All Rights Reserved, Copyright 1994, RKC INSTRUMENT INC.
Page 3
Thank you for purchasing the RKC instrument. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please
place this manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
!
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not
taken, damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
: This mark indicates where additional information may be located.
WARNING
!
An external protection device must be installed if failure of this instrument
z
could result in damage to the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned on to prevent electric
z
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to prevent
z
fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
z
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
z
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
z
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
IMSRM04-E8
i-1
Page 4
CAUTION
This is a Class A instrument. In a domestic environment, this instrument may cause radio
z
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide
z
reinforced insulation between the wire for the input signal and the wires for instrument
power supply, source of power and loads.
This instrument is designed for installation in an enclosed instrumentation panel. All high-
z
voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the
z
instrument or equipment.
All wiring must be in accordance with local codes and regulations.
z
To prevent instrument damage or failure, protect the power line and the input/output lines
z
from high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
z
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric
z
shock, fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
z
Do not connect wires to unused terminals as this will interfere with proper operation of the
z
instrument.
Turn off the power supply before cleaning the instrument.
z
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
z
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
z
panel with a hard object.
NOTICE
z
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
z
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
z
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
z
Periodic maintenance is required for safe and proper operation of this instrument. Some
components have a limited service life, or characteristics that change over time.
z
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in
this manual is subject to change without prior notice.
z
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior
written approval from RKC.
ETX (03H), ACK (06H), NAK (15H)
Codes in brackets ( ) are in hexadecimal.
3 seconds
00 to 15
Temperature measured value
Temperature set value
Check of alarm state and setting of alarms
4
IMSRM04-E8
Page 11
1.5 Terminal Voltage and Signal Logic
RS-422A and RS-485
1. SPECIFICATIONS
Name
T (A)
Send data
T (B)
R (A)
Receive data
R (B)
Voltage between T (A) and T (B) is the voltage of T (A) to the T (B) terminal.
Voltage between R (A) and R (B) is the voltage of R (A) to the R (B) terminal.
RS-232C
Signal voltageLogic
+ 3V or more0 (Space status)
- 3V or less1 (Mark status)
Voltage between T (A) and T (B)
Voltage between R (A) and R (B)
(Stop bit and signal 1)
Mark state
(Start bit and signal 0)
−2 VVoltage between T (A) and T (B) +2 V
−2 VVoltage between R (A) and R (B) +2 V
Space state
IMSRM04-E8
5
Page 12
2.CONNECTING
WARNING
!
To prevent electric shock or instrument failure, turn off the power before
connecting or disconnecting the instrument and peripheral equipment.
Connect connectors correctly in the right position. If it is forcibly pushed in with pins in the
wrong positions, the pins may be bent resulting in instrument failure.
When connecting or disconnecting the connectors, do not force it too far to right and left or
up and down, but move it as straight as possible. Otherwise, the connector pins may be bent,
causing instrument failure.
When disconnecting a connector, hold it by the connector itself. Disconnecting connectors
by yanking on their cables can cause breakdowns.
In order to prevent malfunction, never touch the contact section of a connector with bare
hands or with hands soiled with oil or the like.
In order to prevent malfunction, connect cable connectors securely, then firmly tighten the
connector fastening screws.
In order to prevent damage to cables, do not bend cables over with excessive force.
If the instrument is easily affected by noise, use the ferrite core in the both ends of the cable
(nearest the connector).
6
IMSRM04-E8
Page 13
2. CONNECTING
2.1 Connection Block Diagram
2.1.1 When connecting control unit with host computer directly
The communication interface for control unit are RS-232C and RS-422A. When using the RS-422A, a
maximum of 16 control units can be connected.
However, when connecting to the computer which only has a RS-232C driver, conversion of the
communication interface will be necessary.
Host computer
RS-232C
Control unitControl unit
When RS-232C is selected for the
control unit communications, only
one control unit may be connected.
RS-232C
RS-422A
RS-422A
Host computer
RS-232C/RS-422A
converter
Maximum of 16 units
Our recommended RS-232C/RS-422A converter are shown below:
RS-232C/RS-422A converter: COM-A
For details on the RS-232C/RS-422A converter, see the RS-232C/RS-422A converter
instruction manual.
IMSRM04-E8
7
Page 14
2. CONNECTING
2.1.2 When using operation panel
The communication interface for operation panel are RS-232C, RS-422A and RS-485. When using
the RS-422A or RS-485, a maximum of 16 control units (OPC/OPC-H: 32 control units) can be
connected.
However, when connecting to the computer which only has a RS-232C driver, conversion of the
communication interface will be necessary.
Host computer
RS-232C (Only one unit may be connected)
Junction branch box
RS-422A or
RS-232C
RS-232C/RS-422A or
RS-232C/RS-485
converter
RS-485
Junction branch box
RS-422A
RS-485
RS-422A
RS-485
RS-422A
RS-485
or
or
or
Operation panel
Operation panel
Operation panel
RS-422A
RS-422A
Maximum of 8 units
RS-422A
RS-422A
Maximum of 8 units
RS-422A
Maximum of 8 units
Control unit
Control unit
Control unit
RS-422A
or
RS-485
Maximum of 16 units
Operation panel
RS-422A
Maximum of 8 units
Control unit
Our recommended RS-232C/RS-422A or RS-232C/RS-485 converter and junction branch
boxes are shown below:
Converter:COM-A (RS-232C/RS-422A), COM-B (RS-232C/RS-485)
Junction branch box: BRA-100B-4 (RS-422A), BRA-100B-2 (RS-485)
For details on the RS-232C/RS-422A (or RS-232C/RS-485) converter and junction branch
boxes, see the each instruction manuals.
8
IMSRM04-E8
Page 15
2.2 Connection Between the Control Unit and a Host
Computer
2.2.1 When the dedicated cable is not used
RS-422A
2. CONNECTING
PCP module
RS-232C
Connection by the
modular connector
R(A)
R(B)
SG
T(B)
T(A)
Shield
Connection by the
modular connector
RS-422A
Paired wire
Shielded twisted
pair wire
RS-232C
Host computer or
RS-232C/RS-422A converter
T(A)
T(B)
SG
T(B)
T(A)
Host computer
PCP module
IMSRM04-E8
Not used
SD
SG
RD
Not used
Shield
Shielded wire
The 6 pins type modular connector should be used.
(TM4P-66P to HEROSE ELECTRIC CO., LTD. or equivalent)
SD
SG
RD
*
RS
CS
*RS and CS should be shorted
inside the connector.
9
Page 16
2. CONNECTING
2.2.2 When using the dedicated cable
RS-422A
RS-232C/RS-422A converter
Connect to terminal
block
RS-232C
Host computer
Connect to the
communication connector
Control unit
RS-422A
Connect to the modular connector
Ferrite core
Connect according to the label names as they are without crossing
the wires.
R(B)
R(A)
T(B )
T(A )
SG
RKC special cable type: W-BF-01-3000 (Sold separately)
on the PCP module [COM.PORT1].
R(B)
R(A)
T(B)
T(A)
SG
[Standard cable length: 3m]
RS-232C
Host computer
Connect to the
communication connector
We recommend to use the ferrite core (ZCAT1325-0530 to TDK Ltd. or equivalent) in the
both ends of the cable to connect the operation panel and host computer to decrease the
noise.
D-SUB (25P type) modular
conversion connector (TM12RV64-H to HIROSE ELECTRIC CO.,
LTD. or equivalent.)
RS-232C
Ferrite core
RKC special cable type: W-BF-02-3000 (Sold separately)
Control unit
Connect to the modular connector
on the PCP module [COM.PORT1].
[Standard cable length: 3m]
10
IMSRM04-E8
Page 17
2. CONNECTING
2.3 Connection Between the Operation Panel and a Host
Computer
2.3.1 OPL or OPL [CE/UL/CSA Conformed] connection
Modular cable pin numbers
1 to 6
1
to
6
Control
unit
100 to 240 V AC [OPL-A ∗ ]
Operation
panel
24 V DC [OPL-A ∗ ]
CE/UL/CSA Conformed
100 to 240 V AC,
24 V DC
[OPL-A ∗ /CE]
Control unit
Connect to the modular connector
on the PCP module [COM.PORT1].
Connect to the modular connector on
the oparation panel [COM.PORT].
RKC special cable type : W -BF-02-3000 (Sold separately)
[Standard cable length: 3m]
The cable type partially differs depending
on the cable length when ordering.
IMSRM04-E8
For the CE/UL/CSA approved instrument, install the ferrite cores attached to the operation
panel to both ends of the cable.
11
Page 18
2. CONNECTING
RS-422A
Pin number and signal name
Pin No. Mark Name
2T(A)Send data
6T(B)Send data
5SGGround for signal
4R(A)Receive data
8R(B)Receive data
Contents of communication cable wiring
Operation panel
T (A)
T (B)
SG
R (A)
R (B)
(Maximum connections: 16 units)
RS-485
2
6
5
4
8
Shielded twisted
Paired wire
pair wire
Signal Direction
Operation panelHost computer
Host computer
TXD
TXD
SG
RXD
RXD
TXD and RXD : negative logic.
Pin number and signal name
Pin No. Mark Name
2T/R(A)Send data/Receive data
6T/R(B)Send data/Receive data
5SGGround for signal
Contents of communication cable wiring
Paired wire
Operation panel
T/R (A)
T/R (B)
SG
(Maximum connections: 16 units)
2
6
5
Shielded twisted
pair wire
Signal Direction
Operation panelHost computer
Host computer
TXR/RXD
TXR/RXD
SG
TXD and RXD : negative logic.
12
IMSRM04-E8
Page 19
RS-232C
Pin number and signal name
2. CONNECTING
Pin No. Mark Name
3SD (TXD)Send data
2RD (RXD)Receive data
5SG (GND)Ground for signal
Contents of communication cable wiring
Operation panel
SD (TXD)
RD (RXD)
SG (GND)
(Maximum connections: 1 unit)
3
2
5
RS-232C
Shield wire
Signal Direction
Operation panelHost computer
Host computer
SD (TXD)
RD (RXD)
SG (GND)
RS (RTS)
*
CS (CTS)
*Short RS and CS
within connector
IMSRM04-E8
13
Page 20
2. CONNECTING
2.3.2 OPM or OPM Z-191 connection
Operation panel
Connector pin numbers
1
1425
RS-422A
13
Pin number and signal name
RS-422A
RS-485
RS-232C
Connect to the
host communication
connector [HOST]
Connector used: SDBB-25S
(Manufactured by HIROSE ELECTRIC CO.,LTD.)
