REX - C100REX - C700
REX - C400REX - C900
REX - C410
INITIAL SETTING MANUAL
RKC RKC INSTRUMENT INC.
F.MFRANKLIN PTY LTD
PH. (07) 3391 4865
This is a manual for the initial setting of the REX-C100, -C400, -C410, -C700, & -C900. Do not
touch or adjust parts other than those covered in this manual. The instrument was manufactured
and delivered under close quality control by us. However, is some subject troubled or noted, your
kindly announce and advice to our business department, nearest business office also agent where
you bought is very much appreciated.
(1)Press the key to display the set data locking parameter
symbol on the measured-value (PV) display unit.
At this time, the least significant digit on the set-value (SV)
display unit lights brightly. The digit which lights brightly is
settable.
(2)Press the key to shift the digit which lights brightly up to
the hundreds digit. The digit which lights brightly shifts as
follows every time the key is pressed.
(3)Press the key to set “ ”. Pressing the key increments
numerals, and pressing the key decrements numerals.
:No initial set mode locked
(4)Hold both the (A) and (B) keys simultaneously
until appears.
Cautions
1.In order to enter the initial set mode, always set the data locking
to “ ”. Any setting other than “ ”
cannot enter the initial set mode.
2.If the controller is set to the initial set mode, all outputs are turned OFF.
3.An example of the REX-C900 is described here, but the same procedure applies to other
controllers (REX-C100, -C400, -C410, and -C700).
-1-
1.2Exiting the initial set mode
(1)Exits from the initial set mode
Keep pressing both the key (A) and (B) keys simultaneously for more than 5 seconds can enter the
PV/SV display mode.
‰ Even if the controller exits from the initial set mode at any point, the setting mode so far set becomes valid.
(2)Locks the initial set mode (Change the content of set data lock setting)
1.Press the key to enter the parameter setting mode.
2.Press the key by required number of times to show “ ” on the measured-value (PV) display
3.Press the key and keys to set “ ”. Press the key to register “ ”.
Caution
If the controller exits from the initial set mode, confirm that set data lock setting is set to “ ”.
•Setting prior to power failure is valid
•Instantaneous power failure (within 20 msec.) does not exert bad influence on the instrument.
•If long power failure occurs, the instrument exits from its initial set mode. After power recovery, the instrument
unit.
< Each status when power failure occurs in the initial set mode >
is set to the PV/SV display mode. The measured-value (PV) at this time shows that at the time of power
recovery, and the set-value (SV) is the same as that before power failure.
-2-
2.S e t t i n g
2.1Description of each parameter
“ ” appears on the display, and every press of the key advances the parameter symbol as shown in
the following table. After one cycle, the display shows “ ”.
MEASURED-VALUE (PV)
DISPLAY UNIT
SETTING DESCRIPTION
Input type selection
Engineering unit selection (EC, EF)
Heater break alarm (HBA) selection
Control loop break alarm (LBA) selection
Special specification [Z-132] selection
Selection of control loop break alarm output terminals
First alarm (ALM1) type selection
First alarm (ALM1) hold action selection
Second alarm (ALM2) type selection
Second alarm (ALM2) hold action selection
Direct / reverse action selection
Control action type selection
Control output type selection (Heating / cooling side)
Energize / de-energize alarm selection
Special specification [Z-124] selection
“ ” cannot be set.
PV bias setting
Differential gap setting of ON / OFF action
Differential gap setting of first alarm (ALM1)
‰ No display appears when no first alarm (ALM1)
function is provided.
Differential gap setting of second alarm (ALM2)
‰ No display appears when no second alarm (ALM2)
function is provided.
High-limit setting for set-value (SV)
Low-limit setting for set-value (SV)
-3-
2.2Each parameter setting
uMethod of setting
(2)Press the key to display the input type selection parameter
symbol ( ) on the measured-value (PV) display unit.
At this time, the least significant digit on the set-value (SV)
display unit lights brightly. The digit which lights brightly is
settable.
(3)Press the key to shift the digit which lights brightly up to
the tens digit. The digit which lights brightly shifts as follows
every time the key is pressed.
(4)Press the key to set “ ”. Pressing the key increments
numerals, and pressing the key decrements numerals.
