RKC INSTRUMENT MA900, MA901 Instruction Manual

Page 1
Multi-point Di gital Controller
MA900/MA901
Instruction Manual
Thank you for purchasi ng the RKC product. In order t o achieve maximum performance and ensur e pr oper operat ion of your new instrument, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference.
SYMBOLS

WARNING

CAUTION

: This mark indicates precautions that must be
taken if there is danger of electric shock, fire, etc., which could result in loss of life or injury.
: This mark indicat es that i f these pr ecautions and
operating procedures are not taken, damage to the instrument may result.
: This mark indicates that all precautions should be
!
taken for safe usage.
: This mark indicates important information on
installation, handling and operating procedures.
: This mark indic ates suppl emental informat ion on
installation, handling and operating procedures.
: This mark indic ates where additional informati on
may be located.
!"
This instrument is designed for installation in an enclosed instrumentation panel. All high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel.
!"
All precautions described in this manual should be taken to avoid damage to the instrument or equipment.
!"
All wiring must be in accordance with local codes and regulations.
!"
All wiring must be completed before power is turned on to prevent electric shock, ins trument failure, or incorrect ac tion. The power must be turned of f before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.
!"
To prevent instrument damage or failure, protect the power line and the input/output l ines from hi gh currents with a protect ion device such as fuse, circuit breaker, etc.
!"
Prevent metal fragments or lead wi re s c raps f rom f alling inside instrument cas e to avoid electric shock, fire or malfunction.
!"
Tighten each terminal screw to the specifi ed torque found in the manual to avoid electric shock, fire or malfuncti on.
!"
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
!"
Do not connect wires to unused ter minals as t his will interfere with proper operation of the instrument.
!"
Turn off the power suppl y before cleaning the instrument.
!"
Do not use a volatile solvent suc h as paint t hinner t o clean t he instrument. Deformation or discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
!"
To avoid damage to instrument display, do not rub with an abrasive material or push front panel with a hard object.
!"
Do not connect modular connectors to telephone line.
WARNING
!
!"
An external protection device must be installed if failure of this instrument could result in damage to the instrument, equipment or injury to personnel.
!"
All wiring must be completed before power is turned on to prevent electric shock, fire or damage to instrument and equipment.
!"
This instrument must be used in accordance with the specifications to prevent fire or damage to instrument and equipment.
!"
This instrument is not intended for use in locations subject to flammable or explosive gases.
!"
Do not touch high-voltage connections such as power supply terminals, etc. to avoid electric shock.
!"
RKC is not responsible if this ins trument is repaired, modified or disassembled by other than factory­approved personnel. Malfunction can occur and warranty is void under these conditions.
CAUTION
!"
This is a Clas s A instrument. In a domestic envi ronment, this instrument may cause radio interference, in which case the user may be required to t ake adequate measures.
!"
This instrument is protected from electric shock by r einforced insulation. Provi de reinforced insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
!"
Be sure to provide an appropriate surge control circuit respectively for the following:
If input/output or signal lines wit hin the building are longer than 30 meters.
If input/output or signal lines leave the bui lding, regardless the length.
All Rights Reserved, Copyri ght  2001, RKC INSTRUMEN T IN C.
®
!"
This manual assumes that the reader has a fundamental knowledge of the principles of electricity, process control, computer technology and c ommunications.
!"
The figures, diagrams and numeri c values used in t his manual are only for purpose of illustration.
!"
RKC is not responsible for any damage or injur y that i s c aus ed as a result of using this instrument, instrument failure or indirect damage.
!"
Periodic maintenanc e is required for safe and proper operation of this instrument. Some components have a limited service life, or characteristics that change over time.
!"
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior noti ce.
!"
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored, processed or retrieved through any mechanical, electronic, optical or other means without prior written approval fr om RKC.
1. OUTLINE
2. MOUNTING
3. WIRING
4. PARTS DESCRIPTION
5. SETTING
6. OPERATION
7. FUNCTIONS
8. ERROR DISPLAYS
9. REMOVING THE INTERNAL ASSEMBLY
10. SPECIFICATIONS
RKC INSTRUMENT INC.
NOTICE

CONTENTS

・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
・・・・・・・・・・・・・・・・・・・・・・・・・・・
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
・・・・・・・・・・
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
1 3 4 5 6
14 16 19 19 20
Page 2

1. OUTLINE

As a multi-point digital controller of a DIN size 96 × 96 mm, there are MA900 of 4-channel type and MA901 of 8-channel t ype. This manual describes the specifications, setting, mounting and wiring. For the communication function, see the
Manual (IMR01H02-E
####
)
.
Communication Instruction

1.1 Checking the Product

When unpacking your new instrument, please confirm that the following products are included. If any of the products are missing, damaged, or if your manual is incomplete, please contact RKC sales office or the agent.
!
MA900 (MA901): 1
!
Instruction Manual:1 (IMR01H01-E4)
!
Mounting brackets: 2 (Waterproof/dustproof option: 4)
!
Mounting screws [with hexagon nuts]: 2 (Water proof/dustproof option: 4)

1.2 Confirmation of the Model Code

Check whether the delivered product is as specified by referring to the following model code list. If the product you received is not the one ordered, please cont act RKC sales offi ce or the agent.
MA900 - 4 MA901 - 8
$ $$$ $ $$$
- $ $ -
- $ $ -
(1)(2) (3) (4) (5) (6) (7) (8) (9) (10)(11) (12)
(1) Number of channel
4: 4 channels (MA900) 8: 8 channels (MA901)
(2) Control act ion type
F: PID control with autotuning (Reverse action) D: PID control with autotuning (Direct action) W: Heat/cool PID control wi th autotuning (Water cooling) A: Heat/cool PID control with aut otuning (Air cooling)
(3) Input type/Input range (This code is common to all channels.)
%%%%
Input Range Table (P. 21)
See
(4) Output 1 (OUT1 to OUT4)
2
M: Relay contact output 7: Current output (0 t o 2 0 m A D C ) V: Voltage pulse output 8: Current output (4 to 2 0 m A D C ) T: Triac output
(5) Output 2 (OUT5 to OUT8)
2
N: No output 7: Current output (0 t o 2 0 m A D C ) M: Relay contact output 8: Current output (4 to 2 0 m A D C ) V: Voltage pulse output T: Triac output
(6) Power supply voltage
3: 24 V AC/DC 4: 100 to 240 V AC
(7)
Alarm 1
3
A: Deviation hi gh alarm J: Process low alar m B: Deviation l ow alarm K: Process high alarm C: Deviation high/low alarm L: Process low alarm D: Band alarm M: FAI L alarm E: Deviation hi gh alarm F: Deviation low alarm G: Deviation high/low alarm
4
4
R: Control loop break alarm V: SV high alarm
4
W: SV l ow alarm
H: Process high alarm Alarm 2 (option)
(8)
3
N: No alarm J: Process low alarm A: Deviation hi gh alarm K: Process high alarm B: Deviation l ow alarm L: Process low alarm C: Deviation high/low alarm M: FAIL alarm D: Band alarm P: Heat e r b r e a k a l a rm ( C TL 6P ) E: Deviation hi gh alarm F: Deviation low alarm G: Deviation high/low alarm
4
4
S: Heater break alarm (CTL12) V: SV high alarm
4
W: SV l ow alarm
H: Process high alarm
1
1
4
4
4
4
$∗$ $ $ $∗$ $ $
(9) Alarm 3 (option)
- $ $ / $ / Y
- $ $ / $ / Y
3
N: No alarm H: Process high alarm A: Deviation hi gh alarm J: Process low alarm B: Deviation l ow alarm K: Proces s high alarm C: Deviation high/low alarm L: Process low alarm D: Band alarm M: FAIL alarm E: Deviation hi gh alarm F: Deviation low alarm G: Deviation high/low alarm
(10) Contact input (option)
N: No contact input D: Contact input (RUN/STOP, Memory area transfer)
(11) Communication Interface (option)
N: No communication function 1: RS-232C (RKC communication) 4: RS-422A (RKC communication) 5: RS-485 (RKC communication) 6: RS-485 (Modbus) 7: RS-422A (Modbus) 8: RS-232C (Modbus)
(12) Waterproof/dustproof (option)
N: No waterproof/dustproof 1: Waterproof/dustproof
1
In case of MA901, heat/c ool P ID action can not be specif i ed.
2
Output assignment of output 1 and output 2:
Control
action
F
or D action
type
(OUT1 to OUT4)
Control output (CH1 to CH4)
(MA900)
F
or D action
type
Control output (CH1 to CH4)
(MA901)
Heat-side control output (CH1 to CH4)
5, 6
5, 6
W
or A action
type
(MA900)
a
When the FAIL alarm is specified, t he out put 2 is not output. FAIL alarm is output from the contact output of alarm 3 (terminal No.51 and 52).
b
When the alarm 3 is specif ied as the output 2, output type i s only relay contact output.
3
The selection of the alarm action type is common to all channels.
4
With hold act i on
5
For three-phase heater break alarm, special specified code “Z-168” must be specifi ed at the end of the model code. Three-phase heater break alarm cannot be specified with MA901.
6
If the heater break alarm is selected, contact input and communicati on function cannot be select ed (MA901 onl y).
4
V: SV high alarm
4
W: SV low alarm
4
Output 1
4
4
Output 2
(OUT5 to OUT8)
Alarm 3 output
a, b
(CH1 to CH4) [Option]
Control output (CH5 to CH8)
Cool-side control output (CH1 to CH4)
2
IMR01H01-E4
Page 3

2. MOUNTING

This chapter describes installation environment, mounti ng cautions, dimensi ons and mounting procedures.
"
"
!
WARNING
To prevent electric shock or instrument failure, always turn off the power before mounting or removing the instrument.

2.1 Mounting Environment

(1) This instrument is intended to be used under the following
environmental conditions. (
IEC61010-1
)
[OVERVOLTAGE CATE GORY II, P OLLU TION DE GREE 2]
(2) Avoid the followi ng conditions when selecting the mounti ng
location:
Ambient temperature less than 0 °C or more than 50 °C.
Ambient humidity of less than 45 % or more than 85 % RH.
Rapid changes in ambient temperature which may cause
condensation. Corrosive or inflammable gases.
Direct vibration or shock to the mainframe.
Water, oil, chemicals, vapor or steam splas hes.
Excessive dust, salt or iron particles.
Excessive inducti on noise, static electricit y, magnetic fields or
noise. Direct air flow from an air conditi oner.
Exposure to direct s unlight.
Excessive heat accumul ation.