The customer must prepare the communication cables.
These cables (excluding RS-485) are also available from RKC.
Recommended connector type: SDBB-25P
(Manufactured by HIROSE ELECTRIC CO.,LTD.)
Specify when ordering
Connect to the
communication
connector
Host computer
Pin No. Mark Name
2T(A)Send data
14T(B)Send data
8SGGround for signal
4R(A)Receive data
16R(B)Receive data
Contents of communication cable wiring
Operation panel
T (A)
T (B)
SG
R (A)
R (B)
2
14
8
4
16
(Maximum connections: 16 units)
Paired wire
Shielded twisted
Signal Direction
Operation panelHost computer
Host computer
TXD
TXD
SG
RXD
RXD
TXD and RXD : negative logic.
pair wire
14
IMSRM04-E8
Page 21
RS-485
Pin number and signal name
2. CONNECTING
Pin No. Mark Name
2T/R(A)Send data/Receive data
14T/R(B)Send data/Receive data
8SGGround for signal
Contents of communication cable wiring
Paired wire
Operation panel
T/R (A)
T/R (B)
SG
(Maximum connections: 16 units)
RS-232C
2
14
8
Shielded twisted
Signal Direction
Operation panelHost computer
Host computer
TXR/RXD
TXR/RXD
SG
pair wire
TXD and RXD : negative logic.
Pin number and signal name
Pin No. Mark Name
2SD (TXD)Send data
3RD (RXD)Receive data
7SG (GND)Ground for signal
4RS (RTS)Request to send
5CS (CTS)Clear to send
Contents of communication cable wiring
Operation panel
SD (TXD)
RD (RXD)
SG (GND)
RS (RTS)
CS (CTS)
(Maximum connections: 1 unit)
2
3
7
*
4
5
RS-232C
Shield wire
Signal Direction
Operation panelHost computer
Host computer
SD (TXD)
RD (RXD)
SG (GND)
*
RS (RTS)
CS (CTS)
*Short RS and CS within connector
IMSRM04-E8
15
Page 22
2. CONNECTING
2.3.3 OPM Z-191 [CE/UL/CSA Conformed] connection
Operation panel
Connect to the host communication
connector [HOST]
Connector pin numbers
15
6
9
Connector used: SDEB-9P
(Manufactured by HIROSE ELECTRIC CO.,LTD.)
We recommend to use the ferrite core (ZCAT1325-0530 to TDK Ltd. or equivalent) in
the both ends of the cable to connect the operation panel and host computer to decrease
the noise.
The connector for the connection with operation
panel is attached to this instrument.
RS-422A
RS-485
RS-232C
Ferrite cores
The customer must prepare the communication cables.
Specify when ordering
Host computer
Connect to the
communication
connector
RS-422A
Pin number and signal name
Pin No. Mark Name
2T(A)Send data
6T(B)Send data
5SGGround for signal
4R(A)Receive data
8R(B)Receive data
Contents of communication cable wiring
Operation panel
T (A)
T (B)
SG
R (A)
R (B)
2
6
5
4
8
Paired wire
Signal Direction
Operation panelHost computer
Host computer
TXD
TXD
SG
RXD
RXD
(Maximum connections: 16 units)
16
Shielded twisted
pair wire
TXD and RXD : negative logic.
IMSRM04-E8
Page 23
RS-485
Pin number and signal name
2. CONNECTING
Pin No. Mark Name
2T/R(A)Send data/Receive data
6T/R(B)Send data/Receive data
5SGGround for signal
Contents of communication cable wiring
Paired wire
Operation panel
T/R (A)
T/R (B)
SG
(Maximum connections: 16 units)
RS-232C
2
6
5
Shielded twisted
Signal Direction
Operation panelHost computer
Host computer
TXR/RXD
TXR/RXD
SG
pair wire
TXD and RXD : negative logic.
Pin number and signal name
Pin No. Mark Name
3SD (TXD)Send data
2RD (RXD)Receive data
5SG (GND)Ground for signal
Contents of communication cable wiring
Operation panel
SD (TXD)
RD (RXD)
SG (GND)
(Maximum connections: 1 unit)
3
2
5
RS-232C
Shield wire
Signal Direction
Operation panelHost computer
Host computer
SD (TXD)
RD (RXD)
SG (GND)
RS (RTS)
*
CS (CTS)
*Short RS and CS
within connector
IMSRM04-E8
17
Page 24
2. CONNECTING
2.3.4 OPM-H Z-191 connection
Operation panel
1
2
3
4
5
6
7
8
9
Connect to the
host communication
connector [HOST]
The connector for the connection with operation
panel is attached to this instrument.
RS-422A
RS-485
RS-232C
Specify when ordering
Connect to the
communication
connector
Host computer
Connector pin numbers
1
RS-422A
5
96
Connector used: SDEB-9P
Connector locking device type: HD-LN (4-40) (02)
(Manufactured by HIROSE ELECTRIC CO.,LTD.)
The customer must prepare the communication cables.
These cables (excluding RS-485) are also available from RKC.
Recommended connector type: SDEB-9S
(Manufactured by HIROSE ELECTRIC CO.,LTD.)
Pin number and signal name
Pin No. Mark Name
2T(A)Send data
6T(B)Send data
5SGGround for signal
4R(A)Receive data
8R(B)Receive data
Contents of communication cable wiring
Operation panel
Paired wire
Signal Direction
Operation panelHost computer
Host computer
T (A)
T (B)
SG
R (A)
R (B)
(Maximum connections: 16 units)
18
2
6
5
4
8
Shielded twisted
TXD
TXD
SG
RXD
RXD
TXD and RXD : negative logic.
pair wire
IMSRM04-E8
Page 25
RS-485
Pin number and signal name
2. CONNECTING
Pin No. Mark Name
2T/R(A)Send data/Receive data
6T/R(B)Send data/Receive data
5SGGround for signal
Contents of communication cable wiring
Paired wire
Operation panel
T/R (A)
T/R (B)
SG
(Maximum connections: 16 units)
RS-232C
2
6
5
Shielded twisted
Signal Direction
Operation panelHost computer
Host computer
TXR/RXD
TXR/RXD
SG
pair wire
TXD and RXD : negative logic.
Pin number and signal name
Pin No. Mark Name
3SD (TXD)Send data
2RD (RXD)Receive data
5SG (GND)Ground for signal
7RS (RTS)Request to send
8CS (CTS)Clear to send
Contents of communication cable wiring
Operation panel
SD (TXD)
RD (RXD)
SG (GND)
RS (RTS)
CS (CTS)
(Maximum connections: 1 unit)
3
2
5
7
*
8
RS-232C
Shield wire
Signal Direction
Operation panelHost computer
Host computer
SD (TXD)
RD (RXD)
SG (GND)
*
RS (RTS)
CS (CTS)
*Short RS and CS within connector
IMSRM04-E8
19
Page 26
3.SETTING FOR COMMUNICATION
In order to make communication between the SR Mini HG SYSTEM and the host computer, it is
necessary to set the communication speed, data configuration and address.
3.1 When Connecting Control Unit with Host Computer
Directly
Host communication setting (data configuration, communication speed, unit address, etc.) are to be set
by the PCP module of the control unit.
Set the same communication setting to both the control unit and connecting host computer.
Control unit
Host communication setting
Host computer
-Data configuration
-Communication speed
-Unit address, etc.
Setting the data configuration and communication speed
1. To separate the mainframe of the module from the mother block, pull the mainframe upward
with the upper connection of the mainframe set to the fulcrum while pressing thesection
of the mainframe (removal lever ) with your index finger.
Module mainframe
Mother block
Module mainframe
Upper
section
Lower
section
Mother block
20
IMSRM04-E8
Page 27
3. SETTING FOR COMMUNICATION
2. Set the desired data configuration and communication speed by the dip switches located in the
PCP module.
4
3
2
Upper section
View from the rear with the
mother block removed.
1
OFF
ON
12Data configuration34Communication speed
OFFOFF8-bit non parityOFFOFF2400 bps
OFFON7-bit even parityOFFON4800 bps
ONOFF7-bit odd parityONOFF9600 bps
ONON(Don't set this one)ONON19200 bps
3. After completing the setting, engage the upper connection of the mainframe with that of the
mother block, then perform the reverse order of separation to engage the lower part of the
mainframe with the mother block with the upper connection set to the fulcrum. Firmly engage
the mainframe with the mother block until a click sound is produced.
Unit address setting
CAUTION
Set the unit address so that its setting is different from other address settings on the same
line. Otherwise, problems or malfunction may result.
Setting procedure:
Set the address by the PCP
module unit address setting
switch on each control unit.
For this setting, use a small
slotted screwdriver.
Unit address setting switch
1
0
2
F
3
E
D
C
4
5
6
B
7
A
8
9
IMSRM04-E8
Setting range: 0 to F (hexadecimal)
Addresses 0 to 15
PCP module
21
Page 28
3. SETTING FOR COMMUNICATION
3.2 When Using Operation Panel
The host communication setting between the operation panel and host computer is made (on these
operation panel and host computer); the communication setting between the operation panel and
control unit is made (on these operation panel and control unit) and computer/local selection is made
(on the operation panel).
Host computer
Host
communication
setting
Host communication setting
-Data configuration
-Communication speed
-Operation panel address, etc.
Communication setting
-Data configuration
-Communication speed, etc.
Computer/Local transfer
Operation panel
Communication
setting
Control unit
Communication setting
-Data configuration
-Communication speed
-Unit address, etc.
3.2.1 Host communication setting
Host communication setting (data configuration, communication speed, operation panel address, etc.)
are to be set on the screen of the operation panel.
Set the same host communication setting to both the operation panel and connecting host computer.
For details on the setting and operating procedure, see the each operation panel instruction manuals.
OPM:See the Host Communication Initialize screen in the Operation panel OPM
Instruction Manual (IMSRM03-E
)
OPM [Z-191]:See the Host Communication Initialize screen in the Operation panel OPM [Z-
191] Instruction Manual (IMSRM21-E
)
OPL:See the Host Communication Initialize screen in the Operation panel [OPL]
Instruction Manual (IMSRM11-E
)
OPM-H [Z-191]: See the Host Communication Initialize screen of the Operation panel OPM-H
[Z-191] Instruction Manual (IMSRM26-E
)
22
IMSRM04-E8
Page 29
3. SETTING FOR COMMUNICATION
3.2.2 Between operation panel and control unit communication setting
Set the same communication setting to both the control unit and connecting operation panel.
