 38400 bps):
2 seconds/control unit
NO
PCP communication
state = 1 ?
YES
If 1 (Writing on monitor data) is set to PCP communication state in the PLC, this indicates tha temperature set value data have been read to star writing SR Mini HG SYSTEM data items such as temperature measured values (PV) etc. (attribute: RO) into the PLC.
A
Continued on the next page.
S
IMS01J06-E1
13
6. COMMUNICATION DATA
R
t
t
p
p
Continued from the previous page.
A
Set “2” to the request command
NO
PCP communication
state = 3 ?
YES
Wait time
NO
PCP communication
state = 1 ?
YES
End
[Confirmation of setting data]
When 2 (Set value monitor) is set to request command,
SR Mini HG SYSTEM starts writing the temperature
the set value data set to the PLC side.
If 3 (Writing on setting data) is set to PCP communication state in the PLC, this indicates that
Mini HG SYSTEM temperature set value data are being
written into the PLC.
Reserve data write time as wait time. In addition,
rocess data in each item as indefinite during this eriod.
Waiting time (for 38400 bps):
1 second/control unit
If 1 (Writing on monitor data) is set to PCP communication state in the PLC, this indicates tha temperature set values have been written to star writing SR Mini HG SYSTEM data items such as temperature measured values (PV), etc. (attribute: RO) into the PLC.
S
14
IMS01J06-E1
6. COMMUNICATION DATA

6.2 Data Processing Precautions

With PLC communication, the maximum number of channels per unit address is 20.
Read data of unused channel and undefined address is 0.
The data type is treated as binary data with a sign and without a decimal point. For this reason,
carefully express and set the data. (excluding the TIO status)
[Example] Heat-side proportional band
Initial value of internal data: 3.0 Communication data: 30
If the data range error occurs during data setting, “Setting error” (bit 8 in the TIO status) is set to
ON in the channel where the error occurs. The SR Mini HG SYSTEM continues operation at the present set value without updating the data.
Any attempt to write to an unused channel is not processed as an error.
The autotuning (AT) function starts its execution with PID/AT transfer and the request command
set to “1: AT operation” and “1: Setting,” respectively. After the autotuning function finishes its execution, PID/AT transfer returns to “0: PID control operation” and thus the PID constants are updated.
When the PLC communication status is selected by selecting the H-PCP-J module DO type
(Identifier VU), the digital output (DO) is turned on or off according to the status of communication between the H-PCP-J module and PLC.
Communication error
When the communication is error after the power ON immediately
When the communication is error during operation
PLC communication status
(H-PCP-J module DO)
OFF “1: Monitor”
OFF
Operation mode
Same as mode before the
communication error
If communication between the H-PCP-J module and PLC is ready, the PLC communication status (H-PCP-J module DO) is turned on to enable operation to continue.
The H-PCP-J module DO type selection (Identifier VU) is set by host communication. For the host communication, see the Power Supply/CPU Module H-PCP-J Instruction
Manual (IMS01J02-E).
IMS01J06-E1
15
6. COMMUNICATION DATA
Some communication data may become invalid depending on the module selection or the
configuration of the SR Mini HG System control unit. If any one of the conditions listed below occurs and data items written are within the setting range, read data becomes 0. Under these conditions, no error response message will occur.
When heat/cool control, manual output value and auto/manual transfer are invalid.
When heat control, cool-side manipulated output, cool-side proportional band, overlap/deadband
and cool-side proportioning cycle time are invalid.
When ON/OFF control, cool-side manipulated output, heat-side and cool-side proportional band, integral time, derivative time, overlap/deadband and cool-side proportioning cycle time are invalid.
When the H-CT-A module is not provided, current transformer input measured value 2, heater break alarm set value 2 and CT channel setting are invalid.
16
IMS01J06-E1

6.3 Communication Data List

Name
: Item stored in the memory area. [ ]: The functional module name that data becomes valid is written.
Attributes RO: At the time of request command “0: Monitor,” SR Mini HG SYSTEM writes in data.
(SR Mini HG SYSTEM PLC)
R/W: At the time of request command “1: Setting,” SR Mini HG SYSTEM read out data.
At the time of request command “2: Set value monitor,” SR Mini HG SYSTEM writes in data. (SR Mini HG SYSTEM PLC)
WO: At the time of request command “1: Setting,” SR Mini HG SYSTEM read out data.
(SR Mini HG SYSTEM PLC)
Structure C: Data for each channel U: Data for each unit address
Name
Attri-
bute
Struc-
ture
Data range
6. COMMUNICATION DATA
Factory
set value
Temperature set value (SV) [H-TIO-, H-CIO-A]
R/W C
TC/RTD input:
Within input range (Within setting limiter)
Current/voltage input:
Within display scale range (Within setting limiter)
Motor speed set value [H-SIO-A]
Alarm 1 set value [H-TIO-, H-CIO-A, H-SIO-A]
Alarm 2 set value
R/W C
R/W C
Within display scale range
(Within setting limiter)
TC/RTD input:
Within input range or span range
Current/voltage input, H-SIO-A: Within display scale range or span range
[H-TIO-, H-CIO-A, H-SIO-A]
* Factory set value table of Alarm 1/Alarm 2 set value
Input type Alarm type Alarm 1 set value Alarm 2 set value
TC/RTD input
Current/voltage input
Process low alarm 0.0 % 0.0 % Deviation high alarm, Deviation
Deviation low alarm
No alarm function 100.0 % 0.0 %
Process high alarm Input range (high limit) Input range (high limit) Process low alarm Input range (low limit) Input range (low limit) Deviation high alarm, Deviation
high/low alarm, Band alarm Deviation low alarm
No alarm function Input range (high limit) Input range (low limit) Process high alarm 100.0 % 100.0 %
high/low alarm, Band alarm
50 °C 50 °C
50 °C 50 °C
50 % 50 %
50 % 50 %
Continued on the next page.
0
The position of the decimal point differs depending on the input range.
See Factory
set value table of Alarm 1/ Alarm 2 set value *
IMS01J06-E1
17
6. COMMUNICATION DATA
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Heater break alarm set value [H-CT-A]
Operation mode transfer [H-TIO-, H-CIO-A, H-SIO-A]
R/W C
R/W C
0.0 to 100.0 A or 0.0 to 30.0 A
For the current transformer (CT) input of the H-CT-A module.
Allocates the channels for H-TIO- module to the input channels of H-CT-A module by CT channel setting. For the CT channel setting, see the Power
Supply/CPU Module H-PCP-J Instruction Manual (IMS01J02-E).