2.2 Mounting Cautions

Take the following point s int o consider ation when mounti ng this instrument in the panel.
Provide adequate ventilation space so that heat does not build
up. Do not mount this inst rument directly above equipment that
generates large amount of heat (heater s, tr ansform ers, semi­conductor functional devices, large-wattage resis tors). If the ambient temperature rises above 50 °C, cool this
instrument with a for ced air fan, cool er, or the lik e. However, do not allow cooled air to blow this instr ument directly. In order to improve safety and the immunity to withstand noise,
mount this instrument as far away as possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel. Power lines: Separate at least 200 mm. Rotating machinery: Separate as far as possible. Mount this instrument in the horizontal direction for panel. If
you did installation except a horizont al direction, this c auses malfunction.

2.3 Dimensions

External dimensions
!"
(Unit: mm)
Up to 4 mounting brackets can be used.
Rubber (option)
*
Mounting bracket
91.8
!"
Panel cutout
(Unit: mm)
Indiv idual mounti ng
For mount ing of the MA900/MA901, panel thickness must be bet ween 1 to 10 mm. When mounting multiple MA900/MA901s close together, the panel strength should be checked to ensure proper support .
If the MA900/MA901s have waterproof/dustproof options, protection will be compromised and not meet IP65 by close mount ing.
+0.8
0
92
25
0
+0.8
92
30
Close mounting
+0.8
L
0
+0.8
×n-
0
4
L = 96
n
: Number of i nstr uments (2
≤n≤
0
+0.8
92
6)

2.4 Mounting Procedures

When the ins trument is mount ed, always sec ure with two mounting brackets either top and bottom.
The waterproof/dustproof option on the front of the instrument confor ms t o For effective waterproof/dustproof, the gasket must be securely placed between instrument and panel without any gap. If gasket is damaged, pleas e contact RKC s ales office or the agent .
!"
Mounting to the panel
Prepare the panel cutout as specified in 2. 3 Dimensions.
1.
Insert the ins trument through the panel cutout.
2.
Insert the mounting br acket int o the mounting gr oove of the
3.
instrument . (Fig.1) Push the mounting bracket forward unt il t he bracket is f irm ly
4.
secured to the panel. (Fig.2) The other mounting bracket should be installed the same
5.
way described in
Fig. 1
!"
Mounting to the panel
.
and 4.
3
Mounting bracket
In addition, the mounting assembly also include two screws which can be used with the bracket s to secure the ins trument to the panel. Procedure 1. and 2. are the same as in the above. For the procedure
3.
to 6., see the following figures.
3.
Mounting bracket
(2) Insert the mounting
screw.
when mounted on the panel.
IP65
Fig. 2
(When using the mounting screws)
4.
Insert the L-shaped hook of the mounting bracke t into the groove .
96
IMR01H01-E4
96
9.2
(1) Insert the hexagon nut.
図3
5.
91.8
110.8
1*
100 8.2
Pull till click sounds to the direction shown by the arrow.
図5
図4
When using the mounting screws,
6.
only turn one full revolution after the screw touches the panel.
図6
3
Page 4

3. WIRING

3, 4
1
3
2
This chapter describes wiring c autions and terminal c onfiguration.
" "
!
WARNING
To prevent electric shock or instrument failure, do not turn on the power until all the wiring is completed.

3.1 Wiring Cautions

For thermocouple input, use the appropriate c ompensation wire.
#"
For RTD input, use low resistance lead wire with no difference in r esistance between the three lead wires.
#"
To avoid noise induct ion, keep input signal wire away f rom instrument power line, load l ines and power lines of other elec tric
#"
equipment. If there is electrical noise in the vicinity of the instrument that could affect operat ion, use a noise fil ter.
#"
Shorten the distanc e between the twisted power supply wire pitches to achieve the most effective noise reduct ion.
-
Always install the noi se fi lt er on a grounded panel. Mini mize t he wiri ng dis t ance bet ween the nois e f il ter output and t he ins t r ument
-
power supply terminal s to achieve the most effective noise reduction. Do not connect fuses or switches to the noise filter output wiring as this will reduce the effectiveness of the noise f ilter.
-
About four seconds are required as preparation t ime for contac t output every t ime the instr ument is tur ned on. Use a delay relay
#"
when the output line is used for an external interlock circuit. Power supply wiring must be twisted and have a low voltage drop.
#"
For an instrument with 24 V power supply, supply power from a SELV circuit.
#"
This instrument is not furnis hed with a power supply sw itch or fus e. Therefore, i f a fuse or power suppl y switch i s required, install
#"
close to the ins trument.
Recommended fuse rating: Rated voltage 250 V, Rated current 1 A Fuse type: Time-lag fuse
Use the solderles s terminal appropriate to the screw size.
#"
Screw size: M3×6 Recommended tightening torque: 0.4 N・m (4 kgf・cm)

3.2 Terminal Configuration

!"
MA900
(1) (2)
(3)
10 11 12
(3) Outp ut 1 1
Relay contact
OUT1
NO
OUT2
NO
OUT3
NO
OUT4
NO
1 2 3 4 5 6 7 8 9
5
6
7
8
9
10
11
12
(5)
(6)
37
49
38
50
39
51
40
52
41
53
42
54
43
55
44
56
45
57
46
58
47
59
48
60
(4)
(7)
Voltage pulse/
Current OUT1
5
+
6
-
OUT2
7
+
8
-
OUT3
9
+
10
-
OUT4
11
+
12
-
(8) (9)
25 26 27 28 29 30 31 32 33 34 35 36
OUT1
SSR
OUT2
SSR
OUT3
SSR
OUT4
SSR
13 14 15 16 17 18 19 20 21 22 23 24
Triac
(1) Power
AC L
100-240 V
N
(2) Alarm output
Relay contact
ALM1
NO
(4) Outp ut 2 (option) 1
Relay contact
OUT5
5
NO
6
OUT6
7
NO
8
OUT7
9
NO
10
11
12
OUT8
NO
AC L
1
24 V
2
N
3
(NO: Normally Open)
4
Voltage pulse/
Current OUT5
53
+
54
-
OUT6
55
+
56
-
OUT7
57
+
58
-
OUT8
59
+
60
-
(9) Input
Thermocouple
14
+
TC1
15
-
17
+
TC2
18
-
20
+
TC3
21
-
23
+
TC4
24
-
RTD
13
A
RTD1
14
B
15
B
16
A RTD2
17
B
18
B
19
A RTD3
20
B
21
B
22
A RTD4
23
B
24
B
Voltage
14
15
17
18
20
21
23
24
IN1
IN2
IN3
IN4
+
-
+
-
+
-
+
-
49
50
51
52
(Option)
SG
T (A)
T (B)
R (A)
R (B)
(6) Contact input
RUN/STOP
37
38
Memory area
transfer
39
40
41
42
DI SET
43
RS-485
44
45
46
RS-232C
44
45
46
(5) Alarm output
+
DC
1
24 V
2
-
Triac
OUT5
53
SSR
54
OUT6
55
SSR
56
OUT7
57
SSR
58
OUT8
59
SSR
60
Relay contact
1
ALM2
2
NO
ALM3
NO
53
(7) Communication (op tion)
54
RS-422A
44
55
45
56
46
57
47
58
48
59
60
DI
DI1
DI2
DI4
(Option)
SG
T/R (A)
T/R (B)
SG
SD
RD
(8) CT input 2
25
CT1
26
CT2
27
28
CT3
29
CT4
30
31
CT5
32
CT6
33
34
CT7
35
CT8
36
(Option)
Not isolated between each channel. Relationship between CT input and channel number, see
7.8 Heater Break Alarm (HBA) Function. ( P. 18) RTD and voltage inputs:
Not isolated between each input channel.
4
Input terminals (TC1 to TC4, RTD1 to RTD4, IN1 to IN4) correspond to channel num bers 1 to 4 (CH1 to CH4).
4
IMR01H01-E4
Page 5
!"
3, 4
2, 3
2
MA901
With communication or contact input function
(5)
(6)
37
49
1
(1) (2)
(3)
2 3 4 5 6 7 8
9 10 11 12
50 51 52 53 54 55 56 57 58 59 60
(4)
38 39 40 41 42 43 44 45 46 47 48
(7)
With heater break alarm function
(5)
37
49
1
(1) (2)
(3)
(1) Power
AC L
100-240 V
N
AC L
24 V
N
+
DC
24 V
-
2
3
4
5
6
7
8
9 10 11 12
50 51 52 53 54 55 56 57 58 59 60
(4)
1
2
1
2
1
2
38 39 40 41 42 43 44 45 46 47 48
(2) Alarm output
(NO: Normally Open)
(10)
25 26 27 28 29 30 31 32 33 34 35 36
(10) (9) (8)
25 26 27 28 29 30 31 32 33 34 35 36
Relay contact
ALM1
NO
49
50
51
52
(6) Contact input
RUN/STOP
37
DI
38
Memory area
transfer
39
DI1
40
DI2
41
DI4
42
DI SET
43
(Option)
(5) Alarm output
(9)
13 14 15 16 17 18 19 20 21 22 23 24
13 14 15 16 17 18 19 20 21 22 23 24
Relay contact
ALM2
NO
ALM3
NO
(Option)
1
Not isolated between each channel.
Relationship between CT input and channel number, see
7.8 Heater Break Alarm (HBA) Function. ( P. 18)
3
RTD and voltage inputs: Not isolated between each input channel.
4
Input terminals (TC1 to TC8, RTD1 to RTD8, IN1 to IN8) correspond to channel num bers 1 t o 8 (CH1 to CH8).
(3) Outp ut 1 1
Relay contact
3
NO
4
NO
NO
NO
OUT1
OUT2
OUT3
OUT4
Voltage pulse/
5
6
7
8
9
10
11
12
+
-
+
-
+
-
+
-
Current OUT1
OUT2
OUT3
OUT4
Triac
OUT1
5
SSR
6
OUT2
7
SSR
8
OUT3
9
SSR
10
OUT4
11
SSR
12
(7) Communication (option)
RS-422A
44
SG
45
T (A)
46
T (B)
47
R (A)
48
R (B)
RS-485
44
SG
45
T/R (A)
46
T/R (B)
RS-232C
44
45
46
(4) Outp ut 2 1
Relay contact
OUT5
5
6
7
8
9
10
11
12
NO
NO
NO
NO
OUT6
OUT7
OUT8
53
54
55
56
57
58
59
60
SG
SD
RD
Voltage pulse/
Current OUT5
53
+
54
-
OUT6
55
+
56
-
OUT7
57
+
58
-
OUT8
59
+
60
-
(8) CT input 2
37
CT1
38
39
40
CT3
41
42
43
CT5
44
45
46
CT7
47
48
(Option)
Triac
OUT5
SSR
OUT6
SSR
OUT7
SSR
OUT8
SSR
CT2
CT4
CT6
CT8
53
54
55
56
57
58
59
60
(9) Input
Thermocouple
14
TC1
15
17
TC2
18
20
TC3
21
23
TC4
24
(10) Input
Thermocouple
26
TC5
27
29
TC6
30
32
TC7
33
35
TC8
36
RTD
13
A
RTD1
14
B
+
15
-
B
16
A RTD2
17
B
+
18
-
B
19
A RTD3
20
B
+
21
-
B
22
A RTD4
23
B
+
24
-
B
Voltage
14
15
17
18
20
21
23
24
IN1
IN2
IN3
IN4
+
-
+
-
+
-
+
-
RTD
25
A RTD5
26
B
+
27
-
B
28
A RTD6
29
B
+
30
-
B
31
A RTD7
32
B
+
33
-
B
34
A RTD8
35
B
+
36
-
B
Voltage
26
27
29
30
32
33
35
36
IN5
IN6
IN7
IN8
+
-
+
-
+
-
+
-