Operation panel
Communication setting (data configuration, communication speed, etc.) are to be set on the screen of
the operation panel. For details on the setting and operating procedure, see the each operation panel
instruction manuals.
OPM :See the Communication Initialize screen in the Operation panel OPM
Instruction Manual (IMSRM03-E
OPM [Z-191]:See the Communication Initialize screen in the Operation panel OPM [Z-191]
Instruction Manual (IMSRM21-E
)
)
OPL:See the Communication Initialize screen in the Operation panel [OPL]
Instruction Manual (IMSRM11-E
OPM-H [Z-191]: See the Communication Initialize screen of the Operation panel OPM-H [Z-191]
Instruction Manual (IMSRM26-E
Control unit
Communication setting (data configuration, communication speed, unit address, etc.) are to be set by
the PCP module of the control unit.
Dip switch
It refers to
configuration and communication speed.
Unit address setting switch
It refers to
one operation panel.
Setting range: 0 to 7
Setting the data configuration and communication speed and it sets data
Unit address setting and it sets unit address. Up to 8 control units can be connected to
)
)
IMSRM04-E8
23
Page 30
3. SETTING FOR COMMUNICATION
3.2.3 Computer/Local transfer
SR Mini HG SYSTEM has two communication modes: local mode and computer mode. The host
computer can perform only monitoring (polling) in local mode. In computer mode, it can perform
monitoring and setting (selecting).
These computer/local transfer can be selected on the screen of the operation panel. For details on the
setting and operating procedure, see the each operation panel instruction manuals.
OPM :See the Computer/Local Selection screen in the Operation panel OPM
Instruction Manual (IMSRM03-E
OPM [Z-191]:See the Computer/Local Selection screen in the Operation panel OPM [Z-191]
Instruction Manual (IMSRM21-E
OPL :See the Computer/Local Selection screen in the Operation panel [OPL]
Instruction Manual (IMSRM11-E
)
)
)
OPM-H [Z-191]: See the Computer/Local Selection screen of the Operation panel OPM-H
[Z-191] Instruction Manual (IMSRM26-E
)
24
IMSRM04-E8
Page 31
4.COMMUNICATION PROTOCOL
p
[
]
]
[
]
[
]
[
]
A
A
Q
To establish the data link, the polling/selecting method is employed. The basic procedure follows
ANSI X 3.28 subcategory 2.5, B1 and JIS basic data transmission control. For selecting, fast selecting
is employed.
z
In the polling/selecting method, the device is entirely controlled by the host computer to allow
only data transfer with the host computer. In order to make the device send or receive data
messages, send the messages from the host computer in accordance with the polling or selecting
procedure (Centralized operation).
z
For communication, ASCII codes including transmission control characters are used.
Transmission control characters used in the device:
EOT (04H), ENQ (05H), ACK (06H), NAK (15H), STX (02H), ETB (17H), ETX (03H)
( ) : Hexadecimal number
4.1 Polling
Polling is an action that host computer requesting one of the device which selected among multi-drop
connected, to send the data. The polling procedure is as follows.
Host com
E
Address
O
T
(1)
ID: Identifier
uter send
ID
(2)
←
(9)
SR Mini
SYSTEM
send
→
Time
out
→
(Next data
→
send)
→
→
(Same
data
send)
→→→
E
O
T
Host
computer
send
E
O
T
(10)
Host
SR Mini SYSTEM send
E
N
No response
computer
send
(5)
E
→
O
T
(4)
E
(3)
E
or[ BCC
T
T
X
B
(8)
No
response
Indefinite
S
T
X
→
ID
Data
(6)
C
K
N
K
←
←
(7)
Polling procedure
IMSRM04-E8
25
Page 32
4. COMMUNICATION PROTOCOL
4.1.1 Polling procedure
(1) Data link initialize
In order to initialize the data link before sending the polling sequence, send [EOT] from the host
computer.
(2) Polling sequence send
Send the polling sequence from the host computer in the following format.
dc
e
AddressENQ
Address
cccc
This is the unit address of this device being polled.
It is expressed by a 4-digit decimal ASCII code.
When the connection is directly to the control unit and not to the operation panel, the operation
panel address number is abbreviated into 2 digits.
0000
Identifier
dddd
A code which identifies the data requested from this device.
It is expressed using a 2-digit alphanumeric ASCII code.
For details on the identifiers, see 5. COMMUNICATION IDENTIFIERS.
[ENQ]
eeee
This transmission control character signifies the end of the polling sequence. After sending this,
the host computer waits for a response from this device.
Identifier
Control unit address number (2 digits)
Operation panel address number (2 digits)
(3) Data send from this device
This device sends data in the following format if it received the polling sequence correctly.
dhfec
IdentifierDataBCCETBSTX
or
dhgec
IdentifierDataBCCETXSTX
If the length of send data (from [STX] to [BCC]) exceeds 128 bytes, it is divided into blocks
by [ETB]. In this case, the succeeding divided data is sent after [STX].
26
IMSRM04-E8
Page 33
4. COMMUNICATION PROTOCOL
(
)
(
)
(
)
(
)
(
)
(
)
(
)
(
)
(
)
(
)
(
)
(
)
(
)
[STX]
cccc
Transmission control character showing the beginning of the text (identifier and data).
Identifier
dddd
A code which identifies the data to be sent to the host computer. It is expressed using a 2-digit
alphanumeric ASCII code.
For details on the identifiers, see 5. COMMUNICATION IDENTIFIERS
Data
eeee
.
Data which is indicated by an identifier of this device, consisting of channel Nos., data, etc. Each
channel No. and data are delimited by a space (20H). The data and the next channel No. are
delimited by a comma.
Channel No.: 2-digit ASCII code, not zero-suppressed. Channels without channel Nos. may exist
depending on the type of identifier.
Data:ASCII code, zero-suppressed with spaces (20H). The number of digits varies
depending on the type of identifier.
The number of digits (length) and data configuration vary depending on the type of identifier. For
details on the number of data digits and data configuration, see 4.3 Communications Data
Configuration and 5. COMMUNICATION IDENTIFIERS
[ETB]
ffff
.
Transmission control character indicating the end of the block.
[ETX]
gggg
Transmission control character indicating the end of the text.
[BCC]
hhhh
Block check character for error-detection, uses horizontal parity. [BCC] is calculated by horizontal
parity (even number).
Calculation method
[BCC] is obtained by EX-OR (exclusive OR) of all characters from the character next to [STX] to
[ETB] or [ETX]. No [STX] is included.
Example:
The calculation method for the following data is shown below.
This device sends [EOT] in the following cases to terminate the data link.
z
When there is no specified identifier
z
When the specified identifier is not valid
z
When an error exists in the data format
z
When all data have been sent
(5) No response of this device
If the polling sequence is not received correctly (if the address differs or if there is an error in the
data), this device does not respond. In this case, take necessary measures for recovery by time-out
on the host computer side if required.
(6) Acknowledge [ACK]
If the host computer receives data sent correctly from this device, send [ACK]. The device then sends
data next to the identifier just sent . In order to stop sending data from this device, send [EOT] from
the host computer to terminate the data link.
(7) Negative acknowledge [NAK]
If the host computer does not correctly receive the data sent from this device, send [NAK]. The device
then re-sends the same data. As the number of re-send times is not specified, take necessary
measures for recovery on the host computer side if it does not recover.
(8) No response from host computer
If data sending from the host computer becomes no response, this device sends [EOT] after the timeout time (10 sec) has elapsed to terminate the data link.
(9) Indefinite response from host computer
If the response from the host computer is indefinite, this device sends [EOT] to terminate the data
link.
(10) Data link termination [EOT]
To terminate communication with this device or to terminate the data link as a result of no response
from this device, send [EOT] from the host computer.
28
IMSRM04-E8
Page 35
4. COMMUNICATION PROTOCOL
4.1.2 Polling procedure example
(When the host computer requests data)
Above example data is with 1 digit below decimal point. The data sent from control unit is
different from the specification of control unit.
29
Page 36
4. COMMUNICATION PROTOCOL
p
[
]
A
A
4.2 Selecting
Selecting is an operation in which the host computer selects one set from among the devices multidrop connected and then of recommending data receive. The selecting procedure is as follows. As
this device employs fast selecting, data is sent continuously to the selected address.
Host
computer
send
E
O
T
(7)
E
O
T
(1)
Address
(2)
Host com
S
[ ID ]
T
X
uter send
[ Data ]
E
T
B
(3)
or
E
T
X
[ BCC ]
SR Mini SYSTEM send
→→→→
No response
(6)
→
C
K
(4)
→
N
(5)
←
←
ID: Identifier
K
Selecting procedure
4.2.1 Selecting procedure
(1) Data link initialize
Send [EOT] from the host computer to initialize the data link before sending the selecting sequence.
(2) Selecting sequence send
Send the selecting address for the selecting sequence from the host computer.
Address
This is the unit address of this device to be selected.
It is expressed by a 4-digit decimal ASCII code.
When the connection is directly to the control unit and not to the operation panel, the operation panel
address number is abbreviated into 2 digits.
0000
Control unit address number (2 digits)
Operation panel address number (2 digits)
30
IMSRM04-E8
Page 37
4. COMMUNICATION PROTOCOL
(3) Data send
Send data in the following formats following the selecting sequence. The data format is the same as
that of polling.
IdentifierDataBCCETBSTX
to h, see 4.1 Polling.
c
For
or
IdentifierDataBCCETXSTX
If the length of send data (from [STX] to [BCC]) exceeds 128 bytes, it is divided into blocks
by [ETB]. In this case, send the succeeding data divided into blocks after [STX].
(4) Acknowledge response [ACK]
If this device receives data sent correctly from the host computer, it sends [ACK] to the host computer.
Then, if there is data to be sent next from the host computer, send it to the device. After the data has
been sent, send [EOT] to terminate the data link.
(5) Negative acknowledge [NAK]
This device sends [NAK] in the following cases. In this case, take necessary measures for recovery
such as re-sending the data on the host computer side.
z
When an error occurs in the line (parity error or framing error)
z
When a BBC check error occurs
z
When there is no specified identifier
z
When the specified identifier is not valid
z
When an error exists in the data format
z
When normal receive data exceeds the setting range
(6) No response
If this device does not receive the selecting address correctly, it is set to no response. Also, it is set
to no response if it does not receive [STX], [ETB], [EXT], or [BCC] correctly.
(7) Data link termination [EOT]
To terminate the data link when there is no more data to be sent from the host computer or this device
is set to no response, send [EOT] from the host computer.