0: Unused
If set to “Unused,” no control, monitor or alarm monitor is performed.
1: Monitor
If set to “Monitor,” only the monitor is performed. No control or alarm monitor is performed.
2: Alarm
If set to “Alarm,” monitor or alarm monitor is performed. No control is performed.
3: Normal
Selected to normal mode to perform control, monitor or alarm monitor.
0.0
3
Auto/Manual transfer [H-TIO-, H-CIO-A]
Manual output value [H-TIO-, H-CIO-A]
Overlap/deadband [H-TIO-, H-CIO-A]
Heat-side proportional band [H-TIO-, H-CIO-A, H-SIO-A]
Cool-side proportional band [H-TIO-, H-CIO-A]
R/W C
0: Auto
0
1: Manual
Setting will be invalid in ON/OFF control and heat/cool control.
R/W C
5.0 to +105.0 %
0.0
Setting will be invalid in ON/OFF control and heat/cool control.
R/W C −10.0 to +10.0 % of span 0.0
R/W C 0.1 to 1000.0 % of span
H-TIO-, H-CIO-A:
3.0 H-SIO-A:
300.0
R/W C 0.1 to 1000.0 % of span 3.0
Continued on the next page.
18
IMS01J06-E1
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
6. COMMUNICATION DATA
Factory
set value
Integral time [H-TIO-, H-CIO-A, H-SIO-A]
R/W C 1 to 3600 seconds
H-TIO-, H-CIO-A: 240 H-SIO-A: 2
Derivative time [H-TIO-, H-CIO-A, H-SIO-A]
R/W C 0 to 3600 seconds (0: PI action)
H-TIO-, H-CIO-A: 60 H-SIO-A: 0
PID/AT transfer * [H-TIO-, H-CIO-A, H-SIO-A]
R/W C
0: PID control operation 1: AT (Autotuning) operation
The autotuning (AT) function starts its
0
execution with PID/AT transfer and the request command set to “1: AT operation” and “1: Setting,” respectively. After the autotuning function finishes its execution, PID/AT transfer returns to “0: PID control operation.”
* Autotuning (AT) is the function which automatically measures, calculates and sets the optimum PID
constants according to the set temperature.
Caution for using the Autotuning (AT) When a temperature change (UP and/or Down) is 1C or less per minute during Autotuning, Autotuning may be cancelled before calculating PID values. In that case, adjust the PID values manually. It is possible to happen when the set value is around the ambient temperature or is close to the maximum temperature achieved by the load.
The following is the conditions necessary to carry out autotuning and the conditions which will cause the autotuning to stop.
Conditions necessary for autotuning: The autotuning should be executed after satisfying all of the following conditions:
Operation mode conditions:
Auto/Manual transfer Auto mode
PID/AT transfer PID control mode
Control RUN/STOP transfer Control RUN mode
The measured value (PV) is without input error range [Input error determination point (high) > Measured value (PV) > Input error determination point (low)].
The output limiter high limit should be more than 0.1 % and the output limiter low limit should be
less than 99.9 %.
When operation mode is set to “Normal (Can be controlled ).”
When the autotuning is finished, the display of each channel automatically returns to “0: PID control operation.”
Continued on the next page.
IMS01J06-E1
19
6. COMMUNICATION DATA
Continued from the previous page.
Conditions which will cause the autotuning to stop:
When the temperature set value (SV) is changed.
When the memory area is changed.
When the PV bias value is changed.
When the AT bias value is changed.
When transfer to Manual mode using the Auto/Manual transfer.
When the measured value (PV) goes to input error range [Measured value (PV) Input error determination point (high) or Input error determination point (low) Measured value (PV)].
When the power is cut off.
When FAIL occurs in the module whose channel is under the autotuning. Otherwise, when FAIL
occurs in the H-PCP-J module.
When transfer to the PID control mode by the PID/AT transfer.
When operation mode is set to “Unused,” “Monitor” or “Alarm.”
When the Control RUN/STOP function is changed to the “Control STOP” function.
When the above-mentioned conditions to stop the autotuning occurs, the autotuning is immediately stopped and switch over to the PID control mode. The PID constants return to the values at the start of the autotuning.
20
Continued on the next page.
IMS01J06-E1
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
6. COMMUNICATION DATA
Factory
set value
Temperature measured value (PV) [H-TIO-, H-CIO-A]
Motor speed measured value [H-SIO-A]
Heat-side manipulated output value [H-TIO-, H-CIO-A]
Cool-side manipulated output value [H-TIO-, H-CIO-A]
Current transformer input measured value [H-CT-A]
TIO status [H-TIO-, H-CIO-A, H-SIO-A]
Set value monitor [H-TIO-, H-CIO-A, H-SIO-A]
RO C
TC/RTD input:
Current/voltage input:
RO C
RO C
RO C
Within display scale range
0.5 to +105.0 %
0.5 to +105.0 %
0.0 to 100.0 A or 0.0 to 30.0 A Current transformer (CT) input measured
value of the H-CT-A module. Allocates the channels for H-TIO- module to the input channels of H-CT-A module by CT channel setting. For the CT channel setting, see the Power
Supply/CPU Module H-PCP-J Instruction Manual (IMS01J02-E).
RO C
Each operation status is assigned as a bit image in binary numbers.
Bit data
Data 0: OFF 1: ON
Bit image: 0000000000000000 [Decimal number: 0 to 509]
RO C
TC/RTD input:
Current/voltage input:
Within input range
Within display scale range
bit 0: Heat-side manipulated output status bit 1: Unused bit 2: Alarm 1 status bit 3: Alarm 2 status bit 4: Burnout status bit 5: Heater break alarm status bit 6: Control loop break alarm (LBA) status bit 7: Temperature rise completion status bit 8: Setting error bit 9 to 15: Unused
bit 15·························· bit 0
Within input range
Within display scale range
Continued on the next page.
IMS01J06-E1
21
6. COMMUNICATION DATA
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Request command [H-PCP-J]
R/W U
0: Monitor
Command which requests the SR Mini HG SYSTEM to write data such as temperature measured values, etc. (attribute: RO) to the PLC side. The SR Mini HG SYSTEM always repeats data writing until “1: Setting” or “2: Set value monitor” is set to the request command. The PCP communication status is set to “1: Writing on monitor data” during data transfer.