4. PARTS DESCRIPTION

This chapter describes various di splay units and the key functions.
Channel (CH) display
Memory area display
Indication lamp
Channel key
AREA
PV
CH
SV
OUT3OUT2OUT1OUT4
AT
CH
MA900
OUT5OUT6OUT7OUT8
ALM1ALM2ALM3
R/S
SET
Set key
(The above figure is MA900. The figure of MA901 is the same as a MA900.)
Measured value (PV) display [Green]
Displays PV or various parameter symbols.
Set value (SV) display [Orange]
Displays SV or various parameter set value.
Channel (CH) display [Green]
Displays channel number.
Displays character “A” showing batch
setting.
Memory area (AREA) display [Orange]
Displays memory area number.
Measured value (PV) display
Set value (SV) display
UP key
DOWN key
Shift & R/S key
Indication lamps: Autotuning (AT) lamp [Green]
Flashes with the autotuning activated in the displayed channel
Output (OUT1 to OUT8) lamp [Green]
Lights when the output corresponding to each lamp is ON.
Alarm lamp *
(ALM1 to ALM3) [Red]
ALM1: Lights when alarm1 is turned on. ALM2: Lights when alarm2 is turned on. ALM3: Lights when alarm3 is turned on.
Bright lighting:
*
Indicates that the display channel is alarm state. Dim lighting: Indicates that other channel except a display channel is alarm state.
Channel key
Used when the channel number is
changed. Used to display the character “A”
showing batch setting. Used for start /stop of scan display.
Shift & R/S key
Shift digits when settings are changed.
Selects the RUN/STOP.
Set key
.
Used for parameter c alling up and set value registrat ion.
Up key DOWN key
he avoid damage to the instr ument,
T
Increase numerals. Decrease numerals
never use a sharp object to press keys.
IMR01H01-E4
5
Page 6

5. SETTI NG

This chapter descr ibes the oper ation flowc hart of mode and the s etting item of each mode. This instrument class es sett ing item in four kinds of mode. The mode can be selected by pressing the SET or <R/S key

5.1 Operation Flowchart of Mode

Regardless of the di splay time of the input type or i nput range, control st arts about 4 seconds
Power ON
Input type/Input range Display
Diplay changes automatically
after the power is turned on. If the key is not pr es s ed for more t han one minut e, the di spl ay will automatically return to the
PV/SV monitor mode. If the function is not selected f or all of the channels , that parameter symbol is not displayed.
In case of MA901, parameter symbols of the following are not displayed;
Current transf ormer 2 monitor, cool-side proportional band, overlap/deadband, heater break alarm 2, cool-side proport ioning cycle time
Press the SET key for 2 seconds.
Press the <R/S key while pressing the SET key.
PV/SV Monitor Mode (P. 7)
Measured value (PV)
Set value (SV)
Press the <R/S key for 1 second.
Set value (SV)
RUN state
STOP state
Press the SET key
SV Setting & CT Monitor Mode
(P. 7)
S
et value (SV) setting
SV
SET key
Memory area transfer
ArE
SET key
Current transformer 1 monitor
CT1
SET key
Current transformer 2 monitor
CT2
SET key
To PV/SV monitor mode
Input type/Input Range Display
This instrument displays input type code and input range just after power supply ON by each 2 seconds.
PVCH
AREA SV
PVCH
AREA SV
Input Type Symbol Table
Symbol
Input Type
K J R SBE T N
Symbol
Input Type
RTD
JPt 100Pt100
Symbo
l
Input type symbol (SeeTable)
Engineering unit (Voltage input: No display)
Input range high
Input range low
Thermocouple
Voltage
W5Re/
PL
II
W26Re
U L
Parameter Setting Mode (P. 10)
Control loop break
LbA
Lbd
AL1
AL2
AL3
P
I
d
Ar
Pc
db
SVrL
CH E
:
alarm
SET key
Control loop break alarm deadband
SET key
Alarm 1
SET key
Alarm 2
SET key
Alarm 3
SET key
Proportional band
SET key
Integral time
SET key
Derivative time
SET key
Anti-reset windup
SET key
Cool-side proportional band
SET key
Overlap/deadband
SET key
Setting changing rate limiter
SET key
Used/unused of channels
SET key
Setting item for memory area function
: These items are not displayed with MA901.
Press the
R/S key
while pressing the SET key.
Press the SET key for 2 seconds.
Setup Setting Mode (P. 8)
Autotuning (AT)
ATU
SET key
Heater break alarm 1
HbA1
SET key
Heater break alarm 2
HbA2
SET key
PV bias
*
Pb
SET key
Digital filter
dF
SET key
Proportioning cycle time
T
SET key
t
SET key
Add
SET key
bPS
SET key
bIT
SET key
InT
SET key
SCAn
SET key
LCK1
SET key
LCK2
SET key
Set the parameter for each channel.
*
*
Cool-side proportioning cycle time
Device address
Communication speed
Data bit configuration
Interval time
Scan interval time
Lock level 1
Lock level 2
*
*
*
*
6
IMR01H01-E4
Page 7

5.2 PV/SV Monitor Mode

PV/SV monitor mode can confirm the measured value (PV) and the set value (SV). Usually, set to this mode during control execution. For checking the measured value (PV) and set value (SV) during operation, the following two methods are available.
Checking PV and SV corresponding to each channel
!"
In PV/SV monitor mode, the PV and SV correspondi ng to the dis played channel c an be checked. Each ti me the CH key is pr essed, the SV corresponding to eac h channel wit hin the memor y area (herei nafter cal led “cont rol area” ) used for cont rol can be c hecked for each channel.
Display example:
Indicates that PV / SV now on display corresponds to channel 1 within cont rol area 1.
Indicates that memory area number 1 is selected as a control area.
When the setting change rate limit er is set, a condit ion in which the set value ( SV) goes changing according t o that rate of change is displayed.
If the instrument needs to be switched to RUN or STOP mode, press the <RS key in PV/SV monitor mode. In addition, RUN/STOP can be selected by key operation or by open or closed contact input ( option).
6.3 Transfer of RUN/STOP (P. 14)
Checking SV corresponding to all of the channels within the control area
!"
The SV corresponding to al l the channels within the control area are automatically check ed at each scan interval time.
5.4 Setup Setting Mode (P. 8), 7 .5 Scan Display Functi on ( P . 16)
PV/SV monitor mode display
PVCH
SVAREA
Indicates that PV corresponding to channel 1 within the control area is 300 °C
Indicates that PV corresponding to channel 1 within the control area is 350 °C.

5.3 SV Setting & CT Monitor Mode

SV setting & CT monitor mode i s us ed to set the set value ( SV) and cont rol ar ea or to moni tor t he curr ent value ( cur rent t ransf ormer 1, current transformer 2). Press the SET key with state of PV/SV monitor mode to shift to this mode. The UP, DOWN or <R/S key is used to change the numeric value, and the SET key is used to change the parameter as well as to register the numeric value.
Description of each parameter
!"
Set value (SV) setting
PVCH
SVAREA
Memory area transfer
PVCH
SVAREA
Current transformer 1 monitor
PVCH
SVAREA
Set the set value (SV) which is the desir ed value for control. Setting range: Within input range Factory set value: Temperature input 0 °C [°F] or 0.0 °C [°F] Voltage input 0.0 %
Up to eight memories per channel can be set with one set value (SV) assumed to be one
memory. The set values (SV) corr esponding to all of the channels withi n the s ame control area can be
simultaneously s et as the same value. No setting can be changed when “1 (Lock)” is selected by the lock level 1.
Selects the memory ar ea used for control ( H ereafter called the control area). Setting range: 1 to 8 Factory set value: 1
No setting can be changed when “1 (Lock)” is selected by the lock level 2.
One set value (SV) and up to eight setting items of the parameter setting mode per channel
can be stored.
For details of the setting items of parameter setting mode, see
5.5 Parameter Setting
Mode. (P. 10)
Displays the input value of the current transf ormer 1 used when the instrument i s provided with the heater break alarm 1. Display range: 0.0 to 100.0 A
(Option)
Current transformer 2 monitor
PVCH
SVAREA
(Option)
To PV/SV monitor mode
IMR01H01-E4
Not displayed when this instrument is not provided with the heater break alarm 1 function.
Displays the input value of the current transformer 1 used when the instrument is provided with
the heater break alar m 2 (Z-168).
[ Correspond to only MA900]
Displays the input value of the current transf ormer 2 used when the instrument i s provided with the heater break alarm 2 ( Z-168). Display range: 0.0 to 100.0 A
Not displayed when this instrument is not provided with the heater break alarm 2 function.
In case of MA901, this monitoring scr een is not provided.
7
Page 8