IMSRM04-E8
31
Page 38
4. COMMUNICATION PROTOCOL
4.2.2 Selecting procedure example
(When the host computer sends data)
The data (Input range, decimal point etc.) should be conformed to the specifications of the
instruments to be used. (Above example is with 1 digit below decimal point). The SR
Mini HG SYSTEM sends [NAK] if the receiving of different data to specification.
0Operations normal
1Back-up data check error
2RAM read/write error
3System structure error
4Internal communications error
5A/D converter error
6Adjustment data error
IMSRM04-E8
33
Page 40
4. COMMUNICATION PROTOCOL
4.4 Examples of Selecting and Polling Check Programs
The following is the sample program for NEC PC-9800 series computers in BASIC language for
carrying out polling and selecting checking by RS-422A (4-wire system) or RS-232C specification.
Please be noted that there will be some differences in the computer languages according to the type of
computer.
Before executing the program, confirm that there is no mistake in the wiring of the communications
cable and check that the control unit data bit structure is set to 8 for data bit and None for parity
check.
In addition, the communications speed setting should be set to match the host computer speed setting.
Example of temperature set values polling check program
1000 '-------------------- Identifier setting ---------------------1010 ID$="S1"
1020 '
1030 '--------------- Communications initial setting --------------1040 CM$="N81NN"
1050 INPUT "Control unit address=";ADD$
1060 STX$=CHR$(&H2) : EOT$=CHR$(&H4) : ENQ$=CHR$(&H5)
1070 ACK$=CHR$(&H6) : NAC$=CHR$(&H15): ETX$=CHR$(&H3)
1080 OPEN "COM1:"+CM$ AS #1
1090 CONSOLE ,,,1
1100 COLOR 7:CLS 3
1110 '
1120 '------------------ Program main routine --------------------1130 *POL
1140 PRINT " (Polling check) "
1150 PRINT "*********Receiving the set values************"
1160 PRINT " "
1170 DT$=EOT$+ADD$+ID$+ENQ$
1180 GOSUB *TEXT
1190 GOSUB *RXDT
1200 '
1210 *J10
1220 J=0
1230 '
1240 *IF1
1250 IF LOC(1)=0 THEN J=J+1:IF J<500 THEN *IF1 ELSE PRINT "
TIME OUT ":END
1260 '
1270 K$=INPUT$(1,#1)
1280 IF K$=ETX$ GOTO *ETXRX
1290 IF K$=NAK$ THEN PRINT " NAK":END
1300 IF K$=EOT$ THEN PRINT " EOT":END
1310 IF K$=ACK$ THEN PRINT " ACK":END
1320 '
1330 DT$=DT$+K$
1340 GOTO *J10
1350 '
Identifier setting
Communications data configuration setting
Control unit address input
Communications character setting
Open RS-232C circuit
Data configuration setting
Setting of the receiving waiting time
(Timeout processing)
Communications condition checking
(Continued on the next page.)
34
IMSRM04-E8
Page 41
1360 *ETXRX
1370 DT$=DT$+K$
1380 BCCRX$=INPUT$(1,#1)
1390 BCCRX=ASC(BCCRX$)
1400 GOSUB *BCCCH
1410 IF BCC<>BCCRX THEN GOSUB *NAKTX
1420 IF BCC<>BCCRX THEN GOSUB *RXDT GOTO *J10
1430 '
1440 PRINT "Data has been correctly received"
1450 PRINT "Received data=";DT$ : END
1460 '
1470 '--------------------- Sub-routine ---------------------1480 '
1490 *NAKTX
1500 PRINT "BCC error"
1510 DT$=NAK$
1520 GOSUB *TEXT
1530 RETURN
1540 '
1550 *RXDT
1560 DT$=""
1570 RETURN
1580 '
1590 *TEXT
1600 PRINT #1,DT$;
1610 RETURN
1620 '
1630 *BCCCH
1640 FOR II=1 TO LEN(DT$)
1650 BCCA$=MID$(DT$,II,1)
1660 IF BCCA$=STX$ THEN BCC=0 : GOTO *IINEXT
1670 BCC=BCC XOR ASC(BCCA$)
1680 *IINEXT
1690 NEXT II
1700 RETURN
4. COMMUNICATION PROTOCOL
BCC checking
Display of received data and
closing of RS-232C circuit
Processing on occurrence of a BCC error
Clearing of circuit buffer
Transfer of polling identifier
BCC calculation
(The items after the mark of " ' " can be omitted.)
Setting of the receiving waiting time : If timeout occurs in using high speed computer (Except no
response), the numeral value of 500 in the program should
be changed to an appropriately-sized numeral value.
IMSRM04-E8
35
Page 42
4. COMMUNICATION PROTOCOL
Example of temperature set values selecting checking program
1000 '-------------------- Identifier setting ---------------------1010 ID$="S1"
1020 '
1030 '--------------- Communications initial setting --------------1040 CM$="N81NN"
1050 STX$=CHR$(&H2) : EOT$=CHR$(&H4) : ENQ$=CHR$(&H5)
1060 ACK$=CHR$(&H6) : NAC$=CHR$(&H15): ETX$=CHR$(&H3)
1070 OPEN "COM1:"+CM$ AS #1
1080 CONSOLE ,,,1
1090 COLOR 7:CLS 3
1100 '
1110 '------------------ Program main routine --------------------1120 *SEL
1130 PRINT " (Selection check) "
1140 PRINT "********Transmission of set values*********"
1150 PRINT "
1160 INPUT "Unit No.=";ADD$:INPUT "Channel No.=";C$
:INPUT "Setvalue=";S$
1170 DT$=EOT$+ADD$+STX$+Z$+C$+" "+S$+ETX$
1180 PRINT "Transmitting data=";DT$
1190 GOSUB *BCCCH
1200 DT$=DT$+CHR$(BCC)
1210 GOSUB *TEXT
1220 GOSUB *RXDT
1230 '
1240 *J20
1250 J=0
1260 '
1270 *IF2
1280 IF LOC(1)=0 THEN J=J+1:IF J<500 THEN *IF1 ELSE PRINT "
TIME OUT ":END
1290 '
1300 K$=INPUT$(1,#1)
1310 IF K$=NAK$ THEN PRINT " NAK":END
1320 IF K$=ACK$ THEN PRINT "Control unit has received the data":END
1330 '
1340 '
1350 '
1360 '--------------------- Sub-routine ---------------------1370 '
1380 *RXDT'
1390 DT$=""
1400 RETURN
1410 '
1420 *TEXT
1430 PRINT #1,DT$;
1440 RETURN
Identifier setting
Communications data configuration setting
Communications character setting
Opening of RS-232C circuit
Input of the unit and channel number,
and the temperature set value
Data configuration setting 1
Display of transmitting data
Data configuration setting 2
Setting of the receiving waiting time
(Timeout processing)
Communications condition check,
Display of communication result,
and closing of RS-232C circuit
Clearing of circuit buffer
Transfer of selection data
36
(Continued on the next page.)
IMSRM04-E8
Page 43
4. COMMUNICATION PROTOCOL
1450 '
1460 *BCCCH
1470 FOR II=1 TO LEN(DT$)
1480 BCCA$=MID$(DT$,II,1)
1490 IF BCCA$=STX$ THEN BCC=0 : GOTO *IINEXT
1500 BCC=BCC XOR ASC(BCCA$)
1510 *IINEXT
1520 NEXT II
1530 RETURN
(The items after the mark of " ' " can be omitted.)
Setting of the receiving waiting time : If timeout occurs in using high speed computer (Except no
BCC calculation
response), the numeral value of 500 in the program should
be changed to an appropriately-sized numeral value.
IMSRM04-E8
37
Page 44
5.COMMUNICATION IDENTIFIERS
5.1 List of Communication Identifiers
( AttributesRO : Read only R/W : Read and Write WO : Write only)
Name
Measured value (PV)
input
First alarm condition
Second alarm condition
Burnout alarm condition
Manipulated output
(Heat-side)
Manipulated output
(Cool-side)
Heater break alarm
CT input measured
value 1
CT input measured
value 2
Iden-
tifier
M1
AA
AB
B1
O1
O2
AC
M3
M4
Digits
Attri-
bute
6ROWithin input range
1RO0: OFF 1: ON
1RO0: OFF 1: ON
1RO0: OFF 1: ON
6RO-5.0 to +105.0 %
6RO-5.0 to +105.0 %
1RO0: OFF 1: ON
6RO0.0 to 100.0 A or
0.0 to 30.0 A (Measured
value of the TIO module)
6RO0.0 to 100.0 A or
0.0 to 30.0 A (Measured
value of the CT module)
Data range
Factory
set
value
−
−
−
−
−
−
−
−
−
Refer-
ence
page
41
41
42
42
43
43
Set value monitor
Temperature rise
completion condition
Error code
PID/AT transfer
Temperature set value
Heat-side proportional
band
Cool-side proportional
band
Integral time
Derivative time
: Memory area response settings group (See page 62)Continued on the next page.
MS
HE
ER
G1
S1
P1
P2
I1
D1
6ROWithin input range
1RO0: Rise not complete
1: Rise completed
1RO0 to 6
1R/W0: PID control operation
1: AT (Autotuning) operation
6R/WWithin input range
(Within setting limiter)
6R/W0.1 to 1000.0 % of span3.054
6R/W0.1 to 1000.0 % of span3.0
6R/W1 to 3600 sec.240
6R/W0 to 3600 sec.60
−
−
−
051
053
45
46
50
38
IMSRM04-E8
Page 45
Continued from the previous page
5. COMMUNICATION IDENTIFIERS
Name
Deadband/Overlap
Control response
parameters
First alarm set value
Second alarm set value
Heater break alarm
(HBA) set value 1
Heater break alarm
(HBA) set value 2
Operation mode transfer
Iden-
tifier
V1
CA
A1
A2
A3
A4
EI
Factory
Digits
Attri-
bute
Data range
set
value
6R/W-10.0 to +10.0 % of span0.054
1R/W0: Slow 1: Medium
*155
2: Fast
6R/WWithin input range or span
*256
range
6R/WWithin input range or span
*2
range
6R/W0.0 to 100.0 A or
0.043
0.0 to 30.0 A (For the CT
input of the TIO module)
6R/W0.0 to 100.0 A or
0.0
0.0 to 30.0 A (For the CT
input of the CT module)
1R/W0: Unused 1: Monitoring
357
2: Alarm 3: Normal
Refer-
ence
page
Heat-side proportioning
cycle
T0
6R/W1 to 100 sec.
(Setting will be invalid in
*358
continuous output of
current/voltage.)
Cool-side proportioning
cycle
T1
6R/W1 to 100 sec.