1: Setting
Command which requests the SR Mini HG SYSTEM to read data such as temperature set values, etc. (attribute: RW or WO) from the PLC side. Just when “1: Setting” is set to the request command, the SR Mini HG SYSTEM starts reading the data from the PLC side. The PCP communication status is set to “2: Reading out setting data” during data transfer. After the data is transferred, the request command and PCP communication status returns to “0: Monitor” and “1: Writing on monitor data,” respectively.
2: Set value monitor
Command which requests the SR Mini HG SYSTEM to write data such as temperature set values, etc. (attribute: RW) to the PLC side. Just when “2: Set value monitor” is set to the request command, the SR Mini HG SYSTEM starts writing the data to the PLC side. The PCP communication status is set to “3: Writing on setting data” during data transfer. After the data is transferred, the request command and PCP communication status returns to “0: Monitor” and “1: Writing on monitor data,” respectively.
0
PCP communication status [H-PCP-J]
22
RO U
1: Writing on monitor data
2: Reading out setting data
3: Writing on setting data
During monitor data of attribute RO is written to PLC
During setting data of attribute R/W or WO is read from PLC
During setting data of attribute R/W is written to PLC
Continued on the next page.
IMS01J06-E1
Continued from the previous page.
Name
Attri-
bute
PCP normal communication flag [H-PCP-J]
Memory area number [H-TIO-, H-CIO-A, H-SIO-A]
Control RUN/STOP transfer * [H-PCP-J]
PV bias [H-TIO-, H-CIO-A, H-SIO-A]
RO
Struc-
ture
U
The numbers 0 and then 1 are repeated in
Data range
every communication period.
The SR Mini HG SYSTEM rewrites 0 and 1 in this area alternately like 0 1 0 in every communication period. It is possible to determine whether or not the SR Mini HG SYSTEM makes communication by monitoring this area periodically using the PLC program.
WO U
1 to 8 Data reading is always made from the PLC
regardless of the request command. Any numeric value other than 1 to 8 becomes invalid. Changing the memory area automatically writes each set value to the PLC.
WO U
0: Control STOP 1: Control RUN
R/W C −5.00 to +5.00 % of span
ZK-1103 specification:
Input span to +Input span
6. COMMUNICATION DATA
Factory
set value
0.00
ZK-1103:
a
0
Setting change rate
R/W C 0.0 to 100.0 % of span/minute 0.0
limiter [H-TIO-, H-CIO-A, H-SIO-A]
When the control RUN/STOP holding setting is set to “Not hold” or “Hold”:
*
The control RUN/STOP transfer setting is always read from the PLC regardless of the request command. Any numeric value other than 0 and 1 becomes invalid.
When the control RUN/STOP holding setting is set to “Start-up from control RUN status”:
As the control RUN/STOP transfer setting is always set to “1: Control RUN,” any value set to the control RUN/STOP transfer becomes invalid.
The Control RUN/STOP holding (Identifier X1) is set by host communication. For the host communication, see the Power Supply/CPU Module H-PCP-J Instruction Manual (IMS01J02-E).
a
Unit (°C, °F, etc.) and decimal point position (No decimal place, One decimal place, Two decimal places or Three decimal places) depends on input range type.
IMS01J06-E1
23

7. DATA MAP

7.1 Reference to Data Map

This data map summarizes the data (M register and D register) addresses, channels and names that can be used with PLC. For details on each data range, see the 6.3 Communication Data List (P. 17).
(a)
(c)
Unit
address
0
MW0000 to MW0019 MW0020 to MW0039
Unit
address
1
MW0500 to MW0519 MW0520 to MW0539
Unit
address
2
MW1000 to MW1019 MW1020 to MW1039
(a) Unit address: Unit address of SR Mini HG SYSTEM
(b) Name: Data names
(c) Address: Data (M register and D register) addresses
Register address is expressed in decimal number M register: GLOFA-GM series D register: MASTER-K series
Unit
address
3
MW1500 to MW1519 MW1520 to MW1539
Temperature set value (SV) CH1 to CH20 Alarm 1 set value CH1 to CH20
(b)
Name
24 IMS01J06-E1

7.2 Data Map List

7.2.1 GLOFA-GM series

Unit address 0 to 3 (Group 1)
Unit
address
0
MW0000 to MW0019 MW0020 to MW0039 MW0040 to MW0059 MW0060 to MW0079
MW0080 to MW0099 MW0100 to MW0119 MW0120 to MW0139 MW0140 to MW0159 MW0160 to MW0179 MW0180 to MW0199 MW0200 to MW0219 MW0220 to MW0239 MW0240 to MW0259 MW0260 to MW0279 MW0280 to MW0299 MW0300 to MW0319 MW0320 to MW0339
MW0340 to MW0359 MW0360 to MW0379
MW0380 MW0880 MW1380 MW1880 Request command
MW0381 MW0881 MW1381 MW1881 PCP communication status
Unit
address
1
MW0500 to MW0519 MW0520 to MW0539 MW0540 to MW0559 MW0560 to MW0579
MW0580 to MW0599 MW0600 to MW0619 MW0620 to MW0639 MW0640 to MW0659 MW0660 to MW0679 MW0680 to MW0699 MW0700 to MW0719 MW0720 to MW0739 MW0740 to MW0759 MW0760 to MW0779 MW0780 to MW0799 MW0800 to MW0819 MW0820 to MW0839
MW0840 to MW0859 MW0860 to MW0879
Unit
address
2
MW1000 to MW1019 MW1020 to MW1039 MW1040 to MW1059 MW1060 to MW1079
MW1080 to MW1099 MW1100 to MW1119 MW1120 to MW1139 MW1140 to MW1159 MW1160 to MW1179 MW1180 to MW1199 MW1200 to MW1219 MW1220 to MW1239 MW1240 to MW1259 MW1260 to MW1279 MW1280 to MW1299 MW1300 to MW1319 MW1320 to MW1339
MW1340 to MW1359 MW1360 to MW1379
Unit
address
3
MW1500 to MW1519 MW1520 to MW1539 MW1540 to MW1559 MW1560 to MW1579
MW1580 to MW1599 MW1600 to MW1619 MW1620 to MW1639 MW1640 to MW1659 MW1660 to MW1679 MW1680 to MW1699 MW1700 to MW1719 MW1720 to MW1739 MW1740 to MW1759 MW1760 to MW1779 MW1780 to MW1799 MW1800 to MW1819 MW1820 to MW1839
MW1840 to MW1859 MW1860 to MW1879
Name
Temperature set value (SV) CH1 to CH20
Alarm 1 set value CH1 to CH20
Alarm 2 set value CH1 to CH20
Heater break alarm set value (H-CT-A module) CH1 to CH20
Operation mode transfer CH1 to CH20
Auto/Manual transfer CH1 to CH20
Manual output value CH1 to CH20
Overlap/deadband CH1 to CH20
Heat-side proportional band CH1 to CH20
Cool-side proportional band CH1 to CH20
Integral time CH1 to CH20
Derivative time CH1 to CH20
PID/AT transfer CH1 to CH20
Temperature measured value (PV) CH1 to CH20 Heat-side manipulated output value CH1 to CH20 Cool-side manipulated output value CH1 to CH20 Current transformer input measured value (H-CT-A module) CH1 to CH20
TIO status CH1 to CH20
Set value monitor CH1 to CH20
Continued on the next page.