5.4 Setup Setting Mode

Setup setting mode is used to set the heater beak alarms, PV bias, digital filter, communi cation, and to lock the set data. The instrument can be switched to AT start or AT canc el. Pres s the <R/S key whi le pres si ng the SET key wi th st at e of PV/SV monit or mode, SV se tting & CT monitor mode, or parameter s ett ing mode t o s hif t t o thi s mode. The UP, DOWN or <R/S key is us ed to c hange the numer ic val ue, and the SET key is used to change the parameter as well as to register the numeric value.
Description of each parameter
!"
Execution of autotuning (AT)
PVCH
PVCH
SVAREA
SVAREA
Heater break alarm 1 (HBA1)
PVCH
PVCH
SVAREA
SVAREA
(Option)
The AT function is execut ed to the control area now in operation. Setting range: ON: AT start or execution OFF: AT end or cancel Factory set value: OFF
The batch setting al lows the autotuning to be executed simultaneously in all channels.
When instrument displays data without a channel, an AT lamp does not flash during AT
execution.
HBA1 set value is set by referring to monitor value from the current transformer 1. Used for single-phase or three-phase. Displayed only for when the heat er break alarm is selected as alarm 2. Setting range: 0.0 to 100.0 A OFF: HBA1 function OFF Factory set value: OFF
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
HBA is not available on a current output.
Set HBA1 set value to a value about 85 % of current transformer 1 input value.
When power supply variations are large, set the HBA1 set value to a slightly smal ler value. In
addition, when two or more heaters are connected in parallel, set t he HBA1 set value to a slightly larger value so that it is activated even with only one heater broken (However, wi thin the value of current transformer 1). When no current transformer is connected in any s etting other than “OFF, ” the heater break
alarm is turned on.
Heater break alarm 2 (HBA2)
PVCH
HBA2 set value is set by referring to monitor value from the current transformer 2. Used only for three­phase. Displayed only for when the heater break alarm (Z-168) is selec ted as alarm 2.
SVAREA
Setting range: 0.0 to 100.0 A OFF: HBA2 function OFF Factory set value: OFF
(Option)
PV bias
PVCH
Set the PV bias to add to measured value f or sens or corr ect ion, et c. The PV bi as is us ed to cor rec t the individual variations in the sensors or when there is differ ence between the measured values (PV) of
SVAREA
other instruments. Setting range: -s pan to +span (Within -1999 to +9999 digits ) Factory set value: Temperature input 0 °C [°F] or 0.0 °C [°F] Voltage input 0.0 %
Digital filter
PVCH
Set the time of the first-order lag filter which rejects any noise contained in the measured input. Setting range: 1 to 100 seconds OFF: Digital filter function OFF
SVAREA
Factory set value: OFF
[Correspond to only MA900]
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
HBA is not available on a current output.
Set HBA2 set value to a value about 85 % of current transformer 2 input value.
When power supply variations are large, set the HBA2 set value to a slightly smal ler value. In
addition, when two or more heaters are connected in parallel, set t he HBA2 set value to a slightly larger value so that it is activated even with only one heater broken (However, wi thin the value of current transformer 2). When no current transformer is connected in any s etting other than “OFF, ” the heater break
alarm is turned on. In case of MA901, this setting item is not provided.
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
Proportional cycle time
PVCH
SVAREA
(A)
8
Set control output cycle. For heat/c ool PID action: Heat-side proportional cycle time Setting range: 1 to 100 seconds Factory set value:Relay contact output 20 seconds Voltage pulse output, triac output 2 seconds
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
Not displayed for c urrent output.
Continued on the next page.
IMR01H01-E4
Page 9
Continued from the previous page.
(A)
[Correspond to only MA900]
Cool-side proportional cycle t ime
PVCH
Displayed only for heat/cool PID control. Set the cool-side contr ol output cycle for the heat/cool PID control.
SVAREA
Setting range: 1 to 100 seconds Factory set value: Relay contact output 20 seconds Voltage pulse output, triac output 2 seconds
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
Not displayed for c urrent output.
In case of MA901, this setting item is not provided.
Device address (Slave address) Communication speed Data bit configur ation Interval time
PVCH
PVCH
PVCH
PVCH
SVAREA
SVAREA
These parameter is di splayed when the communication function is provided.
For details, s ee the
Communication Instruct ion Manual (IMR01H02-E
Scan interval time
PVCH
Sets the time until changed to the next screen when s can-displayed. Setting range: 1 to 10 seconds
SVAREA
Factory set value: 2 seconds
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
Only the relevant parameter corresponding to t he cannel set to “MonI” or “ConT” in
“used/unused channels” of the parameter s etting mode can be scan-di splayed.
Lock level 1
PVCH
SVAREA
Set to the control area now in operation to res trict parameter setting changes by the key operation. Setting range: (1) I tems other than SV and alarms (ALM1 to ALM3)
0: Unlock 1: Lock (2) Alarms (ALM1 to ALM3) 0: Unlock 1: Lock (3) SV 0: Unlock 1: Lock
(4) (3)(2)(1)
(4) No setting (“0” Fixed)
Factory set value: 0000
The lock level 1 can be changed even when the whole set data is locked.
SVAREA
.
####
)
SVAREA
Lock level 2
PVCH
SVAREA
(4) (3)(2)(1)
Set to the control area now in operation to rest rict RUN/STOP and memory area changes. Setting range: (1) RUN/STOP transfer 0: Unlock 1: Lock
Factory set value: 0000
The lock level 2 can be changed even when the whole set data is locked.
Return to first parameter “Execution of autotuning (AT)”
IMR01H01-E4
(2) Memory area transfer 0: Unlock 1: Lock (3) No setting (“0” Fixed) (4) No setting (“0” Fixed)
9
Page 10

5.5 Parameter Setting Mode

The parameter setting mode is used to set various settings relating to control, to change various alarm settings and also to set the setting change rate limiter and us ed/unused channels . Setti ng items bel onging to the parameter setti ng mode correspond t o the multi -memory area functions and can be stored up to eight memories. Press the SET key for 2 seconds with state of PV/SV monitor mode, SV setting & CT monitor mode, or setup setting mode to shift to this mode. The UP, DOWN or <R/S key is used to change the numeric value, and the SET key is used to change the parameter as well as to register the numeric value.
Description of each parameter
!"
Control loop break alarm ( LBA)
PVCH
SVAREA
Control loop break alarm deadband ( LBD)
PVCH
SVAREA
Alarm 1 (ALM1)
PVCH
SVAREA
Monitors measured val ue variations and also s ets the time to detect any abnormal control loop. Displayed only for when the LBA i s selected as alar m 1. Setting range: 0.1 to 200. 0 minutes OFF: LBA function OFF Factory set value: 8.0 minut es
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
We recommend that the set value of LBA be twi ce the value of the integral time (I).
If the autotuning function is used, the LBA setting time twice as large as the int egral time is automatically set.
Set the area of not outputting LBA. Displayed only for when the LBA is selected as alarm 1. Setting range: 0 to span (0: LBD OFF) Factory set value: Temperature input 0 °C [°F] or 0.0 °C [°F] Voltage input 0.0 %
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
Set the ALM1 set value. Displayed when any one of the deviation, pr ocess and SV alarms is selected as the alarm 1. Setting range: Process alarm, SV alarm: Same as input range
Deviation alarm: -span to +span (Within -1999 to +9999 digits)
Factory set value: Temperature input 50 °C [°F] or 50.0 °C [°F] Voltage input 5.0 %
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
Not displayed when FAIL alarm or control loop break alarm is selected for alarm 1.
Alarm 2 (ALM2)
PVCH
SVAREA
(Option)
Alarm 3 (ALM3)
PVCH
SVAREA
(Option)
Proportional band (P)
PVCH
SVAREA
Integral time (I)
PVCH
SVAREA
Set the ALM2 set value. Displayed when any one of the deviation, pr ocess and SV alarms is selected as the alarm 2. Setting range: Process alarm, SV alarm: Same as input range
Deviation alarm: - span to +span (Within -1999 to +9999 digit s)
Factory set value: Temperature input 50 °C [°F] or 50.0 °C [°F] Voltage input 5.0 %
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
Not displayed when FAIL alarm or heater break alarm is selected for alarm 2.
Set the ALM3 set value. Displayed when any one of the deviation, pr ocess and SV alarms is selected as the alarm 3. Setting range: Process alarm, SV alarm: Same as input range
Deviation alarm: - span to +span (Within -1999 to +9999 digit s)
Factory set value: Temperature input 50 °C [°F] or 50.0 °C [°F] Voltage input 5.0 %
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
Not displayed when FAIL alarm is selected for alarm 3.
Set the proportional band for the P control, PI control or PD control. For heat/cool PID ac tion: Proportional band setting on the heat-side. Setting range: 0 (0.0) to span (However, 9999 digi ts or less) Factory set value: Temperature input 30 °C [°F] or 30.0 °C [°F] Voltage input 3.0 %
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
ON/OFF action when set to 0 (0.0).
Set the time of integral action which eliminates the offs et occurring in pr oportional control. Setting range: 1 to 3600 seconds OFF (0 second) : Integral action OFF (PD action) Factory set value: 240 sec onds
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
10
(A)
Continued on the next page.
IMR01H01-E4
Page 11
Continued from the previous page.
(A)
Derivative time ( D )
PVCH
Set the time of derivative action which prevents ripples by predi cting output changes and thus improves control stability.
SVAREA
Setting range: 1 to 3600 seconds OFF (0 second): Derivative action OFF (PI action) Factory set value: 60 sec onds
Anti-reset windup
PVCH
In order to prevent an over shoot caused by the integral effect, sets the value to rest rict the effective range of integral ac tion.
SVAREA
Setting range: 0 to 100 % of proportional band (0: Integral action OFF) Factory set value: 100 %
Cool-side proportional band
PVCH
Displayed only for heat/cool PID control. Set the cool-side proportional band for the heat/cool PID control.
SVAREA
Setting range: 1 to 1000 % of heat-side proporti onal band Factory set value: 100 %
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
[Correspond to only MA900]
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
In case of MA901, this setting item is not provided.
Overlap/deadband
PVCH
SVAREA
[Correspond to only MA900]
Setting change rate limiter
PVCH
SVAREA
Displayed only for heat/cool PID control. Set the deadband between the heat-side proportional band and the cool-side proportional band. Setting range: -s pan to +span (Within -1999 to +9999 digits ) Factory set value: Temperature input 0 °C [°F] or 0.0 °C [°F] Voltage input 0.0 %
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
In case of MA901, this setting item is not provided.
Minus (-) setting results in overlap.
SV
DB
Cool-side proportional band
Cool-side output value
Temperature
OL: Overlap DB: Deadband
Manipulated output (MV)
100 %
Heat-side output value
0 %
Heat-side proportional band
(In proportional control)
OL
Set the amount of set value (SV) change per 1 minute when the SV is changed. Setting range: 0 (0.1) to span/min. OFF: Setting change rate limiter OFF Factory set value: OFF
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
The set value (SV) while the setting change rate limiter can be chec ked in PV/SV monitor
mode. When the power i s turned on or the operation is changed from STOP to RUN, the setting
change rate limiter functions towar d the set value (SV) from the measured value (PV) when started. If the autotuning (AT) function is ac tivated while the setting change rate limiter functions, PID
control conti nues until the limiter completes it s functioning, and the AT function is act ivated after the limiter completes its functioning.
Used/unused of channels
PVCH
SVAREA
Return to first parameter setting item.
IMR01H01-E4
Select the used or unused of each channel for each memory area. Setting range: (oFF): Unused (MonI): Used for only alarm
(ConT): Used for control and alarm
Factory set value: ConT
No setting can be changed when “1 (Lock)” is selected by the lock level 1.
During display scanning, each unused channel is skipped. When the channel number is
selected by the CH key, any unused channel is dis played.
11
Page 12