(Setting will be invalid in
*3
continuous output of
current/voltage and heat
action.)
PV bias
Control Run/Stop
Initialize setting mode
PB
SR
IN
6R/W-5.00 to +5.00 % of span0.0059
1R/W0: Stop 1: Run160
1R/W0: Normal communication
061
1: Extended communication
Memory area number
Alarm interlock release
Auto/Manual transfer
Manual output value
: Memory area response settings group (See page 62)Continued on the next page.
ZA
AR
J1
ON
1R/WNumber 1 to 8162
1WO1: Release (1 only)
−
1R/W0: Auto 1: Manual064
6R/W-5.0 to +105.0 %0.0
63
IMSRM04-E8
39
Page 46
5. COMMUNICATION IDENTIFIERS
Continued from the previous page
Name
Temperature rise
completion range
Temperature rise
completion trigger
Temperature rise
completion soak time
LBA alarm condition
LBA use selection
LBA time
LBA deadband
Local/Computer transfer
*1Heat control: 0
Heat/cool control: 2
Iden-
tifier
HD
HS
T3
AP
HP
C6
V2
C1
Factory
Digits
Attri-
bute
Data range
set
value
6R/W1 to 10 °C or 1 to 20 °F10°C
20°F
1R/W0: Unused 1: Used0
6R/W0 to 360 min.0
1RO0: OFF 1: ON
−
1R/W0: Unused 1: Used066
6R/W1 to 7200 sec.480
6R/WInput span0
1RO0: Local mode
−
1: Computer mode
(Only valid when connected
with the Operation Pane)
Refer-
ence
page
46
66
70
*2Depends on specifications
*3Relay contact output: 20
Voltage pulse output, open collector output, triac output: 2
40
IMSRM04-E8
Page 47
5. COMMUNICATION IDENTIFIERS
5.2 Identifiers Function Explanation
Identifier M1: Measured value (PV) input
Read only identifier which defines the input measured value from the control unit.
Data range: Within input range
Polling example:
E
O
T
Operation
panel
address
Unit
address
*
Identifier
E
N
Q
S
T
X
Identifier
01400. 0, 02 ...ET
Channel
No.
Space
Data (6 digits)
Comma
SR Mini SYSTEM send
Channel
No.
Host computer sendHost computer send
B
C
X
C
Next to identifier
A
C
K
* Omit the operation panel address when the connection is made directly to control unit.
Identifier AA: First alarm condition
Identifier AB: Second alarm condition
Read only identifier which defines each channel alarm condition of the control unit.
Data range: 0: OFF
1: ON
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
Identifier
E
N
Q
S
T
X
Identifier
Space
Comma
010, 02 ...ET
Channel
No.
SR Mini SYSTEM send
Data
(1 digit)
Channel
No.
A
C
K
B
Next to identifier
C
X
C
* Omit the operation panel address when the connection is made directly to control unit.
IMSRM04-E8
41
Page 48
5. COMMUNICATION IDENTIFIERS
Identifier B1: Burnout alarm condition
Read only identifier which defines each channel burnout condition of the control unit.
Data range: 0: OFF
1: ON
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
Identifier
E
N
Q
S
T
X
Identifier
CommaSpace
010, 02 ...ET
Channel
No.
SR Mini SYSTEM send
Data
(1 digit)
Channel
No.
B
C
X
C
A
C
K
Next to identifier
* Omit the operation panel address when the connection is made directly to control unit.
Read only identifier which defines the manipulated output value from the control unit.
Data range: -5.0 to +105.0 %
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
Identifier
E
N
Q
S
T
X
Identifier
0180.0,02 ...ET
Data (6 digits)Channel
No.
Space
SR Mini SYSTEM send
Channel
No.
Comma
A
C
K
B
C
X
C
Next to identifier
* Omit the operation panel address when the connection is made directly to control unit.
42
IMSRM04-E8
Page 49
5. COMMUNICATION IDENTIFIERS
Identifier AC: Heater break alarm (HBA)
Read only identifier which defines the heater break alarm condition.
Data range: 0: OFF
1: ON
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
ACEN
Identifier
CommaSpace
Q
S
TXAC010, 02 ...ET
Identifier
Channel
No.
SR Mini SYSTEM send
Data
(1 digit)
Channel
No.
X
A
C
K
B
Next to identifier
C
C
* Omit the operation panel address when the connection is made directly to control unit.
Identifier M3: CT input measured value 1
Identifier M4: CT input measured value 2
Identifier A3: Heater break alarm (HBA) set value 1
Identifier A4: Heater break alarm (HBA) set value 2
Identifier used when the heater break alarm function is used.
M3: CT input measured value 1, A3: Heater break alarm set value 1
The CT input measured value 1 indicates the measured current value detected by the CT sensors of
each channel of the TIO module that is optionally set to the heater break alarm function. The
heater break alarm set value 1 is the set value of the heater break alarm of each of these channels.
Data range: 0.0 to 100.0 A or 0.0 to 30.0 A
M4: CT input measured value 2, A4: Heater break alarm set value 2
The CT input measured value 2 indicates the measured current value detected by the CT sensors of
each channel of the CT module. The heater break alarm set value 2 is the set value of the heater
break alarm of each of these channels.
Data range: 0.0 to 100.0 A or 0.0 to 30.0 A
• CT input measured values 1 and 2:Read only
• Heater break alarm set values 1 and 2:Read and write
IMSRM04-E8
Continued on the next page.
43
Page 50
5. COMMUNICATION IDENTIFIERS
p
TIO moduleCT module
TIO-DTIO-B
CTCTCTCT
CH5
CT1
CH6
CT2
CH7
CT3
CH8
CH7CH5
CH8CH6CH4CH3CH2CH1
CT4
CT5
CT6
CT input measured value 1
(Identifier: M3),
Heater break alarm set value 1
(Identifier: A3)
CT input measured value 2
(Identifier: M4),
Heater break alarm set value 2
(Identifier: A4)
When sending and receiving data, note that identifiers M3 and A3 will be the channel numbers
of the TIO module and that M4 and A4 will be the channel numbers of the CT module.
For the details of the form to allocate each CT input of the CT module to the TIO module channels,
see the separate Hardware Instruction Manual (IMSRM02-E). Further, for the allocation
method, see the Supplementary Information for Initialize Settings (Extended Communications).
Heater break alarm
This function determination whether or not there is a break in the heater by comparing the value of
the current flowing through the heater with the previously set current value that is considered to be
abnormal.
The heater break alarm function in this instrument can not be used with continuous analog
output.
Heater break detection:
When the CT input measured value (heater current)
read from the CT is less than the currently set heater
break alarm set value even if a control signal is
output, a heater break alarm is output.
Welding detection:
When the CT input measured value (heater current)
read from the CT is more than the currently set
heater break alarm set value even if a control signal
is not output, a heater break alarm is output.
O
eration unit
Heater
CT
Sensor
CT input
Control
output
TIO
CT
[Setting example]
A numerical value of approx. 85% of the CT input measured value (Identifiers: M3 or M4) should
be set as the heater break alarm set value (Identifiers: A3 or A4).
However, for a heater with the characteristic of a slight delay in the rise of the current, change the set
value such as to reduce if necessary.
44
IMSRM04-E8
Page 51
5. COMMUNICATION IDENTIFIERS
Polling example:
Host computer sendHost computer send
E
O
T
E
N
Q
S
Operation
panel
address
Unit
address
*
Identifier
T
X
Identifier
0115.0,02 ...ET
Channel
No.
Space
Data (6 digits)
SR Mini SYSTEM send
Channel
No.
Comma
* Omit the operation panel address when the connection is made directly to control unit.
A
C
K
B
C
X
C
Next to identifier
Selecting example (Heater break alarm set value 1 and Heater break alarm set value 2 only):
Host computer sendHost computer send
E
O
T
S
T
0115. 0, 02 ...ET
X
B
C
X
C
E
O
T
A
Operation
panel
address
Unit
address
*
Identifier
Channel
No.
Space
Data (6 digits)
Comma
Channel
No.
SR Mini SYSTEM send
C
K
* Omit the operation panel address when the connection is made directly to control unit.
Identifier MS: Set value monitor
Read only identifier which defines the set value now used for control.
Data range: Within input range
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
MSEN
Identifier
Q
S
TXMS01145. 6, 02 ...ET
Identifier
Channel
No.
Space
Data (6 digits)
SR Mini SYSTEM send
Channel
No.
Comma
X
Next to identifier
A
C
K
B
C
C
* Omit the operation panel address when the connection is made directly to control unit.
IMSRM04-E8
45
Page 52
5. COMMUNICATION IDENTIFIERS
Identifier HE: Temperature rise completion condition
Identifier HD: Temperature rise completion range
Identifier HS: Temperature rise completion trigger
Identifier T3: Temperature rise completion soak time
Identifier used for each setting related to the presence or absence of the temperature rise completion
trigger function.
HE: Temperature rise completion condition (Read only)
Data range: 0: Rise not complete
1: Rise completed
HD: Temperature rise completion range (Read and write)
Data range: 1 to 10 °C or 1 to 20 °F
HS: Temperature rise completion trigger (Read and write)
Data range: 0: Unused
1: Used
T3: Temperature rise completion soak time (Read and write)
Data range: 0 to 360 min.
Temperature rise completion condition, temperature rise completion trigger
and temperature rise completion range
Used when a temperature rise is assumed to be completed when the temperature set value (PV) is
within the width set on both sides from the temperature set value (SV).
The width from the temperature set value at this time becomes the temperature rise completion range,
and thus the temperature rise completion condition can be checked by the output. "Used/Unused" of
the temperature rise completion function can be selected depending on whether the temperature rise
completion trigger.
If the function is set to two or more channels, the temperature rise is completed when the temperature
rise in all the channels in which this function is set has been completed. In addition, even when the
measured temperature is finally within the temperature rise completion range as a result of a
temperature drop, if the measured temperature is first higher than the set temperature, this is
determined to be in the temperature rise completion condition.
46
Temperature
set value (SV)
PV2
PV1
Temperature rise completion trigger point
(Rise completion)
+
Temperature rise
completion range
−
IMSRM04-E8
Page 53
5. COMMUNICATION IDENTIFIERS
Temperature rise completion soak time
Time (min.) until the temperature rise completion state is output after all channels reach the
temperature set value.