7. DATA MAP
IMS01J06-E1 25
7. DATA MAP
Continued from the previous page.
Unit
address
0
Unit
address
1
Unit
address
2
Unit
address
3
Name
MW0382 MW0882 MW1382 MW1882 PCP normal communication flag
MW0383 to MW0389
MW0883 to MW0889
MW1383 to MW1389
MW1883 to MW1889
Do not use this address range
MW0390 MW0890 MW1390 MW1890 Memory area number
MW0391 MW0891 MW1391 MW1891 Control RUN/STOP transfer
MW0392 to MW0399 MW0400 to MW0419 MW0420 to MW0439 MW0440 to MW0499
MW0892 to MW0899 MW0900 to MW0919 MW0920 to MW0939 MW0940 to MW0999
MW1392 to MW1399 MW1400 to MW1419 MW1420 to MW1439 MW1440 to MW1499
MW1892 to MW1899 MW1900 to MW1919 MW1920 to MW1939 MW1940 to MW1999
Do not use this address range
PV bias CH1 to CH20
Setting change rate limiter CH1 to CH20
Do not use this address range
Unit address 4 to 7 (Group 2)
Unit
address
4
MW2000 to MW2019 MW2020 to MW2039 MW2040 to MW2059 MW2060 to MW2079
MW2080 to MW2099 MW2100 to MW2119 MW2120 to MW2139 MW2140 to MW2159 MW2160 to MW2179 MW2180 to MW2199 MW2200 to MW2219
Unit
address
5
MW2500 to MW2519 MW2520 to MW2539 MW2540 to MW2559 MW2560 to MW2579
MW2580 to MW2599 MW2600 to MW2619 MW2620 to MW2639 MW2640 to MW2659 MW2660 to MW2679 MW2680 to MW2699 MW2700 to MW2719
Unit
address
6
MW3000 to MW3019 MW3020 to MW3039 MW3040 to MW3059 MW3060 to MW3079
MW3080 to MW3099 MW3100 to MW3119 MW3120 to MW3139 MW3140 to MW3159 MW3160 to MW3179 MW3180 to MW3199 MW3200 to MW3219
Unit
address
7
MW3500 to MW3519 MW3520 to MW3539 MW3540 to MW3559 MW3560 to MW3579
MW3580 to MW3599 MW3600 to MW3619 MW3620 to MW3639 MW3640 to MW3659 MW3660 to MW3679 MW3680 to MW3699 MW3700 to MW3719
Name
Temperature set value (SV) CH1 to CH20
Alarm 1 set value CH1 to CH20
Alarm 2 set value CH1 to CH20
Heater break alarm set value (H-CT-A module) CH1 to CH20
Operation mode transfer CH1 to CH20
Auto/Manual transfer CH1 to CH20
Manual output value CH1 to CH20
Overlap/deadband CH1 to CH20
Heat-side proportional band CH1 to CH20
Cool-side proportional band CH1 to CH20
Integral time CH1 to CH20
Continued on the next page.
26
IMS01J06-E1
Continued from the previous page.
Unit
address
4
MW2220 to MW2239 MW2240 to MW2259 MW2260 to MW2279 MW2280 to MW2299 MW2300 to MW2319 MW2320 to MW2339
MW2340 to MW2359 MW2360 to MW2379
Unit
address
5
MW2720 to MW2739 MW2740 to MW2759 MW2760 to MW2779 MW2780 to MW2799 MW2800 to MW2819 MW2820 to MW2839
MW2840 to MW2859 MW2860 to MW2879
Unit
address
6
MW3220 to MW3239 MW3240 to MW3259 MW3260 to MW34279 MW3280 to MW3299 MW3300 to MW3319 MW3320 to MW3339
MW3340 to MW3359 MW3360 to MW3379
Unit
address
7
MW3720 to MW3739 MW3740 to MW3759 MW3760 to MW3779 MW3780 to MW3799 MW3800 to MW3819 MW3820 to MW3839
MW3840 to MW3859 MW3860 to MW3879
Name
Derivative time CH1 to CH20
PID/AT transfer CH1 to CH20
Temperature measured value (PV) CH1 to CH20 Heat-side manipulated output value CH1 to CH20 Cool-side manipulated output value CH1 to CH20 Current transformer input measured value (H-CT-A module) CH1 to CH20
TIO status CH1 to CH20
Set value monitor CH1 to CH20
MW2380 MW2880 MW3380 MW3880 Request command
MW2381 MW2881 MW3381 MW3881 PCP communication status
MW2382 MW2882 MW3382 MW3882 PCP normal communication flag
MW2383 to MW2389
MW2883 to MW2889
MW3383 to MW3389
MW3883 to MW3889
Do not use this address range
MW2390 MW2890 MW3390 MW3890 Memory area number
MW2391 MW2891 MW3391 MW3891 Control RUN/STOP transfer
MW2392 to MW2399 MW2400 to MW2419 MW2420 to MW2439 MW2440 to MW2499
MW2892 to MW2899 MW2900 to MW2919 MW2920 to MW2939 MW2940 to MW2999
MW3392 to MW3399 MW3400 to MW3419 MW3420 to MW3439 MW3440 to MW3499
MW3892 to MW3899 MW3900 to MW3919 MW3920 to MW3939 MW3940 to MW3999
Do not use this address range
PV bias CH1 to CH20
Setting change rate limiter CH1 to CH20
Do not use this address range
7. DATA MAP
IMS01J06-E1
27
7. DATA MAP
Unit address 8 to B (Group 3)
Unit
address
8
MW4000 to MW4019 MW4020 to MW4039 MW4040 to MW4059 MW4060 to MW4079
MW4080 to MW4099 MW4100 to MW4119 MW4120 to MW4139 MW4140 to MW4159 MW4160 to MW4179 MW4180 to MW4199 MW4200 to MW4219 MW4220 to MW4239 MW4240 to MW4259 MW4260 to MW4279 MW4280 to MW4299 MW4300 to MW4319 MW4320 to MW4339