5.6 Setting Procedure

5.6.1 Usual setting (Setting f or each channel)

Some examples of changing the set value (SV) are described in the following. The same setting procedure applies when other parameters are also set.
When the SV is changed
!"
When CH1 set val ue (SV) of the control area 1 is change from 0
C to 300 °C:
°
Press the SET key in PV/SV monitor
1.
PVCH
mode state to transfer to SV setting & CT monitor mode.
Press the <R/S key t o light brightl y
2.
SVAREA
PVCH
the hundreds digit. The brightly lit digit indicates which digit can be
SVAREA
set. Every time the <R/S key is pressed,
the brightly lit digit moves as follows.
AREA SV
Press the UP key to change to 3.
3.
Bright lighting
PVCH
SVAREA
When another area set value (SV) is changed without
!"
changing control area
When changing the set value (SV) cor responding to channel 2 in memory area 3 from 150 °C to 100 °C with the memory area set to memory area 1:
Press the SET key in PV/SV monitor
1.
PVCH
mode state to transfer to SV setting & CT monitor mode.
Press the <R/S key t o light brightl y
2.
the AREA display. The brightly lit digit indicates which digit can be
SVAREA
PVCH
SVAREA
set. Every time the <R/S key is pressed,
Bright lighting
the brightly lit digit moves as follows.
AREA SV
Press the UP key to change to 3.
3.
PVCH
The SV display shows the channel 1 set value (SV) of the memory area
SVAREA
number 3. Also, the number of AREA display flashes.
Flashing
Press the SET key to register the
4.
value thus set. The di splay changes to the next parameter (Memory area
PVCH
SVAREA
transfer display).
The following is also available when changing the set value.
Set value increase ( When 199 °C is changed to 200 °C):
!"
Press the <R/S key to light brightly t he least significant digit.
1.
Press the UP key to change to 0.
2.
The display changes to
PV
SV
Set value decrease (When 200 °C is changed to 190 °C):
!"
Press the <R/S key to light brightly t he tens digit.
1.
Press the DOWN key to change to 9.
2.
The display changes to
PV
SV
Minus (-) value setting (When 200 °C is changed to -100 °C):
!"
Press the <R/S key to light brightly t he hundreds digit.
1.
Press the DOWN key (three times) to change to -1.
2.
The display changes to
PV
SV
200
190
-100.
.
PV
SV
.
PV
SV
PV
SV
Press the CH key to change to 2.
4.
The SV display shows the channel 2 set value (SV) of the memory area number 3.
Press the DOWN key to change to
5.
0
in the tens digit.
Press the SET key to register the
6.
value thus set. The dis play changes to the next parameter (Memory area transfer display).
The changed set value is registered by pressing the SET key or also at the time when any of the following key operations is performed.
When the channel number is changed by the CH key
When the memory ar ea number is changed
PVCH
SVAREA
Flashing
PVCH
SVAREA
Flashing
PVCH
SVAREA
12
IMR01H01-E4
Page 13

5.6.2 Batch setting (All channels batch setting)

The parameters select ed from one memory area and cor r espondi ng to all of the channel s c an be si mult aneous ly set as the s ame val ue. The set values (SV) as well as the parameters set for each channel can be simultaneously set. Some examples of changing the set value (SV) simultaneous ly are described in t he following. The same sett ing procedure applies when ot her parameters for each channel are also set.
When the SV is changed in batch setting
!"
When all s et value (SV) of the c ontrol area (memory area 1) is change from 0 °C to 300 °C:
Press the SET key in PV/SV monitor
1.
PVCH
mode state to transfer to SV setting & CT monitor mode.
Press the CH key. Display the
2.
SVAREA
PVCH
character A on the CH display and “----“ on the SV display. The
SVAREA
character A indicates that the bat ch setting.
Every time the CH key is pressed, the channel number changes as follows .
Press the <R/S k ey to light bright ly
3.
PVCH
the hundreds digit.
SVAREA
Bright lighting
The set values (SV) in other memory areas are
!"
simultaneously set to the same value without changing the control area
When changing t he set values (SV) correspondi ng to all of the channels in memory area 2 fr om 0 °C to 300 °C with the control area corresponding t o memory area 1:
Press the SET key in PV/SV monitor
1.
PVCH
mode state to transfer to SV setting & CT monitor mode.
Press the CH key. Display the
2.
SVAREA
PVCH
character A on the CH display and “----“ on the SV display. The
SVAREA
character A indicates t hat the batc h setting.
Every time the CH key is pressed, the channel number changes as follows .
Press the <R/S key t o light brightl y
3.
PVCH
the AREA display.
SVAREA
Bright lighting
Press the UP key to change to
4.
Press the SET key. The value thus
5.
set is regist ered simultaneously for all of the channels. The display changes to the next parameter (Memory area transfer).
3.
PVCH
Press the UP key to change to 2.
4.
PVCH
The number of AREA display flashes.
SVAREA
PVCH
Press the <R/S key t o light brightl y
5.
SVAREA
Flashing
PVCH
the hundreds digit.
SVAREA
Press the UP key to change to 3.
6.
Press the SET key. The value thus
7.
SVAREA
Bright lighting
PVCH
SVAREA
PVCH
set is regist ered simultaneously for all of the channels. The display
SVAREA
changes to the next parameter (Memory area transfer).
The set value (SV) corresponding to any unused channel is also subjected to the batch setting. For details of s hifting, see page 12.
IMR01H01-E4
13
Page 14

6. OPERATION

This chapter describes instrument operation, the inst rument operation, RUN/STOP transfer, and control area transfer, etc.

6.1 Power ON

After power on, this instrument st arts control in about 4 seconds.
When a power failur e of more than 30 ms occurs, t he instrument assumes that the power has been turned off. When power ret urn, the ins trument per forms t he same operation as that at the time of power on.

6.2 Change of the Set Value (SV)

To change the set value (SV) , set the instrument to SV
setting & CT monitor mode.
5.1 Operation Flowchart of Mode (P. 6),
5.6 Setting Procedure (P. 12)
The set values (SV) corresponding to all of the channels
within the same control area can be simultaneously set as the same value.
5.6.2 Batch setting (P. 13)
The set values (SV) i n other memory areas can be changed
without changing the c ontrol area.
5.6.1 Usual setting (P. 12), 5.6.2 Batch setting (P. 13)
While t he set value (SV) is locked by Lock Level 1, no s et
value (SV) can be changed.
5.4 Setup Setting Mode (P. 8)
When the contact input state is RUN mode, RUN/STOP can be selected by k ey operation.
Only key operation is in the STOP mode.
:
Only contact input is in the STOP mode.
:
Both key operation and contact input are in
:
the STOP mode.
Conditions when changed to STOP mode:
Control:
Alarm:
AT:
RUN/STOP transfer by key operation
$"
$"
$"$"
OFF OFF Cancel (The PID constants are not updated)
When changing RUN t o STOP in the state without RUN/STOP transfer by contact input.
PVCH
Press the <R/S key for 1 s econd
1.
in PV/SV monitor mode.
SVAREA
RUN state
PVCH
The mode is changed to STOP
2.
from RUN. The PV display
SVAREA
shows the character s of showi ng the relevant STOP state.
STOP state

6.3 Transfer of RUN/STOP

RUN/STOP can be selected by contact input (option) or communication (option) other than the key operation. In addition, at STOP the key operation and contact state are displayed on the PV display. Relationships between key operation, RUN/STOP and the characters to indic ate the STOP state are shown in the followi ng. When the RUN/ STOP is transfer red by communication, see t he
(IMR01H02-E
RUN/STOP with Key Operation
).
####
After the cont act is clos ed, it takes a short time* until the action of this device is actually selected. Therefore, pay attention to thi s delay time if the device is used together with a sequenc er, etc.
0.5 seconds (shortest)
*
Communication Instruction Manual
RUN/STOP with Contact Input
RUN
(Contact closed)
STOP
(Contact open)
RUN RUN STOP
STOP
is not
displayed
STOP STOP STOP
(KSTP) (SToP)
(dSTP)
Also when changing from STOP to RUN, press the <R/S key for 1 second whil e on the PV/SV monitor display.
No RUN/STOP transfer by k ey oper ati on c an be made when “1 (Lock)” is selected by the l ock level 2.
RUN/STOP transfer by contact input (Option)
$"
RUN/STOP can be selected according to the open or closed state of the terminal numbers 37 and 38.
37
RUN/STOP
38
Terminal No. RUN STOP
37 - 38
Contact closed Contact open
After the cont act is clos ed, it takes a short time* until the action of this device is actually selected. Therefore, pay attention to thi s delay time if the device is used together with a sequenc er, etc.
0.5 seconds (shortest)
*
14
Only
is displayed at the time of STOP in the
SToP
state without RUN/STOP transfer by contact input.
IMR01H01-E4
Page 15

6.4 Transfer of Control Area

The memory area used for this control (control area) can be selected by contact input (option) or communication (option) other than the key operation. The memory area transfer by contact input and the key operation is shown in t he following. When the memory area is transferr ed by communication, see the
Communication Instruct ion Manual (IMR01H02-E!).
Control area transfer by key operation
"#
When the cont rol ar ea is c hanged from memor y area number 1 to 3.
PVCH
SVAREA
Press the SET key in PV/SV
1.
monitor mode state to transfer to SV setting & CT monitor mode.