:Thermocouple type L
(5)After finishing the setting, press the key to
register (shifts to next parameter).
Cautions
1.If no key operation is performed for more than 60 sec. during setting or when any
parameter other than
“ ” is displayed, the display returns to “ ”.
2.An example of the REX-C900 is described here, but the same procedure applies to other controllers
(REX-C100, -C400, -C410, and -C700).
-4-
(1)Input type selection ( )
Set-value (SV) display unit
VALUEINPUT TYPEHARDWARE
K
J
L
E
TC
RTD
Voltage
N
R
S
B
W5Re / W26Re
PLII
T
U
Pt100 S (JIS / IEC)
J Pt100 S (JIS)
0 to 5 V DC
1 to 5 V DC
a
b
c
d
0 to 20 mA DC
Current
Cautions
1.Conduct setting so as to meet the instrument specification (input type).
Setting change between different symbols may cause malfunction, but the setting can be changed when
hardware types have the same symbol. However, when the setting is changed, always reset “ ” and
“ ”. (See page 14).
2.“ ” setting displays are only “ ”and “ ”.
4 to 20 mA DC
-5-
e
(2)Engineering unit and cooling type selection ( )
Set-value (SV) display unit
VALUEDESCRIPTION
ECEngineering unit
EFselection
Air-cooling (Type A) ‰ 1Cooling type
Water-cooling (Type W) ‰ 2selection
Fixed
‰ 1Type A : Heating / cooling PID action (Air-cooling)
‰ 2Type W : Heating / cooling PID action (Water-cooling)
Cautions
1.For the voltage and current input types, the engineering unit setting of EC or EF is ignored.
2.When control action is of the type D (PID action [direct action] or type F (PID action [reverse action] ), “Cooling
type selection” setting is ignored.
3.Do not set the upper 2 digits to numeric values other than “ ” since they are not used.
4.“ ” setting displays are only “ ”and “ ”.
-6-
(3)Selection of break alarm (HBA, LBA) etc. ( )
Set-value (SV) display unit
VALUEDESCRIPTION
Without HBA functionHeater break alarm (HBA)
With HBA functionselection
Without LBA functionControl loop break alarm
With LBA function(LBA) selection
Without Z-132 specificationSpecial specification
With Z-132 specification ‰[Z-132] selection
First alarm sideSelection of control loop
Second alarm sidebreak alarm output terminals
‰ Z-132 specification : Heater break alarm output is delayed.
Cautions
1.“With HBA function” setting is ignored for the following instruments :
CInstrument with deviation or process alarm as the second alarm (ALM2)
CInstrument with control loop break alarm (LBA)
CInstrument whose control output is the current output type
2.“With LBA function” setting is ignored for the following instruments :
CInstrument with deviation or process alarm as the first alarm (ALM1) and second alarm (ALM2)
CInstrument with heater break alarm (HBA)
CInstrument whose control action is type W (Heating / cooling PID action [Water-cooling] ) or type A
(Heating / cooling PID action [Air-cooling] ).
3.For the instrument without heater break alarm (HBA), “With Z-132 specification” setting is ignored.
4.“ ” setting displays are only “ ”and “ ”.
-7-
(4)First-alarm (ALM1) type selection ( )
Set-value (SV) display unit
VALUEDESCRIPTION
No first alarm
High alarm
Low alarmDeviationFirst alarm (ALM1)
High / Low alarmalarmtype selection
Band alarm(See page 10)
High alarmProcess
Low alarmalarm
Without alarm hold actionFirst alarm (ALM1)
With alarm hold actionhold action selection
Cautions
1.The following instrument is set to “ ”.
CInstrument without the first alarm (ALM1).
CInstrument which outputs control loop break alarm (LBA) from the first alarm side. [
setting details : For “ ” ]
2.“ ” setting displays are only “ ”and “ ”.
-8-
(5)Second-alarm (ALM2) type selection ( )
Set-value (SV) display unit
VALUEDESCRIPTION
No second alarm
High alarm
Low alarmDeviationSecond alarm (ALM2)
High / Low alarmalarmtype selection
Band alarm(See page 10)
High alarmProcess
Low alarmalarm
Without alarm hold actionSecond alarm (ALM2)
With alarm hold actionhold action selection
CInstrument without the second alarm (ALM2).