MW4340 to MW4359 MW4360 to MW4379
MW4380 MW4880 MW5380 MW5880 Request command
MW4381 MW4881 MW5381 MW5881 PCP communication status
MW4382 MW4882 MW5382 MW5882 PCP normal communication flag
MW4383 to MW4389
Unit
address
9
MW4500 to MW4519 MW4520 to MW4539 MW4540 to MW4559 MW4560 to MW4579
MW4580 to MW4599 MW4600 to MW4619 MW4620 to MW4639 MW4640 to MW4659 MW4660 to MW4679 MW4680 to MW4699 MW4700 to MW4719 MW4720 to MW4739 MW4740 to MW4759 MW4760 to MW4779 MW4780 to MW4799 MW4800 to MW4819 MW4820 to MW4839
MW4840 to MW4859 MW4860 to MW4879
MW4883 to MW4889
Unit
address
A
MW5000 to MW5019 MW5020 to MW5039 MW5040 to MW5059 MW5060 to MW5079
MW5080 to MW5099 MW5100 to MW5119 MW5120 to MW5139 MW5140 to MW5159 MW5160 to MW5179 MW5180 to MW5199 MW5200 to MW5219 MW5220 to MW5239 MW5240 to MW5259 MW5260 to MW5279 MW5280 to MW5299 MW5300 to MW5319 MW5320 to MW5339
MW5340 to MW5359 MW5360 to MW5379
MW5383 to MW5389
Unit
address
B
MW5500 to MW5519 MW5520 to MW5539 MW5540 to MW5559 MW5560 to MW5579
MW5580 to MW5599 MW5600 to MW5619 MW5620 to MW5639 MW5640 to MW5659 MW5660 to MW5679 MW5680 to MW5699 MW5700 to MW5719 MW5720 to MW5739 MW5740 to MW5759 MW5760 to MW5779 MW5780 to MW5799 MW5800 to MW5819 MW5820 to MW5839
MW5840 to MW5859 MW5860 to MW5879
MW5883 to MW5889
Name
Temperature set value (SV) CH1 to CH20
Alarm 1 set value CH1 to CH20
Alarm 2 set value CH1 to CH20
Heater break alarm set value (H-CT-A module) CH1 to CH20
Operation mode transfer CH1 to CH20
Auto/Manual transfer CH1 to CH20
Manual output value CH1 to CH20
Overlap/deadband CH1 to CH20
Heat-side proportional band CH1 to CH20
Cool-side proportional band CH1 to CH20
Integral time CH1 to CH20
Derivative time CH1 to CH20
PID/AT transfer CH1 to CH20
Temperature measured value (PV) CH1 to CH20 Heat-side manipulated output value CH1 to CH20 Cool-side manipulated output value CH1 to CH20 Current transformer input measured value (H-CT-A module) CH1 to CH20
TIO status CH1 to CH20
Set value monitor CH1 to CH20
Do not use this address range
Continued on the next page.
28
IMS01J06-E1
Continued from the previous page.
Unit
address
8
Unit
address
9
Unit
address
A
Unit
address
B
Name
MW4390 MW4890 MW5390 MW5890 Memory area number
MW4391 MW4891 MW5391 MW5891 Control RUN/STOP transfer
MW4392 to MW4399 MW4400 to MW4419 MW4420 to MW4439 MW4440 to MW4499
MW4892 to MW4899 MW4900 to MW4919 MW4920 to MW4939 MW4940 to MW4999
MW5392 to MW5399 MW5400 to MW5419 MW5420 to MW5439 MW5440 to MW5499
MW5892 to MW5899 MW5900 to MW5919 MW5920 to MW5939 MW5940 to MW5999
Do not use this address range
PV bias CH1 to CH20
Setting change rate limiter CH1 to CH20
Do not use this address range
Unit address C to F (Group 4)
Unit
address
C
MW6000 to MW6019 MW6020 to MW6039 MW6040 to MW6059 MW6060 to MW6079
MW6080 to MW6099 MW6100 to MW6119 MW6120 to MW6139 MW6140 to MW6159 MW6160 to MW6179 MW6180 to MW6199 MW6200 to MW6219 MW6220 to MW6239 MW6240 to MW6259
Unit
address
D
MW6500 to MW6519 MW6520 to MW6539 MW6540 to MW6559 MW6560 to MW6579
MW6580 to MW6599 MW6600 to MW6619 MW6620 to MW6639 MW6640 to MW6659 MW6660 to MW6679 MW6680 to MW6699 MW6700 to MW6719 MW6720 to MW6739 MW6740 to MW6759
Unit
address
E
MW7000 to MW7019 MW7020 to MW7039 MW7040 to MW7059 MW7060 to MW7079
MW7080 to MW7099 MW7100 to MW7119 MW7120 to MW7139 MW7140 to MW7159 MW7160 to MW7179 MW7180 to MW7199 MW7200 to MW7219 MW7220 to MW7239 MW7240 to MW7259
Unit
address
F
MW7500 to MW7519 MW7520 to MW7539 MW7540 to MW7559 MW7560 to MW7579
MW7580 to MW7599 MW7600 to MW7619 MW7620 to MW7639 MW7640 to MW7659 MW7660 to MW7679 MW7680 to MW7699 MW7700 to MW7719 MW7720 to MW7739 MW7740 to MW7759
Name
Temperature set value (SV) CH1 to CH20
Alarm 1 set value CH1 to CH20
Alarm 2 set value CH1 to CH20
Heater break alarm set value (H-CT-A module) CH1 to CH20
Operation mode transfer CH1 to CH20
Auto/Manual transfer CH1 to CH20
Manual output value CH1 to CH20
Overlap/deadband CH1 to CH20
Heat-side proportional band CH1 to CH20
Cool-side proportional band CH1 to CH20
Integral time CH1 to CH20
Derivative time CH1 to CH20
PID/AT transfer CH1 to CH20
Continued on the next page.
7. DATA MAP
IMS01J06-E1
29
7. DATA MAP
Continued from the previous page.