6.5 Autotuning (AT)

The AT function automatical ly measures, computes and sets the optimum PID and LBA constant s. If the AT funct ion is activated, the optimum PID const ants concerning the s et value (SV) in the control area and the LBA sett ing time can be automatically set (Limit cycl e system is adopted) . This functi on is act ivated power ­ON, during temperature rise and/or when control is stabilized from any process stat e. The result obtained by AT is r eflected to the parameters (P, I , D and LBA) of the parameter setting mode.
AT start
"#
Start AT when all foll owing conditions are s atisfied:
$#
Prior to star ti ng the AT, end all t he par ameter s ett ings ot her
-
than PID and LBA. Both the lock l evel 1 and the lock level 2 should be set to
-
0000
RUN/STOP is in the RUN mode.
-
PVCH
SVAREA
PVCH
SVAREA
PVCH
SVAREA
Press the SET key to change
2.
the display to
(memory
ArE
area transfer di splay).
Press the UP key to change to 3.
3.
Press the SET key to register
4.
the value thus set. The AREA display shows the memor y area number 3. (The figure at left shows the curr ent transformer 1 monitor display)
For memory area numbers, the number changed last is effective.
The memory area number (contr ol area) can be changed at either RUN or STOP.
Control area transfer by contact input (Option)
"#
The control area can be selec ted ac c or ding t o the open or c l ose state of the terminal numbers 39 to 43. The memory area number is selected acc ording to the open or close stat e of the terminal number 39 to 42, and the selected memory area number is registered when the t erminal number 39 and 43 (DI SET) changes from the open state to the close state.
$#
Procedure:
PVCH
Change the mode to the setup
1.
setting mode to show the
SVAREA
execution of autotuning (AT) display.
PVCH
Press the UP key to change to
2.
on.
SVAREA
Press the SET key.
3.
After this function is executed, the autotuning lamp flashes.
When the AT is finished, the execution of autotuning (AT) will automatically return to show
(AT lamp
oFF
OFF).
AT cancellation
"#
The AT is canceled if any of the following conditions exist:
When the SV is changed
When the PV bias value is changed
When the PV becomes abnormal when burnout occurs
When the AT does not end in nine hours after AT started
When the power i s turned off
When the RUN/STOP is changed to the STOP mode
When a power fai lure longer than 30 ms occ urs
When the control area is changed
39
DI1
40
DI2
41
DI4
42
DI SET
43
After the contact is closed, it takes a short time* until the action of this device is ac tually selected. Therefore, pay attention to this delay time if the device is used together with a sequenc er, etc.
S
*
terminals are closed.
IMR01H01-E4
Terminal
No.
39 - 40 39 - 41 39 - 42
elect the area in a period 0.5 seconds after the DI SET
Memory area number
12345678
×−×−×−×− ××−−××−− ××××−−−−
: Contact open−: Contact closed
×
If the AT is canceled, the controller immediately changes to PID control. The PID and LBA constants will be the same as before AT was activated.
When AT is competed, the controller immediately changes to PID control. If the control system does not allow the AT cycling process, do not use AT and set each PID constant t o meet the needs of the application.
15
Page 16

7. FUNCTIONS

This chapter describes an outline of function of MA900/MA901.

7.1 PV Bias Function

The value set in the PV bias is added to t he input value (act ual measured value) to c orr ec t t he input val ue. The PV bias i s us ed to correct t he individual vari ations i n the sensors or when there is difference between the measured values (PV) of other instruments.
5.4 Setup Setting Mode (P. 8)

7.2 Digital Filter Function

This is a software filter which reduces input value variations caused by noise. If the time constant of this filter is set appropriately to match the characteristics of the controlled object and the noise level, the effects of input noise can be suppressed. However, i f the t ime cons tant i s too s mall , the f ilt er may not be effective, whi le i f t he ti me c onst ant is t oo lar ge, t hen the input response may actually deteriorat e.
5.4 Setup Setting Mode (P. 8)

7.3 Multi-Memory Area Function

This function is to store the paramet ers such as temperature set value (SV), etc. in up to 8 memories . The paramet ers whi ch c an be stored as one of memories are set value (SV), alarm 1, alarm 2, alarm 3, propor tional band, integral time, derivati ve time, anti­reset windup, cool-side proportional band, overlap/deadband, setting change rate limiter and use/unused of channels. The parameters stored in one of 8 memories retrieved at nec essity and used for contr ol. The memory area used for this control is called the contr ol area.
5.3 SV Setti ng & CT Monitor Mode (P. 7 ) ,
5.5 Parameter Setting Mode (P. 10)
Memory area
6
5
4
3
2
1
These setting items can not be set in MA901.
Control area
Set value (SV)
8
Control loop break alarm
7
Control loop break alarm deadband Alarm Alarm Alarm Proportional band Integral time Derivative time Anti-reset windup Cool-side proportional band * Overlap/deadband * Setting change rate limiter Use/unused of channels
Parameter CH1 CH2 CH3 CH4
1 2 3

7.5 Scan Display Function

The scan display function is for automatically selecting the PV/SV monitor at the scan int erval time for the measured values (PV) and set values ( SV) corresponding to all of the c hannels within the control area. This function enables the control trend of each channel to be checked.
The transfer speed of t he scan dis play is set wi th the i nterval
time of setup setting mode (P. 9). Use the CH key to s top or st art of t he scan dis play funct ion.
The CH key operation is as follows.
Press the CH key for 2 sec Scan s tart. Press the CH key Scan stop.
The channel number can be changed like 1→2→3→4→1 during scan stopping.*
* In case of MA901: 1→2→3→4→5→6→7→8→1
During display scanning, each unused channel is skipped.
The unused channel means the channel set to used/unused channels of the parameter setting mode.
When the channel number is manually changed, both PV and
SV corresponding to any unused channel are also scan­displayed.
The scan display can be made even at any of RUN and STOP.
Scanning display examples:
When scanni ng PV/ SV c or res pondi ng to c hannel 1 t o c hannel 4 in the control ar ea 1 at 2 seconds intervals:
AREA
AREA
CH
PV
Press the CH key for 2 sec.
SV
CH
PV
SV
2 sec
AREA
AREA
CH
PV
SV
CH
PV
SV
・・・
・・・
in
oFF
2 sec2 sec

7.4 Setting Change Rate Limiter Function

The setting change rate limiter functions so as to change the set value (SV) gradually towar d the set value after bei ng changed. This limiter set s how much the set val ue is changed upward or downward per minute.
5.5 Parameter Setting Mode (P. 10)
Example:
<Increasing set value to higher value>
SV
SV
[After change]
SV
[Before change]
Increase gradually
Change set value at this point
16
<Decreasing set value to lower value>
SV
[Before change]
[After change]
Time
SV
SV
Change set value at this point
Decrease gradually
Time
When scanni ng PV/ SV c or res pondi ng to c hannel 1 t o c hannel 4 (channel 3: unused c hannel) in the control ar ea 1 at 2 sec onds intervals:
AREA
CH
PV
Press the CH key for 2 sec.
SVAREA
PVCH
SV
CH
PV
SVAREA
2 sec2 sec
IMR01H01-E4
Page 17

7.6 Batch Setting Function

The batch setting f unction enables the set ting of the parameters selected within one memory area simultaneously to the same value for all of the c hannels. The set val ues (SV) as well as the parameters set f or each channel can be simultaneously set.
5.6.2 Batch setting (P. 13)
The set value (SV) corresponding to any unused channel is also subjected to the batch setting.
All channels of all memory area can not be simultaneously s et as the same value.

7.7 Alarm Function

Alarm function s ets up the alarm state when the measured value (PV) or the deviation reaches the alarm s et values. In the alarm state, the al arm output is output, and the alarms are used to drive the equipment danger signals or the safety equipment.
The output specifi cations are the rel ay contact output.
The alarm output conditi on can be determined by the type of
alarm action value
1
Specify when ordering
2
Setting item of the parameter sett ing m ode
Alarm action type
"#
Deviation high alarm
*(Alarm status where the alarm set value is set to plus)
Low High
*(Alarm status where the alarm set value is set to minus)
Low High
Deviation low alarm
*(Alarm status where the alarm set value is set to plus)
Low High
*(Alarm status where the alarm set value is set to minus)
Low High
Deviation high/low alarm
Low High
Band alar m
Low High
1
2
, the output destination1 and each alarm set
.
OFF ON
OFF
OFF OFF ON
( : SV : Alarm set value)
ON
OFF ON
OFF ON
OFF ON ON
Alarm differential gap
"#
If measured value (PV) is close to the alarm set value, the alarm relay contact may repeatedly turn on and off due to input fluctuations. By the differential gap, repeated turning ON and OFF of the relay contac t can be prevented.
Low alarm
Low High
ON
High alarm
Low High
Alarm di fferen t ia l gap: Tem perature input 2 (2. 0) °C [°F] Volt age in p ut 2.0 %
Alarm hold action
"#
Differential g ap
Low alarm set v a lue
OFF
(Specify when ordering)
OFF
SV
Differential g ap
ON
High alarm set v a lue SV
This hold action is used to mak e alarm invalid unt il the PV exits once from the alarm region by ignoring the alarm s tate even if the PV is in the alarm state when the power is turned on.
The alarm hold action is act ivated when not only the power is turned on, but also the following conditions
When the RUN/STOP is changed to the RUN mode
When the SV is changed
When the memory ar ea (control area) i s changed
Example:
W ith alarm hold action
Measured value (PV)
SV
Alarm set va lue
Alarm hold area
Alarm status
OFF ON
W ithout alarm hold action
Measured value (PV)
Alarm set va lue
SV
Alarm status
ON
PV
Deviation
Time
PV
Deviation
Time
OFF ON
Process high alarm
Low High
OFF ON
Process low alarm
Low High
ON
OFF
SV high alarm
Low High
OFF ON
SV low alarm
Low High
Alarm output
"#
ON
OFF
The alarm output (fact ory set value) of the alar m 1, alar m 2 and alarm 3 are as follows.
Alarm 1
OR
output of the alarm 1 in all channels
(Energized)
Alarm 2
(Option)
Alarm 3
(Option)
OR
output of the alarm 2 in all channels
(Energized)
OR
output of the alarm 3 in all channels
(Energized)
IMR01H01-E4