CInstrument with the heater break alarm (HBA).
Cautions
1.The following instrument is set to “ ”.
CInstrument without the second alarm (ALM2).
CInstrument with the heater break alarm (HBA).
CInstrument which outputs control loop break alarm (LBA) from the second alarm side. [
setting details : For “ ” ]
2.“ ” setting displays are only “ ”and “ ”.
-9-
A L A R M T Y P E S
[ g : Set-value (SV)Î : Alarm set-value: Alarm status (ALM1 or ALM2 LED lighting) ]
<D E V I A T I O N A L A R M >
High alarmâ_______________________________________________________________‰ 1
lowgÎ high
High alarmã_______________________________________________________________‰ 2
‰ 1Alarm status where the alarm set-value is set to plus (+) side for the set-value (SV).
‰ 2Alarm status where the alarm set-value is set to minus (-) side for the set-value (SV).
‰ 3Status when alarm is activated at 2 equal deviation points from the set-value (SV) with the alarm set-value
(absolute deviation) is set.
-10-
(6)Control-output selection etc. ( )
Set-value (SV) display unit
VALUEDESCRIPTION
Direct action (Type D)Direct / reverse action
Reverse action (Type F, A, W)selection
1.Conduct setting so as to meet the instrument specification. An incorrect setting may cause a malfunction.
2.When control action is of the type D or F, “Control output type selection (Cooling side)” setting is ignored.
3.For the REX-C100, always set the control action type selection to PID action.
4.“ ” setting displays are only “ ”and “ ”.
-11-
(7)Energize / de-energize alarm selection etc. ( )
Set-value (SV) display unit
VALUEDESCRIPTION
Energize alarmEnergize / de-energize
De-energize alarm(First alarm side)
Energize alarmEnergize / de-energize
De-energize alarm(Second alarm side)
Without Z-124 specificationSpecial specification
With Z-124 specification ‰(First alarm side)
Without Z-124 specificationSpecial specification
alarm selection
alarm selection
[Z-124] selection
[Z-124] selection
With Z-124 specification ‰(Second alarm side)
‰ Z-124 specification : No alarm action caused by burnout is performed.
Cautions
1.Instrument without the first alarm (ALM1) and second alarm (ALM2) is set to “ ”.
CInstrument without the first alarm (ALM1).
[ setting details : For “ ”]
CInstrument without the second alarm (ALM2).
[ setting details : For “ ”]
2.“ ” setting displays are only “ ”and “ ”.
-12-
(8)PV bias setting ( )
Set-value (SV) display unit
(Setting range)
(1)TC and RTD inputs
CFor a resolution of 1EC [EF]:-1999 to 9999EC [EF]
CFor a resolution of 0.1EC [EF]:-199.9 to +999.9EC [EF]
(2)Voltage and current inputs:-199.9 to +200.0%
(9)Differential gap setting of ON / OFF action [ ]
Set-value (SV) display unit
(Setting range)
(1)TC and RTD inputs:0 to 100 or 0.0 to 100.0
(2)Voltage and current inputs:0.0 to 10.0
(10)Differential gap setting of first alarm (ALM1) [ ]
Set-value (SV) display unit
(Setting range)
(1)TC and RTD inputs:0 to 100 or 0.0 to 100.0
(2)Voltage and current inputs:0.0 to 10.0
Caution
No display appears when no alarm function is provided.
[ setting : “ ”].
(11)Differential gap setting of second alarm (ALM2) [ ]
Set-value (SV) display unit
(Setting range)
(1)TC and RTD inputs:0 to 100 or 0.0 to 100.0
(2)Voltage and current inputs:0.0 to 10.0
Caution - No display appears when no alarm function is provided.
[ setting : “ ”].
-13-
(12)High-limit setting for set-value (SV) [ ]
Set-value (SV) display unit
INPUT TYPERANGE
K0 to 1372EC 0 to 2502EF
J0 to 1200EC 0 to 2192EF
L0 to 800EC 0 to 1600EF
E0 to 1000EC 0 to 1832EF
N0 to 1300EC 0 to 2372EF
TCR, S0 to 1769EC 0 to 3216EF
B0 to 1820EC 0 to 3308EF
W5Re / W26Re0 to 2320EC 0 to 4000EF
PLII0 to 1390EC 0 to 2534EF
T-199.9 to +400.0EC -199.9 to +752.0EF
U-199.9 to +600.0EC -199.9 to +999.9EF
Pt100S (JIS / IEC)
RTD
Voltage0 to 5V DC
Current0 to 20mA DC
J Pt100S (JIS)
Pt100S
(Conforming to JIS / IEC)
1 to 5V DC
0 to 20mA DC
‰ 1IEC (International Electrotechnical Commission) is equivalent to JIS, DIN and ANSI.
‰ 2Limit setting becomes $ .
Caution : Prior to conducting limiter setting change, see “Input range table” on page 16.
(13)Low-limit setting for set-value (SV) [ ]
Set-value (SV) display unit
(Setting range)
See the above table.
Limit setting becomes $ .
-199.9 to +649.0EC
-199.9 to +999.9EF
0.0 to 100.0% (Fixed)
0.0 to 100.0% (Fixed)
Caution : Prior to conducting limiter setting change, see “Input range table” on page 16.
When changing the high-limit [ ] and the low-limit [ ] limiter settings, always set the set-value (SV) within the limiter
range. High-limit setting $ set-value (SV) $ low-limit setting
-14-
2.3E a c h P a r a m e t e r c h e c k s
(1)When all the settings are finished, press the key to check each parameter.
(2)When the contents of the initial setting are changed, change the model code plate stuck to inside of the controller and outside of the case
by referring to the following table.
(3)After each parameter has been checked, return the controller to the control mode by referring to “1.2 Exiting the initial set mode” (P.2).
MODEL CODEDESCRIPTION
C100
C400
REX-
Control action
Input typeGSee page 16. Input Range Table “MODEL CODE”
Input rangeGSee page 16. Input Range Table “MODEL CODE”
First control output [OUT(1)]
(Heating side)
Second control output [OUT(2)]
(Cooling side)
First alarm (ALM1)
C410
C700
C900
GGGGGGG
F
D
W
A
M
V
8
G
None
M
V
8
N
A
B
C
D
E
F
G
H
J
K
L
R
48 x 48 mm
96 x 48 mm
48 x 96 mm
72 x 72 mm
96 x 96 mm
Relay contact
Voltage pulse
Current 4 to 20mA DC
Trigger (for triac driving)
No second control output (Control action : D, F)
Relay contact i
Voltage pulse i
Current 4 to 20mA DC i
No first alarm (ALM1)
Deviation high alarm (without hold action)
Deviation low alarm (without hold action)
Deviation high / low alarm (without hold action)
Band alarm
Deviation high alarm (with hold action)
Deviation low alarm (with hold action)
Deviation high / low alarm (with hold action)
Process high alarm (without hold action)
Process low alarm (without hold action)
Process high alarm (with hold action)
Process low alarm (with hold action)
Control loop break alarm
N
No second alarm (ALM2)
A
Deviation high alarm (without hold action)
B
Deviation low alarm (without hold action)
C
Deviation high / low alarm (without hold action)
D
Band alarm
E
Deviation high alarm (with hold action)
Second alarm (ALM2)
F
Deviation low alarm (with hold action)
G
Deviation high / low alarm (with hold action)
H
Process high alarm (without hold action)
J
Process low alarm (without hold action)
K
Process high alarm (with hold action)
L
Process low alarm (with hold action)
P
Heater break alarm (CTL-6)
S
Heater break alarm (CTL-12)
‰ For the REX-C100, the content marked with i cannot be selection.
‰ When control output is trigger output for triac driving, only the first alarm is available (For the REX-C100).