Unit
address
C
MW6260 to MW6279 MW6280 to MW6299 MW6300 to MW6319 MW6320 to MW6339
MW6340 to MW6359 MW6360 to MW6379
Unit
address
D
MW6760 to MW6779 MW6780 to MW6799 MW6800 to MW6819 MW6820 to MW6839
MW6840 to MW6859 MW6860 to MW6879
Unit
address
E
MW7260 to MW7279 MW7280 to MW7299 MW7300 to MW7319 MW7320 to MW7339
MW7340 to MW7359 MW7360 to MW7379
Unit
address
F
MW7760 to MW7779 MW7780 to MW7799 MW7800 to MW7819 MW7820 to MW7839
MW7840 to MW7859 MW7860 to MW7879
Name
Temperature measured value (PV) CH1 to CH20 Heat-side manipulated output value CH1 to CH20 Cool-side manipulated output value CH1 to CH20 Current transformer input measured value (H-CT-A module) CH1 to CH20
TIO status CH1 to CH20
Set value monitor CH1 to CH20
MW6380 MW6880 MW7380 MW7880 Request command
MW6381 MW6881 MW7381 MW7881 PCP communication status
MW6382 MW6882 MW7382 MW7882 PCP normal communication flag
MW6383 to MW6389
MW6883 to MW6889
MW7383 to MW7389
MW7883 to MW7889
Do not use this address range
MW6390 MW6890 MW7390 MW7890 Memory area number
MW6391 MW6891 MW7391 MW7891 Control RUN/STOP transfer
MW6392 to MW6399 MW6400 to MW6419 MW6420 to MW6439 MW6440 to MW6499
MW6892 to MW6899 MW6900 to MW6919 MW6920 to MW6939 MW6940 to MW6999
MW7392 to MW7399 MW7400 to MW7419 MW7420 to MW7439 MW7440 to MW7499
MW7892 to MW7899 MW7900 to MW7919 MW7920 to MW7939 MW7940 to MW7999
Do not use this address range
PV bias CH1 to CH20
Setting change rate limiter CH1 to CH20
Do not use this address range
30
IMS01J06-E1

7.2.2 MASTER-K series

Unit address 0 to 3 (Group 1)
Unit
address
0
DW0000 to DW0019 DW0020 to DW0039 DW0040 to DW0059 DW0060 to DW0079
DW0080 to DW0099 DW0100 to DW0119 DW0120 to DW0139 DW0140 to DW0159 DW0160 to DW0179 DW0180 to DW0199 DW0200 to DW0219 DW0220 to DW0239 DW0240 to DW0259 DW0260 to DW0279 DW0280 to DW0299 DW0300 to DW0319 DW0320 to DW0339
DW0340 to DW0359 DW0360 to DW0379
DW0380 DW0880 DW1380 DW1880 Request command
DW0381 DW0881 DW1381 DW1881 PCP communication status
DW0382 DW0882 DW1382 DW1882 PCP normal communication flag
DW0383 to DW0389
Unit
address
1
DW0500 to DW0519 DW0520 to DW0539 DW0540 to DW0559 DW0560 to DW0579
DW0580 to DW0599 DW0600 to DW0619 DW0620 to DW0639 DW0640 to DW0659 DW0660 to DW0679 DW0680 to DW0699 DW0700 to DW0719 DW0720 to DW0739 DW0740 to DW0759 DW0760 to DW0779 DW0780 to DW0799 DW0800 to DW0819 DW0820 to DW0839
DW0840 to DW0859 DW0860 to DW0879
DW0883 to DW0889
Unit
address
2
DW1000 to DW1019 DW1020 to DW1039 DW1040 to DW1059 DW1060 to DW1079
DW1080 to DW1099 DW1100 to DW1119 DW1120 to DW1139 DW1140 to DW1159 DW1160 to DW1179 DW1180 to DW1199 DW1200 to DW1219 DW1220 to DW1239 DW1240 to DW1259 DW1260 to DW1279 DW1280 to DW1299 DW1300 to DW1319 DW1320 to DW1339
DW1340 to DW1359 DW1360 to DW1379
DW1383 to DW1389
Unit
address
3
DW1500 to DW1519 DW1520 to DW1539 DW1540 to DW1559 DW1560 to DW1579
DW1580 to DW1599 DW1600 to DW1619 DW1620 to DW1639 DW1640 to DW1659 DW1660 to DW1679 DW1680 to DW1699 DW1700 to DW1719 DW1720 to DW1739 DW1740 to DW1759 DW1760 to DW1779 DW1780 to DW1799 DW1800 to DW1819 DW1820 to DW1839
DW1840 to DW1859 DW1860 to DW1879
DW1883 to DW1889
Name
Temperature set value (SV) CH1 to CH20
Alarm 1 set value CH1 to CH20
Alarm 2 set value CH1 to CH20
Heater break alarm set value (H-CT-A module) CH1 to CH20
Operation mode transfer CH1 to CH20
Auto/Manual transfer CH1 to CH20
Manual output value CH1 to CH20
Overlap/deadband CH1 to CH20
Heat-side proportional band CH1 to CH20
Cool-side proportional band CH1 to CH20
Integral time CH1 to CH20
Derivative time CH1 to CH20
PID/AT transfer CH1 to CH20
Temperature measured value (PV) CH1 to CH20 Heat-side manipulated output value CH1 to CH20 Cool-side manipulated output value CH1 to CH20 Current transformer input measured value (H-CT-A module) CH1 to CH20
TIO status CH1 to CH20
Set value monitor CH1 to CH20
Do not use this address range
Continued on the next page.
7. DATA MAP
IMS01J06-E1
31
7. DATA MAP
Continued from the previous page.