7.8 Heater Break Alarm (HBA) Function

The heater break alarm (HBA) function is used to detect the current flowing through the load (heater) by using a current transformer (CT) , to compare the current thus detect ed to the heater break alarm set value, and thus to produce a heater break alarm when any of the following causes occurs.
5.3 SV Setti ng & CT Monitor Mode (P. 7 ) ,
5.4 Setup Setting Mode (P. 8)
Occurrence of heater break alarm
"#
When heater current does not flow (Heater break, malfunction of the cont rol device, etc.):
Alarm is issued when the i nput value of the cur rent transf ormer is below the heater break alarm set val ue with the control output turned on. However, no alarm may be normally i s sued when t he control output i s turned on for less than 2 seconds.
When heater current goes following ( welded relay contact, etc.):
Alarm is issued when the i nput value of the cur rent transf ormer is above the heater break alarm set value with the control output turned off. However, no alarm may be normally issued when the control output i s turned off for less than 2 seconds.
17
Page 18
Three-phase heater break alarm function (Z-168) :
A heater break alarm occurs in the following configuration. The inputs of CT1 and CT5 are compared with the set values of HBA1 and HBA2, respectively t o decide heater break or wel ding. [Corresponding to MA900]
Input Occurrence of alarm Output
CT1 (CH1) HBA1 CT5 (CH1) HBA2 Relationship between CT input and channel number:
The following table shows whic h CT input cor r esponds to what input channel number and what CT monitor ing display you can check it with.
Single-phase heater br eak alarm
CH
No.CTinput CH1 CT1 No.25 to 26 No.37 to 38 CH2 CT2 No.25 to 27 No.37 to 39 CH3 CT3 No.28 to 29 No.40 to 41 CH4 CT4 No.28 to 30 No.40 to 42 CH5 CT5 No.43 to 44 CH6 CT6 No.43 to 45 CH7 CT7 No.46 to 47 CH8 CT8 No.46 to 48
Three-phase heater break alarm (Z-168)
CH
No.CTinput CH1 CT1 No.25 to 26 CH2 CT2 No.25 to 27 CH3 CT3 No.28 to 29 CH4 CT4 No.28 to 30 CH1 CT5 No.31 to 32 CH2 CT6 No.31 to 33 CH3 CT7 No.34 to 35 CH4 CT8 No.34 to 36
7.9 Control Loop Break Alarm
The control loop break alar m (LBA) functi on is used to detec t a load (heater) break or a failure in the external ac tuator (magnet relay, etc.) , or a failure in the control loop caused by an input (sensor) break. The LBA function is activated when PID computed value (output ON time/cycle) falls below 0 % or exceeds 100 %. The time required for the LBA output to tur n on includes both the ti me from the ini tial occur rence of loop failure and the LBA setting time.
5.5 Parameter Setting Mode (P. 10)
MA900
Terminal No.
Unused
MA900
Terminal No.
MA901
Terminal No.
MA901
Terminal No.
No function
(LBA)
HBA output
CT monitoring
display
CT monitoring
display
Function
Control loop break alarm deadband (LBD)
"#
"#
"#"#
The control loop break alar m may be produced by dis turbanc es (other heat sour ces) even i f the contr ol s ystem is not abnor mal. In such a case, an area in which no alarm is produced can be set by setting the desired LBD. When the measured value (PV) is within the LBD area, no alarm is produced even if all of the conditions to produce the alarm are satisfied. Therefore, carefully set the LBD.
5.5 Parameter Setting Mode (P. 10)
Alarm area Alarm area
Low High
Cautions for LBA
"#
"#
"#"#
When AT functi on is turned on, the LBA function can not be
activated. No LBA function can be used at heat/cool PID action.
If LBA setting time does not match the controlled object
requirements, the LBA setting time should be lengthened. If setting time is not correct, the LBA will malfunction by turning on or off at inappropriate times or not turning on at all.
The LBA output is tur ned off when any of the foll owing cas es
occurs with t he LBA output turned on.
When the measured val ue (PV) ris es beyond (or falls bel ow)
-
the LBA triggering widt h within the LBA setting ti me
When the measured value (PV) is withi n the LBD
-
LBD differential gap
Non-alarm area
A B
SV LBD set value
A: During temperature rise: Alarm area
During temperature fall: Non-alarm area
B: During temperature rise: Non-alarm area
During temperature fall: Alarm area

7.10 Set Data Lock Function

The set data lock func tion permit s lock ing of cr itic al parameter s and prevents unauthorized personnel from changing parameters. This instrument has the following two loc k levels. The two loc k levels can be changed even when the whol e set data is locked.
Lock level to restrict parameter setting changes by key
operation (Lock level 1) Lock level to restr ict RUN/STOP and memory area changes
(Lock level 2)
5.4 Setup Setting Mode (P. 8)
Alarm action
"#
Heat control : LBA triggering width:
Voltage input 2 % fixed
When the PID computed value fall s below 0 %
For direct act ion:
This alarm is produced when the measured value (PV) does not rise beyond the LBA triggering width within the LBA setting time. For reverse action:
This alarm is produced when the measured value (PV) does not fall below the LBA t riggering width within the LBA set ting time.
When the PID computed value exceeds 100 %
For direct act ion:
This alarm is produced when the measured value (PV) does not fall below the LBA t riggering width within the LBA set ting time. For reverse action:
This alarm is produced when the measured value (PV) does not rise beyond the LBA triggering width within the LBA setting time.
Temperature input 2 °C [°F] fixed
:
:
18

7.11 Contact Input Function (Option)

The external contact signal of this instrument can do the RUN/STOP and the memory area changes.
Transfer of RUN/STOP
"#
"#
"#"#
The RUN or STOP selects by external contact input
6.3 Transfer of RUN/STOP (P. 14)
Transfer of Control Area
"#
The memory area select s by external contac t input. Sel ect one memory area among memorized 8 memory area and change memory area.
6.4 Transfer of Control Area (P. 15)
.
IMR01H01-E4
Page 19

8. ERROR DISPLAYS

f
9. REMOVING THE INTERNAL
Self-diagnostic error
!"
If an error is detected by the self-diagnostic, the PV display flashes “
,” and the SV displ ay shows the error code. When
Err
two or more errors occur simultaneously, the error code numbers are totaled and displayed as one number.
Error number
Description
Adjusted data error
EEPROM error
A/D conversion error
Board configuration error
Watchdog timer error
When the adjusted data error and A/D conversion error occurs simultaneously
Flashing
Action (Output)
Contol output: All the output is OFF.
Alarm output: All the output is OFF. However, FAIL alarm is turned off.
The SV display shows the number 5 obtained by adding 1 (Adjusted data error) to 4 (A/D conversion error).
Solution
Turn off the power once. If error occurs after the power is turned on again, please contact RKC sales office or the agent.
ASSEMBLY
Usually, this i nstrument is not neces sary to remove the internal assembly from the c ase. W hen removing the i nternal as sembly without disconnecting the external wiring, take the following steps.
"
"
To prevent electric shock or instrument failure, only
#"
qualified personnel should be allowed to pull out the internal assembly.
To prevent electric al shock or instr ument failure, always
#"
turn off the power before pulling out the internal assembly. To prevent injury or i nstrument failure, do not touc h the
#"
internal printed wiring board.
Lock (upper)
!
WARNING
Overscale and Underscale
!"
Measured value (PV) is flashing
[Flashing]
[Flashing]
Underscale
PV display
unit
: The range to be displayed differ depending on the input type or the setting limit.
α
Description Display
Input error
PV is outside of input range.
Overscale
PV is above the high input display range limit.
Underscale
PV is below the low input display range limit.
PV flashing
display
α
Input range
Effective input range
(Input range
PV display
Solution
WARNING
!
To prevent electric shock, always turn of the power before replacing the sensor.
Check the sensor or input lead.
)
α
PV flashing
display
α
Overscale
Recommended tool: Blade screwdriver
Lock (low e r)
Unlock using such a blade screwdriver. Gently press down on handle for the upper lock and lift up for the lower lock.
B
lade width: 6
mm or less
Apply pressure very c arefully when removing internal assembly to avoid damage to the frame.
To conform to
IEC61010-1
requirements for protect ion from electric shock, the internal assembly of this instrument can only be removed with an appropriate tool.
IMR01H01-E4
19
Page 20