Temperature set value
or Temperature rise
completion range
Temperature rise start
(All channels simultaneously)
c
The a) channel has reached the temperature rise completion range.
d
The b) channel has reached the temperature rise completion range.
e
The c) channel has reached the temperature rise completion range.
f
Temperature rise completion is assumed for the first time after the soak time has elapsed.
a)
b)
For the allocation of the temperature rise completion condition output to the PCP module for
DO output, see the separate Hardware Instruction Manual (IMSRM02-E).
Polling example (Temperature rise completion condition):
c)
Soak time
edc
Temperature
rise completion
f
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
HEEN
Identifier
Q
S
TXHE0ET
Identifier
SR Mini SYSTEM send
Data
(1 digit)
X
A
C
K
B
Next to identifier
C
C
* Omit the operation panel address when the connection is made directly to control unit.
IMSRM04-E8
47
Page 54
5. COMMUNICATION IDENTIFIERS
Polling example (Temperature rise completion range):
E
O
T
HDEN
Q
S
Operation
panel
address
Unit
address
*
Identifier
TXHD015, 02 ...ET
Identifier
Channel
No.
Space
Data (6 digits)
SR Mini SYSTEM send
Channel
Comma
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example (Temperature rise completion range):
No.
Host computer sendHost computer send
B
C
X
C
Next to identifier
A
C
K
Host computer sendHost computer send
E
O
T
S
TXHD015, 02 ...ET
B
C
X
C
E
O
T
A
Operation
panel
address
Unit
address
*
Identifier
Channel
No.
Space
Data (6 digits)
Comma
Channel
No.
SR Mini SYSTEM send
C
K
* Omit the operation panel address when the connection is made directly to control unit.
Polling example (Temperature rise completion trigger):
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
HSEN
Identifier
Space
Comma
Q
S
TXHS010, 02 ...ET
Identifier
Channel
No.
SR Mini SYSTEM send
Data
(1 digit)
Channel
No.
X
A
C
K
B
Next to identifier
C
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example (Temperature rise completion trigger):
CommaSpace
Host computer sendHost computer send
E
O
T
S
TXHS0 10 , 0 2 ...ET
B
C
X
C
E
O
T
A
Operation
panel
address
Unit
address
*
Identifier
Channel
No.
Data
(1 digit)
Channel
No.
SR Mini SYSTEM send
C
K
* Omit the operation panel address when the connection is made directly to control unit.
48
IMSRM04-E8
Page 55
Polling example (Temperature rise completion soak time):
5. COMMUNICATION IDENTIFIERS
Host computer send
E
O
T
Operation
panel
address
Unit
address
*
T3EN
Identifier
Q
S
TXT30ET
Identifier
Data (6 digits)
SR Mini SYSTEM send
Host computer send
A
C
K
B
Next to identifier
C
X
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example (Temperature rise completion soak time):
Host computer send
E
O
T
Operation
panel
address
Unit
address
*
S
TXT30ET
Identifier
Data (6 digits)
SR Mini SYSTEM send
Host computer send
B
C
X
C
E
O
T
A
C
K
* Omit the operation panel address when the connection is made directly to control unit.
The temperature rise completion function will be effective even if "Unused" is selected in
the operation mode transfer for each channel on the operation mode screen. If the
operation mode is selected as unused and if the temperature rise completion function is also
required to be made invalid, set the above-mentioned temperature rise completion trigger
selection to "None."
IMSRM04-E8
49
Page 56
5. COMMUNICATION IDENTIFIERS
Identifier ER: Error code
If the system abnormality occurs during operation or power on, error data is transmitted from the
control unit or Operation Panel.
Error code data description
DataDescription
0Operations normal
1Back-up data check error
2RAM read/write error
3System structure error
4Internal communications error
5A/D converter error
6Adjustment data error
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
EREN
Identifier
Q
S
TXER0ET
Identifier
SR Mini SYSTEM send
Data
(1 digit)
X
A
C
K
B
Next to identifier
C
C
* Omit the operation panel address when the connection is made directly to control unit.
50
IMSRM04-E8
Page 57
5. COMMUNICATION IDENTIFIERS
Identifier G1: PID/AT transfer
Identifier which defines the transfer to either PID (Normal control) and AT (Autotuning) mode.
Data range: 0: PID control operation
1: Autotuning execution operation
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
G1EN
Identifier
CommaSpace
Q
S
TXG1010, 02 ...ET
Identifier
Channel
No.
SR Mini SYSTEM send
Data
(1 digit)
Channel
No.
X
A
C
K
B
Next to identifier
C
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
CommaSpace
Host computer sendHost computer send
E
O
T
S
TXG1 0 10 , 0 2 ...ET
B
C
X
C
E
O
T
A
Operation
panel
address
Unit
address
*
Identifier
Channel
No.
Data
(1 digit)
Channel
No.
SR Mini SYSTEM send
C
K
* Omit the operation panel address when the connection is made directly to control unit.
IMSRM04-E8
51
Page 58
5. COMMUNICATION IDENTIFIERS
Autotuning conditions
Autotuning (AT) is the function which automatically measures, calculates and sets the optimum PID
constants according to the set temperature. The following is the conditions necessary to carry out
autotuning and the conditions which will cause the autotuning to stop.
Conditions necessary for autotuning:
The autotuning should be executed after satisfying all of the following conditions :
(1) Operation mode conditions:
z
Auto/Manual transfer (Identifier: J1): Auto mode
z
PID/AT transfer (Identifier: G1): PID mode
z
Control Run/Stop (Identifier: SR): Control Run mode
(2) The input value should not be an underscale or overscale displayed.
(3) The output limiter high limit should be more than 0.1% and the output limiter low limit should be
less than 99.9%. (Setting by Initialize set communication)
(4) When operation mode is set to "Normal."
When the autotuning is finished, the mode display of each channel automatically returns to "PID."
Conditions which will cause the autotuning to stop:
z
When the set value (SV) is changed.
z
When the memory area is changed.
z
When the PV bias value is changed.
z
When the AT bias value is changed.
z
When transfer to Manual mode using the Auto/Manual transfer.
z
When the input value becomes an underscale or overscale display.
z
When the power is cut off.
z
When "FAIL" occurs in the module whose channel is under the autotuning. Otherwise, when
"FAIL" occurs in the PCP module.
z
When transfer to the PID mode by the PID/AT transfer.
z
When operation mode is set to "Normal."
z
When the Control Run/Stop function is changed to the "Control stop" function.
52
When the above-mentioned conditions to stop the autotuning occurs, the autotuning is
immediately stopped and switch over to the PID (PID control) mode. The PID constants
return to the values at the start of the autotuning.
IMSRM04-E8
Page 59
Identifier S1: Temperature set value
Identifier which defines the temperature set value.
Data range: Within input range (Within setting limiter)
Polling example:
E
O
T
Operation
panel
address
address
*
Unit
S1EN
Identifier
Q
S
TXS10115.0,02 ...ET
Identifier
Channel
No.
Space
5. COMMUNICATION IDENTIFIERS
Data (6 digits)
Comma
SR Mini SYSTEM send
Channel
No.
Host computer sendHost computer send
B
C
X
C
Next to identifier
A
C
K
* Omit the operation panel address when the connection is made directly to control unit
Selecting example:
Host computer sendHost computer send
E
O
T
S
TXS10115. 0, 02 ...ET
B
C
X
C
E
O
T
A
Operation
panel
address
Unit
address
*
Identifier
Channel
No.
Space
Data (6 digits)
Comma
Channel
No.
SR Mini SYSTEM send
C
K
* Omit the operation panel address when the connection is made directly to control unit.
IMSRM04-E8
53
Page 60
5. COMMUNICATION IDENTIFIERS
Identifier P1: Heat-side proportional band
Identifier P2: Cool-side proportional band
Identifier I1: Integral time
Identifier D1: Derivative time
Identifier V1: Overlap/Deadband
Identifier which defines the temperature control parameter.
P1 : Heat-side proportional band, P2 : Cool-side proportional band
Data range: 0.1 to 1000.0 % of span
I1 : Integral time
Data range: 1 to 3600 sec.
D1 : Derivative time
Data range: 0 to 3600 sec.
V1 : Overlap/Deadband
Data range: -10.0 to +10.0 % of span
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
Identifier
E
N
Q
S
T
X
Identifier
0115.0,02 ...ET
Channel
No.
Space
Data (6 digits)
Comma
SR Mini SYSTEM send
Channel
No.
Next to identifier
A
C
K
B
C
X
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
address
*
Unit
S
T
X
Identifier
0115. 0, 02 ...ET
Comma
Channel
No.
SR Mini SYSTEM send
Channel
No.
Space
Data (6 digits)
B
C
X
C
E
O
T
A
C
K
* Omit the operation panel address when the connection is made directly to control unit.
54
IMSRM04-E8
Page 61
5. COMMUNICATION IDENTIFIERS
Identifier CA: Control response parameters
Identifier which defines the control response parameters.
Data range: 0: Slow
1: Medium
2: Fast
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
CAEN
Identifier
CommaSpace
Q
S
TXCA010, 02 ...ET
Identifier
Channel
No.
SR Mini SYSTEM send
Data
(1 digit)
Channel
No.
X
A
C
K
B
Next to identifier
C
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
CommaSpace
Host computer sendHost computer send
E
O
T
S
TXCA0 10 , 0 2 ...ET
B
C
X
C
E
O
T
A
Operation
panel
address
*
Omit the operation panel address when the connection is made directly to control unit.
Unit
address
*
Identifier
Channel
No.
Data
(1 digit)
Channel
No.
SR Mini SYSTEM send
C
K
In order to perform PID control by using the fussy function, specify "FAST." The fuzzy
function is effective to restrict overshoot or undershoot occurring at operation start, or
resulting from set value changes. (TIO-P module only)
IMSRM04-E8
55
Page 62
5. COMMUNICATION IDENTIFIERS
Identifier A1: First alarm set value
Identifier A2: Second alarm set value
Identifier which defines each channel alarm set value.
Data range: Within input range or span range
Polling example:
E
O
T
Operation
panel
address
Unit
address
*
Identifier
E
N
Q
S
T
X
Identifier
0150, 02 ...ET
Channel
No.
Data (6 digits)
Space
SR Mini SYSTEM send
Comma
Channel
No.
Host computer sendHost computer send
B
C
X
C
Next to identifier
A
C
K
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
Host computer sendHost computer send
E
O
T
S
T
0150, 02 ...ET
X
B
C
X
C
E
O
T
A
Operation
panel
address
Unit
address
*
Identifier
Channel
No.
Space
Data (6 digits)
Comma
Channel
No.
SR Mini SYSTEM send
C
K
* Omit the operation panel address when the connection is made directly to control unit.