Unit
address
0
Unit
address
1
Unit
address
2
Unit
address
3
Name
DW0390 DW0890 DW1390 DW1890 Memory area number
DW0391 DW0891 DW1391 DW1891 Control RUN/STOP transfer
DW0392 to DW0399 DW0400 to DW0419 DW0420 to DW0439 DW0440 to DW0499
DW0892 to DW0899 DW0900 to DW0919 DW0920 to DW0939 DW0940 to DW0999
DW1392 to DW1399 DW1400 to DW1419 DW1420 to DW1439 DW1440 to DW1499
DW1892 to DW1899 DW1900 to DW1919 DW1920 to DW1939 DW1940 to DW1999
Do not use this address range
PV bias CH1 to CH20
Setting change rate limiter CH1 to CH20
Do not use this address range
Unit address 4 to 7 (Group 2)
Unit
address
4
DW2000 to DW2019 DW2020 to DW2039 DW2040 to DW2059 DW2060 to DW2079
DW2080 to DW2099 DW2100 to DW2119 DW2120 to DW2139 DW2140 to DW2159 DW2160 to DW2179 DW2180 to DW2199 DW2200 to DW2219 DW2220 to DW2239 DW2240 to DW2259
Unit
address
5
DW2500 to DW2519 DW2520 to DW2539 DW2540 to DW2559 DW2560 to DW2579
DW2580 to DW2599 DW2600 to DW2619 DW2620 to DW2639 DW2640 to DW2659 DW2660 to DW2679 DW2680 to DW2699 DW2700 to DW2719 DW2720 to DW2739 DW2740 to DW2759
Unit
address
6
DW3000 to DW3019 DW3020 to DW3039 DW3040 to DW3059 DW3060 to DW3079
DW3080 to DW3099 DW3100 to DW3119 DW3120 to DW3139 DW3140 to DW3159 DW3160 to DW3179 DW3180 to DW3199 DW3200 to DW3219 DW3220 to DW3239 DW3240 to DW3259
Unit
address
7
DW3500 to DW3519 DW3520 to DW3539 DW3540 to DW3559 DW3560 to DW3579
DW3580 to DW3599 DW3600 to DW3619 DW3620 to DW3639 DW3640 to DW3659 DW3660 to DW3679 DW3680 to DW3699 DW3700 to DW3719 DW3720 to DW3739 DW3740 to DW3759
Name
Temperature set value (SV) CH1 to CH20
Alarm 1 set value CH1 to CH20
Alarm 2 set value CH1 to CH20
Heater break alarm set value (H-CT-A module) CH1 to CH20
Operation mode transfer CH1 to CH20
Auto/Manual transfer CH1 to CH20
Manual output value CH1 to CH20
Overlap/deadband CH1 to CH20
Heat-side proportional band CH1 to CH20
Cool-side proportional band CH1 to CH20
Integral time CH1 to CH20
Derivative time CH1 to CH20
PID/AT transfer CH1 to CH20
Continued on the next page.
32
IMS01J06-E1
Continued from the previous page.
Unit
address
4
DW2260 to DW2279 DW2280 to DW2299 DW2300 to DW2319 DW2320 to DW2339
DW2340 to DW2359 DW2360 to DW2379
Unit
address
5
DW2760 to DW2779 DW2780 to DW2799 DW2800 to DW2819 DW2820 to DW2839
DW2840 to DW2859 DW2860 to DW2879
Unit
address
6
DW3260 to DW34279 DW3280 to DW3299 DW3300 to DW3319 DW3320 to DW3339
DW3340 to DW3359 DW3360 to DW3379
Unit
address
7
DW3760 to DW3779 DW3780 to DW3799 DW3800 to DW3819 DW3820 to DW3839
DW3840 to DW3859 DW3860 to DW3879
Name
Temperature measured value (PV) CH1 to CH20 Heat-side manipulated output value CH1 to CH20 Cool-side manipulated output value CH1 to CH20 Current transformer input measured value (H-CT-A module) CH1 to CH20
TIO status CH1 to CH20
Set value monitor CH1 to CH20
DW2380 DW2880 DW3380 DW3880 Request command
DW2381 DW2881 DW3381 DW3881 PCP communication status
DW2382 DW2882 DW3382 DW3882 PCP normal communication flag
DW2383 to DW2389
DW2883 to DW2889
DW3383 to DW3389
DW3883 to DW3889
Do not use this address range
DW2390 DW2890 DW3390 DW3890 Memory area number
DW2391 DW2891 DW3391 DW3891 Control RUN/STOP transfer
DW2392 to DW2399 DW2400 to DW2419 DW2420 to DW2439 DW2440 to DW2499
DW2892 to DW2899 DW2900 to DW2919 DW2920 to DW2939 DW2940 to DW2999
DW3392 to DW3399 DW3400 to DW3419 DW3420 to DW3439 DW3440 to DW3499
DW3892 to DW3899 DW3900 to DW3919 DW3920 to DW3939 DW3940 to DW3999
Do not use this address range
PV bias CH1 to CH20
Setting change rate limiter CH1 to CH20
Do not use this address range
7. DATA MAP
IMS01J06-E1
33
7. DATA MAP
Unit address 8 to B (Group 3)
Unit
address
8
DW4000 to DW4019 DW4020 to DW4039 DW4040 to DW4059 DW4060 to DW4079
DW4080 to DW4099 DW4100 to DW4119 DW4120 to DW4139 DW4140 to DW4159 DW4160 to DW4179 DW4180 to DW4199 DW4200 to DW4219 DW4220 to DW4239 DW4240 to DW4259 DW4260 to DW4279 DW4280 to DW4299 DW4300 to DW4319 DW4320 to DW4339
DW4340 to DW4359 DW4360 to DW4379
DW4380 DW4880 DW5380 DW5880 Request command
DW4381 DW4881 DW5381 DW5881 PCP communication status
DW4382 DW4882 DW5382 DW5882 PCP normal communication flag
DW4383 to DW4389
Unit
address
9
DW4500 to DW4519 DW4520 to DW4539 DW4540 to DW4559 DW4560 to DW4579
DW4580 to DW4599 DW4600 to DW4619 DW4620 to DW4639 DW4640 to DW4659 DW4660 to DW4679 DW4680 to DW4699 DW4700 to DW4719 DW4720 to DW4739 DW4740 to DW4759 DW4760 to DW4779 DW4780 to DW4799 DW4800 to DW4819 DW4820 to DW4839
DW4840 to DW4859 DW4860 to DW4879
DW4883 to DW4889
Unit
address
A
DW5000 to DW5019 DW5020 to DW5039 DW5040 to DW5059 DW5060 to DW5079
DW5080 to DW5099 DW5100 to DW5119 DW5120 to DW5139 DW5140 to DW5159 DW5160 to DW5179 DW5180 to DW5199 DW5200 to DW5219 DW5220 to DW5239 DW5240 to DW5259 DW5260 to DW5279 DW5280 to DW5299 DW5300 to DW5319 DW5320 to DW5339
DW5340 to DW5359 DW5360 to DW5379
DW5383 to DW5389
Unit
address
B
DW5500 to DW5519 DW5520 to DW5539 DW5540 to DW5559 DW5560 to DW5579
DW5580 to DW5599 DW5600 to DW5619 DW5620 to DW5639 DW5640 to DW5659 DW5660 to DW5679 DW5680 to DW5699 DW5700 to DW5719 DW5720 to DW5739 DW5740 to DW5759 DW5760 to DW5779 DW5780 to DW5799 DW5800 to DW5819 DW5820 to DW5839
DW5840 to DW5859 DW5860 to DW5879
DW5883 to DW5889
Name
Temperature set value (SV) CH1 to CH20
Alarm 1 set value CH1 to CH20
Alarm 2 set value CH1 to CH20
Heater break alarm set value (H-CT-A module) CH1 to CH20
Operation mode transfer CH1 to CH20
Auto/Manual transfer CH1 to CH20
Manual output value CH1 to CH20
Overlap/deadband CH1 to CH20
Heat-side proportional band CH1 to CH20
Cool-side proportional band CH1 to CH20
Integral time CH1 to CH20
Derivative time CH1 to CH20
PID/AT transfer CH1 to CH20
Temperature measured value (PV) CH1 to CH20 Heat-side manipulated output value CH1 to CH20 Cool-side manipulated output value CH1 to CH20 Current transformer input measured value (H-CT-A module) CH1 to CH20
TIO status CH1 to CH20
Set value monitor CH1 to CH20
Do not use this address range
Continued on the next page.