-15-
I N P U T R A N G E T A B L E
INPUT TYPEINPUT RANGEMODEL CODE
0 to 200EC
0 to 400EC
0 to 600EC
0 to 800EC
0 to 1000EC
0 to 1200EC
0 to 1372EC
0 to 800EF
0 to 1600EF
0 to 2502EF
‰
0 to 200EC
0 to 400EC
0 to 600EC
0 to 800EC
0 to 1000EC
0 to 1200EC
0 to 800EF
0 to 1600EF
0 to 2192EF
‰
0 to 1600EC
0 to 1769EC
0 to 3200EF
0 to 3216EF
‰
0 to 1600EC
0 to 1769EC
0 to 3200EF
0 to 3216EF
‰
400 to 1800EC
0 to 1820EC
800 to 3200EF
0 to 3308EF
‰
0 to 800EC
0 to 1000EC
0 to 1600EF
0 to 1832EF
‰
0 to 1200EC
0 to 1300EC
0 to 2300EF
0 to 2372EF
‰
-199.9 to +400.0EC
-199.9 to +100.0EC
-100.0 to +200.0EC
0.0 to 350.0EC
-199.9 to +752.0EF
-100.0 to +200.0EF
-100.0 to +400.0EF
0.0 to 450.0EF
0.0 to 752.0EF
‰
0 to 2000EC
0 to 2320EC
0 to 4000EF
‰
K
J
R
S
B
E
N
T
W
T
H
E
R
M
O
C
O
U
P
L
E
K
(JIS / IEC)
J
(JIS / IEC)
R
(JIS / IEC)
S
(JIS / IEC)
B
(JIS / IEC)
E
(JIS / IEC)
N
(NBS)
T
(JIS / IEC)
W5Re / W26Re
(ASTM)
01
02
03
04
05
06
07
A1
A2
A3
ZZ
01
02
03
04
05
06
A1
A2
A3
ZZ
01
02
A1
A2
ZZ
01
02
A1
A2
ZZ
01
02
A1
A2
ZZ
01
02
A1
A2
ZZ
01
02
A1
A2
ZZ
01
02
03
04
A1
A2
A3
A4
A5
ZZ
01
02
A1
ZZ
INPUT TYPEINPUT RANGEMODEL CODE
T
H
E
R
M
O
C
O
U
P
L
E
R
T
D
V C
OU
L R
T R
A E
GN
E T
PLII
(NBS)
U
(DIN)
L
(DIN)
Pt100
(JIS / IEC)
Pt100
(Conforming to
JIS / IEC)
J Pt100
(JIS)
5V
0 to 5V
1 to 5V
0 to 20mA
4 to 20mA
Special input
‰When the range is specified separately, the
“MODEL CODE” becomes “GZZ”
0 to 1300EC
0 to 1390EC
0 to 2400EF
0 to 2534EF
‰
-199.9 to +600EC
-199.9 to +100.0EC
0.0 to 400.0EC
-199.9 to +999.9EF
-100.0 to +200.0EF
0.0 to 999.9EF
‰
0 to 400EC
0 to 800EC
0 to 800EF
0 to 1600EF
‰
-199.9 to +649.0EC
-199.9 to +200.0EC
-100.0 to + 50.0EC
-100.0 to +100.0EC
-100.0 to +200.0EC
0.0 to 50.0EC
0.0 to 100.0EC
0.0 to 200.0EC
0.0 to 300.0EC
0.0 to 500.0EC
-199.9 to +999.9EF
-199.9 to +400.0EF
-199.9 to +200.0EF
-100.0 to +100.0EF
-100.0 to +300.0EF
0.0 to 100.0EF
0.0 to 200.0EF
0.0 to 400.0EF
0.0 to 500.0EF
‰
-199.9 to +649.0EC
-199.9 to +200.0EC
-100.0 to + 50.0EC
-100.0 to +100.0EC
-100.0 to +200.0EC
0.0 to 50.0EC
0.0 to 100.0EC
0.0 to 200.0EC
0.0 to 300.0EC
0.0 to 500.0EF
‰
0.0 to 100.0%
0.0 to 100.0%
0.0 to 100.0%
0.0 to 100.0%
0.0 to 100.0%
A
U
L
D
P
4
6
7
8
9
01
02
A1
A2
ZZ
01
02
03
A1
A2
A3
ZZ
01
02
A1
A2
ZZ
01
02
03
04
05
06
07
08
09
10
A1
A2
A3
A4
A5
A6
A7
A8
A9
ZZ
01
02
03
04
05
06
07
08
09
10
ZZ
01
01
01
01
01
100.0%
-16-
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.