56
IMSRM04-E8
Page 63
5. COMMUNICATION IDENTIFIERS
Identifier EI: Operation mode transfer
Changes each channel operation mode of TIO module.
[Data range]
0: Unused mode
If set to "Unused," no control, monitor or alarm monitor is performed. Use this when replacing the
module, or during equipment maintenance and inspection.
1: Monitor mode
If set to "Monitor," only the operation relating to monitor is performed. (capture of measured value
(PV)). No control or alarm monitor is performed. Use this when equipment operation is temporarily
stopped.
2: Alarm mode
If set to "Alarm," monitor or alarm monitor is performed, but no normal mode to perform control,
monitor or alarm monitor. No control is performed. Use this mode when stopping equipment
operation temporarily.
3: Normal mode
Selected to normal mode to perform control, monitor or alarm monitor.
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
EIEN
Identifier
Space
Comma
Q
S
TXEI 013, 02 ...ET
Identifier
Channel
No.
SR Mini SYSTEM send
Data
(1 digit)
Channel
No.
X
A
C
K
B
Next to identifier
C
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
CommaSpace
Host computer sendHost computer send
E
O
T
Operation
panel
address
address
*
S
TXEI 0 13, 0 2 ...ET
Unit
Identifier
Channel
No.
Data
(1 digit)
Channel
No.
B
C
X
C
E
O
T
A
C
K
SR Mini SYSTEM send
* Omit the operation panel address when the connection is made directly to control unit.
Even if the temperature rise completion function is set to the Unused mode, it will continue
to be effective. If the temperature rise completion function is also to be made invalid,
change the setting of the temperature rise completion trigger function to "No."
Identifier which defines the heat-side proportioning cycle and cool-side proportioning cycle.
Data range: 1 to 100 sec.
Setting will be invalid in continuous output of current and voltage.
Cool-side proportioning cycle: Setting will be invalid in heat action.
Polling example:
E
O
T
Operation
panel
address
Unit
address
*
Identifier
E
N
Q
S
T
X
Identifier
0120, 02 ...ET
Channel
No.
Space
Data (6 digits)
SR Mini SYSTEM send
Channel
No.
Comma
Host computer sendHost computer send
B
C
X
C
Next to identifier
A
C
K
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
Host computer sendHost computer send
E
O
T
S
T
0120, 02 ...ET
X
B
C
X
C
E
O
T
A
Operation
panel
address
Unit
address
*
Identifier
Channel
No.
Space
Data (6 digits)
Comma
Channel
No.
SR Mini SYSTEM send
C
K
* Omit the operation panel address when the connection is made directly to control unit.
58
IMSRM04-E8
Page 65
5. COMMUNICATION IDENTIFIERS
Identifier PB: PV bias
Identifier which defines data to forcibly change (increase or decrease in displayed value) the
measured value (PV).
The value set in the PV bias is added to the actual input value to correct the input value. The PV
bias is used to correct the individual variations in the sensors or when there is difference between the
measured values (PV) of other instruments.
Example: When the temperature is measured by two instruments.
When the measured values (PV) are as shown in the diagram :
Main unit = 198 °C
Recorder = 200 °C
If a PV bias correction value of +2 °C is added to the measured
value the main unit, the displayed value become:
Displayed value = Measured value (PV) + PV bias =
198 °C + 2 °C = 200 °C
In this instrument, for a span of 400 °C, the PV bias should be set to:
PV bias = 0.5 % (400 °C × 0.5 % = 2 °C)
Main unit = 198 °C
Recorder = 200 °C
Data range: -5.00 to +5.00 % of span
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
Identifier
E
N
Q
S
T
X
Identifier
010. 00, 02 ...ET
Channel
No.
Space
Data (6 digits)
Comma
SR Mini SYSTEM send
Channel
No.
Next to identifier
A
C
K
B
C
X
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
address
*
Unit
S
T
X
Identifier
010. 00, 02 ...ET
Comma
Channel
No.
SR Mini SYSTEM send
Channel
No.
Space
Data (6 digits)
B
C
X
C
E
O
T
A
C
K
* Omit the operation panel address when the connection is made directly to control unit.
IMSRM04-E8
59
Page 66
5. COMMUNICATION IDENTIFIERS
Identifier SR: Control Run/Stop
Identifier which defines data to start or stop control.
Data range: 0: Stop
1: Run
Polling example:
E
O
T
Operation
panel
address
address
*
Unit
SREN
Identifier
Q
S
TXSR1ET
Identifier
SR Mini SYSTEM send
Data
(1 digit)
Host computer sendHost computer send
A
C
K
B
Next to identifier
C
X
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
Host computer send
E
O
T
Operation
panel
address
Unit
address
*
S
TXSR1ET
Identifier
Data
(1 digit)
SR Mini SYSTEM send
Host computer send
B
C
X
C
A
C
K
E
O
T
* Omit the operation panel address when the connection is made directly to control unit.
If this identifier is changed to control stop, both control and alarm outputs are turned off.
60
IMSRM04-E8
Page 67
5. COMMUNICATION IDENTIFIERS
Identifier IN: Initialize setting mode
Identifier which defines data to select initialize mode (extended communication).
When you change to the initialize setting mode, the contents of the identifiers in the separate
supplementary information can be changed or switched. For more details, see the supplementary
information in this manual.
When the control is started, it is impossible to change the settings to the extended
communications. For the change to the extended communications, the control must be first
stopped by the control Run/Stop (Identifier: SR).
It is impossible to start the control in the extended communication mode. For the re-start
of the control change to the normal communications mode beforehand.
Data range: 0: Normal communication
1: Extended communication
Polling example:
Host computer send
E
O
T
Operation
panel
address
Unit
address
*
INEN
Identifier
Q
S
TXIN0ET
Identifier
SR Mini SYSTEM send
Host computer send
B
C
X
C
Data
(1 digit)
A
C
K
Next to identifier
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
Host computer send
E
O
T
Operation
panel
address
Unit
address
*
S
TXIN0ET
Identifier
Data
(1 digit)
SR Mini SYSTEM send
Host computer send
B
C
X
C
A
C
K
E
O
T
* Omit the operation panel address when the connection is made directly to control unit.
IMSRM04-E8
61
Page 68
5. COMMUNICATION IDENTIFIERS
Identifier ZA: Memory area number
Identifier which defines the memory area number of the control unit.
The memory area function is the function which stores the parameter values such as the set value
(SV) etc. in up to 8 memories. When required, read in the appropriate 1 memory out of the 8
memories and to use its parameters for the control. The memory area which is used for the control is
defined as control area.
The parameter values to be stored in one memory
Temperature set value:S1Integral time:I1
First alarm set value:A1Derivative time:D1
Second alarm set value:A2Control response parameter: CA
Heat-side proportional band: P1Overlap/deadband:V1
Cool-side proportional band: P2
Data range: 1 to 8
Memory
8
6
5
4
3
2
1
Control area
Temperature set value: S1
First alarm set value: A1
Second alarm set value: A2
Heat-side proportional band: P1
Cool-side proportional band: P2
Integral time: I1
Derivative time: D1
Control response parameter: CA
Overlap/deadband: V1
Polling example:
Host computer send
E
O
T
Operation
panel
address
Unit
address
*
ZAEN
Identifier
Q
S
TXZA1ET
Identifier
SR Mini SYSTEM send
Host computer send
B
C
X
C
Data
(1 digit)
A
C
K
Next to identifier
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
Host computer send
E
O
T
Operation
panel
address
Unit
address
*
S
TXZA1ET
Identifier
Data
(1 digit)
SR Mini SYSTEM send
Host computer send
B
C
X
C
A
C
K
E
O
T
* Omit the operation panel address when the connection is made directly to control unit.
62
IMSRM04-E8
Page 69
Identifier AR: Alarm interlock release
Identifier which release the alarm interlock.
Data range: 1: Release (1 only)
Selecting example:
5. COMMUNICATION IDENTIRIERS
Host computer send
E
O
T
S
TXAR1ET
Host computer send
B
C
X
C
E
O
T
A
Operation
panel
address
Unit
address
*
Identifier
Data
(1 digit)
SR Mini SYSTEM send
C
K
* Omit the operation panel address when the connection is made directly to control unit.
IMSRM04-E8
63
Page 70
5. COMMUNICATION IDENTIFIERS
Identifier J1: Auto/Manual transfer
Identifier ON: Manual output value
Identifier which defines auto (Normal automatic control operation) or manual (Manual operation)
transfer and control output value during manual operation.
When you switch over to the manual mode, set the control output value with the manually output
value (Identifier: ON).
J1: Auto/Manual transfer
Data range: 0: Auto
1: Manual
ON: Manual output value
Data range: -5.0 to +105.0 %
Polling example (Auto/Manual transfer):
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
J1EN
Identifier
CommaSpace
Q
S
TXJ1010, 02 ...ET
Identifier
Channel
No.
SR Mini SYSTEM send
Data
(1 digit)
Channel
No.
X
A
C
K
B
Next to identifier
C
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example (Auto/Manual transfer):
CommaSpace
Host computer sendHost computer send
E
O
T
Operation
panel
address
address
*
S
TXJ1010, 02 ...ET
Unit
Identifier
Channel
No.
Data
(1 digit)
Channel
No.
B
C
X
C
E
O
T
A
C
K
SR Mini SYSTEM send
* Omit the operation panel address when the connection is made directly to control unit.
64
IMSRM04-E8
Page 71
5. COMMUNICATION IDENTIRIERS
Polling example (Manual output value):
Host computer sendHost computer send
E
O
T
ONEN
Q
S
Operation
panel
address
Unit
address
*
Identifier
TXON010. 0, 02 ...ET
Identifier
Channel
No.
Space
Data (6 digits)
SR Mini SYSTEM send
Channel
No.
Comma
* Omit the operation panel address when the connection is made directly to control unit.
A
C
K
B
C
X
C
Next to identifier
Selecting example (Manual output value):
Host computer sendHost computer send
E
O
T
S
TXON010. 0, 02 ...ET
B
C
X
C
E
O
T
A
Operation
panel
address
Unit
address
*
Identifier
Channel
No.
Space
Data (6 digits)
Comma
Channel
No.
SR Mini SYSTEM send
C
K
* Omit the operation panel address when the connection is made directly to control unit.
When ON/OFF control and heat/cool control are specified for the control unit, the manual
output set value becomes invalid. At the same time, the Auto/Manual transfer of the
operation mode changing will also become invalid.