34
IMS01J06-E1
Continued from the previous page.
Unit
address
8
Unit
address
9
Unit
address
A
Unit
address
B
Name
DW4390 DW4890 DW5390 DW5890 Memory area number
DW4391 DW4891 DW5391 DW5891 Control RUN/STOP transfer
DW4392 to DW4399 DW4400 to DW4419 DW4420 to DW4439 DW4440 to DW4499
DW4892 to DW4899 DW4900 to DW4919 DW4920 to DW4939 DW4940 to DW4999
DW5392 to DW5399 DW5400 to DW5419 DW5420 to DW5439 DW5440 to DW5499
DW5892 to DW5899 DW5900 to DW5919 DW5920 to DW5939 DW5940 to DW5999
Do not use this address range
PV bias CH1 to CH20
Setting change rate limiter CH1 to CH20
Do not use this address range
Unit address C to F (Group 4)
Unit
address
C
DW6000 to DW6019 DW6020 to DW6039 DW6040 to DW6059 DW6060 to DW6079
DW6080 to DW6099 DW6100 to DW6119 DW6120 to DW6139 DW6140 to DW6159 DW6160 to DW6179 DW6180 to DW6199 DW6200 to DW6219 DW6220 to DW6239 DW6240 to DW6259
Unit
address
D
DW6500 to DW6519 DW6520 to DW6539 DW6540 to DW6559 DW6560 to DW6579
DW6580 to DW6599 DW6600 to DW6619 DW6620 to DW6639 DW6640 to DW6659 DW6660 to DW6679 DW6680 to DW6699 DW6700 to DW6719 DW6720 to DW6739 DW6740 to DW6759
Unit
address
E
DW7000 to DW7019 DW7020 to DW7039 DW7040 to DW7059 DW7060 to DW7079
DW7080 to DW7099 DW7100 to DW7119 DW7120 to DW7139 DW7140 to DW7159 DW7160 to DW7179 DW7180 to DW7199 DW7200 to DW7219 DW7220 to DW7239 DW7240 to DW7259
Unit
address
F
DW7500 to DW7519 DW7520 to DW7539 DW7540 to DW7559 DW7560 to DW7579
DW7580 to DW7599 DW7600 to DW7619 DW7620 to DW7639 DW7640 to DW7659 DW7660 to DW7679 DW7680 to DW7699 DW7700 to DW7719 DW7720 to DW7739 DW7740 to DW7759
Name
Temperature set value (SV) CH1 to CH20
Alarm 1 set value CH1 to CH20
Alarm 2 set value CH1 to CH20
Heater break alarm set value (H-CT-A module) CH1 to CH20
Operation mode transfer CH1 to CH20
Auto/Manual transfer CH1 to CH20
Manual output value CH1 to CH20
Overlap/deadband CH1 to CH20
Heat-side proportional band CH1 to CH20
Cool-side proportional band CH1 to CH20
Integral time CH1 to CH20
Derivative time CH1 to CH20
PID/AT transfer CH1 to CH20
Continued on the next page.
7. DATA MAP
IMS01J06-E1
35
7. DATA MAP
Continued from the previous page.
Unit
address
C
DW6260 to DW6279 DW6280 to DW6299 DW6300 to DW6319 DW6320 to DW6339
DW6340 to DW6359 DW6360 to DW6379
Unit
address
D
DW6760 to DW6779 DW6780 to DW6799 DW6800 to DW6819 DW6820 to DW6839
DW6840 to DW6859 DW6860 to DW6879
Unit
address
E
DW7260 to DW7279 DW7280 to DW7299 DW7300 to DW7319 DW7320 to DW7339
DW7340 to DW7359 DW7360 to DW7379
Unit
address
F
DW7760 to DW7779 DW7780 to DW7799 DW7800 to DW7819 DW7820 to DW7839
DW7840 to DW7859 DW7860 to DW7879
Name
Temperature measured value (PV) CH1 to CH20 Heat-side manipulated output value CH1 to CH20 Cool-side manipulated output value CH1 to CH20 Current transformer input measured value (H-CT-A module) CH1 to CH20
TIO status CH1 to CH20
Set value monitor CH1 to CH20
DW6380 DW6880 DW7380 DW7880 Request command
DW6381 DW6881 DW7381 DW7881 PCP communication status
DW6382 DW6882 DW7382 DW7882 PCP normal communication flag
DW6383 to DW6389
DW6883 to DW6889
DW7383 to DW7389
DW7883 to DW7889
Do not use this address range
DW6390 DW6890 DW7390 DW7890 Memory area number
DW6391 DW6891 DW7391 DW7891 Control RUN/STOP transfer
DW6392 to DW6399 DW6400 to DW6419 DW6420 to DW6439 DW6440 to DW6499
DW6892 to DW6899 DW6900 to DW6919 DW6920 to DW6939 DW6940 to DW6999
DW7392 to DW7399 DW7400 to DW7419 DW7420 to DW7439 DW7440 to DW7499
DW7892 to DW7899 DW7900 to DW7919 DW7920 to DW7939 DW7940 to DW7999
Do not use this address range
PV bias CH1 to CH20
Setting change rate limiter CH1 to CH20
Do not use this address range
36
IMS01J06-E1
The first edition: SEP. 2004 [IMQ00]
The fifth edition: OCT. 2003 [IMQ00]
RKC INSTRUMENT INC.
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN
PHONE: 03-3751-9799 (+81 3 3751 9799)
E-mail: info@rkcinst.co.jp
FAX: 03-3751-8585 (+81 3 3751 8585)
IMS01J06-E1 SEP. 2004
Loading...