10. SPECIFICATIONS

Input
!"
!"
!"!"
Number of inputs:
Thermocouple: Isolated between each input channel RTD, Voltage: Not isolated between each input channel
Input type:
Thermocouple: K, J, R, S, B, E, T, N, PLII, W5Re/W26Re,
RTD: Pt100, JPt100 Voltage: 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC
Input range: Sampling cycle: Signal source resistance effect: Influence of input lead:
Approx. 0.01 %/Ω of reading (10 Ω or less per wire)
Input filter: PV bias:
Action at input beak:
Thermocouple: Up-scale or downscale (Specify when ordering) RTD: Up-scale Voltage: Downscale
Action at input short circuit:
Control action
!"
!"
!"!"
Control method:
ON/OFF, P, PI, or PD actions is available Heat/cool action is available (Specify when ordering) [Only MA900]
Control output
!"
Number of outputs:
MA900: 4 points *, 8 points (Heat/cool type) * MA901: 8 points * * Not isolated between each output channel
Output type:
Relay contact output250 V AC, 3A ( R esistive load)
Contact type 1a contact Electrical life300,000 times or more (Rated load)
Voltage pulse output
0/12 V DC (Load resist ance 600 Ω or more)
Current output 0 to 20 mA DC, 4 to 20 mA DC
Triac output 0.5 A (Ambient temperature 40 °C or less)
Performance
!"
Display accuracy:
Thermocouple:
±
RTD:± (0.3 % of display value + 1 digit) or ± 0.8 °C [1.6 °F] Voltage:± (0.3 % of span + 1 digit)
Insulation resistance:
Between measuring terminal and grounding: Between power terminal and grounding:
Withstand voltage:
Between measuring terminal and grounding: 1 minute at 1000 V AC Between power terminal and grounding:
Between power and measuring ter m inals:
Power failure effect:
No influence is exerted upon the instrument for power fail ure of less than 30 ms.
Memory backup:
Backed up by EEPROM Number of write times:Approx. 100,000 times Data storage period: Approx. 10 years
Withi n the value whichever is the greater Withi n the value whichever is the greater
20 MΩ or more at 500 V DC 20 MΩ or more at 500 V DC
1 minute at 1500 V AC 1 minute at 2300 V AC
MA900: 4 channels MA901: 8 channels
U, L Input impedance : Approx. 1 M
See
Input range table
MA900: 0.5 seconds MA901: 1 second
First order l ag digital filter 1 to 100 seconds (0: OFF)
±
span (Within -1999 to +9999 digits)
Downscale (RTD)
PID control (With autotuning function)
(Load resistance 600 Ω or less)
(0.3 % of display value + 1 digit) or ± 2 °C [4 °F]
Approx. 0.2 µV/
Alarm function
!"
!"
!"!"
Number of points: Alarm type:
Deviation high alarm FAIL alarm Deviation low alarm Deviation high alarm with hold acti on Deviation high/low alarm Deviation low alarm with hold action Band alarm Deviation high /lo w a larm with hold a ctio n Process high alarm Process high alarm with hold act ion Process low alarm Process low alarm with hold action SV high alarm SV low alarm
Setting range:
Deviation alarm Process alarm, SV alarm Same as input range
Differential gap: Output method:
ALM1 to ALM3: Contact type 1a contact Rating 250 V AC, 1A (Resisti ve load) Electrical life 300,000 times or more (Rat ed load) OUT5 to OUT8 (MA901 can not be specified): Contact type 1a contact Rating 250 V AC, 3A (Resisti ve load) Electrical life 300,000 times or more (Rat ed load)
Control loop break alarm (LBA) function
!"
LBA time setting: LBA deadband:
Differential gap Temperature input: 0.8 °C [°F]
Alarm output:
Heater break alarm function (option)
!"
Input: Heater current display range:
Heater current display accuracy: Setting range:
Alarm output:
Contact input function (option)
!"
!"
!"!"
Number of inputs: Input method:
less
Functions:
Communication function (option)
!"
Interface: Protocol:
Power
!"
!"
!"!"
Power supply voltage:
90 to 264 V AC (Power supply voltage range), 50/60 Hz
21.6 to 26.4 V AC (Power supply voltage range), 50/60 Hz
21.6 to 26.4 V DC (Power supply voltage range)
Power consumption:
14 VA max. (at 100 V AC) 20 VA max. (at 240 V AC) 11 VA max. (at 24 V AC) 330 mA max. (at 24 V AC)
General specifications
!"
Ambient temperature: Ambient humidity: Operating environment:
There should be neither c orrosive gases nor much dust
Weight:
Specify when ordering
Current transf ormer (CT) output CTL-6-P-N: 0 to 30 A, CTL-12-S56-10L-N: 0 to 100 A
Based on RS-232C, RS422A, or RS-485 EIA standard ANSI X3.28 subcategory 2. 5, A4 Modbus
Rating: 100 to 240 V AC Rating: 24 V AC Rating: 24V DC
Approx. 560 g
3 points (Option: 2 points)
±
span (Within -1999 to 9999 digits)
0 to span (However, 9999 digi ts or less)
Relay contact output (Independent common)
0.1 to 200.0 minutes 0 to span (However, 9999 digi ts or less)
Voltage input: 0.8 % of span
LBA can be selected for ALM1
0.0 to 100.0 A
±
Withi n the value whichever is the greater
0.0 to 100.0 A HBA can be selected for ALM2
5 points Dry contact input At open 500 kΩ or more, At close 10 Ω or
RUN/STOP transfer 1 point Memory area transfer 4 points
0 to 50 °C 45 to 85 % RH (Non-condensing)
5 % of input value or ±2 A
20
IMR01H01-E4
Page 21
Input range table
!"
!"
!"!"
Thermocouple input and RTD input
#
Type Range Code
0 to 200 °CK01 0 to 400 °CK02 0 to 600 °CK03 0 to 800 °CK04 0 to 1000 °CK05 0 to 1200 °CK06 0 to 1372 °CK07
-199.9 to +300.0 °C
1
0.0 to 400.0 °CK09
0.0 to 800.0 °CK10 0 to 100 °CK13
K
0 to 300 °CK14 0 to 450 °CK17 0 to 500 °CK20
0.0 to 200.0 °CK29
0.0 to 600.0 °CK37
-199.9 to +800.0 °C
1
0 to 800 °FKA1 0 to 1600 °FKA2 0 to 2502 °FKA3
0.0 to 800.0 °FKA4
20 to 70 °FKA9
-199.9 to 999.9 °F
1
0 to 200 °CJ01 0 to 400 °CJ02 0 to 600 °CJ03 0 to 800 °CJ04 0 to 1000 °CJ05
-199.9 to +300.0 °C
J
0 to 1200 °CJ06
1
0.0 to 400.0 °CJ08
0.0 to 800.0 °CJ09 0 to 450 °CJ10
0.0 to 200.0 °CJ22
0.0 to 600.0 °CJ23
-199.9 to +600.0 °C
1
0 to 800 °FJA1 0 to 1600 °FJA2 0 to 2192 °FJA3
-199.9 to 999.9 °F
R
S
B
0 to 400 °FJA6
0.0 to 800.0 °FJB6 0 to 1600 °C 0 to 1769 °C 0 to 1350 °C 0 to 3200 °F 0 to 3216 °F 0 to 1600 °C 0 to 1769 °C 0 to 3200 °F 0 to 3216 °F
400 to 1800 °CB01
0 to 1820 °C
800 to 3200 °FBA1
0 to 3308 °F
1
2 2
2 2 2
2
2 2 2
2
2
*1 R01 *1 R02 *1 R04
*1 RA2 *1 S01 *1 S02
*1 SA2
*1 B02
*1 BA2
0 to 800 °CE01
E
0 to 1000 °CE02 0 to 1600 °FEA1 0 to 1832 °FEA2 0 to 1200 °CN01 0 to 1300 °CN02
N
0.0 to 800.0 °CN06 0 to 2300 °FNA1 0 to 2372 °FNA2
-199.9 to +400.0 °C
-199.9 to +100.0 °C
T
0.0 to 999.9 °FNA5
1
*2 T01
1
*2 T02
-100.0 to +200.0 °CT03
K08
K38
KB2
J07
J30
JA9
RA1
SA1
Thermocouple input and RTD input
#
Type Range Code
0.0 to 350.0 °CT04
-199.9 to +752.0 °F
-100.0 to +200.0 °F *2 TA2
T
1
*2 TA1
-100.0 to +400.0 °FTA3
0.0 to 450.0 °FTA4
0.0 to 752.0 °FTA5
W5Re/
W26Re
0 to 2000 °CW01 0 to 2320 °CW02 0 to 4000 °FWA1 0 to 1300 °CA01 0 to 1390 °CA02
PL II
0 to 1200 °CA03 0 to 2400 °FAA1 0 to 2534 °FAA2
-199.9 to +600.0 °C 1*2 U01
-199.9 to +100.0 °C 1*2 U02
U
0.0 to 400.0 °CU03
-199.9 to +999.9 °F
1
*2 UA1
-100.0 to +200.0 °F *2 UA2
0.0 to 999.9 °FUA3 0 to 400 °CL01
L
0 to 800 °CL02 0 to 800 °FLA1 0 to 1600 °FLA2
-199.9 to +649.0 °CD01
-199.9 to +200.0 °CD02
-100.0 to +50.0 °CD03
-100.0 to +100.0 °CD04
-100.0 to +200.0 °CD05
0.0 to 50.0 °CD06
0.0 to 100.0 °CD07
0.0 to 200.0 °CD08
0.0 to 300.0 °CD09
Pt100
0.0 to 500.0 °CD10
-199.9 to +999.9 °FDA1
-199.9 to +400.0 °FDA2
-199.9 to +200.0 °FDA3
-100.0 to +100.0 °FDA4
-100.0 to +300.0 °FDA5
0.0 to 100.0 °FDA6
0.0 to 200.0 °FDA7
0.0 to 400.0 °FDA8
0.0 to 500.0 °FDA9
-199.9 to +649.0 °CP01
-199.9 to +200.0 °CP02
-100.0 to +50.0 °CP03
-100.0 to +100.0 °CP04
JPt100
-100.0 to +200.0 °CP05
0.0 to 50.0 °CP06
0.0 to 100.0 °CP07
0.0 to 200.0 °CP08
0.0 to 300.0 °CP09
0.0 to 500.0 °CP10
1
Accuracy is not guaranteed between -199.9 to -100.0 °C (-199.9 to -148.0 °F)
2
Accuracy is not guaranteed between 0 to 399 °C (0 to 751 °F)
Voltage input
#
Type Range Code
0 to 5 V DC 0.0 to 100.0 % 4 01 0 to 10 V DC 0.0 to 100.0 % 5 01 1 to 5 V DC 0.0 to 100.0 % 6 01
IMR01H01-E4
21
Page 22

Memory Area Data List

(Copy this sheet for its use.)
Sheet No. Date: Name:
Memory area No.
ItemDisplay
Set value (SV) Control loop break alarm Control loop break alarm deadband Alarm 1 Alarm 2 Alarm 3 Proportional band Integral time Derivative time Anti-reset windup
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
Set value
Memory area No.
Cool-side proportional band Overlap/deadband Setting changing rate limiter Used/unused of channels
ItemDisplay
Set value (SV) Control loop break alarm Control loop break alarm deadband Alarm 1 Alarm 2 Alarm 3 Proportional band Integral time Derivative time
Set value
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
Anti-reset windup Cool-side proportional band Overlap/deadband Setting changing rate limiter Used/unused of channels
The first edition: APR.2001 The fourth edition: JUL.2002 [IMQ00]
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN
RKC INSTRUMENT INC.
®
PHONE:03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst. co.jp FAX: 03-3751-8585 (+81 3 3751 8585)
JUL. 2002 IMR01H01-E4
Loading...