IMSRM04-E8
65
Page 72
5. COMMUNICATION IDENTIFIERS
Identifier AP: LBA alarm condition
Read only memory which defines the LBA (Loop break alarm) state
Data range: 0: OFF
1: ON
Polling example:
Host computer send
E
O
T
Operation
panel
address
Unit
address
*
APEN
Identifier
Space
Comma
Q
S
TXAP010, 02 ...ET
Identifier
Channel
No.
SR Mini SYSTEM send
Data
(1 digit)
Channel
No.
Host computer send
A
C
K
B
Next to identifier
C
X
C
* Omit the operation panel address when the connection is made directly to control unit.
Identifier HP: LBA use selection
Identifier C6: LBA time
Identifier V2: LBA deadband
Identifier used to select used or unused of LBA and to set LBA.
HP: LBA use selection
Data range: 0: Unused
1: Used
C6: LBA time
Data range: 1 to 7200 sec.
V2: LBA deadband
Data range: Input span
Polling example (LBA use selection):
Host computer send
E
O
T
HPEN
Q
Space
Comma
S
Operation
panel
address
*
Omit the operation panel address when the connection is made directly to control unit.
address
*
Unit
Identifier
TXHP011, 02 ...ET
Identifier
Channel
No.
SR Mini SYSTEM send
Data
(1 digit)
Channel
No.
Host computer send
A
C
K
B
Next to identifier
C
X
C
66
IMSRM04-E8
Page 73
5. COMMUNICATION IDENTIRIERS
Selecting example (LBA use selection):
CommaSpace
Host computer sendHost computer send
E
O
T
S
TXHP0 11 , 0 2 ...ET
B
C
X
C
E
O
T
A
Operation
panel
address
Unit
address
*
Identifier
Channel
No.
Data
(1 digit)
Channel
No.
SR Mini SYSTEM send
C
K
* Omit the operation panel address when the connection is made directly to control unit.
Polling example (LBA time, LBA deadband):
Host computer sendHost computer send
E
O
T
Operation
panel
address
Unit
address
*
Identifier
E
N
Q
S
T
X
Identifier
010. 0, 02 ...ET
Channel
No.
Space
Data (6 digits)
Comma
SR Mini SYSTEM send
Channel
No.
Next to identifier
A
C
K
B
C
X
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example (LBA time, LBA deadband):
Host computer sendHost computer send
E
O
T
Operation
panel
address
address
*
Unit
S
T
X
Identifier
010. 0, 02 ...ET
Comma
Channel
No.
SR Mini SYSTEM send
Channel
No.
Space
Data (6 digits)
B
C
X
C
E
O
T
A
C
K
* Omit the operation panel address when the connection is made directly to control unit.
IMSRM04-E8
67
Page 74
5. COMMUNICATION IDENTIFIERS
Control loop break alarm (LBA) function
The LBA function detects the abnormality in the control loop such as the break of load (heater), the
abnormality of external operating unit (magnet relay etc.), the break of input (sensors), etc.
When the output reaches 100 % or 0 % (or output limiter low limit) the LBA function starts to
monitor periodically the change of measured value (PV) at previously set time and detects the break
of heater and input. For the TIO-K module (Position proportioning control), LBA functions with the
opening value set to output.
(1) LBA alarm condition
For heat control
When output becomes less than 0 %
(or output limiter low limit)
For
reverse
action
For
direct
action
The variation width determined by the LBA : Fixed 2 °C (°F)
For heat/cool control
For
heat/cool
control
When measured value (PV) does not fall
below the variation width determined by
the LBA within the LBA set time.
When measured value (PV) does not rise
beyond the variation width determined by
the LBA within the LBA set time.
When the output on the heat-side
becomes more than 100 % (or output
limiter high limit) and the output on the
cool-side becomes less than 0 %
When measured value (PV) does not rise
beyond the variation width deter-mined by
the LBA within the LBA set time.
When output becomes more than
100 % (or output limiter high limit)
When measured value (PV) does not rise
beyond the variation width determined by
the LBA within the LBA set time.
When measured value (PV) does not fall
below the variation width determined by
the LBA within the LBA set time.
When the output on the heat-side
becomes less than 0 % and the output
on the cool-side becomes more than
100 % (or output limiter low limit)
When measured value (PV) does not fall
below the variation width determined by
the LBA within the LBA set time.
The variation width determined by the LBA : Fixed 2 °C (°F)
When autotuning is used, the LBA set time which is twice the integral time thus set is
automatically set. (No LBA set time changes even if the integrated value is changed.)
68
IMSRM04-E8
Page 75
(2) Detected errors
LBA output is turned on if any of the following errors are detected.
Controlled object trouble .. Heater break, no power supply, incorrect wiring, etc.
d
Sensor trouble ................... Sensor disconnected, shorted, etc.
e
Actuator trouble ................ Weld relay contact, incorrect wiring, relay contact not closed, etc.
f
Output circuit trouble........ Weld internal relay contact, relay contact not open or closed, etc.
g
Input circuit trouble........... The measured value does not change even if input changes, etc.
However, the cause of the above trouble cannot be identified, so check the control system
step by step.
(3) LBA deadband (LBD)
The LBA may enter the alarm condition due to a disturbance (Other heat sources, etc.) even if there is
no error in the control system. In this case, an area in which no alarm occurs can be set by setting
the LBA deadband (LBD). Set the LBD carefully because no alarm occurs even if alarm conditions
occur while the measured value (PV) is within the LBD area.
zThe LBA function detects the occurrence of an error in the control loop, but cannot locate the error
point. Therefore in this case, check each control system in order.
zNo LBA function is activated in the following cases.
-While autotuning is being executed
-If operation mode is set to any mode other than "Normal."
zIf the LBA set time is shorter than anticipated or it does not match the controlled object, the LBA
may not turn on or off. In this case, change the LBA set time depending on the situation.
zLBA output turns off in the following cases with LBA output turned on.
-When measured value (PV) rises (or falls) beyond (or below) the variation width determined by
the LBA within the LBA set time.
-When measured value (PV) enters the LBA deadband
Identifier C1: Local/computer transfer
When the operation panel is located between the host computer and the control unit, this identifier
which defines the settings by the operation panel (Local mode) or by the computer (Computer mode).
Only valid when connected with the Operation Panel.
Data range: 0: Local mode
1: Computer mode
Polling example:
Host computer sendHost computer send
E
O
T
Operation
panel
address
C1EN
Identifier
*
Q
S
TXC1 0ET
Identifier
SR Mini SYSTEM send
Data
(1 digit)
X
* Omit the operation panel address when the connection is made directly to control unit.
I
n the computer mode, the host computer has the priority for the settings and all changes on
the operation panel for the settings becomes invalid. (Except for the local/computer mode
transfer setting.)
A
C
K
B
Next to identifier
C
C
70
IMSRM04-E8
Page 77
6.TROUBLESHOOTING
6.1 Troubleshooting
WARNING
!
To prevent electric shock or instrument failure, always turn off the system
z
power before replacing the instrument.
To prevent electric shock or instrument failure, always turn off the power
z
before mounting or removing the instrument.
To prevent electric shock or instrument failure, do not turn on the power until
z
all the wiring is completed.
To prevent electric shock or instrument failure, do not touch the inside of the
z
instrument.
All wiring must be performed by authorized personnel with electrical
z
experience in this type of work.
IMSRM04-E8
71
Page 78
6. TROUBLESHOOTING
In this section, an explanation is given of the presumed causes and measures of general problems
when transmission can not be carried out correctly.
When abnormalities are suspected in the control, operation, operation panel or control unit (Hardware
related problems), see the troubleshooting items in the appropriate separate Operation PanelInstructionManual or Hardware Instruction Manual.
SymptomPresumed causeSolution
No responseThe control unit power is not turned onTurn on the power
There is a mistake in the communication cable
Confirm the connection method
connections
Breakage in the communication cableReplace the cable
Detachment of the communication cableConfirm the connection condition
Problems with the connectors or contactsCheck and replace the wiring in the
connector
The communication speed or bit structure
Confirm each setting
settings are different
The address specification is differentConfirm the address numbers
There is a difference in the structure of the
transmission data
Change to a structure that matches
the identifier
Breakdown of this instrumentReplace the instrument or request
repairing
EOT has been
The identifier has been mistakenConfirm the identifier
transmitted
The identifier specified is not in this
Confirm the identifier
instrument specification
NAK has been
transmitted
The block data length of the transmission
exceeds 128 bytes
The data exceeds the setting range of this
instrument
The data length exceeds the specification of
this instrument
See 6.2 Error code descriptions (Identifier: ER)
has been
transmitted
72
IMSRM04-E8
Page 79
6. TROUBLESHOOTING
6.2 Error Code Descriptions (Identifier: ER)
When the following errors have occurred, replace or request repair for the controller in which the
error has occurred. (The module that has the FAIL lamp lit.)
Error code data
DataDescriptionExplanation
0Operations normal
1Back-up data check errorThe control data has been destroyed or written
wrongly
2RAM read/write errorProblem with the system RAM
3System structure errorThe system structure has been changed
4Internal communications errorAbnormality in the internal communications
5A/D converter errorProblem with the A/D converter
6Adjustment data errorThe adjustment data has been written wrongly
Presumed causes of occurrence:
a) When errors 1, 2 or 5 have occurred, a breakdown in the RAM, ROM or A/D converter should be
suspected.
b) Error 3 occurs when the module structure is different from the initial structure. An example would
be if a module is replaced by a different model of module. In this situation, replace with the same
model of module. Further, this error will also occur when module initialize has not been carried
out after changing the module structure.
c) Error 4 occurs in the situation where a module is removed while the power is still on, etc.
d) If errors 5 or 6 occur, there is a possibility that too much noise, surge or strong shock has been
applied to the control unit.
IMSRM04-E8
73
Page 80
7.ASCII CODE TABLE
ASCII 7-bit code table
b700001111
b600110011
b501010101
b5 to b7b4b3b2b101234567
00000NULDLE SP0@P‘p
00011SOHDC1 !1AQaq
00102STXDC2 ”2BRbr
00113ETXDC3 #3CScs
01004EOTDC4 $4DTdt
01015ENQNAK %5EUeu
01106ACKSYM &6FVfv
01117BELETB ’7GWgw
10008 BS CAN (8HXhx
10019 HT EM)9IYiy
1010A LF SUB *:JZjz
1011B VT ESC +;K[k{
1100C FF FS,<L¥l |
1101D CR GS-=M]m}
1110E SO RS.>N^n˜
1111F SI US/?O_o DEL
74
IMSRM04-E8
Page 81
The 1st edition:Aug. 1994
The 8th edition:Oct. 1999
Page 82
RKC INSTRUMENT INC.
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN